HomeMy WebLinkAboutProducts ReviewSLC -_mom _ Library 25T. Repi __ m _
Unit Dimensions Commercial Rooftop » a#i.;g Units (Midrange)
#m Al a oAx z Ipak
MPE2
§k)(!\§§§§
)«\!B=§§\}
- §!2§!
0
\/
\///-)
E-
/_.��=::#K�
§wzso(.;z
F.__w«.as»z__# Equipment___ Page aa
_a
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
1 1.
TYPICAL PEDESTAL AND BASE
DIMENSION DRAWING
SHIPS
FIELD
CASK
PEDESTAL
ROOFCURB
TYPICAL PEDESTAL AND BASE PAN DETAIL TYPICAL ROOF CURB AND BASE PAN DETAIL
DETAIL DETAIL
LIFTING LUG
"LONG
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 10 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
ELECTRICAL / GENERAL DATA
TONS
GAS HEATING - PERFORMANCE
Model (Tonnage):
SAHLF25 (25 Ton)
Heating Input:
Unit Operating Voltage Range:
414-506
Heating Output:
Unit Primary Voltage:
460
Capacity Steps:
Unit Hertz:
60
Unit Phase:
3
HEATING - GENERAL DATA
Gas inlet pressure: (in w.c.)
EER:
114, EER
Gas Pipe Connection Size:
IEER:
14.5 EER
COMPRESSOR
ELECTRIC HEATER
Compressor 1 Count:
1.00 Each
Electric Heater Kw:
Compressor 1 RLA:
22.20 A
Electric Heater Full Load Amps:
Compressor 2 Count:
1.00 Each
Compressor 2 RLA:
19.10 A
0 mpressor3 Count:
Value not available
Compressor 3 RLA:
Value not available
SUPPLY FAN MOTOR
EXHAUST / RETURN FAN MOTOR SECTION
Number of Fans:
2.00 Each
Number: Value not available
Number of Motors:
1
Horsepower (Each): None
Total Horsepower:
15 hp FC
ExhausVReturn Fan Motor FLA: Value not available
Supply Fan Motor Full Load Amps:
16.00 A
Supply Fan EBiciency:
45.53 %
CONDENSER FAN MOTOR
FILTERS - TYPE
Number:
3
Type:
Horsepower (each):
1.0
Furnished YES
Condenser Fan Motor Full Load Amps (Total):
5.4
Number: 12
Recommended Size: 20" x20" x2"
PREFILTERS
EVAPORATIVE CONDENSER pl
Pump Horsepower.
N/A
Furnished:
Pump Full Load Amps:
IN
Number:
Sump Heater Full Load Amps:
IN
Recommended Size:
Sump Heater kW:
REFRIGERANTTYPE let
FINAL FILTERS - TYPE
Charge Type:
R-410A
TYPe:
Factory Charge (Circuit pl):
31.31b
Furnished:
Factory Charge (Circuit k2):
Value not available
Number:
Recommended Sure:
PREFILTERS
Furnished:
Number:
Recommended Size:
Notes:
1. LOAD 1=Current of the largest motor (compressor or fan motor); LOAD 2-Sum of the currents of all remaining motors; LOAD 3 =Current of electric heaters
LOAD 4 =Control Power Transformer (20-40 and 24-48 ton units add 3 FL amps for wire sizing formula, 50-75 and 59 - 89 ton units add 6 FL amps)
2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and healing modes. (When determining LOADS, the compressors
do not operate when the unit is in heating mode) (On 70-89 ton single source units, heating Load 4 = 12 amps on 200,230 vole units and
9 amps on 460,575 volt units)
3. If selected Max Over Cur is less than the Min Cir Amp, then select the lowest maximum fuse size which is equal to or larger than the Min Cir
Amp, provided the selected fuse size does not exceed 800 amps.
4. If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value, then select the Recommended Dual
Element fuse size value to equal the Max Over Protection value.
5. Compressor KW at AHRI rating conditions of 80/67-95
6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions.
7. Sump Heater is an optional feature.
It. Total Horsepower is the combined Horsepower for the Supply Fan Motors.
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 11 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Fan Curve - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
SW
c� 5.5 -
5.0 -
4.5 -
4.0 -
3.5 -
3.0 -
,2.5-
2.0 -
0 1.5 -
~ 1.0 -
EM
EMMMEEMEEMM
EMMIMMMEEMM
SENEEMMEENEEME
SEENEENEEMMMM
EMMMMMMM
®
EMMMEEMMEME
MMMEEMMMEMI
5000 10000 15000 20000 25000 30000 35000 40000
Airflow (cfm)
63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Outdoor Noise: -1 1 1 1 1 1 1 -1
Supply Duct: 1 1 1 1 1 1 1 1
Return Duct: -1 -1 -1 -1 -1 -1 -1 -1
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 12 of 24
Others
SLC - Morningside Library 25T Ipak Repl
Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
CLEARANCE
Note:
When 2 or more units are to be placed side by side, the distance between the units
should be increased to 150%of the recommended single unit clearance. The units
should also be staggered to reduce span deflection & assure proper diffusion of
exhaust air.
CLEARANCE
F-7-7
96"
CLEARANCE
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 13 of 24
Others
SLC - Morningside Library 25T Ipak Repl
Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
PL 2, X1
PL 4, X2
Center of Gravity X: 13.20 ft
Point load X location 1:
4.000 in
Center of Gravity Y: 3.87 fi
Point load X location 2:
104.000 in
Point load X location 3:
199.000 in
Point Load 1:
358.2 lb
Point load X location 4:
238.000 in
Point Load 2:
386.4 lb
Point load X location 5:
N/A
Paint Load 3:
514.2 lb
Point load X location 6:
N/A
Point Watl 4:
542.3lb
Point load X location 7:
N/A
Point Wad 5:
662.31b
Point load X location 8:
N/A
Point Watl 6:
690.5lb
Point load Y location 1:
4.000 in
Point Load 7:
Point Wad 8:
723.1 lb
751.3lb
Point load Y location 2:
87.000 in
Total Weight: 4628.3 lb
Added Weight Isl
1. Double wall
Notes:
1. The actual weight is stamped on the unit nameplate.
2. The weight shown represents the typical unit operating weight for the configuration selected.
Esbo ated at a/- 109% of the nameplate weight. .
3. Add weight to the total unit weight.
4. Design Special weights are not displayed. Any weight added through COD (Custom Order Cason)
will not be accounted in the t/- 10%estimate
5. When 2 or more units are to be placed sitle by sitle, the distance between the units shouts be
ceased to 150%of theremended single unit clearance. The units should also be staggered
to reduce span deflection & assure proper diffusion of exhaust air.
