HomeMy WebLinkAboutManj (1) Air Calcs LLC Load Short Form Job: 672 Date: Feb 12,2020 Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Blower door Inside db(°F) 70 75 Shielding/stories 3(partial)/1 Design TD(°F) 29 15 Pressure/AVF 50 Pa/0 cfm Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Generic Make Generic Trade Trade Model SEER 18.0,HSPF 9.1 Cond SEER 18.0,HSPF 9.1 AHRI ref Coil AHRI ref Efficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling 3875 Btuh Heating output 5508 Btuh @ 47°F Latent cooling 1661 Btuh Temperature rise 27 °F Total cooling 5535 Btuh Actual airflow 185 cfm Actual airflow 185 cfm Air flow factor 0.034 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.79 Capacity balance point=39°F ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) G Clst 18 0 0 0 0 G Bath 48 1147 450 39 20 G House 198 4253 3694 145 164 Guest House d 264 5400 4144 185 185 Other equip loads 0 0 Equip.@ 0.95 RSM 3953 Latent cooling 1118 TOTALS 264 5400 5071 185 185 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Apr-06 18:35:15 At� M;.ek „n"e a«awa.=mP=. Right-Srite®Uriversal 2021 21.0.03 RSU27054 Page 1 ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Air Calcs LLC Load Short Form Job: 672 Date: Feb 12,2020 House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Information Htg Clg Infiltration Outside db(°F) 41 90 Method Blower door Inside db(°F) 70 75 Shielding/stories 3(partial)/1 Design TD(°F) 29 15 Pressure/AVF 50 Pa/0 cfm Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-041-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259379 Efficiency 80AFUE Efficiency 13.0 EER, 16 SEER Heating input 0 kW Sensible cooling 27650 Btuh Heating output 0 Btuh Latent cooling 11850 Btuh Temperature rise 0 °F Total cooling 39500 Btuh Actual airflow 1317 cfm Actual airflow 1317 cfm Air flow factor 0.057 cfm/Btuh Air flow factor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Bath 2 55 163 202 9 10 Bed 2 160 1451 1481 82 75 Bed 3 186 3725 2562 211 130 Great Room 429 6762 9520 383 481 Hallway 140 0 0 0 0 Kitchen/Nook 330 5334 7225 302 365 Laundry 42 125 834 7 42 Linen 9 0 0 0 0 Master Bath 98 1021 595 58 30 Master Suite 288 4140 3343 235 169 Pantry 39 0 0 0 0 WIC 52 515 271 29 14 Wtr Htr 14 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Apr-06 18:35:15 At� M;.ek „n"e a«awa.=mP=. Right-Srite®Uriversal 2021 21.0.03 RSU27054 Page 2 ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N House d 1840 23235 26032 1317 1317 Other equip loads 1543 819 Equip.@ 0.95 RSM 25616 Latent cooling 7560 TOTALS 1840 24778 33176 1317 1317 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Apr-06 18:35:15 A II,-=Iae,-"e--.,I—— Right-Sute®Urrversal202121.0.03RSU27054 Page 3 ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 From Door faces: N Buildin Anal sis Job: 672 Air Calcs, LLC g Y Date: Feb Feb 12,zozo Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(°F) 70 75 Elevation: 26 ft Design TD(°F) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(°F) 41 90 Infiltration: Daily range(°F) - 15 ( L ) Method Blower door Wet bulb(°F) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm amme Component Btuh/ft2 Btuh %of load Walls 2.6 1215 22.5 Ducts Glazing 9.0 280 5.2 walls Doors 3.7 63 1.2 Ceilings 1.0 260 4.8 Floors 7.1 1864 34.5 Infiltration Infiltration 2.7 1035 19.2 Glazing Ducts 682 12.6 Piping 0 0 other Humidification 0 0 Ceilings Ventilation 0 0 Adjustments 0 Total 5400 100.0 Floors • • • Component Btuh/ft2 Btuh %of load Walls 1.8 855 20.6 Glazing 13.3 414 10.0 walls Doors 3.7 64 1.5 Internal Gains Ceilings 1.8 474 11.4 Floors 0 0 0 Infiltration 0.8 308 7.4 Glazing Ducts 799 19.3 Ventilation 0 0 Internal gains 1230 29.7 Other Blower 0 0 Ceilings Adjustments 0 Ducts Total 1 141441 100.0 1 Infiltration Latent Cooling Load=1118 Btuh Overall U-value=0.121 Btuh/ft2-0F Data entries checked. wrightsoft- 