HomeMy WebLinkAboutConstruction Plans1. 24 GAGE GALVANIZED STEEL STORM PANELS. .,.STEEL SHALL CONFORM TO ASTM A653, STRUCTURAL QUALITY GRADE 40, WITH G60 GALVANIZED COATING AND. MINIMUM Fy=44 KSI. 2. THIS SYSTEM HAS BEEN TESTED AND EVALUATED AS A LARGE MISSILE IMPACT. PROTECTIVE SYSTEM COMPLYING WITH SECTION 1609.1.4 OF THE 2007 FLORIDA BUILDING CODE AND ASTM STANDARDS E1886/E1996 &E330',PROVEN PERFORMANCE IS MISSILE LEVEL 'D', WIND ZONE 3, 3. THESE'PR❑DUCT EVALUATION DOCUMENTS ARE PREPARED BY THE PRODUCT ENGINEER AND ARE GENERIC. THEY DO NOT INCLUDE INFORMATION PREPARED FOR A SPECIFIC SITE. 4. USE OF THESE APPROVAL DOCUMENTS SHALL COMPLY WITH CHAPTER 61GIS-23 OF THE FLORIDA ADMINISTRATIVE CODE. 5, THE 33-1/3% INCREASE IN ALLOWABLE STRESS S N BEEN USED IN THE DESIGN OF THIS PRODUCT, 6. PERMIT HOLDER SHALL VERIFY THE ADEQUACY OF THE EXISTING STRUCTURE TO WITHSTAND ANCHORAGE LOADS IMPARTED TO THE STRUCTURE. 7. ALL ALUMINUM EXTRUSIONS SHALL BE 6063-T6 •UNLESS OTHERWISE NOTED. TOP & BOTTOM MOUNTING DETAILS MAY BE INTERCHANGED AS FIELD CONDITIONS DICTATE. PANELS MAY BE MOUNTED HORIZONTALLY WHERE APPLICABLE. 8. ALL BOLTS & WASHERS SHALL BE ZINC .COATED STEEL, GALVANIZED STEEL, STAINLESS STEEL OR 2024-T4 ALUMINUM ALLOY WITH A MINIMUM TENSILE YIELD STRENGTH OF 33 KSI. 9. STORM . PANELS ARE NOT AIR PERMEABLE. THEREFORE, MINIMUM SPACING BETWEEN PANES AND GLAZING IS NOT REQUIRED. FRACTURE OF GLAZING IS ACCEPTABLE WITH THIS PRODUCT. 10. SHUTTER'S MANUFACTURER LABEL SHALL CONTAIN THE MINIMUM INFORMATION OF: TOWN & COUNTRY INDUSTRIES - - - - -FT. LAUDERDALE, F.ORI LDA _ _ LIMITATIONS THIS PRODUCT HAS BEEN EVALUATED AND IS IN COMPLIANCE WITH THE 2007 FLORIDA BUILDING CODE EXCLUDIN 'HIGH VELOCITY HURRICANE ZONE., MISSILE IMPACT TESTING WAS PERFORMED TO WIND ZONE 3 (BASIC WIND SPEED < 140 MPH) MISSILE LEVEL D REQUIREMENTS. THIS PRODUCT HAS NOT BEEN EVALUATED FOR ENHANCED PROTECTION OF ESSENTIAL FACILITIES AS DEFINED IN ASTM E1996. TYPICAL ELEVATION 24 GA. STEEL STORM PANEL TYPICAL PLAN VIEW 2-PANELS SHOWN 0 4) NOTCH VERTICAL - LEG ONLY AS REQUIRE "U" HEADE SEGMENTS mw& Rm. my (am" .J "" \ { T— .0 .0 " 1 .6 KEYHOLE PUNCH WITH FOR �APPROVED_BOTTOM MOUNT CONNECTION RADIUS "U" HEADER WING NUT (TYP) OR APPROVED ANCHOR (TYP) O Ln vm mO n LjC� tl� Q a z ° tz a, a, a, N -Ya ] Lq c. eo QJiw Wax o, o, u w u :l M � Z d a,x0 x W =Uo �� lzo Cl► A 3�w �iyo tY � � Lj j � LLJ,., W. 0W O 3� ��A W(<r3N psi z 'NF� vu d- .,(LI> J L3 ' W Ld z -O z v/{ a 0 _ J O DATES 28 NOV. 200E DRAWN' I CHECKED ' BWM I ANR PROJECT NUMBER 07070009 08120002 SHEET 1 OF 9 2Z Ozc,-mdcg ZearB