HomeMy WebLinkAboutProject Information- wrightsoft® Project Summary Entire House QUICK CA(CS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772 Fax 772.46M796 Email: For. DIFRANCESCO RESIDENCE, TREFELNER CONSTRUCTION HICKORY DRIVE, FORT PIERCE, FL 34982 Notes: Job: Date: JAN. 11, 2021 By: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Structure 20377 Btuh Ducts 4609 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 24985 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Area Heating!768, Co 1768 (ft� Volume (ft� 199581 19958 Air changes/hour 0.38� 0.20 Equiv. AVF (cfm) 126 67 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 7.3 kW 24985 Btuh 23 OF 980 cfm O.039 cfm/Btuh 1.00 in H2O Sensible Cooling Equipment Load Sizing Structure 15975 Btuh Ducts 6482 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturers data n Ratelswing multiplier 0.95 Equipment sensible load 21334 Btuh Latent Cooling Equipment Load Sizing Structure 2779 Btuh Ducts 1718 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4497 Btuh Equipment Total Load (Sen+Lat) 25832 Btuh Req. total capacity at 0.70 SHR 2.5 ton Cooling Equipment Summary Make Trane Trade TRANE Cond 4TTR4031L1 Coil TEM6AOC36H31++TDR AH R I ref 7567544 Efficiency 13.0 EER, 16 SEER Sensible cooling 20580 Btuh Latent cooling 8820 Btuh Total cooling 29400 Btuh Actual air flow 980 cfm Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - wrilgilstscWt- 2021-Jan-1109:25:08 �� •"""•"' �•"°^��^�-^ Right-Suiteral Universal 2021 21.0.02 RSU08101 Page 1 ..mnets\Wrightsoft HVAC\DIFRANCESCO RESIDENCE.rup CaIc=MJ8 Front Doorfaces: E -�- wrightsoft' Right,J@iWorksheet Job: Entire House Date: JAN. 11, 2021 QUICK CALCS, INC. By. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fau 772-466-6796 Ernail: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area Entire House 172.0 ft 11.3 ft 1768.0 ft2 BEDROOM 3 26.0 ft 9.3 ft heat/cool 1.0 x 176.0 ft 176.0 ft2 Ty Construction number U-value (Btuh/ft2--°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W 13A-40cs 2 glazing, clr low-e 2 glazing, cir low.(L___ 13AAocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazinq, clr lower 13A-0ocs 2 glazing, clr low-e - 2 glazing, cir low-e 2 glazing, clr low-e 2_glazinq, dr low a 16A-30md _22A_tph 0.143 0.320 -- __. _ 0,320 0.143 0.320 0.320 0.320 0.143 0.320 0:320 0.143 0.320 0.320 0.320 n n n a a a e_ s s -s_ w w w _ w �� -__ 4.00 8.96 _ - 8.96 4.00 8.96 8.96 _ 8.96 i 4.00 8.96 _ _8.96.' 1 4.00 8.96 8.96 _ 8_96 _�0;90 38.02 2.19 9.41 - 9.41 2.19 24.75 25.20 �25.20 2.19 9.41 2.19 23.95 24.75 25.20 -�2,24 0.00 316 20 15 587 30 16 24 281 0 _ 0 517 2 1 1 1126 179 134 615 188 0 0 f 0 0 0 0 0 0 - `0 0 0 0 115 0 0 0 _- 0 0 0 __ 0 461 0 387 0 134 0 989 0 0 ._ 0 0 0 _ 0 - 252 0 211 0 371 0 0. W -� fl--G 2070 269 143 215 1122 54 2002 81 269 430 1131 743 403 605 613 56 1094 216 743 1209 3960 0 F--G ��-��--_CGGG_ w 316 6 587 9 30 48 280 6 500 1 2 2 _ 130 0 112 0 15 0 ..Zglazmg,_clrlow_e_ VN13AAocs 97 0 1 0 _ 26 F 0.032 - 1.358 _ 1768 1768 176.8 _172 __1584 