PL 6, X3 PL8, X4
PL 3,X2 PL 5, X3 PL 7, X4
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 14 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
,& WARNING
& AVERTISSEMENT
A°. ADVERTENCIA
HAZARDOUS VOLTAGE!
TENSION DANGEREUSE!
iVOLTAJE PELIGROSO!
DISCONNECTALL ELECTRIC POWER
COURIER TOUTES LES TENSIONS ET
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS
OUVRIR LES SECTIONNEURSA DISTANCE,
INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUTAND TAG
PUIS SUIVRE LES PROCEDURES DE
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING.
VERROUILLAGE ET DES ETIQUETTES AVANT
ETIQUETADO ANTES DE PROCEDERAL
INSURETHATALLMOTOR
TOUTE INTERVENTION. VERIFIER QUE TORUS
SERVICIO. ASEGURESE DE QUE TODOS
CAPACRORB HAVE DISCHARGED
LES CONDENSATEURS DES MOTEURS SONT
LOS CAPACITORES DEL MOTOR HAYAN
STORED VOLTAGE. UNITS WITH
RECHARGES. DANS LE CAS D'UNRES
DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER
COMPORTANT DES ENTRAINEMENTSA
PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR
VITESSE VARAIBLE, BE REPORTER AUX
DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE.
INSTRUCTIONS DE L'ENTRAINEMENT POUR
CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS.
DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
NE PAS RESPECTER CES MESURES DE
EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY.
PRECAUTION PEUT ENTRAINER DES
INDICADO, RODER OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANTETRE
O SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION
IMPORTANT!
USE COPPER CONDUCTORS ONLYI
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUTAND
UNIT TERMINALS ARE NOT DESIGNED TO
START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS.
BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT.
ATTENTION
N'UTILISER QUE DES CONDUCTEURS EN
CUIVREI
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRES TYPES
DE CONDUCTEURS.
L'UTILISATION DE TOUTAUTRE CONDUCTEUR eA,NO ED
PELT ENDOMMAGER L'EQUIPEMENT. SEOnOR
PRECAUCION CONDENSI
SECTION
IUTILICE UNICAMENTE CONDUCTORES DE
COBREI
LASTERMINALES DE LA UNIDAD NO ESTAN \
DISENADAS PARAACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DANO AL
EQLIPO.
CONNECT STEAM OR CIRCURTAa C—U-1
AREA VICE PREFIX LOOCOgTTI CODE SHOWNATERION "T'WH�E15RL0 RED ELECTRIC HEKT UNIS 0V230V/90 HZ� �t MAIN UNIT CONTROL
INSIDE UNIT CONTROL BOX E NRB LY
a1M
HYDRONCHEAT 36ATeztt9
L �asis
S A' HANDLER SECTION ILtd Lz LS Ia tLz L3
CTION
SPLICE SPUCE
s EXTERNAL FIELD MOLINTED DEVICE
Note: I I _
All wiring and c,,Panama Shown dashed to be 1+) y I I a a supplied and installed by the customer in Tt
accordance with local electrical codes.
eS
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 15 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
ZE WARNING
0 AVERTISSEMENT
/K ADVERTENCIA
HAZARDOUS VOLTAGE!
TENSION DANGEREUSE!
iVOLTAJE PELIGROSO!
DISCONNECTALL ELECTRIC POWER
COUPER TOUTES LES TENSIONS ET
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS
OUVRIR LES SECTIONNEURSA DISTANCE,
INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG
PUIS SUIVRE LES PROCEDURES DE
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING.
VERROUILLAGE ET DES ETIQUETTES AVANT
ETIQUETADO ANTES DE PROCEDERAL
INSURETHATALLMOTOR
TOUTE INTERVENTION. VERIFIER QUE TOILS
SERVICIO. ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED
LES CONDENSATEURS DES MOTEURS SONT
LOS CAPACITORES DEL MOTOR HAVAN
STORED VOLTAGE. UNITS WITH
RECHARGES. DANS LE CAS D'UNITES
DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER
COMPORTANT DES ENTRAINEMENTSA
PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR
VITESSE VARAIBLE, SE REPORTER AUX
DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE.
INSTRUCTIONS DE L'ENTRAINEMENT POUR
CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS.
DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
NE PAS RESPECTER CES MESURES DE
EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY.
PRECAUTION PEUT ENTRAINER DES
INDICADO, PODRIA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANTETRE
O SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION
IMPORTANT!
USE COPPER CONDUCTORS ONLVI
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNITTERMINALS ARE NOT DESIGNED TO
START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS.
BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT.
ATTENTION
N'UTILISER QUE DES CONDUCTEURS EN
CUIVREI
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRESTYPES
DE CONDUCTEURS.
LUTILISATION DE TOUTAUTRE CONDUCTEUR
PEUT ENDOMMAGER L'EQUIPEMENT.
PRECAUCION
IUTILICE UNICAMENTE CONDUCTORES DE
COBREI
LASTERMINALES DE LA UNIDAD NO ESTAN
DISENADAS PARAACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DANO AL
EQUIPO.
DEVICE PREFIX LOCATION CODE
AREA
LOCATION
INSIDE UNIT CONTROL I-C
S
MR HANDLER SE -ON
nNOS—ON
Note:
All wiring and comp..... shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
F
22 (ET)
2s 1.051E
ND — dee —
CNo _ don — soo4. — (-) p10 VDC
— 500 —, — 500
— 1.1� IA091
r
I I
I
I I
eId
_
r
aa5
i
as, s
_ ------
'----}
'
r—
r—
r—
a
d dee
d
dne
j
J
—I
rr—
5 5e5
;]
jj
r-
.1
e
----
-r--- -1
I
I
I I I I I I
I
z2 lI �qE —495
FAILURE--l!
