HomeMy WebLinkAboutEvaluation Report; Polyglass Roof UnderlaymentsEXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 TRINITY I ERA 3 TIAN STREET, UNIT #13 ' OXFORD, CT 06478 QO »a `'"` PHONE. (203) 262 9245 i FAX: (203) 262-9243 EVALUATION REPORT Polyglass USA, Inc. Evaluation Report P12060.02.09 150 Lyon Drive FL5259-R5 Fernley, NV 98408 Date of Issuance: 02/24/2009 SCOPE: This Evaluation Report is issued under Rule 9B-72 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been designed to comply with the 2007 Florida Building Code. DESCRIPTION: Polyglass Roof Underlayments LABELING: Each unit shall bear labeling in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words''TrinitylERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. , This Evaluation Report consists �of pages 1 through 8. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANEI983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 02/24/2009 This does not serve as an electronically signed document. Signed, sealed hardcopies have been transmitted to the Product Approval Administrator and to the named client CERTIFICATION OF INDEPENDENCE: 1. TrinityiERD does not have, nor does It Intend to acquire or will it acquire, a financial Interest In any company manufacturing or distributing products It evaluates. 2. Trinity iERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest In any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nleminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. ITY I ERD ROOFING COMPONENT EVALUATION: FILE C_ - 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the Florida Building Code (non-HVHZ) through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1507.2.4, 1507.2.9.2, 1507.3.3, Physical Properties (Polystick) ASTM D1970 2001 1507.5.3, 1507.6.3 1507.2.3, 1507.3.3, 1507.5.3, Physical Properties ASTM D226 1997 1507.7.3, 1507.8.3, 1507.9.3, (PolyProtector, Elastobase, 1507.9.4 Elastobase Poly) 1507.11.2 Physical Properties (Elastoflex ASTM D6164 2000 S6G) 1507.11.2 Physical Properties (Polyflex ASTM D6222 2002 G, Polyflex SAP) 1504.6 Accelerated Aging (Polystick) ASTM G154 2000 1504.6 Accelerated Aging (Polystick ASTM G155 2004 MTS, Elastoflex, Polyflex) 1504.3.1 Wind Uplift FM 4470 1992 3. REFERENCES: Entity Examination Reference Date PRI (TST 5878) Physical Properties PRIO1111 04/08/2002 PRI (TST 5878) Physical Properties PUSA-005-02-01 01/31/2002 PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) . Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 MTI (TST 2508) Physical Properties JX20H7A 04/01/2008 MT-1 (TST 2508) Physical Properties RX14E8A 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ICC-ES (EVL 2396) IBC Compliance ESR-1697 01/01/2005 ICC-ES (EVL 2396) IBC Compliance ESR-1160 03/01/2005 Miami -Dade (CER 1592) HVHZ Compliance NOA Current Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 UL (QUA1743) Quality Control File No. R14571, Vol 1 Exp. 