2021-Apr-06 18:35:15 �� A-1-1-11 °^.111-,1^,p°11 Right-SuiteO Universal 2021 21.0.03 RSU27054 Page 1 ACCA ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Buildin Anal sis Job: 672 Air Calcs, LLC g Y Date: Feb Feb 12,zozo House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm amme Component Btuh/ft2 Btuh %of load Walls 2.6 2946 11.9 walls Ventilation Glazing 8.7 2883 11.6 Doors 3.7 73 0.3 Ceilings 1.0 1817 7.3 Glazin Ducts Floors 2.7 4933 19.9 other Infiltration 2.7 4026 16.3 Ducts 6557 26.5 Ceilings Piping 0 0 Humidification 0 0 Ventilation 1543 6.2 Adjustments 0 Floors Infiltration Total 24778 1 100.0 • • • Component Btuh/ft2 Btuh %of load Walls 2.2 2468 9.2 Walls Ventilation Glazing 20.1 6643 24.7 Internal Gains Doors 3.7 74 0.3 Ceilings 1.8 3308 12.3 Floors 0 0 0 Glazing Infiltration 0.8 1199 4.5 Ducts 7321 27.3 Ventilation 819 3.1 Internal gains 5020 18.7 other Blower 0 0 Ducts Adjustments 0 Ceilings Total 126852 100.0 1 Infiltration Latent Cooling Load=7560 Btuh Overall U-value=0.084 Btuh/ft2-0F Data entries checked. wrightsoft- 2021-Apr-06 18:35:15 �� A-1-1-11 °^.111-,1^,p°11 Right-SuiteO Universal 2021 21.0.03 RSU27054 Page 2 ACCA ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Component Constructions Job: 672 Air Calcs, LLC Date: Feb 12,2020 House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Block R-9 Wall:Blk Wall,Stucco Ext,8"Thk,R-9 Foam Fill, 1/2"DW ne 282 0.089 9.0 2.58 726 2.16 608 se 306 0.089 9.0 2.58 790 2.16 662 sw 261 0.089 9.0 2.58 672 2.16 563 nw 294 0.089 9.0 2.58 758 2.16 635 all 1143 0.089 9.0 2.58 2946 2.16 2468 Partitions (none) Windows Impact,Low-e: Impact,Low-e;NFRC rated(SHGC=0.21);50%blinds ne 18 0.300 0 8.70 157 17.2 309 45°,medium;50%outdoor insect screen;foreground=green grass (0.23);2 ft overhang(3 ft window ht, 1 ft sep.);6.68 ft head ht nw 18 0.300 0 8.70 157 17.2 309 all 36 0.300 0 8.70 313 17.2 619 Impact,Lowe: Impact,Lowe;NFRC rated(SHGC=0.19);50%blinds ne 23 0.310 0 8.99 206 16.3 374 45°,medium;50%outdoor insect screen;foreground=green grass (0.23);5 ft overhang(5.2 ft window ht, 1 ft sep.);6.68 ft head ht Impact,Lowe: Impact,Lowe;NFRC rated(SHGC=0.21);50%blinds se 16 0.300 0 8.70 136 13.9 216 45°,medium;50%outdoor insect screen;foreground=green grass se 46 0.300 0 8.70 400 13.9 637 (0.23);2 ft overhang(5.2 ft window ht, 1 ft sep.);6.68 ft head ht sw 23 0.300 0 8.70 200 13.9 318 nw 42 0.300 0 8.70 362 17.2 715 nw 31 0.300 0 8.70 271 17.2 536 all 157 0.300 0 8.70 1369 15.4 2423 Impact,Low-e: Impact,Low-e;NFRC rated(SHGC=0.21);foreground= sw 52 0.300 0 8.70 452 11.0 573 green grass(0.23);8 ft overhang(6.5 ft window ht, 1 ft sep.);6.68 ft head ht Impact,Lowe: Impact,Lowe;NFRC rated(SHGC=0.21);50%blinds sw 10 0.300 0 8.70 90 9.17 95 45°,medium;50%outdoor insect screen;foreground=green grass (0.23);8 ft overhang(5.2 ft window ht, 1 ft sep.);6.68 ft head ht Impact,Lowe: Impact,Lowe;NFRC rated(SHGC=0.28);foreground= nw 13 0.300 0 8.70 113 25.8 335 green grass(0.23);2 ft overhang(6.5 ft window ht, 1 ft sep.);6.68 ft head nw 39 0.300 0 8.70 339 18.7 728 ht all 52 0.300 0 8.70 452 20.4 1063 wrightsoft- 2021-Apr-06 18:35:16 i.. Right-Sutee Universal 2021 21.0.03 RSU27054 Page 1 'CA ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Doors Door,Mtl Fbrgl Type ne 20 0.127 7.0 3.69 73 3.73 74 Ceilings Attic,Shingle Roof,R-30 Ceil Ins,5/8"DW 1840 0.034 30.0 0.99 1817 1.80 3308 Floors On grade depth,Tile flr fnsh 172 0.989 0 28.7 4933 0 0 wrightsoft- 2021-Apr-06 18:35:16 i.. Right-Site®Urrversal 2021 21.0.03 RSU27054 Page 2 'CA ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Component Constructions Job: 672 Air Calcs, LLC Date: Feb 12,2020 Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl,FL,US Indoor temperature(T) 70 75 Elevation: 26 ft Design TD(T) 29 15 Latitude: 28°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/Ib) 2.4 56.9 