Loading...
HomeMy WebLinkAboutEvaluation Report; Series 8100 PVC Single Hung Large Missile Impacti URNER 2428 Old Natchez Trace Trail Camden, TN 38320 Ph. 941-380-1574 ENGINEERING & FBPE C.O.A. #29779 .CONSULTING, INC. Evaluation Report 155E August 03,2020 Product Description: Series 8100 PVC Single Hung, Large Missile Impact, 53 1/8" x 76" unit size at up to +/-67.5 PSF, 36" x 62" unit size at up to +67.5/-75 PSF, 7/8" Insulating Glass consisting of 1/8 Annealed or Tempered outboard lite — Air —5/16 Laminated (1/8Ann-.090PVB-1/8Ann) inboard lite Manufacturer: Custom Window Systems, Inc. 1900 SW 44'l Ave, Ocala, FL 34.474 Statement of Compliance: Thus report evaluates the above -listed product per the requirements of FAC Product Approval Rule Chapter 61 G20-3.005 (4). This product complies with the requirements of the 7t' Edition (2020) Florida Building Code including the High Velocity Hurricane Zone. The product testing standards performed are outlined below. Technical Documentation: I 1) This report, prepared by Lucas A. Turner, PE, at 2428 Old Natchez Trc Trl, Camden, TN 2) Approval drawing CWS !155E, signed and sealed by Lucas A. Turner, P.E. 3) Test Report NCTL-210-3668-1, -IA, -2, -2A, 3669-1, -lA, -2, and -2A, by National Certified Testing Laboratories, Orlando, FL, signed and sealed by Gerard J. Ferrara, with testing performed: TAS 201, 20�, 203 1994, ASTM E 1886, 1996 2002/2005, and AAMA A440 2005. 4) Supplemental Calcs. to support CWS-155E, signed and sealed by Lucas A. Turner, P.E. Installation: Units must be installed according to approval document CWS-155E. Limitations of Use: This product: • May be used in O/X configuration in sizes, design pressures, and with max. glass DLO heights as shown in CWS-155E • Is impact resistant and does not require the use of shutters • May be used in the High Velocity Hurricane Zone • Requires 7/8" Insulating Glass consisting of 1/8 Annealed or Tempered outboard lite (Tempered required above 30 ft in HIVIHZ) —Air— 5116 Laminated (1/8Ann-.090PVB-1/8Ann) inboard lite • Requires Kuraray Butacite PVB Interlayer per Miami -Dade NOA 19-0305.02t • Requires Quanex or Veka white rigid PVC framing per Miami -Dade NOA 17-0206.10t or 17- 0228.00 t I have evaluated the interlayer and framing materials in these. Kuraray, Quanex, and Veka NOAs and find that they comply with the requirements of the 7s' Ed. (2020) Florida Building Code for use in this product. Certification of Independence: I do not have, nor do I intend to acquire, nor will I acquire, a financial interest in Custom Window Systems or in any company manufacturing or distributing products for which this report is being issued. I do not have, nor do I intend to acquire, nor will I acquire, a financial interest in any other entity involved in the testing or approval process of this product. I Lucas Turner 2020.08.06 ='o¢ No:58209 09= 08/03/2020 Oj 15:09:19 = E Lucas A. Turner, P.E. STATE-60 4r FL PE #58201 -OS 100 S., Aft tl I 0 SINGLE HUNG - LARGE MISSILE IMPACT 72° MAX O.A. B FLANGE HEIGHT TABLE OF CONTENTS GENERAL NOTES & ELEVATIONS ..... 