HomeMy WebLinkAboutDuct Leakage Test Results Permit 2003-0366 4.6.2021 - SIGNEDDuct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction:
Job Information
Builder:
Address: SFR - 4710 Palmetto Dr
City: Fort Pierce
Duct Leakage Test Result s 0
System 1 30.7
cfm25
System 2
cfm25
System 3
cfm25
Sum of any
cfm25
Total of all 30.7
cfm25
30.7
_ 1280 = .024 Qn
Total of all
Total Conditioned
systems
Square Footage
PASS FAIL
Community:
Permit #: 2003-0366
State: FL
Prescriptive Method
Lot: NA
Zip: 34982
0 Performance/ERI Method
0 Prescriptive Method cfm25 (Total)
To qualify as "substantially leak free" Qn Total must be less than or
equal to 0.04 if air handler unit is installed. If air handler unit is not
installed, Qn Total must be less than or equal to 0.03. This testing
method meets the requirements in accordance with Section R403.3.3.
Is the air handler unit installed during testing? ❑ YES (` On) ❑ NO (`on)
Performance/ERI Method cfm25 (Out or Total)
To qualify using this method, Qn must not be greater than the
proposed duct leakage Qn specified on Form R405-2017 or R406-201
Leakage Type selected on Form Qn specified on Form R405-2017
R405-2017 (EnergyCalc) or R406-2017 (EnergyCalc) or R406-2017
Proposed Leak Free 0.03
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
Testing Company
Company Name: E-Calcs Plus, Inc. Phone: 239-810-6106
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method.
Digitally signed by Steven
Signature of Teste$teven DeAugustino DeAugustino Date of Test: April 6, 2021
a e: 202 1.04.06 1 6.M:18-04'00'
Printed Name of Tester: Steven DeAugustino
License/Certification #: 5065542
Issuing Authority: BPI
4/6/2021 4:01:18 PM EnergyGauge® USA 6.0.04 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1