Dry bulb(T) 41 90 Infiltration: Daily range(T) - 15 ( L ) Method Blower door Wet bulb(T) - 77 Shielding/stories 3(partial)/1 Wind speed(mph) 15.0 7.5 Pressure/AVF 50 Pa/0 cfm Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF W-T/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Block R-9 Wall:Blk Wall,Stucco Ext,8"Thk,R-9 Foam Fill, 1/2"DW se 108 0.089 9.0 2.58 279 2.16 234 sw 120 0.089 9.0 2.58 310 2.16 260 nw 107 0.089 9.0 2.58 276 2.16 231 all 336 0.089 9.0 2.58 865 2.16 725 Partitions Block R-9 Wall:Blk Wall,Stuc Ext,8"Thk,R-9 Foam Fill, 1/2"Gyp Bd 136 0.089 9.0 2.58 350 0.96 130 Windows Impact,Low-e: Impact,Low-e;NFRC rated(SHGC=0.19);50%blinds se 16 0.310 0 8.99 140 13.3 207 45°,medium;50%outdoor insect screen;foreground=green grass (0.23);2 ft overhang(5.2 ft window ht, 1 ft sep.);6.68 ft head ht sw 16 0.310 0 8.99 140 13.3 207 all 31 0.310 0 8.99 280 13.3 414 Doors Door,Mtl Fbrgl Type nw 17 0.127 7.0 3.69 63 3.73 64 Ceilings Attic,Shingle Roof,R-30 Ceil Ins,5/8"DW 264 0.034 30.0 0.99 260 1.80 474 Floors On grade depth,Tile flr fnsh 65 0.989 0 28.7 1864 0 0 wrightsoft- 2021-Apr-06 18:35:16 i.. Right-Sutee Universal 2021 21.0.03 RSU27054 Page 3 'CA ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Project Summary Job: 672 Air Calcs, LLC 1 ry Date: Feb 12,2020 Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 4718 Btuh Structure 3345 Btuh Ducts 682 Btuh Ducts 799 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 5400 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 3953 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3(ppartial)/1 Pressure/AVF 50 Pa/0 cfi71 Structure 904 Btuh Ducts 214 Btuh Central vent(0 cfm) 0 Btuh Heating Cooling (none) Area(ft�) 264 264 Equipment latent load 1118 Btuh Volume(ft3) 2108 2108 Air changes/hour 0.92 0.52 Equipment Total Load(Sen+Lat) 5071 Btuh Equiv.AVF(cfm) 32 18 Req.total capacity at 0.70 SHR 0.5 ton Heating Equipment Summary Cooling Equipment Summary Make Generic Make Generic Trade Trade Model SEER 18.0,HSPF 9.1 Cond SEER 18.0,HSPF 9.1 AHRI ref Coil AHRI ref Efficiency 9.1 HSPF Efficiency 14.7 EER, 18 SEER Heating input Sensible cooling 3875 Btuh Heating output 5508 Btuh @ 47°F Latent cooling 1661 Btuh Temperature rise 27 °F Total cooling 5535 Btuh Actual airflow 185 cfm Actual airflow 185 cfm Air flow factor 0.034 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.79 Capacity balance point=39°F Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- 2021-Apr-0618:35:16 ^.,.I•I ",1,,...,-°..-,1..,,�r,, Right-Sute®Universal 2021 21.0.03 RSU27054 Page 1 ACCp` ...HVAC\TBD Dun Rd PSL Gardner Residence GBl.rup Calc=MJS Front Door faces: N Project Summary Job: 672 Air Calcs, LLC 1 ry Date: Feb 12,2020 House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project • • For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Notes: Design Information Weather: St Lucie Co Intl,FL,US Winter Design Conditions Summer Design Conditions Outside db 41 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 29 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 16678 Btuh Structure 18712 Btuh Ducts 6557 Btuh Ducts 7321 Btuh Central vent(48 cfm) 1543 Btuh Central vent(48 cfm) 819 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24778 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Infiltration Equipmen�sensible load 25616 Btuh Method Blower door Latent Cooling Equipment Load Sizing Shielding/stories 3(ppartial)/1 Pressure/AVF 50 Pa/0 cfi71 Structure 3538 Btuh Ducts 2152 Btuh Central vent(48 cfm) 1870 Btuh Heating Cooling Outside air Area(ft�) 1840 1840 Equipment latent load 7560 Btuh Volume(ft3) 15858 15858 Air changes/hour 0.48 0.27 Equipment Total Load(Sen+Lat) 33176 Btuh Equiv.AVF(cfm) 126 71 Req.total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-041-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259379 Efficiency 80AFUE