FL # FL10758-RS
Application Type Revision
Code Verslon 2a20
Application Status Approved
Comments
Archived
Product Manufacturer
Address/Phone/Erna-it
Authorized Signature
Technical Representative
Address/Phone/Emall
Quality Assurance Representative
Address/Phone/Email
Category
Subrategory
Compliance Method
Florida Engineer or Architect Name who developed
the Evaluation Report
Florida License
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Owens Corning
One Owens Corning Parkway
Toledo, OH 43659
(740)404-7829
greg-keeler@owenscorning.com
Greg Keeler
9reg.keeler@owenscornirig.com
Greg Keeler
2790 Columbus Road
Granville, Olt 43023
(740) 321-6345
greg.keeIer@OWenscorning.com
Roofing
Roofing Accessories that are an Integral Part of the Roofing System
Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Zachary R. Priest
PE-74021
PRI Construction Materials Technologles, LLC
12/31/2024
Steven M. Urich, PE
-, Validation Checklist - Hardcopy Received
FLI0758 R8 COI_DCR140O3.4 Z020 FBC Eval Vents finalf
https_//www_floridabuilding_orgipr/pr_app_dtl.aspx?param=wGEVXQwtDgrrtdAvIteOYOf2hC3xFtrydggfPhgLACiVmFHfXgoD3ASJQ%3dJ3d page i of 3
Certified By
Sections from the Code
1708.2
Product Approval Method Method 2 Option B
Date Submitted
08JIG/2020
Date Val ldated
12/16/2020
Date Pending FBC Approval
09/18/2020
❑ate Approved
12/17/2020
FL # Model, Numiser or Name
10758.1 VentSure 4-Foot Strip Heat and
Moisture Rldge Vents
Llmits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: NIA
Design Pressure: N/A
Other: Refer to evaluation report
10758.2 EVentSure Low Profile Slant Back
f Roof Vent With Exterior Louver
._........... _
Limits of Use
Approval for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: NIA
Other: Refer to evaluation report.
10758.3 1 Ventsure Rigid Roll Ridge Vent
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: N/A
Other: Refer to evaluation report,
Description
Copolymer plastic low profile attic ridge vents for installation
In shingle roof systems
Installation Instructions
FL10758 R8 II OCR14003.4 20 20 FBC Eval Vent firlalF
Verified By: Zachary R, Priest 74021
Created by Independent Third Party: Yes
Evaluation Reports
FLID758 R8 AE OCRiA .4 202 FBC val Vents final df
Created by Independent Third Party: Yes
Galvanlzed metal roof vent
Installation Instructions
FL10 _U R6 LZ_ Qr.R 14QO3.4 2 120 FSC -val V n s E _pdf
Verified By. Zachary R. Priest 74021
Created by Independent Third Party: Yes
Evaluation Reports
)�L107513_R9 AF—4 2 FBC Evall Vents f _per
Created by Independent Third Party. Yes
Ridge Ventilation System
Installation Instructions
LE 1075_R8 11—C)CR141003.4 2 2Q F C Ev I V fin . df
Verified By: Zachary R. Priest 74021
Created by Independent Third Party: Yes
Evaluation Reports
EL10758 R8&E_0 R4003.4 2024. FBC oval Van c [ina! :per
Created by Independent Third Party: Yes
back hIr_rt
C4nlad Lis 2501B121 Stone 003 i,.7a4ahassoatL 373ao Phnne: asa aa7_in1.r
The State of Florida is an AA�l employer. Cap%"; }t},007-2D13 smt1nr r-i��,na . - Pr, n := Scesslhdlty Sratemenr :: Refund to nt
under Fle ride law, email addresses are public records. If you do not want your e-rrieil address released in response to a pub l ic-reoords request, do not send electronic
maR to this entity, Instead, contact the office by phone or by traditional mall. if you have any questions, please rontart 850.487.1395- "'Pursuant to Section
455.275(I), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address If they have
One. The emalls provided may be used For offECiai communication with the Ilceril Now over email addresses are public record If you do not wish to supply a
personal address, please provide the Department with an email address which can be made ava ill We to the pub ltc. To determine if you are a licensee under Chapter
455, F S-, pfea se click here .