03/21/2010 Exterior Research and Design, LLC. Evaluation Report P12060.02.09 Certificate of Authorization #9503 FL5259-R5 Date of Issuance: 02/24/2009 Page 2 of 8 Table 1: hoof Cover �,�tiorls Y� Asphalt Shingles Ti9c Foam -On 'rile =_c l Wood Shakes O & Shingles Polystick TU Yes Yes Yes No Yes Yes Polystick TU P Yes Yes Yes No Yes Yes Polystick TU Plus Yes Yes Yes Yes Yes Yes Elastoflex S6G Yes Yes No No Yes Yes Polyflex G Yes Yes No No Yes Yes Polyflex SAP Yes Yes No No . Yes Yes 5.4.1 PolyProte for UDL, Elastobase and Elastobase Poly may be used as a rnechanicaily attached base layer followed by a Polystick or Polyflex SAP top layer with allowable roof covers noted CIUVVC Jul Lllc ICalic"ivc rVlyaLlt-M Vt rViyilcA JI-ir Ulluc't iaylllcilla. 5.4.2 Elastobase and Elastobase Poly may be used as a mechanically attached base layer followed by a Elastoflex. S6G in hot asphalt or Polyflex G top layer with allowable roof covers noted auvvc Jul uto lcalicl.11vc LICIalVlic,& JiJv VI ruiyllcA Ll ullucllay111Clita. �.4.3 ' oarn-On! Tile' is lililited to use of Polyioarin Polyset applications urlless data froli! an accredited testing laboratory for alternate f ldaill-adheSive with life subject unUerlayrnent In Q%AVIUCII.IV= VVILII LI..Lr-LJ I-ItrLJG la I:q VVIUUUA .rf ae ili?.l lr1!!1Le,liv �,nl_J_nt.!1__t_I i!j1_i»1 rlifsl ieclil-i /i! eilr. tiy:Sia?i1 i�,/ !i{1flYl lr_f Vr1�C111 1V11 Y.111 Lf_/ll\I\I 111y L!1 Polystick rlT5 followed by Polystick i ► I S, TU, TU P or I U Plus is permissible. -0 V "liv•lYOUIC auuz3fla.i.0-a Jul aCll`aUliCl Illy U IJUCllaylllellla atC IIVLCU UCIVVV. 5.6.1 Polystick or Polyflex SAP Direct -Bond to Deck: ASTM D41 nr:¢ ed .c..tr'...' .:r$t -•...ret2' ( SB; ,Southern Yellow Pine; .Nev. untreated . .. . 1 Y�tf 11/ L.IAtiT Ii Alt 11V 1ti1_}('Vr1f Jim !!fY 1fl 1ypY_. V i.f 11111 }ll11fY 1111111A191/1f ,�It:�ll�lltal Allaf 1111l e�llt'I! Ill meet wind loads for project); J. V. tai 111C3 1110AIMUlll UGa1i_ JI ;Jl4aavl4U Jul vll V._'_-Uv1lU rv!yaUL1A Cipl.!111�auvila LV illy VVVVU VI p1t11iCU plywood is -135 [2sThis is pe&irient For ao.7—m-on tile cclst.er-c and ciiRfssiEnrzc where the ii', be CSf. C:=.e'; ¢-11''=.�`' r - !Ci'•'l EI===Se 4r`==i_'_E_ €=1 fil._! SL"s _t.:, f_Le ConsLlt -_posed `.�" r 5.5.2 Polystick or Polyflex SAP Bond to !Mechanically Attached Base Underlayment: it=A.4 `'Ta .� �i :r ". ,'Qri -ulus iu1 isfamr J4.i —• 1.� tr. n�! r]..� .-.._s- UC^.i✓� �[IGei - -iyi t--iGl.i4ir S_'a PolyPFc c --r HD; , i=lc1S§`.obas' , Elastobase =oly =hall not'" b= left enro-qEd for Onge than vvya alvz! llfz:L01tf2vv11. 4eS _ll r1/1V19J1 .X ITS -AY: 51 lrtll 1fi JI 11Y IC -I!! Y.X1J111t°S1.FIlt JI Il )1111 Y.1 lli.'lll Yil-ifA V1 ['!1l Y.1 11111 111lf9111 /11. • ,.:, TU T-9 PI U Plus,=lG�li3f1C-- SC-G. Polmril x G and Polyflex J'+P shall no be left, CAi.1va^V IVI IVifycil 61al1 36V-6aya a401 I1faLalla6vli. �-6a0.�G 84A4 RG�s�4 C88 t3lel8 tb+rf..Tf4238&_. 6.l=be 6�L•W8>y83E8G988 Ne68Al8db �bsi��6 �sE�+�.