Efficiency 13.0 EER, 16 SEER Heating input 0 kW Sensible cooling 27650 Btuh Heating output 0 Btuh Latent cooling 11850 Btuh Temperature rise 0 °F Total cooling 39500 Btuh Actual airflow 1317 cfm Actual airflow 1317 cfrn Air flow factor 0.057 cfm/Btuh Air flow factor 0.051 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.78 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft 2021-Apr-0618:35:16 M,a Right-Site®Universal 2021 21.0.03 RSU27054 Page 2 ACCp` ...HVAC\TBD Dun Rd PSL Gardner Residence GBl.rup Calc=MJS Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 Guest House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name GuestHouse GClst 2 E)posed wal I 65.0 It 3.0 ft 3 Room height 8.0 It d 8.0 It heat/000l 4 Room dimensions 3.0 x 6.0 It 5 Room area 263.5 fF 18.0 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 0.00 0.00 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 124 108 279 234 0 0 0 0 Impact,Low-e 0.300 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 8.99 13.27 16 7 140 207 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 136 120 310 260 0 0 0 0 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 8.99 13.27 16 7 140 207 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 124 107 276 231 24 24 62 52 G Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 3.69 3.73 17 17 63 64 0 0 0 0 P Block R-9 Wall 0.089 2.58 0.96 136 136 350 130 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 264 264 260 474 18 18 18 32 F On grade depth,Tile 0.989 28.68 0.00 264 65 1864 0 18 3 86 0 6 c)AED excursion 0 0 Envelope loss/gain 3683 1807 166 84 12 a) Infiltration 1035 308 65 19 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 0 0 Appliances/other 1000 0 Subtotal(lines 6 to 13) 4718 3345 230 103 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 -230 -103 14 Subtotal 4718 3345 0 0 15 Dud loads 14% 24%1 6821 799 14% 24%1 0 0 Total room load 5400 4144 0 0 Air required(dm) 185 185 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 1 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 Guest House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name G Bath G House 2 E)posed wal I 14.0 It 48.0 It 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 8.0 x 6.0 It 1.0 x 197.5 It 5 Room area 48.0 ft' 197.5 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 ne 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 0.00 0.00 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 0.00 0.00 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 0 0 0 0 124 108 279 234 Impact,Low-e 0.300 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 8.99 13.27 0 0 0 0 16 7 140 207 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 136 120 310 260 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 8.99 13.27 0 0 0 0 16 7 140 207 Block R-9 Wall 0.089 nw 2.58 2.16 64 64 165 138 36 19 49 41 G Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 0.00 0.00 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 3.69 3.73 0 0 0 0 17 17 63 64 P Block R-9 Wall 0.089 2.58 0.96 48 48 124 46 88 88 227 84 C AttiG Shingle Roof, 0.034 0.99 1.80 48 48 47 86 198 198 195 355 F On grade depth,Tile 0.989 28.68 0.00 48 14 402 0 198 48 1377 0 6 c)AED excursion 0 0 Envelope loss/gain 737 271 2780 1452 12 a) Infiltration 173 51 798 238 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 1 230 Appliances/other 0 1000 Subtotal(lines 6 to 13) 910 322 3578 2919 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 92 41 138 62 14 Subtotal 1002 363 3716 2981 15 Dud loads 14% 24% 145 87 14% 24% 537 712 FFTotal room load 1147 450 4253 3694 Airrequired(dm) 39 20 145 164 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 2 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name House Bath 2 2 E)posed wal I 172.0 It 0 It 3 Room height 8.6 It d 8.0 It heat/000l 4 Room dimensions 8.5 x 6.5 It 5 Room