I I IL—s�Ovzoeo)N.—d,d
IAo)c®
D N..".a
J22
. _SSE J
ze (eos)
NNo — os J
E> s FA Rco
25 FAILUR
E ENc"
(—)
5w - J 5a, l o.,
—J-5a2—17 OVDC 28
— la (ADu)
J �5-5VD
.C— ssSJ — s oD zs
zd yCa
® leas — 1+)
d�-1)
IA12) 2]
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 16 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
NOTES:
a1 ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE
CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES.
a CUSTOMER CONNECTIONS- MAIN UNIT CONTROL (CIRCUIT #1) -ARE LOCATED IN THE
CONDENSER SECTION FOR 20 THRU 75 TON UNITS.
aSEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR
CONNECTION TO MAIN UNIT TERMINAL BLOCK (1TB1/4TB2) OR DISCONNECT
SWITCH (1SW4S15).
a4 WIRES TO THE OPTIONAL STEAM AND/OR HOT WATER HEAT VALVE ARE SUPPLIED WITH
THE UNIT. WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER.
aOPTIONAL51_57 REMOTE ZONE TEMP SENSOR IS USED FOR UNOCCUPIED HEAT/COOL
TEMP CONTROL SENSING.
a7 WHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED, REMOVE 5U58 INTERGRAL ZONE
TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2.
a8 WIRES USE SHI ELDED TWISTED PAIR WIRE.
aUSE SHI ELDED TWISTED PAIR WIRE. WRAP SHIELDS WITH TAPE TO PREVENT CONTACT
WITH GROUND.
10 REMOVE JUMPER (1TB4-1 5 & 1TB4-16) AND INSTALL HIGH DUCT TEMP T STAT/OR
FIELD SUPPLIED DEVICE.
11 REMOVE JUMPER (1TB4-17 & 1TB4-18) WHEN FIELD SUPPLIED
EXTERNALAUTO/STOP SWITCH (5S67) IS INSTALLED.
12 CHANGEOVER (5K87) AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING
GAS HEAT UNITS.
13 ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC.
14 OPTIONAL HEAT MODULE AUX. TEMP (5RT16) IS USED FOR MORNING WARM-UP
CONTROL ON UNITS WITH HEATING OPTION.
15 TERMINAL BLOCK 1TB17 AND ASSOCIATED WIRING REQUIRED WITH GBAS (1 U51)OPTION.
DEMAND LIMIT RELAY (5K89) TO BE PROVIDED BY CUSTOMER.
16 VENTILATION OVERRIDE MODE CONTACTS RATED 12MA@ 24VDC MINIMUM
(5K90 - 5K91 - 5K92 - 5K93 - 5K94) TO BE PROVIDED BY CUSTOMER.
17 WIRE NODES 533 & 534 REQUIRED WITH BASMETWORK COMM MODULE (1 U54) OPTION.
USE SHIELDED TWISTED PAIR WIRE.
18 FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE.
19 15A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 "A TRANSFORMER
WITH 20OV - 23OV - 460V OR 575V UNIT VOLTAGE.
20A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 KVA TRANSFORMER
WITH 380V OR 415V UNIT VOLTAGE.
21 CONTACTS RATED 12 MA@ 24VDC MINIMUM.
22 CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY.
29 REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDE AIR SENSOR
(3RT3) IS INSTALLED AND THE UNIT DOES NOT HAVE ECONOMIZER.
24 FIELD SUPPLIED AND INSTALLED OCCUPIEWUNOCCUPIED CONTACTS (5K86)
FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK (SU58).
25 GBAS 0-5V OPTION CONNECTIONS.
26 GBAS 0-10V OPTION CONNECTIONS.
27 FOR GBAS INPUTS All-AI4,"GBAS 0sV' REQUIRES 0-5V VDC
AND "GBAS 0-10V' REQUIRES 0-10VDC.
28 'ACTIVE DIAGNOSTICS (1305)"APPEAR8 WITH BOTH "GBAS 0-5W AND 'GBAS 0-1 OW.
29 SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES (F40, F41, F42).
30 SWITCH A53, LOCATED ON THE VFD, MUST BE SET TO "U" (OFF).
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 17 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
FUSE REPLACEMENT TABLE
CONDENSER FAN FUSE UNITVOLTAGE 200 230 380 415 460 575
1F1 THRU 1F6 CLASS RK5 TIME DELAY 25A 25A 15A 15A 15A 15A
CONTROL POWER FUSE
CONTROL(1T1) TRANSFORMER RATING
0.25
KVA
0.30
KVA
0.50
KVA
0.75
KVA
1.00
KVA
1.50
KVA
1F7
CLASS CC -TYPE
FNQ-R
20-30 TON
6.25A
6.25A
10A
40 TON
15A
20A
20A
50-60 TON
--
-
15A
--
20A
-
70-75 TON
-
-
--
15A
20A
ELECTRIC HEAT FUSE
4F19 THRU 4F36, 4F46, 47, 48
CLASS K5
BOA
COMPRESSOR PROTECTION FUSE
1F44&1F45
TYPE MTH
6A
TRANSFORMER CIRCUIT FUSE
1 1F72 THRU 1F74
TYPE FNQ-R
15A
VFD PROTECTION FUSES (CLASS'T' FUSES) OPTIONAL SUPPLY VFD 1 F57 - 1 F62, OPTIONAL EXHAUST / RETURN VFD 1 F63-1 F65
BELT DRIVE
MOTOR
20-130 UNITS
UNIT
VOLTAGE
FUSE
RATING
3HP
5HP
7.5 HP
10 HP
15 HP
20 HP
25 HP
30 HP
40 HP
50 HP
200V/60/3
600V
40A
60A
BOA
100A
150A
200A
225A
300A
350A
N/A
230V160/3
600V
30A
45A
70A
90A
125A
175A
200A
250A
300A
N/A
380V/50/3
600V
15A
30A
45A
50A
90A
100A
125A
150A
200A
N/A
415V/50/3
600V
15A
30A
45A
SOA
90A
100A
125A
150A
200A
N/A
460V/60/3
600V
15A
25A
35A
45A
60A
90A
100A
125A
150A
200A
575V/6013
600V
15A
15A
25A
35A
50A
70A
60A
100A
125A
175A
OPTIONAL
DIRECT DRIVE
MOTOR 20-59
UNITS
UNIT
VOLTAGE
FUSE
RATING
3HP
5HP
7.5 HP
10 HP 1K-1.6K
15 HP
RPM
15 HP
1.7K-2.4K
RPM
20 HP
25 HP
30 HP
20OV/60/3
600V
40A
60Atm
A
200A
225A
300A
230V/6013
600V
25A
45A5A
175A
200A
250A
460V/60/3
600V
15A
25AA
90A
100A
125A
575V/60/3
600V
15A
15AA
70A
BOA
100A
OPTIONAL
DIRECTMDIVE
MOTOR
60-89 TON
UNIT
VOLTAGE
FUSE
RATING
10HP
15 HP
1K-1.6K
RPM
15 HP
1.7K-2.4K
RPM
20HP
30 HP 30
1K-1.6K 1.7-2.4K
RPM
HP
RPM
40HP
50HP
200V/60/3
600V
125A
175A
150A
200A
300A
150A
350A
N/A
230Vf60/3
600V
95A
150A
125A
175A
250A
250A
300A
N/A
460V/60/3
600V
45A
70A
60A
I 90A
125A
125A
150A
200A
575V/60/3
600V
40A
60A
SOA
70A
125A
100A
125A
175A
CUSTOMER
CONNECTION
WIRE RANGE
NOTES:
UNITS WITH MAIN POWER
TERMINAL BLOCK (ALL VOLTAGES)
UNITS WITH MAIN POWER
DISCONNECT SWITCH (ALL VOLTAGES)
A. BLOCK SIZE& DISCONNECT SIZE
ARE
CALCULATED BY SELECTING THE
SIZE
GREATERTHAN OREQUALTO1.15 X
(SUM OF UNIT LOADS). SEE UNIT
LITERATURE FOR UNIT LOAD
VALUES.