1 GLAZING DETAILS...............................2 SECTION VIEWS & ALT. FRAME ........ 3 EXTRUSIONS & B.O.M.........................4 ANCHOR SCHEDULE & NOTES .......... 5 INSTALLATION DETAILS.....................6 0 70 3/4" MAX. UNIT HEIGHT 34 5/8" MAX SASH Al L 37" MAX. O.A. FLANGE WIDTH 35 3/4" MAX. UNIT WIDTH 31 9116" GLASS DLO --- A — O I B I GLASS D O X I I I 6 3 3 B" GLASS DLO 4 1 A --a*— 82 15/16" - GLASS DLO 1 4" MAX. SASH WIDTH GENERAL NOTES: 1. THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED claticsd TO COMPLY WITH THE FLORIDA BUILDING CODE (FBC), CURRENT EDITION INCLUDING THE HIGH VELOCITY HURRICANE ZONE (HVHZ) AND 1900 SW 44TH AVE. IS RATED FOR WIND ZONE 4 MISSILE LEVEL D IMPACT USE AS DEFINED OCALA, FLORIDA 34474 IN ASTM E 1096 PER THE FBC. WWW.CWS.CC 2. GLAZING OPTIONS: (SEE SHEET 2) 8100 PVC 3. CONFIGURATIONS: "O/c". SINGLE HUNG 4. DESIGN PRESSURE RATING: IMPACT -NEGATIVE DESIGN LOADS BASED ON, TESTED PRESSURE AND GLASS TABLES ASTM E-1300-04. -POSITIVE DESIGN LOADS BASED ON, TESTED PRESSURE, WATER INFILTRATION TEST PRESSURE AND GLASS TABLES ASTM E-1300-04. c 5. ANCHORAGE: THE 33113% STRESS INCREASE HAS NOT BEEN USED o IN THE DESIGN OF THIS PRODUCT. SEE SHEET 6 FOR ANCHOR DETAILS. WINDLOAD DURATION FACTOR Cd=1.6 WAS USED FOR WOOD w m ANCHOR CALCULATIONS. 6. PRODUCT APPROVED FOR IMPACT RESISTANCE. SHUTTERS ARE NOT U In REQUIRED. N Z 7. ALL FRAMES AND VENTS FULLY WELDED. SMALL JOINT SEAM SEALANT w O USED AT FIXED MEETING RAIL AND JAMB. a a 8. SERIES / MODEL DESIGNATION SH-8100. ¢ 0 0 CL o 9. THE DESIGNATION X AND O STAND FOR THE FOLLOWING: X = OPERABLE SASH, 0 = FIXED SASH ¢ Z 10. SECTION CALLOUTS APPLY TO ALL ELEVATIONS IN A SIMILAR pre LOCATION. `,fltt PND'��,TG�i�i 11. WEEP SLOTS =1/4" x 1-14' LOCATED 4" FROM BOTH ENDS. s`�P • .:1G E Al g c••'Qn. FRAME DESIGN PRESSURE TYPE MAX. UNIT SIZE RATING IMPACT RATING FLANGE 35-3/4" x 70-3/4" +/— 70 PSF LARGE MISSILE IMPACT FIN +/— 65 PSF e '--i No 58201 '`7= •O : : ttir': 9 . STATE OF .14t s�ONA` 101110 'Z117-1 4/11/2015 LUCAS A. TURNER, P.E. FL PE # 58201 1239 JABARA AVE. NORTH PORT, FL 34288 PH. 941-380-1574 IEET DESCRIKION: GENERAL NOTES AND ELEVATIONS IAWN BY: DATE: EMK 09/18/14 VG #: REV.: CWS-958 A ALE: SHEET 1:15 1 OF 6 7/8" OVERALL INSULATED GLASS 1/8" ANNEALED OR TEMPERED 112" AIRSPACE 5116" LAMINATED GLASS 1/8" ANNEALED .090" PVB INTERLAYER BY DUPONT 1/8" ANNEALED DURASEALBYTRUSEAL PURFECT GLAZE "H" OR SIKAFLEX 552 1/2" GLASS BITE FIXED LITE SASH LITE 7/8" OVERALL INSULATED GLASS 1/8" ANNEALED OR TEMPERED 1/2" AIRSPACE 5/16" LAMINATED GLASS 1/8" ANNEALED .090" PVB INTERLAYER BY DUPONT 1/8" ANNEALED — DURASEAL BY TRUSEAL PURFECT GLAZE "H" OR SIKAFLEX 552 WINDOW SYSTEMS k`1 1900 SW 44TH AVE. OCALA, FLORIDA 34474 W W W.CW S.CC 8100 PVC SINGLE HUNG IMPACT co di 00 U) coQLL > N Z W x O 0C as wco 0= U C 1/2" GLASS BITE ?. � = No 58261 STATE OF �-44 4/11/2015 LUCAS