Product Approval Accepts:
M �::] 'G—iii F]
https_l/www.flortdahullding.org/prIpr_app_dtl.aspx?param=wGEVXQwtD4vIdAviteOYOl2hC32Ptrydg9fPhgLACiVmrHfXgoa3A5JQ ,3d13d
Page 2 of 3
Cfedit cni d
Safe
https_//www_floridabullding.❑rg/pr/pr_app_dd-aspOparam=wGEVXQwtDgvfdAviteOYC%2hC3zFtrydggfPhgLACiVmFHfXgoD3A5JQ%3d%3d Page 3 of 3
� • CREEK
Certificate pf Authorization No. 29824
(r 17520 Edinburgh Dr
... Tampa, FL 33647
TECHNICAL SERVICES, LLC (913) 480-3421
EVALUATION REPORT
FLORIDA BUILDING CODE, 7" EDITION (2020)
Manufacturer:
OWENS CORNING ROOFING AND ASPHALT LLC Issued December 15. 2020
1 Owens Corning Parkway
Toledo, OH 43657
(800) 438-7465
www.a,venscornin ,gM
Quality Assurance:
PRI Construction Materials Technologies (QUIA9110)
$CaAE
Category:
Roofing
Subcategory:
Roofing Accessories that are an Integral Part of the Roofing System
Code Sections:
1708.2
Properties:
Roof Ventilation
REFERENCES
ErAL
Report No.
Standard
Year
Architectural Testing, Inc (TST1558)
01 38660.04
TAS 100(A)
1995
Architectural Testing, Inc (TST1558)
01-38660-05
TAS 100(A)
1995
Archltectural Testing, Inc (TST1558)
C1774.01-109-18
TAS 10C(A)
1995
ASTM D 635
2014
ASTM D 1929
2016
PRI Construction Materials Technologies (TST5878)
AVIG-005-02-01
ASTM D 2843
ASTM D 635
2016
2014
ASTM D 1929
2016
PRI Construction Materials Technologies (TST5878)
AVIG-006-02-01
ASTM D 2843
ASTM G 155
2016
2013
PRI Construction Materials Technologies (TST5878)
OCF-111-02-01
ASTM D 635
2014
ASTM D 1929
2016
PRI Construction Materials Technologies (TST5878)
OCF-112-02-01
ASTM D 2843
ASTM G 155
2016
2013
PRI Construction Materials Technologies (ST5878)
OCF-116-02-09
TAS 100(A)
1995
PRI Construction Materials Technologies (TST5878)
OCF-223-02-01
TAS 100(A)
1995
PRI Construction Materials Technologies (TST5878)
OHI-007-02-01
TAS 100(A)
1995
OCR14003.4 FL10758-R8 Pa e 1 of 5
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
f a CREEK
TECHNICAL SERVICES, LLC
PRODUCT 1)ESCRIPTION AND APPLICATION
GWENS CORNING
VentSureO Roof Ventilation
VentSure" 4-Foot Strip 1-114" x 14-718" x 48" low -profile attic ridge vent consisting of a two -layer nylon -
Heat and Moisture Ridge polyester composite- Available vwith or without a polyester fabric moisture barrier for
Vents: installation in shingle roof systems.
irI!i
i
77L6�!1PJp�uak ■Itl llflr]! 1. ++ iva;i`a.. ;: ::�� tla+ ll rlllr lr If 1! i �
Deck Type: Roof deck shall be constructed of closely fitted sheathing for new or existing
construction. Roof deck shall be designed and installed in accordance with FBG
requirements
Roof slope: Minimum 3:12 to maximum 16112
Installation Height- Maximum 60-ft
Attachment Method: Cut a 2-Inch opening (1-inch on each side of the ridge) centered in the deck at the
ridge for ventilation. The slot shall terminate approximately 6-inches from the rake
edges. Apply a %-inch wide bead of ASTM D 4586 roofing cement along the entire
length of the outside edges of the vent to seal the vent to the field shingles, taking
care to not completely cover the weep slots in the vent. Center the vent over the
opening and fasten to the deck using the 11 ga. 2'/-inch galvanized ring shank nails
(shall comply with FBC Section 1506.5) provided with the vent. Fasteners are to be
installed on both sides of the vent 1, 12, 24, 36, and 47-inches from the start of each
vent piece.
Prepare the adjacent vent section by applying the roofing cement along the edges,
snap together with fixed vent, and fasten to the deck in the same manner as the first
section. Fasten the ridge shingles over the vent to the deck on the marked "shingle
nail line" with two (2) minimum 11 ga. 2'/2-inch galvanized ring shank roofing nails
(shall comply with FBC Section 1506.5) provided with the vent or as directed by the
shingle manufacturer's installation instructions.
Allowable Roof Coverings: Asphalt shingles
OCR14003.4 FL10758-RS Pa e 2 of 5
This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid
This evaluation report does not express nor mply warranty, installation, recommended use, or other product attributes that are not
a� CREED
owEnls coRNlrvc
TECHNICAL SERVICES, t,LC VentSuree Roof Ventilation
VentSureW'3 Low Profile 18' x 24' x 2-3116" (32" x 23" flange base) static off -ridge vent composed of ASTM
Slant Back Roof Vent A653 galvanized steel (available with painted finish). Material shall conform with
with Exterior Louver: FRG Section 1507.4.3.