L2 EXISTING GLAZING Cl COMMEC77ON ME REFERENCE ANCHOR SCHEDULE FOR MAX SPACING 6L J EMBED C' CONNEC770AI TYPE EX/SANG CONCREIL; HOLLOW REFERENCE ANCHOR BLOCK OR WORD FRAMING (SEE SCHEDULE FOR mAx ANCHOR SCHEDULE BASED ON TYPE OF STRUCTURE) A WALL MOUNT SECTION Cl, CONNECTION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING •4• a a. X+TIDM 1 I ENGINEER MAY DETERMINE ACCEPTABLE BUILD Mn AINM NW D� CONDITIDNS. 5CLEARANCE TO Q-ASS OR DOOR REMARED, UW ESS SIDE CLOSURES ARE PROVIDED. THEN NO REQUIRED,FROf1 GLASS UIl n-nl 17 !I EMBED-J----j DCISnNG CONCRETE; HOLLOW BLOCK OR WOOD FRAMING (SEE ANCHOR SCHEDULE BASED ON TYPE OF STRUCTURE) -- —s in C l CONNECTION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING �p1 BUILD —OUT SECTION SPECIAL NOTES. ANCHOR, ANCHOR EMBED AND ANCHOR EDGE DISTANCE- SHALL BE AS SPECIFIED ON SHEET 819 AND 9/9. ALL ANCHORS SHALL. BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. STORM PANELS ARE NOT AIR PERMEABLE. THEREFORE, MINIMUM SPACING BETWEEN PANEL AND GLAZING IS NOT REOUIRED. FRACTURE OF GLAZING IS ACCEPTABLE WITH THIS PRODUCT 'A Z5 n HEADER IDEY HEADER OR SILL BUILD mff Ol'TMNAL HaB NTING EXTRUSIONS EXISTING GLAZING 0U) WO ' CONNECTION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING Z � O 4Q Z Lu 8 5 � C 1 CONNECDON TYPE ' REFERENCE ANCHOR ��X/STING CONCRUE, HOLLOW SCHEDULE FOR MAX BLOCK OR WOOD FRAMING (SEE SPACING ANCHOR SCHEDULE BASED ON TYPE OF STRUCTURE) "h" HEADER SECTION v o "t 09 .-# ,us o Lj m =r'nn a: o- O a 'g z z Z Lq (L $.. co Nut of w r- c .s�,4 w v u . Iu3rn oc uJ ro I z d m "d ^:ago ¢I—tL W F- =Lyw >- Q o Qo 0 Ld ' � F- � Zn ci -j UL,J� LWL:A Wu). cu Q tU Qs v. r, > Q LD Ir jWz Ld z z ` r . (j c� s m � v 1 Oa a 0 o DATEt 28 NOV. DRAWN11 CHECKEDt BWM I ANR PROJECT NUMBER 06100009 & 07070009 08120002 SHEET 2 QF 9 EDGE DIST. C2 CONNEC7ION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING EMBED Cl CONNECTION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING MAX. L v � 4 GXG oa LAZIN EX GL ZING 5 W 8 WIID 4' EMBED C3 CONNECTION TYPE JSANG CONCREM HOLLOW EDGE REFERENCE ANCHOR - - -BLOCK OR -WOOF fRAM/NG (SEF" D/ST. - --SCHEDULE-FOR MAX - ANCHOR SCHEDULE BASED ON SPACING TYPE OF STRUCTURE) �U" HEADER SECTION / \' C 1 CONNECTION TYPE REFERENCE ANCHOR �XIS7ING CONCRETE, HOLLOW SCHEDULE FOR MAX BLOCK OR WOOD FRAMING (SEE SPACING ANCHOR SCHEDULE BASED ON TYPE OF STRU07URE7 D BUILD -OUT SECTION SPECIAL HEADER SPFCIA NOTES: ANCHOR, ANCHOR EMBED AND ANCHOR EDGE DISTANCE SHALL BE AS SPECIFIED ON SHEET 8/9 AND 9/9. ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS STORM PANELS ARE NOT AIR PERMEABLE. THEREFORE, MINIMUM SPACING BETWEEN PANEL AND GLAZING IS NOT REQUIRED. FRACTURE OF GLAZING IS ACCEPTABLE WITH THIS PRODUCT. EX/SRNG GLAZING C 1 CONNECTION TYPE REFERENCE ANCHOR SCHEDULE FOR MAX SPACING 3" MAX. �r o TM rLit C) O, eyM�: t1. pZ a:g z to o, �.. Wa,Ln ex`da al� (Ap a1 ej U of U tA X � n o) o n ¢ L- L.L. w _C3f/1 )- OO 'QC p AJ� Qom^ 3�a� w rp m o LAJ � ¢ � 1-4 0 WL,3A L- QW Ld ps v LD cu Q �(U>1 J Q L3 EMBED—}----� C 1 CONNEC770N TYPE REFERENCE ANCHOR - - --SCHEWtE-FOR--MAX- ----- - - - - - NG CONCRE7� HOLLOW SPACING y BLOCK OR WOOD FRAMING (SEE ANCHOR SCHEDULE BASED ON TYPE OF STRUCTURE) F BUILD -OUT SECTION SPECIAL HEADER DATEi 28 NOV. DRAWNi I CHECKED, BWM I ANR PROJECT NUMBER D6100009 & 07070009 08120002 eae4, yj►1 SHEET 3 OF 9 � 2 bEGEMa�rC Z oo S EDGE DIST G"PING EMBED EMBED — C2 COAWMlON ME SLY#DtlLE RFOR r SPACING mx I/ C3 CORENFfR£N EE uoyFOR EXISTING CONCRE7 HOLLOW SCHEDULE FOR MX BLOCK OR WOOD FRAYING (SEE' EDGE SPACING ANCHOR SCHEDULE 84SM ON DIST. - - TYPE OF S7RUC7t/R4 -- - - - - -- - sou" HEADER_ SECTION . 1-718' MIN ti cn Q EXISTING GLAZING 2X4WODf 2' EXISTING BRICK MAX I VENEER Cl CWNEC77oN 7WE REFERENCE ANCHOR SCHEDULE MR Max SPACING MAX. EX/S77NG STEEL ANGLE AS APPLICABLE lt! 1 fa a IXl� RICK SILL o a --- (nGs EXISTING GLAZING rG1 COtmcnoN ME RMERMCE ANCHOR S F SPACM �o Z J �z tz ��„� a 0 o Z z iy 0)0,tn 'q a ° OJ C paj g 0, 0, U mu;},. w U-1 m ; zJ a oj, O n QF_L- x W �U�• 1-p}' DO Oihq A .!0 Q rn O WtW7A LL � LL. Q N Wes~ (U 4 r,(U> J Q - l7 V L / I C 1 CWNEVMN TYPE 1 " MIN EXISTING FLASHING CONNECTION TYPE / m, REFERENCE ANCHOR AS APPLICABLE C 1 REFE7rEnICE ANCHOR NO CONCRETE; HOLLOW SCHEDULE A� FOR AW PENETRATIONU SCHUME FOR MAX MOM OR Mn FRAYING (SEE TYPE OF STRUC7URE IXIS?7NG 2 X 4 WOOD EXISTING 1/2" MIN PLYWOOD REQ. � _ _ _ ACM ANCHOR ��� j� � STUDS-.® iaa O.C. MAX WITH FASTENING -TO STUDS "F" TRACK MOUNTING H BUILD -OUT SECTION BRICK VENEER SPECIAL NOTES: ANCHOR, ANCHOR EMBED AND ANCHOR EDGE DISTANCE SHALL BE AS SPECIFIED ON SHEET 8/9 AND 9/9. ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS STORM PANELS ARE Q AIR PERMEABLE THEREFORE, MINIMUM SPACING BETWEEN PANEL AND GLAZING IS NOT REQUIRED. FRACTURE OF GLAZING IS ACCEPTABLE WITH THIS PRODUCT. Z� O M"IIII DATEc 28 NOV. 200i DRAWN, 1 CHECKEBi BWM ANR • PROJECT NUMBER 06100009 & 07070009 08120002 SHEET 4 OF() :a Z .266 8 125 0.024" , ,�» \ » 1.G5» 4•�-j'.25 2.401 " 1� 2 � 0.50" 0.50" ------ 4.834 — �-� 12 COVERAGE 13.83" TOTAL WIDTH - (iyl2z" PANEL PROFILE --f 2.25" --- 0.062" rep. 0.375" 2.00" r�F. 3 "U" HEADER 