BLOCKSIZE
WIRE QTY CONNECTORWIRERANGE
DISCONNECTSIZE
WIRE CITY
CONNECTOR WIRE RANGE
335 AMP
(1)
#6-350 MGM
1DOAMP
(1)
#14-1/0
760 AMP
(2)
#4-500 MCM
250 AMP
(1)
#4-350 k—il
840 AMP
(2)
#2-600 MCM
400AMP
(1)OR
#1-600 k—il OR
(2)
#1 -250 k—il
600AMP
(2)
250-500 MCM
1000 AMP
(3)
3/0-500k.11
OPTIONAL CONVENIENCE OUTLET FUSE 200V/60/3 230V/60/3 380V15013 415V/50/3 460V/60/3 575V/(K
1 F55 AND 1 F56 (TIME DELAY TYPE FNQ-R FUSE) 12A 10A WA N/A 5A I 4A
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 18 of 24
Others
0 TRANE"
Prepared For:
Sold To:
Submittal
Date: January 18, 2021
Customer P.O. Number:
Customer Project Number:
Job Number:
Job Name:
SLC - Morningside Library 25T Ipak Repl
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Oty Product
1 Commercial Rooftop Air Conditioning Units (25T Intellipak Repl)
Chris Cowling
Trane U.S. Inc.
6965 Vista Parkway North, Suite 11
West Palm Beach, FL 33411
Phone: (561) 683-1521
Cell: (561) 683-1521
Fax: (561) 697-8714
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Product performance and submittal data is valid for a period of 6 months
from the date of submittal generation. If six months or more has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. It is the
customer's responsibility to obtain such verification.
ELECTRONIC SHOP DRAWING REVIEW
By: Salas O'Brien Florida, Inc.
NO EXCEPTIONS TAKEN
Engineer's review is for general conformance with the design concept and
contract documents. Markings or comments shall not be construed as
relieving the Contracor from compliance with the project plans and
specifications, n r departures therefrom. The Contractor remain,
responsible for details and acc,racy, compliance with the Contract
Doc ents and intent, for confirming and coracting all quantities and
dime sions, for selecting appropriate fabrication processes, for techniques
of assembly, and for performance of work in a safe manner.
By: Joseph W. Detig, El 01/26/2021
J:IJOBS146158985121Submittal - 25T Ipak Unit - SLC Morningside Library RTU Rep/ 1-18-21.doc
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
Zt WARNING
HAZARDOUS VOLTAGE!
DISCONNECTALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
AND FOLLOW LOCKOUT AND TAG
PROCEDURES BEFORE SERVICING.
INSURE THATALL MOTOR
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
TO DRIVE INSTRUCTIONS FOR
CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
IN DEATH OR SERIOUS INJURY.
CAUTION
USE COPPER CONDUCTORS ONLVI
UNITTERMINALS ARE NOT DESIGNED TO
ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT.
ATTENTION
N'UTILISER QUE DES CONDUCTEURS EN
CUIVREI
�° AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS A DISTANCE,
PUIS SUIVRE LES PROCEDURES DE
VERROUILLAGE ET DES ETIQUETTES AVANT
TOUTE INTERVENTION. VERIFIER QUE TOILS
LES CONDENSATEURS DES MOTEURS SONT
RECHARGES. DANS LE CAS D'UNITES
COMPORTANT DES ENTRAINEMENTS A
VITESSE VARAIBLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAINEMENT POUR
DECHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRECAUTION PEUT ENTRAINER DES
BLESSURES GRAVES POUVANT ETRE
MORTELLES.
IMPORTANT!
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
START-UP PROCEDURE HAS
BEEN COMPLETED.
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRESTYPES
DE CONDUCTEURS.
LUTILISATION DE TOUTAUTRE CONDUCTEUR
PEUT ENDOMMAGER L'EQUIPEMENT.
PRECAUCION
IUTILICE UNICAMENTE CONDUCTORES DE
COBREI
LASTERMINALES DE LA UNIDAD NO ESTAN
DISENADAS PARAACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DANO AL
EQUIPO.
DEVICE PREFIX LOCATION CODE
AREA
LOCATION
INSIDE UNIT CONTROL ROC
S
MR HANDLER SE -ON
TINGSECTION
Note:
All wiring and comp..... shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
0° ADVERTENCIA
iVOLTAJE PELIGROSOI
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE V
ETIQUETADO ANTES DE PROCEDERAL
SERVICIO. ASEGURESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAVAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCION DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRIA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
MEIRGE Y 9%]
E%TERNALAUTO/STOP
STOP SWITCH
RESE5UPTIONo--1
TT
,0 2, it 21
orvE
EMP 3d
SENSOR
3
L LL_
zds dzd---------� � I
_ _ I
5us]�
a MOTE I---r-- ?_-T-,-
z dog ___r___L- 3 IS
J
s nsaR� r---, -
r - - -I- s
rr---T-----I-T-
rl----r- 19--1----�
rr---r- we 5r ze
,o I-r---� 38 21
d , 630 z2
I I � I I I
�
r-� REMore a r1----------------1---J oe
_1 zoErvsoRP �OrvEArvE�
d
r _ I s �
2tCOMMON _
HE�I-410- 35ODEP UCONTA6C111PTS 24
-dt3�
I 416� I—atz- 6M I - _
1 caoLe 7GN. suea�
I ED
SYS ON - - J13(
M.