�'
jZg
Dock Type: Roof deck shall be constructed of closely fitted sheathing for new or existing
construction- Roof deck shall be designed and installed in accordance with FBC
requirements_
Roof slope- Minimum 3:12
Installation Height: Maximum 33-ft
Attachment Method: Cut an 11 x 11-inch hole through wood sheathing only approximately 18-inches from
the ridge. Apply 114-inch thick by 3-inch wide bed of ASTM D 4586 roofing cement
around inner and outer flange. Race vent directly over the hole, ensuring the vent
sits flat on the roof_ Fasten vent 4-inches a.c. and 1-inch from outside edge of flange
with minimum 12 ga. ring shank roofing nails (shall comply with FBC Section
1506.5), ensuring %-inch penetration through wood deck (Minimum 18 nails per
vent).
Install baffle in %-inch bed of ASTM D 4586 roofing cement and secure with
minimum 12 ga. ring shank roofing nails (shall comply with FBC Section 1506.5)
spaced 8-inches o.c. (total of (3) nails) while ensuring %-inch penetration through
wood deck. Seal all nails and vent flange with ASTM D 4586 roofing cement.
Allowable Roof Coverings: Asphalt shingles
OCR14003.4 FL1 D758 R8
This evaluation repun is provided for State of Florida product approval under Rule 61020-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product Changes or quality assurance changes throughout the duration for which this report is valid
This evaluatlon report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
CREEKGWENS CORNING
i..�',u'M VentsuraS Roof Ventilation
.,:i TECHNICAL SERVICES, LLC
VentSureo Rigid Roll 518' x 11-1/4" x 20' attic ridge vent composed of high density polypropylene with a
Ridge Vent: spun -bond polypropylene fabric -
Deck Type. Roof deck shall he constructed of closely fitted sheathing for new or existing
construction. Roof deck shall be designed and installed in accordance with FBC
requirements.
Roof slope. Minimum 2:12 to maximum 20:12
Instaliation Height: Maximum 60-ft
Attachment Method: Cut a 2-inch opening (1-inch on each side of the ridge) centered in the deck at the
ridge for ventilation. The slot shall terminate approximately 12-inches from the rake
edges. Apply a continuous bead of polyurethane adhesive sealant along the entire
length of the outside edges of the vent to seal the vent to the field shingles. Center
the vent over the opening and fasten the vent 24-inches o,c. to the deck using
minimum 12 ga. ring shank roofing nails (shall comply with FBC Section 1506.5).
ensuring %-inch penetration through wood deck.
Fasten the ridge shingles over the vent to the deck on the marked "shingle nail line'
with two (2) minimum 12 ga. ring shank roofing nails (shall comply with FBC Section
1506.5) or as directed by the shingle manufacturer's installation instructions,
ensuring 1/4-inch penetration through wood deck. Outside edges of the shingles shall
be sealed with flashing cement.
Allowable Roof Coverings: Asphalt shingles
LwTATioms
1) This report is not for use in the HVHZ.
2) Fire Classification is outside the scope of this evaluation
-
3) The roof deck and deck attachment shall be designed by others in accordance with the FBC.
4) Owens Corning vents shall be installed in strict compliance with this evaluation report and the
manufacturers published installation instructions. In the event of conflict, the more restrictive installation
shall be enforced.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion prior to installation.
6) Installation of the roof assembly is outside the scope of this evaluation.
7) Owens Corning vents are intended to provide passive ventilation for an enclosed attic in residential
construction applications.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
OCR14003.4 FL10758-RB Page a of 5
This evaluation report is provided for Stata of Florfda product approval under Rule 61G20-3. The manufacturer shall notify CREEK
TeChnical Services, LLC of any product changes or quality assurance changes Ihrougheut the duration for which this report is valid.
This evaluatlon report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
� CREEK
....<' TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
OWENS CORNING
VentSure(D Roof Ventilation
'rho products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 71h Edition (2020) as evidenced in the referenced documents submitted by the named manufacturer.
•;1'�"1e� rill p frf'�
�i Z 1!
No 74021
STATE OF
�D
CERTIFICATION OF INDEPENDENCE
2020.12.15
1 3:59:34
—V5'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services. LLC Is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
❑CR14003.4 FL10758-R8 Pa e 5 of 5
This evaluation report is provided for State of Florida product approval under Rule 61G20-3 The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid_ This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
�..o.•iFr oll, nr(rirac oc.-! L.oroin