6540 ___ 176 176 6 c)AED ecursion 128 64 Envelope loss/gain 16487 12128 2263 1435 12 a) Infiltration b) Room ventilation 3890 0 1097 0 521 0 147 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 2750 0 0 0 Subtotal Qines 6 to 13) 20377 15975 2784 1581 14 15 Less e)demal load Less transfer Redistribution Subtotal Duct loads 230/6 41% 0 0 0 20377 4609 0 0 0 15975 6482 23% 41% 0 0 118 2902 656 0 0 59 1641 666 Total room load Air required (cm) 24985 980 22457 980 3558 140 2307 101 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -:W 2021-Jan-11 09:25:08 AaeA Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...meets\Wrightsoft WAC\D I FRANC ESCO RESIDENCE.rup Calc=MJB Front Doorfaces: E wrightsoft° Right-.10 Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772.466-6796 Email: QUICKCALCS@AOL.COM Job: Date: JAN.11, 2021 By: 1 2 3 4 5 Room name =ed wall Room height Room dimensions Room area CLST 3 2-0 ft 9.3 ft heat/000l 2.0 x 10.0 ft 20.0 f12 BATH 2 6.0 ft 9.3 ft heat/cool 10.0 x 6.0 ft 60.0 ftz Ty Construction number U-value (Btuh/ftz °F) Or HTM (Btuh/ft� Area or perimeter (ft) Load (Btuh) Area (ftj or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6- 2 blazing, 9 9 2�j �aznS clr low-e g g _ 0.143 0.3 0 - -- n n - 4.00 8.96 2.19 9.41 0 0 0 0 0 0_ 0 0 0 0 0 0 0 0 0 0- 0 0. 0 0 0 0. 0 0 -- 11N 13A flocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazin clr low-e 13A-4ocs - 2'glazing, clr low-e .2.glazing, clrlow_e�__- 23A-0acs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e_ 0.143 0.320 0.320 0 320 0.143 0.320 _.._...•_0.320 0.320 0.320 0.320 0.320 a a a e_ s s s_ w w w w 4.00 8.96 8.96 8.96 i 4.00 .8.96 , a:96 4.96 8.96 8.96 8.96, 2.19 24.75 25.20 25.20 - 2.19 9.41 - 9.4.1 2.96 23.96 24.75 25_20 0 0 0 0 0 0 0 0 0 0 0 0 - 0 0 0 0. 0 0 0 0 -- - 0 0 0 0- 50 6. 0 0 0 0 0 ~ 0 0 0 0 199 54 ---0. 0 0 0 0 _ ._ 0 0 0 0 109 58 -,--._A 0 0 0 0 _T W 0 0- _,.-____0 19 0 0 0 0 0 0 0 0 .____- -0 74 0 0 0 0 0 __0 41 0 0 0 56 6 ____0 0 0 0 0 . _ 19 0 0 0 F 22A,tph 1.358 - _.. -0.90 38.02 2.24 0.00 20 - 20 __-_720 2 .- _ _18. 76 45 ^ - 0 __ ___ 60 __ 60 6 -� __54. 228 0 i 6 c)AED excursion -6 -22 Envelope loss/gain 168 79 535 278 12 a) Infiltration b) Room ventilation 40 0 11 0 120 0 34 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 01 0 0 0 Subtotal (lines 6 to 13) 208 91 655 312 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 23% 41% 0 0 -208 0 0 0 0 -91 0 0 23% 41% 0 0 6 662 150 0 0 15 327 133 Total room load Air required (cfm) 0 0 0 0 1 132 811 460 20 -� wrilghtsoft� Right -Suite® ...mnets\Wdghtsoft WACIDIFRANCESCO F 2021 21.0.02 RSU08101 :E.rup Calc = MJ8 Front Door faces - wrightsoftRight-l® Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM Job: Date: JAN. 11, 2021 By: 1 2 3 4 5 Room name Eq)osed wall Room height Room dimensions Room area BEDROOM 2 26.0 ft 9.3 ft heat/cool 1.0 x 176.0 ft 176.0 ftz CLST 2 20 ft 9.3 ft heat/cool 2.0 x 10.0 ft 20.0 ft2 Ty Construction number U-value (Btuhlft2 °F) Or HTM (Btuh/ft� Area or perimeter (ft) Load (Bt h) orM