HomeMy WebLinkAboutGas , 250 gallon max aboveground hold down detal7/32, 709 GALV.
CABLE 5600#
BREAKING STRENGTH
W/(2)HDG CLAMPS TO
ANCHOR (PULLED
TIGHT) CABLE SHALL
BE COATED, SLEEVED
OR HAVE 1 LAYER
30# FELT AGAINST
TANK
250
GALLON LP
GAS TANK
7/16" GALV. CABLE
W/ (2)HDG CLAMPS
TO ANCHOR (PULLED
TIGHT)
4"X8"X12" SOLID
CMU BLOCK EA. LEG
HELICAL ANCHORS
5/8'X40" SINGLE 6" HELIX
HELICAL ANCHOR NOTE:
2 PAIRS 730#/ANCHOR
250 GALLON MAX ABOVEGROUND HOLD DOWN DETAIL
*- No 40111
=
:ry -
a • L -
�3 STATE OF00
; lu
2021-03-30
GENERAL NOTES:
1. HELICAL ANCHORS SHALL HAVE A PULL—OUT CAPACITY AS SHOWN. ANCHORS SHALL BE
INSTALLED PER ANCHOR MANUFACTURER TO ACHIEVE STATED LOAD CAPACITY. CAPACITY VARIES
WITH SOIL TYPE. VERIFY ANCHOR CAPACITY WITH SOIL TYPE ENCOUNTERED.
2. CHECK FOR UNDERGROUND UTILITIES PRIOR TO ANCHOR INSTALLATION
3. LOCATION OF TANK RELATIVE TO ADJACENT STRUCTURES AND FEATURES ARE DEPENDENT
UPON LOCAL CODES AND IS THE RESPONSIBILITY OF OTHERS.
4. THE TANK AS SHOWN HAS BEEN DESIGNED TO PREVENT FLOTATION, COLLAPSE, OR LATERAL
MOVEMENT DURING THE BASE FLOOD EVENT
5. WIND LOAD DESIGN CRITERIA
160 MPH; EXPOSURE "D", GCpi N/A; Cf = 0.6
COMO OIL AND PROPANE
LOWERY
4901 GROVERS ROAD
FORT PIERCE, FL
® COPYRIGHT 2018 — FARLEY ENGINEERING, LLC
FARLEY ENGINEERING LLC
Consulting Engineer #40111 — CA28108
8800 N. U.S. #1, Suite #2 , Sebastian, Florida 32958
(772) 589.6229 (772) 589.2296 fax