0.0s3" (rya) 114-20 MACHINE SCREW o STUD ® 6" o = N O 1.25" 2" 0.024" t �6" COVERAGE 1a b" PANEL PROFILE NOTE, CAN ONLY BE USED AS AN END PANEL TO CLOSE THE REMAINING OPENING THAT MAY BE LESS THAN A FULL PANEL WIDTH 3.375" - (See Note 1) N 0.086" 1YP 2. o00 BUILD -OUT 5 STUDDED ANGLE 6 "F" TRACK 0.368" .170" 3.000" - -- - 0.312" Lr) �0 0.657" L Ao 8680 67" rO.O. o. l3o"T�� 418" REVERS ED FRONT n 1/4"-20 SQUARE HEADED BOLT NOTES: SaLIRACK 1) TESTING QUALIFIES 1' AND 2' LENGTHS ALSO 2> TESTING QUALIFIES AS -TESTED EXTRUSION THICKNESS AND THICKER (see Note 1) .125 "TYP. 70,a 2" MIN, 5" MAX v o �� 0 co 2.187" 4 Li M a eyn� O Z Q- a N g� z .a88" 5�qn o UI N TYP R .250" s < > 'A v a Ucs N m c d 0 4 2.000" (::2 "h" HEADER ALUMINUM ANGLE � BUILD-OUT/CLOSURE 2.25" . 368" 0.170" F 740 "� 0.312" 3.870 "094 I TYP. 1.25„ 0 1.675" 0.657„ N 0.094" 2.00" 15 SPECIAL BUILD -OUT HEADER 16 "F" TRACK 0.079" 1. 7» 0.215" (:$)_W NG NUT w 3: O Q F- ?��Q UweLd =.A.. W4� 3 WnW z d- .Nw (tJ j 0 DATEl 28 NOV. 13RAWNi I CHECKED DWM ANR PROJECT NUMBER 0s100009 8, 07070009 08120002 SHEET 5 OF 9 2 Z OE CEA0,64,4 2a SELECTED ASSEMBLIES OF COMPONENTS i4"-20 sidewalk SELECTED ANCHOR. S Bolt W/Nut @ 12 O.C. or # 14 SMS. @ 8 " O.C. (a) mq=mmm 1/4' X 2-1/2' PANELMATE (MALE) BUILD -OUT WITH "U" HEADER ,Y422 —20 Sidewalk Bolt W/Nut @ 12" O.C. or #14 SMS @ 8" O.C. BUILD -OUT WITH STUDDED ANGLE / 4"-20. Sidewalk Bolt W/Nut @ 12 O.C. or # 14 SMS @ 8" O.C. bUILU-UU I WITH REV. "E" (b) 1/4' X 7-3/8' PANELMATE (MALE) FOR BRICK VENEER t°� I!s!'lC:lhil'';iliill',l';i1'•:1lY�ll'tl'iiU1 • �;��+�tlpli1�:11111tt1}1C+Il';tl'rd!,111 i�1�113; 1 1/4' X 2--1/2' PANELMATE (FEMALE) 1/4' X 2-1/4' SAMMY ANCHOR (FEMALE) 1/4' X 2-1/2' QUICKSET CONCRETE ANCHOR 1/4' X 2-1/2' TAPCON 1/4' x 2-1/2' WOOD LAG SCREW 1/4'-20 X 5/8' SLOTTED BRASS BUSHING (FEMALE) 1/4'-20 X 2-1/8' PANELMATE INSERT 1/4'-20 X 1' TAMPIN M ® A Lj W (L 6z o,sg .z NG)tA S Y a > Ul vG. g U I'j}r cy-UJ ' d tn 0,, X 0 ►- u. w: =vim o0 AJ� tQ 3�� mho LJ �::D 0 WL3A 3C�)� WA N os H U ¢ c(u > J p Ps jcf) Q Q) Z R 1/4'-20 X 1/2' to 2--1/2' SIDEWALK S.S. BOLT DATEi 28 NOV. DRAWNi I CHECKED BWM I ANR PROJECT NUMBER 06100009 & i } �07070009 08120002 SHEET 6 OF 9 2a big-ciHe4P 20of PUNCH 5/16" DA. HOLE IN ADJACENT PANELS TO RECEIVE 1/4 =2D SIDEWALK BOLTS PLACE PANEL OVER EACH ADJACENT PANEL AND FASTEN WINGNUTS FROM THE INSIDE (TYP). DRILL 5/16" 0 HOLES AT 6" OC IN. 28" X 7" X 1/8" 6061—T6 ALUMINUM PLATF 7/8" WASHERED WING —NUT TWO UFE SAFETY STORM PANELS SHALL BE CUT 2" SHORTER THAN ALL OTHER ADJACENT PANELS t 6061—T6 ALUM. PLATE EMBED. FIRE EGRESS PANEL C3 COMEMM ME RE7MRENCE ANCHOR SCHEDIxE FOR mAx EXISTING STRUCTURE INTERNAL MOUNT CA13111W STHUCTURE EXTERNAL' MOUNT DNNELAON TYPE ommvCE ANCHOR CHSWXE FOR MM 17ACIM 2'-4" 2"� .511600 HOLE FOR " FASTENING PANEL 2 " -- 0--- e . a ) WALL MOUNT 1 MAX. (MAY NOT EXCEED STORM PANEL SPAN TABLE) n � v u� m d 0% o n Lilo~ n n 4 O z lz >u°iir_ 0. 