or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 194-ocs 2 glazing, cir low a 2 glazing, clr low- t -0 143 0.320 _ 0.320 -n n n -e 4.00 8.96 _" 8.96 2..19 9.41 9.41 -2.19 0 0 _ 0 0 0 0 0 0 0 0 0 0 0 0 0_ 0 0 0 0 0 0 0 0 0 w 11 W 13A-4ocs 2 glazing, clr low-e 2 glazing, cir low-e 2 alazgw, cir low_ 13A-4ocs 2 glazing, cir low-e ,2.glazing, clr low_e -_ glazing, 4ocs 2 ing, clr low-e 2 glaz 2 glazing, cir low-e 2 gl_azinp, cir low-e 16A30md --- 22A_tph 0.143 0.320 0.320 0.320 0.143 0.320 0.320 0. 0.320320 0.320 0_320 e a ^e . s s _ s_ w w w w I 4.00 , 8.96 8.96 _ 8_96 4.00 8.96' _ 8.96' 4.00 8.96 8.96 8.96 24.75 25.20 25.20 - 2.19 . 9.41 _____9.41 2.19 23.96 24.75 25.20. 2.24 0.00 112 15 0 0 97 1 0 0 387 134 0 0 ~ 211 371 0 0 18 0 0 - 0 0 0, -___0 0 0 0 0 19 0 0 + 0 0 0 ____d 0 0 0 0 0 _ ~ 74 0 0 0 41 0 0 - 0 0 0 ____-,_0 0 0 0 0 _ W� ^ I� G. F _ 130 0 1.5. 115 0 ___15 0 0 0 0 461 0 _134 0 0 0 0 252 0 ___ 141 0 0 0 0 0 0 -______0. 0 0 0 0 0 0 0 0 00322 1.358�-38.02 �_- _ . _0.90 -V_ 175 176 _-_ 176 26 989 _ ^_ 394 0 _ 20 20 20 2 -._-18 76 ,_- _-45 0 Y - - i 6 c)AED e)cursion j -114 -6 Envelope loss/gain 2263 1256 168 79 12 a) Infiltration b) Room %entilation 521 0 147 0 40 0 11 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 250 0 0 0 Subtotal (lines 6 to 13) 2784 1653 208 91 14 15 Less eMemal load Less transfer Redistribution Subtotal Duct loads 230/6 41% 0 0 118 2902 656 0 0 59 1712 695 231/6 41% 0 0 -208 0 0 0 0 -91 0 0 i Total room load Air required (cfm) 3558 140 2407 105 0 0 0 0 Ed. -FW wr70ht2soTt- I&K Right -Suite® Universal 2021 21.0.02 RSU08101 ...mnets\Wdghtsoft HVAC\D I FRANCESCO RESIDENCExup Calc = MJ8 Front Doorfaces: E 2021-Jan-11 09:26:08 Page 3 wrightsoft Right-M#orksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM Job: Date: JAN. 11, 2021 By: 1 2 3 4 5 Room name Exposed wall Room height Room Room dime dimensions j HALL 0 ft 9.3 ft heaUcool 4.0 x 6.0 ft 24.0 ftz WCHEN 22.0 ft 14.0 ft heat/cool 22.0 x 17.0 ft 374.0 ftZ Ty Construction number U-value (Btuh/ft2 °F) Or HTM ! (Btuh/ft� Area (M or perimeter (ft) Load (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 W 13AAOCS 2 glazing, clrlow-e j,glazing,Sr low-e 0.143 0.320 _ 0.320 n n n 4.00 8.96 _ 8.96 219 , 9.41 _ - 9.41 0 0 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 WiWiWWU4ii��VV 13AAocs 2 glazing, clr low-e 2 glazing, Gr low-e 2 glazmq clr low a 13AAocs 2 glazing "clr low-e .2,glazmg _clr Iow_e_ 13AAocs 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 16A30md^-,__-__a 22A-tph 0.143 0.320 0.320 0._320 0.143 0.320 0.320 0.143 0.320 0.320 0.320 e a a a s s -s_ w w w w_ . a_ 1 4.00 8.96 8.96 _� 8 96 4.00 i 8.96' _. 8 4.00 8.96 8.96 _ 8_96 _ `_ 0.90 38.02 2.19 24.75 25.20 25 20 219 9.41 9 41; 2.19 23.96 24.75 25_20 0 0 0 0_ 0 0 0 0 -' 0 0, ___ 0 0 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 :_ _ 0 0 0 0 0 0 0 0 0 0 0 0 0 _ �- 0 0 0 0 _ _ _ _ 0 0 0 0 W 0 0 _ 0 0 0 0 0 0 0. _- 0 0 0 0 0 0 0 Q 0 0 .-0 251 1 0 2 0 0 - _-, 0. 