area 1840.0 fF 55.3 fF Ty Consh'ucton U-value Or HTM Area OF) Load Area OF) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 343 282 726 608 0 0 0 0 Impact,Low-e 0.300 ne 8.70 17.19 18 0 157 309 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 23 0 206 374 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 20 20 73 74 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 368 306 790 662 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 16 7 136 216 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 46 20 400 637 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 346 261 672 563 0 0 0 0 Impact,Low-e 0.300 sw 8.70 11.02 52 52 452 573 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 23 10 200 318 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 10 10 90 95 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 437 294 758 635 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 13 0 113 335 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 18 0 157 309 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 42 0 362 715 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 31 0 271 536 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 39 0 339 728 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 1840 1840 1817 3308 55 55 55 99 F On grade depth,Tile 0.989 28.68 0.00 1840 172 4933 0 55 0 0 0 6 c)AED excursion 1496 -2 Envelope loss/gain 12652 12493 55 97 12 a) Infiltration 4026 1199 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliances/other 4100 0 Subtotal(lines 6 to 13) 16678 18712 55 97 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 63 48 14 Subtotal 16678 18712 117 145 15 Dud loads 39% 39% 65571 7321 39% 39%1 46 57 FFTotal room load 23235 26032 163 202 Air required(dm) 1317 1317 9 10 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 3 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Bed 2 Bed 3 2 E)posed wal I 10.5 It 30.5 It 3 Room height 8.0 It heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 159.8 ft 1.0 x 186.0 ft 5 Room area 159.8 ft2 186.0 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 ne 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 84 68 176 148 100 77 198 166 Impact,Low-e 0.300 se 8.70 13.86 16 7 136 216 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 23 10 200 318 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 144 121 312 261 Impact,Low-e 0.300 sw 8.70 11.02 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 23 10 200 318 Impact,Low-e 0.300 sw 8.70 9.17 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 0 0 0 0 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 160 160 158 287 186 186 184 334 F On grade depth,Tile 0.989 28.68 0.00 160 11 301 0 186 31 875 0 6 c)AED excursion 62 -40 Envelope loss/gain 771 714 1968 1359 12 a) Infiltration 226 67 658 196 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 250 Subtotal(lines 6 to 13) 997 1031 2626 1805 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 44 34 48 37 14 Subtotal 1041 1065 2674 1841 15 Dud loads 39% 39% 409 417 39% 39%1 1051 720 FFTotal room load 1451 1481 3725 2562 Airrequired(dm) 1 1 82 75 211 130 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 4 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Great Room Hallway 2 E)posed wal I 41.5 ft 4.5 ft 3 Room height 9.5 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 428.8 ft 31.0 x 4.5 ft 5 Room area 428.8 fF 139.5 fF Ty Conshvcton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 ne 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 166 104 268 224 36 36 93 78 Impact,Low-e 0.300 sw 8.70 11.02 52 52 452 573 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 10 10 90 95 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 228 134 346 290 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 13 0 113 335 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 