0,icm ran i_uJ ca j ZJ 6 IAa m 6 i N,X O n x W N hp>' O�� 1�5^ AJN 3yW cj� a\ Qua h WL:)ta LL- I.. WAN (U ¢ l7 O DATE, 28 NOV. DRAWN CHECKED, BWM AMR PROJECT NUMBER 06100009 & 07070009 08120002 z.� vccEye�,Q �oOY SHEET 7 OF 9 �sbrOW P V AWWW PANEL WH 1/4-20 8MM * WA90M WNGNU75 AT 24' as (m) FAM Pwas 7O HOSr AN Y SIRUC7URE OR 70 MWEp 7O COMB? (EACH 500 CORNER CLOSURE PLAN VIEW J � f14 I---2' TO s' J/sue 1114• —T wx r/2- MIAL MMAP ANCHORS AT 0.G SPACING FROM ANCHOR SCHEDULES TRAP MOUNT CLOSURE PLAN VIEW ANCHORS AT i FROM ANCHOR 114" / 114" _MAX MAX �4�-EXIS77NG _T. EXIST STRb HOST STRUCTURE v v.—v . V . WALL MOUNT CLOSURE MOUNT CLOSURE - PLAN VIEW PLAN VIEW ANCHOR SCHEDULE Anchor Schedule., 12" Storm Panel Maximum Allowable Fastener Spacing in Inches Min. 3/4" Edge _ . Distance, -Spans 4'-0" to 12'-0" w cn Connection Type Anchor Type Installation Type C1 C2 C3 1/4" O Lag Screw, 1-27/32" Wall Mount 18 6 5 Min. Thread Penetration, guild Out 18 11 10 Shear Parallel or Egress Panel 18 12 11 Perpendicular to Wood Grain 114" 0Textron Panel -We, I- Wall Mount 18 11 10 0 7/8" Min. Penetration, 1/4-20 Build Out 18 18 18 Q Machine Screw for Female, Egress Panel 18 18 18 114-20 WWN for Male All Points Brass Wood Wall Mount 7 7 .6 Bushing, 1-1/8" Embedment, 1/4" o - 20 x 5/8" Sidew alk Build Out 14 14 12 Egress Panel 15 15 14 Bait SEE SHEET 9 OF'9 FOR ADDITIONAL ANCHORS )0 x M ANGLE - SPAN TABLE 12" Storm Panel Allowable Design Wind Pressure -- Span---- Le th -Wall—Mount P.S.F. -Build-Out - P.S.F. Egress - Panel- — P.S.F. 4'-0" +134.0, -145.0 +67.0, -78.0 +60.5, -70.5 5'-0" +107.2, -116.0 +53.6, --62.4 +48.4, -56.4 6-0" +89.3, -96.7 +44.7, .52.0 +40.3, -47.4 7'-0" +76.6, -82.9 +38.3, -44.6 +34.6, -40.3 8'-0" +67.0, -72.5 +33.5, -39.0 +30.2, -35.2 9'-0" +59.6, -64.4 +29.8, =34.7 +26.9, -31.3 10'-0" +53.6, -58.0 +26.8, -31.2 +24.2, -28.2 11'-0" +48.7, -52.7 +24.4, -28.4 +22.01-25.6 12'-0" +44.7, -48.2 1 +22.3, -'26.0 +20.2, -23.5 v fa i �4 o? 5 tin n d O O IN . Z Z ra C co MoO ApXL ti W. S t— L,.. » ~ O p�Q H0 A_JW 3�w w0E- > 14 W C �Qp� W� to L3A 1t.. Q bi . Wt:)H OS Ov (U Q ._, (U J l7 DATE, 28 NOV. DRAWN CHECKED, BWM AMR PROJECT NUMBER 06100009 & 07070009 08120002 z :t Oc c r.AO,Q 9R 2 oa W SHEET 8 OF 9