Manufacturer: Viwinco, Inc.
Morgantown Business Park
P.O. Box 499
Morgantown, PA 19543
Product Line: Signature/Viwinco Fixed 72" x 84" — Non -Impact
Engineering Evaluation Report
Report No.: 513383A
Compliance:
The above mentioned product has been evaluated for compliance with the requirements of the Florida Department of
Business and Professional Regulation for Statewide Acceptance per Rule 61 G20-3.005 method 1(a). The product listed
herein complies with requirements of the Florida Building Code.
Supporting Technical Documentation:
1. Approval document: drawing number 08-02604, prepared, signed and sealed by Luis Roberto Lomas P.E.
2. Report No.: ATI 73934.01-109-47-R1 signed by Michael D. Stremmel P.E.
Architectural Testing Inc., York, PA
AAMA/WDMA/CSA 101/I.S.2/A440
Design pressure: ±55.17psf
Water penetration resistance 12.12psf
3. Anchor calculations, report number 513383-1, prepared, signed and sealed by Luis Roberto Lomas P.E.
Limitations and Conditions of use:
• Maximum design pressure: ±55.Opsf
• Maximum unit size: 72" x 84"
• Units must be glazed per ASTM E 1300
• This product is not rated to be used in the HVHZ.
• This product is not impact resistant and requires impact protection in wind borne debris regions.
• Frame material to be rigid PVC.
Installation:
Units must be installed in accordance with approval document, 08-02604.
Certification of Independence:
Please note that I don't have nor will acquire a financial interest in any company manufacturing or distributing the
product(s) for which this report is being issued. Also, I don't have nor will acquire a financial interest in any other entity
involved in the approval process of the listed product(s).