42 0 362 715 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 39 0 339 728 0 0 0 0 D Door,MU FbrgITvpe 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 429 429 423 771 140 140 138 251 F On grade depth,Tile 0.989 28.68 0.00 429 42 1190 0 140 5 129 0 6 c)AED excursion 1273 -8 Envelope loss/gain 3585 5005 360 320 12 a) Infiltration 1063 316 97 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 900 0 Subtotal(lines 6 to 13) 4647 6682 457 349 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 206 161 -457 -349 14 Subtotal 4853 6843 0 0 15 Dud loads 39% 39% 19081 2677 39% 39%1 0 0 Total room load 6762 9520 0 100 Airrequired(dm) 383 481 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 5 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Kitchen/Nook Laundry 2 E)posed wal I 37.0 ft 0 ft 3 Room height 9.5 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 22.0 x 15.0 ft 6.5 x 6.5 ft 5 Room area 330.0 fF 42.3 ft2 Ty Conshvcton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 143 105 270 226 0 0 0 0 Impact,Low-e 0.300 ne 8.70 17.19 18 0 157 309 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 20 20 73 74 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 11.02 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 209 160 412 345 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 18 0 157 309 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 31 0 271 536 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 330 330 326 593 42 42 42 76 F On grade depth,Tile 0.989 28.68 0.00 330 37 1061 0 42 0 0 0 6 c)AED excursion 262 -13 Envelope loss/gain 2726 2656 42 63 12 a) Infiltration 947 282 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 2 460 0 0 Appliances/other 1700 500 Subtotal(lines 6 to 13) 3674 5098 42 563 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 155 96 48 37 14 Subtotal 3829 5193 90 599 15 Dud loads 39% 39% 15051 2032 39% 39%1 35 234 FFTotal room load 5334 7225 125 834 Airrequired(dm) 302 365 7 42 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 6 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Linen Master Bath 2 E)posed wal I O ft 6.5 ft 3 Room height 8.0 It heat/000l 8.0 It heat/cool 4 Room dimensions 3.5 x 2.5 ft 15.0 x 6.5 ft 5 Room area 8.8 ft2 97.5 ft' Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 0 0 0 0 52 52 134 112 Impact,Low-e 0.300 ne 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 11.02 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 0 0 0 0 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 9 9 9 16 98 98 96 175 F On grade depth,Tile 0.989 28.68 0.00 9 0 0 0 98 7 186 0 6 c)AED excursion 0 -8 Envelope loss/gain 9 15 417 280 12 a) Infiltration 0 0 140 42 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 9 15 557 322 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution -9 -15 176 106 14 Subtotal 0 0 733 428 15 Dud loads 39% 39%1 01 0 39% 39%1 288 167 Total room load 0 0 1021 595 Air required(dm) 0 0 58 30 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 7 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name Master Suite Pantry 2 E)q)osed wal I 33.5 ft 0 ft 3 Room height 8.0 ft heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 288.0 ft 11.0 x 3.5 ft 5 Room area 288.0 ft' 38.5 ft2 Ty Consbructon U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 120 97 250 209 0 0 0 0 Impact,Low-e 0.300 ne 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 23 0 206 374 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 148 125 322 270 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 23 10 200 318 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 11.02 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 0 0 0 0 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 288 288 284 518 39 39 38 69 F On grade depth,Tile 0.989 28.68 0.00 288 34 961 0 39 0 0 0 6 c)AED excursion -21 -2 