SERVICE I. - 16� !�616--_� ]HEAT _ -
- - 0 COOL (- RE MANE
n IL - s3e t.z 1-I
II-- No tt - I-41s-- 9SYS ON HINTE
- J - 52 COMM 1*112 -610 L _ qa{ - - J21 lil MODULES
I 609� ate--4 1.SERVICE
dVAC 14 - L-aas -- Jz-zl-1
5U88 5UE9
REIAOTE PANEL a LR=�M E-E -EARTH J2-
WRH NSB JI GROUND 1
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 19 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
,& WARNING
0 AVERTISSEMENT
0 ADVERTENCIA
HAZARDOUS VOLTAGE!
TENSION DANGEREUSE!
iVOLTAJE PELIGROSO!
DISCONNECTALL ELECTRIC POWER
COUPER TOUTES LES TENSIONS ET
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS
OUVRIR LES SECTIONNEURSA DISTANCE,
INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG
PUIS SUIVRE LES PROCEDURES DE
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING.
VERROUILLAGE ET DES ETIQUETTES AVANT
ETIQUETADO ANTES DE PROCEDERAL
INSURETHATALLMOTOR
TOUTE INTERVENTION. VERIFIER QUE TOILS
SERVICIO. ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED
LES CONDENSATEURS DES MOTEURS SONT
LOS CAPACITORES DEL MOTOR HAVAN
STORED VOLTAGE. UNITS WITH
RECHARGES. DANS LE CAS D'UNITES
DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER
COMPORTANT DES ENTRAINEMENTSA
PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR
VITESSE VARAIBLE, SE REPORTER AUX
DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE.
INSTRUCTIONS DE L'ENTRAINEMENT POUR
CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS.
DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
NE PAS RESPECTER CES MESURES DE
EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY.
PRECAUTION PEUT ENTRAINER DES
INDICADO, PODRIA OCASIONAR LA MUEmE
BLESSURES GRAVES POUVANTETRE
O SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION
IMPORTANT!
USE COPPER CONDUCTORS ONLVI
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUTAND
UNITTERMINALSARE NOT DESIGNED TO
START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS.
BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT
ATTENTION
N'UTILISER QUE DES CONDUCTEURS EN
CUIVREI
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRESTYPES
DE CONDUCTEURS.
LUTILISATION DE TOUTAUTRE CONDUCTEUR
PEUT ENDOMMAGER L'EQUIPEMENT.
PRECAUCION
IUTILICE UNICAMENTE CONDUCTORES DE
COBREI
LASTERMINALES DE LA UNIDAD NO ESTAN
DISENADAS PARA ACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DANO AL
EQUIPO.
DEVICE PREFIX LOCATION CODE
AREA
LOCATION
INSIDE UNDOW—ROLBOx
S
MR HXNDLER SE -ON
TINGSECTION
Note:
All wiring and comp..... shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
—55Sv VERRI ro�
ovERRIDENA'TOLMTMODE CFLf�
-W""NViEIIIDE
LNQ �� 1LJr Jeln - 5� L =JL—
I I I I r � I I is io
I I I I I I I I I I
I I I I I as ,s I I I I I
_1_ 1 aea ass iz ____J I I
1 1_ z 4so ass is
a sza 5za is — 1
--------------�— a za 1. u-------------
- ___________ J
5 szs E3a t6_____________
r�-
1------------r s US.1n
e sas— — — — — — — — ----��
I I I I I I I I I I I I
I I I I I I I I I I I I
I
��1 azli 1 441 4� 1 1
I 1 I I 1 1 1 Iz
1 L eon J tfi 1 1 23 F—F L�
1� ���� ry Io 1 L JI 1 FS IZ1
M.. VB NT c� I ouIONAL tz sl<e� L �"{ f`—
Al.2' ooO =Acrs 1 wx tfi 1
I
1 sErvsoR
EEc oAc-
I
re
I � wMoroM 4
Is
1 POTrv.roMeTER 1 ~r
WHTRACER a
I � _ 569 I 1 COMMUNICATION. ,T
asa_
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 20 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
ZE WARNING
0 AVERTISSEMENT
/K ADVERTENCIA
HAZARDOUS VOLTAGE!
TENSION DANGEREUSE!
iVOLTAJE PELIGROSO!
DISCONNECTALL ELECTRIC POWER
COUPER TOUTES LES TENSIONS ET
DESCONECTE TODA LA ENERGIA ELECTRICA,
INCLUDING REMOTE DISCONNECTS
OUVRIR LES SECTIONNEURSA DISTANCE,
INCLUSO LAS DESCONEXIONES REMOTAS Y
AND FOLLOW LOCK OUT AND TAG
PUIS SUIVRE LES PROCEDURES DE
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
PROCEDURES BEFORE SERVICING.
VERROUILLAGE ET DES ETIQUETTES AVANT
ETIQUETADO ANTES DE PROCEDERAL
INSURETHATALLMOTOR
TOUTE INTERVENTION. VERIFIER QUE TOILS
SERVICIO. ASEGURESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED
LES CONDENSATEURS DES MOTEURS SONT
LOS CAPACITORES DEL MOTOR HAVAN
STORED VOLTAGE. UNITS WITH
RECHARGES. DANS LE CAS D'UNITES
DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER
COMPORTANT DES ENTRAINEMENTSA
PARA LAS UNIDADES CON EJE DE
TO DRIVE INSTRUCTIONS FOR
VITESSE VARAIBLE, SE REPORTER AUX
DIRECCION DE VELOCIDAD VARIABLE,
CAPACITOR DISCHARGE.
INSTRUCTIONS DE L'ENTRAINEMENT POUR
CONSULTE LAS INSTRUCCIONES PARA LA
DECHARGER LES CONDENSATEURS.
DESCARGA DEL CONDENSADOR.
FAILURE TO DO THE ABOVE
BEFORE SERVICING COULD RESULT
NE PAS RESPECTER CES MESURES DE
EL NO REALIZAR LO ANTERIORMENTE
IN DEATH OR SERIOUS INJURY.
PRECAUTION PEUT ENTRAINER DES
INDICADO, PODRIA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANTETRE
O SERIAS LESIONES PERSONALES.
MORTELLES.
CAUTION
IMPORTANT!
USE COPPER CONDUCTORS ONLVI
DO NOT ENERGIZE UNIT
UNTIL CHECK-OUT AND
UNITTERMINALS ARE NOT DESIGNED TO
START-UP PROCEDURE HAS
ACCEPT OTHER TYPES OF CONDUCTORS.