A. TURNER, P.E. FL PE # 58201 1239 JABARA AVE. NORTH PORT, FL 34288 PH. 941-380-1574 EET DESCRIPTION: GLAZING DETAILS AWN BY: DATE: EMK 09/18/14 IG #: REV.: CWS-958 A 'ALE: SHEET 1:1 20F6 1 1 `i � J is :gym SECTION VIEW A -A 'EF SECTION VIEW B-B NOTE: LEFT SIDE SHOWS FIXED SECTION VIEW, RIGHT SIDE SHOWS SASH SECTION VIEW. SECTION VIEW C-C ALTERNATE FIN FRAME 0309((ow WINDOW SYSTEMS 1900 SW 44TH AVE. OCALA, FLORIDA 34474 W W W.CWS.CC 8100 PVC SINGLE HUNG IMPACT 00 co m p v to N Z W O a P= a w 0 co No 58201 9 • STATE OF .�W: z�- 4/11/2015 LUCAS A. TURNER, P.E. FL PE # 58201 1239 JABARA AVE. NORTH PORT, FL 34288 PH. 941-380-1574 IEET DESCRIPTION: SECTION VIEWS [AWN BY: DATE: EMK 09/18/14 VG #: REV.: CWS-958 A ;ALE: SHEET 1:2 30F6 01 3 6" MAX. (1 6" MAX. 1231, MAX. (TYP. 4" 12 3h MAX. (TYP., ANCHOR LAYOUT - (FLANGE) DP +/- 70 PSF 4" MAX. (TYF E 2 4" MAX. (TYF 8" MAX. O.C. (TYP.) MLG HAIL INSTALLATION ANCHOR CrYR) ANCHOR LAYOUT - (FIN) DP +/- 65 PSF JOTE 2 INSTALLATION ANCHOR (TYP.) NOTES: - - I INSTALL ONE -ANCHOR -AT EACH INSTALLATION LOCATION. SILL ANCHOR SPACING SAME AS HEAD. 2. SHIM AS REQ AT EACH INSTALLATION ANCHOR USING LOAD BEARING SHIMS. MAX. ALLOWABLE SHIM STACK TO BE 1/4". USE SHIMS WHERE SPACE GREATER THAN 1/16" IS PRESENT. LOAD BEARING SHIMS SHALL BE CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER. WOOD SHIMS ARE NOT ALLOWED. 3. ANCHOR TYPE, SIZE, SPACING AND EMBEDMENT SHALL BE AS SPECIFIED IN THESE DRAWINGS, SEE TABLE 1, SHEET 6. 4. ALL INSTALLATION ANCHORS MUST BE MADE OF OR PROTECTED WITH A CORROSION RESISTANT MATERIAL OR COATING. DISSIMILAR METALS OR MATERIALS IN CONTACT WITH PRESSURE TREATED WOOD MUST BE PROTECTED TO PREVENT REACTION. S. INSTALLATION ANCHORS SHALL BE IN ACCORDANCE WITH ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND ANCHORS SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM SPECIFIED IN TABLE 1, SHEET 6. 6. ANCHOR EMBEDMENT TO SUBSTRATE SHALL BE BEYOND WALL DRESSING OR STUCCO. FOR CONCRETE/CMU OPENINGS, EMBEDMENT SHALL BE BEYOND WOOD BUCKS, IF USED, INTO SUBSTRATE. INSTALLATIONS TO SOLID CONCRETE OR GROUT -FILLED CMU MAY INCLUDE BUT DO NOT REQUIRE I WOOD BUCKS BETWEEN THE PRODUCT AND THE SUBSTRATE. INSTALLATIONS TO HOLLOW CMU REQUIRE THE USE OF I BUCKS BETWEEN THE PRODUCT AND SUBSTRATE. 7. A MINIMUM CENTER -TO -CENTER SPACING SHALL BE MAINTAINED BETWEEN ALL FASTENERS: 3" FOR MASONRY, 1" FOR WOOD AND METAL. 8. WOOD OR MASONRY OPENINGS, BUCKS AND BUCK FASTENERS SHALL BE PROPERLY DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD AND INSTALLED TO TRANSFER WIND LOADS TO THE STRUCTURE. SUBSTRATES SHALL MEET THE MINIMUM STRENGTH REQUIREMENTS AS SHOWN IN TABLET, SHEET 6. CONCRETE AND MASONRY SUBSTRATES MAY NOT BE CRACKED. 