Envelope loss/gain 2224 1668 38 68 12 a) Infiltration 722 215 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 500 0 Subtotal(lines 6 to 13) 2946 2383 38 68 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 26 20 -38 -68 14 Subtotal 2972 2403 0 0 15 Dud loads 39% 39% 11681 940 39% 39%1 0 0 Total room load 4140 3343 0 100 T.0, quired(dm) 235 169 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 8 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs, LLC Right-J®Worksheet Job: 672 House Date: Feb 12,2020 By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilyme@aircalcs.com 1 Room name WIC WtrHtr 2 E)posed wal I 4.5 ft 3.5 ft 3 Room height 8.0 It heat/000l 8.0 It heat/000l 4 Room dimensions 4.5 x 11.5 ft ft 4.0 x 3.5 5 Room area 51.8 ft2 14.0 ft2 Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Block R-9 Wall 0.089 ne 2.58 2.16 0 0 0 0 28 28 72 60 Impact,Low-e 0.300 ne 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 ne 8.99 16.28 0 0 0 0 0 0 0 0 D Door,MU FbrglType 0.127 ne 3.69 3.73 0 0 0 0 0 0 0 0 11 VhBlock R-9 Wall 0.089 se 2.58 2.16 36 36 93 78 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 se 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 se 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 sw 2.58 2.16 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 11.02 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 13.86 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 sw 8.70 9.17 0 0 0 0 0 0 0 0 Impact,Low-e 0.310 sw 0.00 0.00 0 0 0 0 0 0 0 0 Block R-9 Wall 0.089 nw 2.58 2.16 0 0 0 0 0 0 0 0 G Impact,Low-e 0.300 nw 8.70 25.80 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 17.19 0 0 0 0 0 0 0 0 Impact,Low-e 0.300 nw 8.70 18.66 0 0 0 0 0 0 0 0 D Door,MU FbrcilTvue 0.127 nw 0.00 0.00 0 0 0 0 0 0 0 0 P Block R-9 Wall 0.089 0.00 0.00 0 0 0 0 0 0 0 0 C AttiG Shingle Roof, 0.034 0.99 1.80 52 52 51 93 14 14 14 25 F On grade depth,Tile 0.989 28.68 0.00 52 5 129 0 14 4 100 0 6 c)AED excursion -5 -3 Envelope loss/gain 273 166 186 83 12 a) Infiltration 97 29 75 22 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 370 195 262 106 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 -262 -106 14 Subtotal 370 195 0 0 15 Dud loads 39% 39% 1451 76 39% 39% 0 0 Total room load 515 271 0 0 Air required(dm) 1 29 141 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ �� rigF�tsoft° 2021-Apr-0618:35:16 ACCP. ..HVAC\T Right-Sute®Urrversal 2021 21.0.03 RSU27054 Page 9 BD Dun Rd PSL Gardner Residence GBI.r p Calc=MJ8 Front Door faces: N Air Calcs LLC Duct System Summary Job: 672 Date: Feb 12,2020 Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.561 /0.139 in H2O 0.561 /0.139 in H2O Lowest friction rate 0.261 in/100ft 0.261 in/100ft Actual airflow 185 cfm 185 cfm Total effective length(TEL) 268 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln(ft) Trunk G Bath h 1147 47 24 0.265 4.0 Ox 0 VI Fx 12.1 200.0 st1 G House-A c 1847 87 99 0.264 6.0 Ox 0 VI Fx 12.8 200.0 st1 G House-B c 1847 87 99 0.261 6.0 Ox 0 VI Fx 14.7 200.0 st1 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1 PeakAVF 221 221 0.261 634 8.0 0 x 0 VinlFlx TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening(in) Matl Trunk rb7 Ox0 221 221 53.2 0.261 501 9.0 Ox 0 VIFx wrightsoft® 2021-Apr-0618:35:17 M;.ek „n"e a«awa.