BEEN COMPLETED.
FAILURE TO DO SO MAY CAUSE DAMAGE TO
THE EQUIPMENT.
ATTENTION
N'UTILISER QUE DES CONDUCTEURS EN
CUIVREI
LES BORNES DE L'UNITE NE SONT PAS
CONCUES POUR RECEVOIR D'AUTRESTYPES
DE CONDUCTEURS.
LUTILISATION DE TOUTAUTRE CONDUCTEUR
PEUT ENDOMMAGER L'EQUIPEMENT.
PRECAUCION
IUTILICE UNICAMENTE CONDUCTORES DE
COBREI
LASTERMINALES DE LA UNIDAD NO ESTAN
DISENADAS PARAACEPTAR OTROS TIPOS DE
CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DANO AL
EQUIPO.
DEVICE PREFIX LOCATION CODE
AREA
LOCATION
INSIDE UNIT CONTROL BOX
S
MR HXNDLER SE -ON
TINGSECTION
Note:
All wiring and comp..... shown dashed to be
supplied and installed by the customer in
accordance with local electrical codes.
NO — 614 —
HUMIDIFICATION NC-615—�
OM — 616 —
13 ALARM OD
OUTPUT ;OM-
22 124 VAC MAXI NC — 450 —
18 NO-445--�
AV BOX
RE —
vac MA% .OM— 446
22 L NC —
I
I I I
1TB16
50] 445 12 — J
2 508 446 13 — = J
— — — 3 5U9 447 14 — J
4 541 448 15 — =
5 542 a49 16
---- 6 543 5017 -- —
! ] 544 614 18 — —1
--- 8 595 61519 --- III
r---- 9 546 616 20 ----J
I 10 812 21
r — 11 613 22
! I I I I
I I I I I
613 SPACE
612—1+11'UMIDITYSENSOR
—548 —NC HEAT MODE RELAY OUTPUT
—545 —CON (HYDRONIC HEAT OR MODULATING 22
— 544 — NO GAS HEAT)
I I I
--543 —NC VO 22
542 — COM RELAY
— — 541 — NO OUTPUT
I
— NC DIR_ 22
COM FILTER 25
I
— (-) 0-10 VDc
(AO1) 26
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 21 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
DANFOSS VARIABLE FREQUENCY DRIVE
PROGRAMMING PARAMETERS
MENU
PARAMETER
DESCRIPTION
SETTING
SET ONLY FOR
1-21
MOTOR POWER
APPLICATIONS USING
3HP HIGH EFFICIENCY
MOTORS
SET ONLY FOR
LOAD/MOTOR
1-22
MOTOR VOLTAGE
200/23OV 60HZ
380/415V 50HZ
APPLICATIONS
1-24
MOTOR CURRENT
SET BASED ON
MOTOR NAMEPLATE
1-25
MOTOR NOMINAL SPEED
1800 RPM
1-73
FLYING START
ENABLED
BRAKES
2-01
DC BRAKE CURRENT
0%
3-15
REFERENCE 1 SOURCE
ANALOG INPUT 53
REFERENCE/
RAMPS
3-41
RAMP I RAMP UP TIME
30SECONDS
3-42
RAMP I RAMP DOWNTIME
30SECONDS
LIMITS/
4-12
MOTOR SPEED LOW LIMIT
22HZ
WARNINGS
4-18
CURRENT LIMIT
100%RATED CURRENT
DIGITAL 5-4010]
FUNCTION RELAY 1
NO ALARM
IN/OUT 5-40p]
FUNCTION RELAY
RUNNING
14-01
SWITCHING FREQUENCY
4.5KHZ
1412
FUNCTION AT MAINS
DERATE
SPECIAL
IMBALANCE
FUNCTIONS
14-20
RESET MODE
AUTOMATIC RESET X3
14-60
FUNCTION AT OVER
DERATE
TEMPERATURE
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 22 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Accessory - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al Qty: 1 Tag(s): 25T Ipak
5/16"
BAYSEN119-ZONE SENSOR
PROGRAMMABLE SENSOR
TEST
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 23 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family - Commercial Rooftop Air Conditioning Units (Midrange)
Item
Tag(s)
Ot
Descri tion
I Model Number
Al
25T Ipak
1
20-75 Ton Packaged Industrial
Rooftop S
SAHLF2540-00C5DD7E11 B'W*-H'
BA--6T-M8--` ----- `
Field Installed Option Description Part/Ordering Number
Programmable zone sensor
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 24 of 24
Others
Table Of Contents
Product Summary
Commercial Rooftop Air Conditioning Units (Midrange) (Item Al)
TagData..................................................................................................................................................3
ProductData............................................................................................................................................ 3
PerformanceData.................................................................................................................................... 4
MechanicalSpecifications........................................................................................................................ 5
UnitDimensions....................................................................................................................................... 9
FanCurve.............................................................................................................................................. 12
Weight, Clearance & Rigging Diagram................................................................................................... 13
Accessory.............................................................................................................................................. 15
Field Installed Options - Part/Order Number Summary
Commercial Rooftop Air Conditioning Units (Midrange)......................................................................... 24
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Tag Data - Commercial Rooftop Air Conditioning Units (Midrange) (Qtv: 1)
Item
Ta s
Oty
I Description
Model Number
Al
25T Ipak
1 1
20-75 Ton Packaged Industrial
Rooftop S
SAHLF2540-00C5DD7E11 B`W`-H`BA--6T-M
8- `----`
Product Data - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al City: 1 Tag(s): 25T Ipak
High efficiency unit
DX Cooling only
R-410A refrigerant
25 Ton unit
460 Volt-60 Hertz-3 Phase
0-100 % Economizer (Motorized Damper)
Sloped Stainless Steel Drain Pan
Grease Lines / Filter Gauge
2.00" [51 mm] internal Spring isolators
MERV 8 High efficiency throwaway filters (1 set)
15 HP FC Fan
VAV (DTC) with supply VFD & bypass
Programmable zone sensor (Fld)
Low ambient damper(s) control
cULus
Unit disconnect switch with high fault SCCR (65k SCR rating)
Motors with internal shaft grounding ring
Hinged access doors
BACnet communication interface module
0-10 volt Generic B.A.S Module
Professionally -applied condenser coil coating
Factory Start-up and 1 s' year Parts, Labor & Refrigerant warranty
2nd-5th year Whole Unit Parts warranty
Excludes: Curb or Curb adapter (re -use existing), Controls wiring or integration labor, Unit casing coating (cond coil
only), Smoke Detectors, Final Filters, Labor warranty, Anything not listed above.
