Loading...
HomeMy WebLinkAboutDuct Leakage Test Results Permit 2003-0366 4.6.2021 - SIGNEDDuct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: Job Information Builder: Address: SFR - 4710 Palmetto Dr City: Fort Pierce Duct Leakage Test Result s 0 System 1 30.7 cfm25 System 2 cfm25 System 3 cfm25 Sum of any cfm25 Total of all 30.7 cfm25 30.7 _ 1280 = .024 Qn Total of all Total Conditioned systems Square Footage PASS FAIL Community: Permit #: 2003-0366 State: FL Prescriptive Method Lot: NA Zip: 34982 0 Performance/ERI Method 0 Prescriptive Method cfm25 (Total) To qualify as "substantially leak free" Qn Total must be less than or equal to 0.04 if air handler unit is installed. If air handler unit is not installed, Qn Total must be less than or equal to 0.03. This testing method meets the requirements in accordance with Section R403.3.3. Is the air handler unit installed during testing? ❑ YES (` On) ❑ NO (`on) Performance/ERI Method cfm25 (Out or Total) To qualify using this method, Qn must not be greater than the proposed duct leakage Qn specified on Form R405-2017 or R406-201 Leakage Type selected on Form Qn specified on Form R405-2017 R405-2017 (EnergyCalc) or R406-2017 (EnergyCalc) or R406-2017 Proposed Leak Free 0.03 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Testing Company Company Name: E-Calcs Plus, Inc. Phone: 239-810-6106 1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Digitally signed by Steven Signature of Teste$teven DeAugustino DeAugustino Date of Test: April 6, 2021 a e: 202 1.04.06 1 6.M:18-04'00' Printed Name of Tester: Steven DeAugustino License/Certification #: 5065542 Issuing Authority: BPI 4/6/2021 4:01:18 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1