=mP=. Right-Sute®Uriversal 2021 2l.O.O3 RSU27054 Page 1 ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Air Calcs LLC Duct System Summary Job: 672 Date: Feb 12,2020 House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Heating Cooling External static pressure 0.70 in H2O 0.70 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.70 in H2O 0.70 in H2O Supply/return available pressure 0.534/0.166 in H2O 0.534/0.166 in H2O Lowest friction rate 0.233 in/100ft 0.233 in/100ft Actual airflow 1317 cfm 1317 cfm Total effective length(TEL) 300 ft SupplyDetail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln(ft) Trunk Bath2 c 202 11 12 0.237 4.0 Ox0 VIFx 25.1 200.0 st3 Bed 2 h 1451 99 90 0.244 6.0 Ox 0 VI Fx 18.8 200.0 st3 Bed 3 h 3725 253 155 0.244 8.0 Ox 0 VI Fx 19.2 200.0 st3 Great Room c 4760 230 289 0.245 9.0 Ox 0 VI Fx 18.0 200.0 st5 Great Room-B c 4760 230 289 0.246 9.0 Ox 0 VI Fx 17.1 200.0 st5 KitcherdNook c 3612 181 219 0.237 8.0 Ox0 VIFx 24.8 200.0 st4 Kitchen/Nook-A c 3612 181 219 0.236 8.0 Ox0 VI Fx 26.2 200.0 st4 Laundry c 834 8 51 0.495 4.0 Ox0 VI Fx 7.8 100.0 Master Bath h 1021 69 36 0.240 5.0 Ox 0 VI Fx 22.1 200.0 st2 Master Suite h 2070 141 101 0.233 7.0 Ox 0 VI Fx 28.6 200.0 st2 Master Suite-A h 2070 141 101 0.233 7.0 Ox 0 VI Fx 28.9 200.0 st2 wlc h 515 35 16 0.239 4.0 Ox0 VI Fx 23.3 200.0 st3 SupplyDetail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 351 239 0.233 643 10.0 0 x 0 VinlFlx st3 PeakAVF 398 274 0.237 730 10.0 0 x 0 VinlFlx st4 PeakAVF 363 438 0.236 804 10.0 0 x 0 VinlFlx st5 PeakAVF 460 578 0.245 736 12.0 0 x 0 VinlFlx wrightsoft® 2021-Apr-0618:35:17 A AI,Tek=11e,•l"e.a«a..,I.m,,�, Right-Suite®Urrversal202121.0.03RSU27054 Page ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening(in) Matl Trunk rb3 Ox 0 317 219 71.3 0.233 580 10.0 Ox 0 VI Fx rb2 Ox0 99 90 41.8 0.398 502 6.0 Ox 0 VIFx rb1 Ox 0 253 155 49.5 0.336 573 9.0 Ox 0 VIFx rb5 Ox 0 911 1115 36.5 0.456 511 20.0 Ox 0 VI Fx wrightsoft® 2021-Apr-0618:35:17 A AI,Tek=11e,•l"e.a«a..,C.m,,�, Right-Sute®UNversal202121.0.03RSU27054 Page ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Manual S Compliance Report Job: 672 Air Calcs, LLC p Date: Feb 12,2020 Guest House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 4144 Btuh Entering coil DB: 76.1°F Outdoor design WB: 77.4°F Latent gain: 1118 Btuh Entering coil WB: 63.1°F Indoor design DB: 75.0°F Total gain: 5262 Btuh Indoor RH: 50% Estimated airflow: 185 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Generic Model: SEER 18.0,HSPF 9.1 Actual airflow: 185 cfm Sensible capacity: 3875 Btuh 94%of load Latent capacity: 1661 Btuh 149%of load Total capacity: 5535 Btuh 105%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 5400 Btuh Entering coil DB: 69.5°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Generic Model: SEER 18.0,HSPF 9.1 Actual airflow: 185 cfm Output capacity: 5508 Btuh 102%of load Capacity balance: 39 °F Supplemental heat required: 0 Btuh Economic balance: -99 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Apr-06 18:35:17 A —=ek=1ae,•.--1—,C.mP Right-Sute®Universal 202121.0.03RSU27054 Pagel ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N Manual S Compliance Report Job: 672 Air Calcs, LLC p Date: Feb 12,2020 House By: Vicki Lynne Barenberg Air Calcs, LLC 7550 Hidden Hammock Ln,Vero Beach,FL32966 Phone:772.800.8413 Email:vickilynne@aircalcs.com Project Information For: Gardner Residence,Groza Builders,Inc TBD Dunn Rd,Port St Lucie,FL 34983 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 26852 Btuh Entering coil DB: 76.6°F Outdoor design WB: 77.4°F Latent gain: 7560 Btuh Entering coil WB: 63.8°F Indoor design DB: 75.0°F Total gain: 34411 Btuh Indoor RH: 50% Estimated airflow: 1317 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: 14ACX-041-230*+CBA27UHE-048-230*++TDR Actual airflow: 1317 ch Sensible capacity: 27650 Btuh 103%of load Latent capacity: 11850 Btuh 157%of load Total capacity: 39500 Btuh 115%of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 24778 Btuh Entering coil DB: 68.5°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Elec furnace Manufacturer: Model: Actual airflow: 1317 cfm Output capacity: 0 Btuh 0%of load Temp.rise: 0 °F Meets all requirements ofACCA Manual S. wrightsoft, 2021-Apr-06 18:35:17 A —=ek=Iae,-"e--.,I—— Right-Sute®Universal 2021 21.0.03 RSU27054 Page 2 ACCP. ...HVAC\TBD Dun Rd PSL Gardner Residence GBI.rup Calc=MJ8 Front Door faces: N