9. SEALING AND FLASHING STRATEGIES FOR OVERALL WATER RESISTANCE OF INSTALLATION SHALL BE DONE BY OTHERS FOLLOWING THE CURRENT VERSION OF THE REFERENCE DOCUMENTS: FMA/AAMA 100(FIN WINDOWS), FMA/AAMA 200(FLANGE WINDOWS), FMAMDMA 2�0(BOX WINDOWS), FMA/AAMA/WDMA 300(EXTERIOR DOORS) WINDOW SYSTEMS Ll 1900 SW 44TH AVE. OCALA, FLORIDA 34474 W W W.CWS.CC 8100 PVC SINGLE HUNG IMPACT -ai No 58201 a : cc 'P STATE OF •: 4/11/2015 LUCAS A. TURNER, P.E. FL PE # 58201 1239 JABARA AVE. NORTH PORT, FL 34288 PH. 941-380-1574 ANCHOR SCHEDULE NOTES EMK 1 09/18/14 CWS-958 A 'ALE: SHEET 1:20 5 OF 6 c c MIN. EMBEDMENT TYPICAL HEAD ANCHORAGE SEE TABLE 1 SUBSTRATE BY OTHERS MIN. EDGE DIST. 1/4" MAX. SHIM SEE TABLE 1 SUBSTRATE BY OTHERS SEE TABLE 1 :MI SEE TABLE 1 EDGE DIST. MIN. EMBEDMENT SEE TABLE 1 PERIMETER SEALANT SEE TABLE 1 BY INSTALLER INSTALLATION ANCHOR INSIDE AND OUT SEE TABLE 1 SEALANT BEHIND O FLANGE BY INSTALLER 1/4" MAX. SHIM / INSTALLATION ANCHOR SEE TABLE-1 SEALANT BEHIND - FLANGE BY INSTALLER PERIMETER SEALANT — BY INSTALLER INSIDE AND OUT SUBSTRATE BY OTHERS SEE TABLE 1 1/4" MAX. SHIM MIN. EMBEDP SEE TABLE 1 PERIMETER SEALANT BYINSTALLER INSIDE AND OUT SEALANT BEHIND FLANGE BY INSTALLER HORIZONTAL SECTION 6 TYPICAL JAMB ANCHORAGE TABLE 1: APPROVED INSTALLATION FASTENERS FRAMETYPE SUBSTRATE TYPE ANCHOR TYPE MIN. EMBEDMENT MIN. EDGE DIST. FLANGE CONCRETE (2.0 KSI MIN.) 3/16" ITW TAPCON 1-1/2" 1-118" FLANGE HOLLOW OR GROUT -FILLED CMU (117 PCF MIN.) 3/16" ITW TAPCON 1" 2" FLANGE CONCRETE (2.85 KSI MIN.) 3/16" ELCO ULTRACON 1" 1" FLANGE GROUT -FILLED CMU (ASTM C-90) 3/16" ELCO ULTRACON 1-1/4" 2-1/2" FLANGE 2XMIN. SOUTHERN PINE (6=0.55) 3/16" ITW TAPCON OR ELCO ULTRACON 1-3/8" 7/8" FLANGE 2X MIN. SOUTHERN PINE (G=0.55) #10 WOOD SCREW 1-3/8" 7/8" FLANGE 16 GAUGE (0.060") MIN. STEEL STUD (33 KSI YIELD MIN) #10-16 HILTI KWIK-FLEXOR RW TEKS SELF -DRILLING SCREW FULL THREAD THRU 0.060" 7/16" FLANGE 1/8" ALUM. (6063-T5 MIN.) OR 1/8" STEEL (33 KSI MIN.) #10 GRADE 5 SELF -TAPPING / DRILLING SCREW FULL THREAD THRU 0.125" 7/16" FIN 2XMIN. SOUTHERN PINE (G=0.55) 1#8 WOOD SCREW 1-1/2" 7/16" MIN. EDGE DIST. SUBSTRATE SEE TABLE 1 � SE OTHERS 114" MAX. SHIM SEE TABLE 1 MIN. EMBEDMENT SEE TABLE 1 L]L PERIMETER SEALANT BY INSTALLER INSIDE AND OUT INSTALLATION ANCHOR SEE TABLE 1 SEALANT BEHIND FIN BY INSTALLER HORIZONTAL SECTION 6 TYPICAL FIN ANCHORAGE HEAD AND SILL SIMILAR FOR FIN INSTALLATION WINDOW! SYSTEMS Il u_-ZJ 1900 SW 44TH AVE. OCALA, FLORIDA 34474 WWW.CWS.CC 8100 PVC SINGLE HUNG IMPACT o H o d > W w O cc EL n~ w Q U o w n a No 58201 STATE_ OF 7� 4/11/2015 LUCAS A. TURNER, P.E. FL PE # 58201 PERIMETER SEALANT 1239 JABARA AVE. BY INSTALLER NORTH PORT, FL 34288 INSIDE AND OUT PH. 941-380-1574 D HORIZONTAL SECTION 6 BOX FRAME INSTALLATION SHEET DESCRIPTION: HEAD AND SILL SIMILAR FOR BOX INSTALLATION INSTALLATION DETAILS FLANGE REMOVAL NOTE: PARTIALLY OR FULLY REMOVING THE FLANGE, UP TO AND INCLUDING A BOX -FRAME APPLICATION IS ACCEPTABLE PROVIDED: DRAWN BY: DATE: EMK 09/18/14 MIN. 1/4" FILLET OF CONSTRUCTION -GRADE ADHESIVE CAULK IS APPLIED Dw#. #: REV.: INSIDE AND OUT, FULL PERIMETER, BY INSTALLER. CWS-958 A - PRODUCT ANCHORAGE IS IN ACCORDANCE WITH REQUIREMENTS AS SHOWN FOR FLANGE WINDOWS. SCALE: SHEET 1:2 60F6