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 24
Others
SLC - Morningside Library 25T Ipak Rep] January 18, 2021
Performance Data - Commercial Rooftop Air Conditioning Units (Midrange)
Tags
25T I ak
Supply airflow cfm
10000
Cooling entering DB F
80.00
Cooling entering WB F
67.00
Ambient DB F
95.00
Cooling leaving coil DB F
57.50
Cooling leaving coil WB F
56.47
Cooling leaving unit DB F
60.62
Cooling leaving unit WB F
57.66
Gross total capacity MBh
331.32
Gross sensible capacity MBh
251.00
Gross latent capacity MBh
80.32
Net total capacity MBh
297.14
Net sensible capacity MBh
216.81
Fan motor heat MBh
34.18
Evaporator face area (sq ft
20.30
Supply duct static pressure in H2O
2.000
Return duct static pressure in H2O
0.500
Component S.P. drop in H2O
0.940
Total static pressure in H2O
3.440
Supply motor bhp (bhp)
11.89
Supply fan rpm (rpm)
1291
Supply fan efficiency %
45.53
System power kW
35.78
EER @ AHRI (EER)
11.0
IEER @ AHRI (EER)
14.5
Minimum circuit am acit A
71.25
Maximum overcurrent protection (A)
90.00
Minimum disconnect switch size (A)
75.00
Recommended dual element A
80.00
Compressor 1 count Each
1.00
Compressor 1 RLA A
22.20
Compressor 2 count Each
1.00
Compressor 2 RLA A
19.10
Supply fan motor FLA A
18.00
Supply motor count
1
Supply fan count Each
2.00
Condenser fan FLA A
5.40
Other FLA A
1.00
R-410A refrigerant charge - circuit 1 Ib
31.3
Installed point load 1 Ib
358.2
Installed point load 2 Ib
386.4
Installed point load 3 Ib
514.2
Installed point load 4 Ib
542.3
Installed point load 5 Ib
662.3
Installed point load 6 Ib
690.5
Installed point load 7 Ib
723.1
Installed point load 8 Ib
751.3
Total installed weight Ib
4628.3
Note: Unit performance based on 10,000 CFM at 80/67 Entering Air Temp and 2.5" ESP. Performance can be re -run at
different conditions if desired.
FLD = Furnished by Trane U. S. Inc. / Installed by Equipment Submittal Page 4 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Midrange)
Item: Al City: 1 Tag(s): 25T Ipak
General - R410A
Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled
and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be
available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam
heating. Filters, outside air system, exhaust air system, optional non -fused disconnect switches and all operating and
safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling
capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and
indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to
control panel doors.
Casing
Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable
enough to withstand a minimum of 672 hours consecutive salt spray application in accordance with standard ASTM
B117. Screws shall be coated with zinc -plus -zinc chromate. Heavy gauge steel hinged access panels with tiebacks to
secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air
fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and
gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction
hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors
and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2" Tuf-Skin
fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members, formed recess and
curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown
points.
Hinged Access Doors
Hinged access doors shall provide easy access to supply fan, filters, exhaust/return fan, and heating section.These
access doors shall feature double wall construction with dual density insulation sandwiched between heavy gauge
galvanized steel panels for strength and durability
Air -Cooled Condenser Coil - R410A
Condenser coils shall have all Aluminum Microchannel coils. All coils shall be leak tested at the factory to ensure
pressure integrity. The condenser coil is pressure tested to 650psig Subcooling circuit(s) shall be provided as standard.
Condenser Fans and Motors
All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with aluminum blades and zinc
plated steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built-in
current and thermal overload protection and weathertight slingers over motor bearings.
Low Ambient
Low ambient dampers shall be provided on condenser fan to allow the unit.
Evaporator Coil - R410A
Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of
configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested.
Sloped Stainless Steel Drain Pan
The double sloping stainless steel drain pan shall promote runoff
of standingwater from condensation inside the unit.Two drain pipes shall be installed through the base channel on each
side of the unit.The evaporator drain pan shall be constructed of 14 gauge stainless steel. On units 40 tons and larger,
the intermediate drain pan shall be constructed of 16 gauge stainless steel.This shall provide protection in corrosive
environments
Compressors - R410A
The Trane Scroll compressor shall be industrial grade, direct drive 3600 RPM maximum speed scroll type. The motor
shall be suction gas-cooled hermetic design. Compressor shall have centrifugal oil pump with dirt separator, oil sight
glass, and oil charging valve. Compressor shall also be provided with thermostatic motor winding temperature control to
protect against excessive motor temperatures resulting from over -/under -voltage or loss of charge, high and low
pressure cutouts, and reset relay.
High Efficiency Unit
High efficiency unit shall meet ASHRAE 189.1-2011 and CEE Tier 2 Commercial Unitary AC and HP Specification for
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 5 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
utility rebate requirements.
Phase Monitor
Shall protect 3-phase equipment from phase loss, phase reversal, and low voltage. Any fault condition shall produce a
Failure Indicator LED, and send the unit into an emergency stop condition. cULus approved. (Standard on 20-75T units)
Supply Fan
Supply fan motors shall be either open drip -proof or enclosed fan cooled. All supply fans shall be dynamically balanced
in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy
Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992
(EPACT).
Forward Curved Supply Fan
Supply fans shall have two double -inlet, forward -curved fans mounted on a common shaft with fixed sheave drive. Fans
shall be factory -tested to reach rated rpm before the fan shaft passes through first critical speed. Fan shaft shall be
mounted on two grease lubricated ball bearings designed for 200,000 hours average life. Optional extended grease
lines shall allow greasing of bearings from unit filter section. Fan motor and fan assembly shall be mounted on common
base to allow consistent belt tension with no relative motion between fan and motor shafts. Entire assembly shall be
completely isolated from unit and fan board by double deflection rubber -in -shear isolators, or by optional 2" deflection
spring isolation.
Variable Frequency Drive
Unit shall include factory -installed and tested variable frequency drivels] (VFD) to provide motor speed modulation. The
VFD shall receive a 0-10VDC speed signal from the unit controller. The drive will respond to the signal by accelerating
or decelerating to maintain the controlling set point (duct static, space pressure, etc). VFD shall also include the
following features:
1. Designed, constructed, and tested in accordance with NEMA ICS, NFPA, and IEC standards and housed in a plastic
IP20 enclosure.
