HomeMy WebLinkAboutGas , 250 gallon max aboveground hold down detal7/32, 709 GALV. CABLE 5600# BREAKING STRENGTH W/(2)HDG CLAMPS TO ANCHOR (PULLED TIGHT) CABLE SHALL BE COATED, SLEEVED OR HAVE 1 LAYER 30# FELT AGAINST TANK 250 GALLON LP GAS TANK 7/16" GALV. CABLE W/ (2)HDG CLAMPS TO ANCHOR (PULLED TIGHT) 4"X8"X12" SOLID CMU BLOCK EA. LEG HELICAL ANCHORS 5/8'X40" SINGLE 6" HELIX HELICAL ANCHOR NOTE: 2 PAIRS 730#/ANCHOR 250 GALLON MAX ABOVEGROUND HOLD DOWN DETAIL *- No 40111 = :ry - a • L - �3 STATE OF00 ; lu 2021-03-30 GENERAL NOTES: 1. HELICAL ANCHORS SHALL HAVE A PULL—OUT CAPACITY AS SHOWN. ANCHORS SHALL BE INSTALLED PER ANCHOR MANUFACTURER TO ACHIEVE STATED LOAD CAPACITY. CAPACITY VARIES WITH SOIL TYPE. VERIFY ANCHOR CAPACITY WITH SOIL TYPE ENCOUNTERED. 2. CHECK FOR UNDERGROUND UTILITIES PRIOR TO ANCHOR INSTALLATION 3. LOCATION OF TANK RELATIVE TO ADJACENT STRUCTURES AND FEATURES ARE DEPENDENT UPON LOCAL CODES AND IS THE RESPONSIBILITY OF OTHERS. 4. THE TANK AS SHOWN HAS BEEN DESIGNED TO PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT DURING THE BASE FLOOD EVENT 5. WIND LOAD DESIGN CRITERIA 160 MPH; EXPOSURE "D", GCpi N/A; Cf = 0.6 COMO OIL AND PROPANE LOWERY 4901 GROVERS ROAD FORT PIERCE, FL ® COPYRIGHT 2018 — FARLEY ENGINEERING, LLC FARLEY ENGINEERING LLC Consulting Engineer #40111 — CA28108 8800 N. U.S. #1, Suite #2 , Sebastian, Florida 32958 (772) 589.6229 (772) 589.2296 fax