1005 81 0 430 0 0 _-,-_,__0 549 216 0 1209 0 F _ 308 9 0 48 ___` 0.032 1.358 _ _2.24 0_00 ___-_-__24 - 2_4 -_-___2_4 0 54 --__374 374 _ 374 22 ___M 837 = __-_._.-22 0 _ 0 _ _ --_ - 6 c)AED excursion -3 514 Envelope loss/gain 22 50 2687 3326 12 a) Infiltration b) Room ventilation 0 0 0 0 663 0 187 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal pines 6 to 13) 22 50 3351 3513 14 15 Less extemal load ! Less transfer Redistribution Subtotal Duct loads 23% 41% 0 0 -22 0 0 0 0 -So 0 0 23% 41% 0 0 98 3449 780 0 0 49 3562 1445 Total room load Air required (cfm) 0 01 0 0 1 1 4229 166 5007 219 ��A Right -Suite® Universal 2021 21.0.02 RSU08101 ...mnetslWrightsoft HMACIDIFRANCESCO RESIDENCExup Calc=MJ8 Front Doorfaces: E 2021-Jan-11 09:25:08 Page 4 wrightsoft Right-J®IWorksheet Entire House QUICK CA CS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 712-4-799 Fax 772466-6795 Email: QUICKCALCS@AOL.COM Job: Date: JAN.11, 2021 By: 1 2 3 4 5 Room name E)osed wall Room height Room dimensions Room area FAMILYROOM 220 ft 14.0 ft heat1cool 22.0 x 17.0 ft 374.0 ft2 MASTER BEDROOM 32.0 ft 9.3 ft heat1cool 16.0 x 16.0 ft 256.0 ftz TY Construction number U-value (Btuh/ft� °F) Or i ! HTM (Btuh/ft�j Area or perimeter (ft) Load (Btuh) Area (ft5 or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1 {N-G 13A flocs '2 glazing, cir low-e 2 glazing, cir low-e 0:143 0.320 ^_ 0.320 n n n 4.00 8.96 8.96 2.19 941 9.41 0 0 0_ 0 0 0 0 0 0 0 0 149 20 0 129 0 0 , 516 179 0 282 188 0 T� G 11 VDU- ;-G 13AAocs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazinq, clr I-ow_e_ 13A-4ocs 2 glazing, clr low-e, 2.glazmg, ctr low2.__ 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 16A.30md 22A_tph 0.143 0.320 0.320 0320 0.143 0.320 -0.320 0.143 0.320 0.320 0320 a a a a ._ s s -s_ w w w w_ 4.00 8.96 8.96 896 4.00 8:96 8..96; 4.00 8.96 8.96 8.96 2.19 24.75 25.20 25.20 119 9.41 _- -9.41 2.19 23.96 24.75 = 25.20 _-2.24 0.00 308 0 16 24 0 0 _.-..__0 0 0 0 0 268 0 1 1 0 0 _--._.._0 0 0 0 0 1073 0 143 215 0 0 _0 586 0 403 605 0 0 -_-___-0 0 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 Q 0 0 _ 0 0 - _ -_._0 0 0 0 0 - _Q 149 0 15 0 _ _w 134 0 1 0 �- -Q 536 0 134 0 ____=0. 293 0 371 0 _ Ca- F _� 01032 URI _-0.90 ,� 38.02 _ --374 374 --37_4 22 335.__-__838 837 0 _ 256 256 256 32 _- 22@ 1.217 0 +_ 6 c)AED excursion -111 -59 Envelope loss/gain 1 2603 2321 2811 1649 12 a) Infiltration b) Room ventilation 663 0 187 01 641 0 181 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 600 0 0 1400 Subtotal Qines 6 to 13) 3266 3108 3452 3229 14 15 Less edemas load Less transfer Redistribution Subtotal Duct loads 23% 41% 0 0 98 3364 761 0 0 49 3157 1281 23% 41% 0 0 0 3452 781 0 0 0 3229 1310 Total room load l Air required (cfm) 4125 162 4438 194 4233 1661 4540 198 - -1'�!- wrfightsoGf!® /�Y..