2. DC link reactors on both the positive and negative rails of the DC bus equal to 3 % impedance to minimize power line
harmonics.
3. Full rated output current continuously - 110 % of rated current for 60 seconds and 160 % of rated current for up to 0.5
second while starting.
4. Isolation between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected
electronic control equipment
from damage caused by voltage spikes, current surges, and ground loop currents.
5. Audible noise reduction through automatic adjustment of the carrier frequency and frequency avoidance.
6. Rated at 40C with a standard operating range of -10 to 50C (14 to 124F) ambient temperatures and 0 to 95 % relative
humidity
7. Self -diagnostics and motor protections such as: cULus listed overload, phase loss, and internal thermal overload
8. Off/Stop and Auto/Start selector switches to start and stop the AC Drive and determine the speed reference
a. On units with bypass, an AC Drive/Off/Bypass hand selector switch shall be provided in the unit control box
b. In DRIVE mode speed reference shall be provided by a 0-10 VDC analog input
9. A keypad interface which shall be programmable by language and feature multiple lines for easy reading.
10. Controlled and/or accessible points such as AC Drive Start/Stop, speed reference, and fault diagnostics.
11. Meter points such as motor power in HP, motor power in kW, motor kW-hr, motor current, motor voltage, hours run,
DC link voltage, thermal load
on motor, Thermal load on AC Drive and Heatsink temperature.
12. Troubleshooting features such as:
a. AC Drive memory storage of the last 10 faults and related operational data
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 6 of 24
Others
SLC - Morningside Library 25T Ipak Repl January 18, 2021
b. Four simultaneous displays: frequency or speed, run time, output amps and output power
c. Keypad which shall display: Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP,
Motor kW, kW
13. Coated circuit boards for protection against corrosive environments
14. Field readable BACnet points to allow for communication of stauts, setpoints and diagnostics to the BAS.
Bypass control
Shall provide full nominal airflow in the event of drive failure.
Internal Shaft Grounding Ring
Motors shall have internal bearing protection for use with VFDs.
Extended Grease Lines
Lines shall be provided to allow greasing of supply and exhaust/return fan bearings through he filter access door.
Two-inch Spring Isolators
Supply and Exhaust/Return fan (if applicable) assemblies shall be isolated with two-inch nominal deflection to reduce
transmission of vibrations
0-100 percent modulating economizer
Operated through the primary temperature controls to automatically utilize OA for "free" cooling. Automatically
modulated return and CA dampers shall maintain proper temperature in the conditioned space. Economizer shall be
equipped with an automatic lockout when the outdoor high ambient temperature is too high for proper cooling. Minimum
position control shall be standard and adjustable at the Human Interface Panel or with a remote potentiometer or
through the building management system. A spring return motor shall ensure closure of CA dampers during unit
shutdown or power interruption. Mechanical cooling shall be available to aid the economizer mode at any ambient. Low
leak economizer dampers shall be standard with a leakage rate of 2.5 percent of nominal airflow (400 CFM/ton) at 1" wg.
static pressure.
Economizer Control with Dry Bulb
An outdoor temperature sensor shall be included for comparing the outdoor dry bulb temperature to a locally adjustable
temperature setpoint. The setpoint shall be programmed at the human interface, or remote human interface, to
determine if outdoor air temperature is suitable for economizer operation.
High efficiency throwaway, MERV 8
Shall be two-inch high efficiency MERV 8 media filters with average dust spot efficiency of 25-35 percent and an
average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52-76.
Differential Pressure Gauge
A factory -installed, dial -type, differential pressure gauge shall be piped to both sides of the filter to indicate status.
Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of -20OF to 120°F. Gauge shall be
flush -mounted with casing outer wall. Filter sections consisting of pre- and post -filters shall have a gauge for each.
Unit Controller
DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to
control CV or VAV applications. The controls shall be factory -installed and mounted in the main control panel. All
factory -installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface
Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full
adjustment and display of control data functions. The unit controls shall be used as a stand-alone controller, or as part of
a building management system involving multiple units.
1
The unit shall be equipped with a complete microprocessor control system. This system shall consist of temperature and
pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted Humaninterface
Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors
shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not
dependent on communications with an on -site PC or a Building Management Network. The microprocessors shall be
equipped with on -board diagnostics, indicating that all hardware, software and interconnecting wiring are
in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from
affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field
wiring to the 1/0 boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring
FLD = Furnished by Trane U. S. Inc. / Installed by Equipment Submittal Page 7 of 24
Others
SLC - Morningside Library 25T Ipak Rep] January 18, 2021
no battery or capacitive backup, while maintaining all data.
2
Zone sensors shall be available in several combinations with selectable features depending on sensor.
3
The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall
be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display (LCD) with blue characters on a
ray/green background which provides high visibility and ease of interface. The display format shall be in clear English.
Two or three digit coded displays are not acceptable.
4
The keypad shall be equipped with 16 individual touch -sensitive membrane key switches. The switches shall be divided
into four separate sections and be password protected from change by unauthorized personnel. The six main menus
shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE.
BACnet Communication Interface Module
Option shall provide control and monitoring of the rooftop by Tracer SC or a 3rd party building management system
utilizing BACnet protocol.
Unit Interrupt Rating (High Fault Short Circuit Current Rating-SCCR)
An optional 65,000 Amp rating (480V) and 25,000 Amp rating (600V) shall be applied to the unit enclosure using a
non -fused circuit breaker for disconnect switch purposes. Fan motors, compressors, and electric heat circuits shall be
included with protective devices that will provide the elevated level of fault protection. The unit shall be marked with
approved cULus markings and will adhere to cULus regulations.
BAYSENS119 Programmable Zone Temperature Sensor Configured as a Variable Air Volume Unit
The electronic programmable sensor shall be Auto or Manual changeover with seven day programming. Programmable
sensor shall have System Off, Auto and Service LCD indicators as standard. Night setback sensor shall have up to four
programs per day which can be individually configured to occupied or unoccupied.
Certified AHRI Performance
Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air -Conditioning,
Heating & Refrigeration Institute (AHRI) Certification Program and display the AHRI Certified® mark as a visual
confirmation of conformance to the certification sections of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR
Part 431 pertaining to Commercial Warm Air Furnaces. The applications in this catalog specifically excluded from the
AHRI certification program are:
-Ventilation modes
-Heat Recovery.
-Units larger than nominal 63 tons in Cooling
-Evaporative Condensers
FLD = Fumished by Trane U.S. Inc. / Installed by Equipment Submittal Page 8 of 24
Others