�..1� Right -Suite® Universal 2021 21.0.02 RSU08101 ...mnets\Wrightsoft WACIDIFRANCESCO RESIDENCE.rup Calc = MJ8 Front Doorfaces: E 2021-Jan-11 09:25:08 Page 5 + wrightsoft' Right-M, Worksheet Job: Entire House Date: JAN. 11, 2021 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 7727466.6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name F)osed wall Room height Room dimensions Room area M WIC 0 ft 9.3 ft heat/cool 6.0 x 11.0 ft 66.0 ftz M BATH 11.0 ft 9.3 ft heat/cool 10.0 x 11.0 ft 110.0 ftZ Ty Construction number U-value (Btuh/ft= °F) Or HTM (BtutUft� Area (ftj or perimeter (ft) Load (Btuh) Area M or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 _ 13AAocs 2 glazing, clr low-e 2 glazing, clr - 0.143 0.320 0.34) n n n 4.00 8.96 8.96 2.19 9.41 9.41 0 0 ~ 0 0 0 0 0 0 U 0 0 0 102 0 15 87 0 0 350 0 134 T 191 0 141 11 13AAocs 2 glazing, clr low-e 2 glazing, clr low-e 2_glazmq, clr low-e 13A-4ocs 2 glazing; clr lowe '.2 glazing, clr low a 13AAocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr lower 16AA 30m(; j-m(L----' 22(�tph 0.143 0.320 0.320 0.320 0.143 0.320 '0. 320 0.143 0.320 0.320 0_320 _ 0_032 1.3358 a a a _e .s s ems_ w w w w ^ 4.00 8.96 8.96 B. "�4.00 I 8.96 f 4.00 8.96 8.96 1 8.96 _ r0.90 38.02 2.19 24.75 25.20 25.20 Z19 9.41 Z 19 23.96 24.75 25.20 2.24 0- 0 0 0 0- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 _ _0 0 0 0 0 0 0 0 �_, U 0 0 0 0 0 0 0 0 0 0 _. _ _ C -'-0 0 0 0 0 -0 0 0 0 0 -_-M 66 0 110 11 418 _ 0 F 0.00 66 0 0 6 c)AED excursion -10 -58 Envelope loss/gain 59 138 1001 521 12 a) Infiltration b) Room ventilation 0 0 0 0 220 0 62 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 250 Subtotal pines 6 to 13) 59 138 1221 833 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 230/6 41% 0 0 0 59 13 0 0 0 138 56 230/6 41% 0 0 0 1221 276 0 0 0 833 338 Total room load Air required (cfm) 73 3 194 8 1497 59 1171 51 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -Fk- wrightscxft- 2021-Jan-11 09:25:08 A&k """ Right -Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...rmets\Wdghtsoft WACIDIFRANCESCO RESIDENCE.rup Calc = MJ8 Front Doorfaces: E - - wrightsoft Right-M Worksheet Job: Entire House Date: JAN. 11, 2021 QUICK CALCS, INC. By: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466.6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area LAUNDRYRM 20.0 ft 9.3 ft heat/cool 1.0 x 91.0 ft 91.0 ft2 M TOILET 3.0 ft 9.3 ft heaticool 7.0 x 3.0 ft 21.0 ft2 Ty Construction number U-value (Btuhlft2--°F) Or HTM (Btuh/ft2) Area (ftj or perimeter (ft) Load (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 ti 13AAocs-0:143 glazing, clriow-e 2 glazing, clriow-e 0.320 0.320 n n n 4.00 8.96 8.96 2.19 9.41 9.41 37 0 0 37 0 0 149 0 0 81 0 0 28 0 0 28 0 0 112 0 0_ 612 0 0 11 WJ I-G 2 glazing, clr low-e 2 13AAocs 2 glazing, clr low-e glazrnq, clr lower 13AAocs 2 glazing, clr iow-e 2.glazing,_clr-1ow;e._- 13AAocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing% clr low2 16A 30md ; 22Atph _ 0.143 0.320 0.320 0 320 0.143 0.320 - 0.320 0.143 0.320 0.320 0.320 a a a a s s' _s w w w w_ 4.00 �8.96 8.96 �_-8 96 4.00 8.96 _`_ 8 96, 4.00 8.96 1 8.96 8:96 2.19 24.75 25.20 _ 25.20 219 9.41 �9..41 2.19 23.96 24.75 25.20 _ 2.24 0_00 __ 149 ' 15 0 0 0 0 _____,- U 0 0 0 0 134 1 0 0 536 134 0 0 293 371 0 0 0 0 0 0 _ - -- 0 0 0 0 0 0 0 0 _ 0 0 0 0 �L�G W 0 0 0 0 0 -,•�0 0 0 0 0 0 0 _--0 0 0 0 0 0 0 0 0 0 0 0 0 0 _-. 0 0 0 0 0 0 0 _ - _0. 0 0 0 0 0 0 -_;-_._...._0 0 0 0 0 _ ������111111IIIIII 0 0 0 0 C F - 0.032_0.90 1.358 38:02 .-- 91 91 _--9-f 20 -_ 8..2 760 ___- 204 - 21 21 --21 3 -- 19 114_ 47 0_ -__0._ 6 c) AED exursion -W -24 Envelope loss/gain 1661 911 245 84 12 a) Infiltration b) Room ventilation 401 0 113 0 60 0 17 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 250 Subtotal pines 6 to 13) 2062 1024 305 351 14 15 Less a demal load Less transfer Redistribution Subtotal Duct loads 23% 41% 0 0 0 2062 466 0 0 0 1024 415 23% 41% 0 0 0 305 69 0 0 0 351 142 Total room load Air required (cfm) 2528 99 1439 63 374 15 493 22 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -00A- wrrightsobft® 2021-Jan-11 09:25:08 lak Right -Suite® Universal 2021 21.0.02 RSU08101 Page 7 ... mnets\Wrightsoft WAC\DIFRANCESCO RESIDENCE.rup Calc = MJB Front Door faces: E wrightsoft® Duct System Summary Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM r-roject intormation For. DIFRANCLSCO RESIDENCE, TREFELNER CONSTRUCTION HICKORY',DRIVE, FORT PIERCE, FL34982 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 980 cfm Job: Date: JAN. 11, 2021 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 980 cfm 207 ft Supply Branch Detail Table Name Design (Btuh) Htg 1 (cfm) � Clg (cfm) Design FR Diam (in) H x W (In) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 811 32 20 1.000 5.0 Ox 0 VIFx 37.9 135.0 st3 BEDROOM 2 h 3558 140. 105 1.000 7.0 Ox 0 VIFx 29.5 135.0 st3 BEDROOM 3 h 3558 140: 101 1.000 7.0 Ox 0 VIFx 48.4 155.0 st4 FAMILY ROOM c 2219 81 97 1.000 7.0 Ox 0 VIFx 33.6 135.0 st3 FAMILY ROOM -A c 2219 81 97 1.000 7.0 Ox 0 VIFx 9.3 115.0 st2 KITCHEN c 2504 83', 109 1.000 7.0 Ox 0 VIFx 51.6 155.0 st4 KITCHEN -A c 2504 83' 109 1.000 7.0 Ox0 VIFx 19.4 115.0 st1 LAUNDRY RM h 2528 99, 63 1.000 6.0 Ox 0 VIFx 5.4 115.0 st2 M BATH h 1497 59; 51 1.000 6.0 Ox 0 VIFx 11.3 115.0 st2 M TOILET c 493 15 22 1.000 4.0 Ox0 VIFx 10.3 115.0 st2 M WIC c 194 3 8 1.000 4.0 Ox 0 VIFx 20.7 115.0 st1 MASTER BEDROOM c 2270 83 99 1.000 7.0 Ox0 VIFx 19.4 115.0 st1 MASTER BEDROOM -A c 2270 831 99 1.000 7.0 Ox0 VIFx 15.9 115.0 st1 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (n) Material Trunk st2 Peak AVF 728 .664 1.000 927 12.0 0 x 0 VinlFlx st1 Peak AVF 252 316 1.000 579 10.0 0 x 0 VinlFlx st4 Peak AVF 222 210 1.000 504 9.0 0 x 0 VinlFlx st3 st3 Peak AVF 475 1 1432 1 1.000 1 719 1 11.0 0 x 0 VinlFlx st2 wrightsoft® 2021-Jan-11 09:25:13 1, ...�-���.M Right -Suite® Universal 2021 21.0.02 RSU08101 �C% Page 1 ...meets\Wrightsoft HVAC\DIFRANCESCO RESIDENCE.rup CaIc=MJB Front Door faces: E Return Branch Detail Table Name Grille Size (in) Htg (cfm) clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (n) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 980 980 0 0 0 0 Ox 0 VIFx -�- wrightsoft® 2021-Jan-11 09:25:13 •�«-�-.. Right -Suite® Universal 2021 21.0.02 RSUOB101 Page 2 ...meets\WdghtsoftHVAC\DIFRANCESCORESIDENCE.rup Calc=MJB Front Door faces: E