^�d2 m r^3z� Yr4-�ii 3Ji9iLG3eP� iBa s256iisv�3a��E'ssaF sf �.-aF2� �Q=_ -�_� %0'f z�/ zviP✓ INITY ERD VC)PI11', mFm I L E k4gww�$' 4111 Pn!vPqnTPr-rnu (Wel iq nnivniptinir. mi_!H-I-iqminPtPrJ mot imfic-ripiumpnt- rnni-Pri with tJV ­;;.—..Pn h;;�zr- zzhrar-' ",A nrn-finriminni-r- R Arn.I';;;zgz (ZR_ a requireinents of- an AbJ 1 M UZZU., i YFje LL Itiff. perforn-jance requirennerucsOTanAJ i M D1226.. i vue II feit. wILII polvolef-inic Min suilace t. A -Si —I M DISP70) d Dr.i v=. ii is v" A-0 .r x.. k. it �licills�Lrencicf-iUO!VeS-Cer-faUri-CSUrt-aCeiA, IMUi7iU). Wid-I a aranuiar surface i. A,'-> 1 Pi U i V U.I. or 00VIG-=0 A -1 D_o Vci FV tZ ;,z ADO e 'ACT.M -.91'1-31 --P V -hm F v n 1; in I lei P n.-.;t zz e '-r ;mp In HIP 1-10-17 5.3 Polvqlass Roof Uriderlayments may be used with any prepared roof cover where the product is rPfqrr-nrPd -,mit-hin FP.0 ;;r%nrnv;:%I rinnimonrq i n . fi,;tr-ri P ran ipqr m7tv hP mnrip FriN_ I bacr—J., r,*, iAA 5.4 Allowable roof covers annfled atop the underlavments are follows, -.an-un Tile Memi Yes Pastebase P i Yes Yes i .-S P F, 1 V'! j F k i9l.ti Y_C Nn 41- E__ __ !�.= C.= — I— — __ I L E ���wrh Y FffRRINITY'iEno 5.8 For the roof installations governed by the FRSA/TRI 07320/8-05 Installation Manual, Fourth Edition, use is limited to the f"oiiowing: Table 2: Tile System Options For Poly9lass Roof Underlayrnerts per FRSA/TRI 073.30/6-05 I _ Underlav ri2 _ ! = e_3e_>'vU"-_ - -l:i3r2 _ - •�-5'-�- �'.�i opiion 1 ' 3.02A I Modified Cap Sheet I Elastoflex S6G or Polyflex G I + Elastobase or Elastobase Poly / Elastoflex i 1 2 3.02B No. 30 /Modified Cap Sheet SIC; or n 1,41ex G ICltn4i]fn f-1n I Mechanically 3 3.02C No. 30 / Modified CSheet Cap C1abLUJC ur Ei=LUUJrU1Y / CidtWfWx UCCC I S6G Unsealed or 1 Unsealed or a 3_mn No. 30 PolyProtector UDL, Elastobase or I Sealed t 1 � L ! .c-.iastc-baz--re %-iy I I Polystick MTS, IR-Xe, TU, TU P or TU Plus i Underlayment !+ Sys em 5 3.02E Self -Adhered Underlayment or Polyflex SAP ! i PolvPr otector UDL. Elastobase or i 5 , 3.02F Elastobase Poiy / Polystick MTS, IR-Xe, TU, TU P or TU Plus or Polytlex SAP i i I 1 1 33.02A �i Modified Car Sheet Elasto- ex S5G or Poiynex G U. .3J, .....7=3:..._ .. :1: L-. C[a- Mechanically "qp F :�s-obase or E base Poly / FIB of e _I_b______ 1_s o____ _I _s _.I_ . 1 Fastened Tile; r4. S;o, ." / r:� S:f;3A sh�.t � S6G i 3 i - -- -- -- - I System 3jlVllf rV�1i I nAn tciv 1 I Al __.. _ _ _ _ r I Underlayment j nla, 30 ; Self -Adhered s.i;re 4 i -L;zu i :[ 17-AciilKsrru y11-r*riaY=' Underlayment ^ 3_02- r 1 fi6rICbIVC-Set � I Va. r; aied ! 1 1 11n Wi I Ccif_AncnroA i „i 4 ! 3.029 1 _ - i 1I nnlyProtert-r U--L, =lamcbrnse or 1 -1u_ n4J��i n..1.. I ndl e:�n,•!. __Are to_v.. -P� LiabLuiyaSe ui iciabiubabe Fu y 1 YDiyba CK 1 U, l U v or 1 U r iwi r Tl� P rr TIJ plus i Ei3ilf; r3S3 o ci r ti r3ww rill' POIyProtectrr lJDL, Uast)Fage or P-last^has^ Poly / Polys*Ick :•: T S, .R-Xc, TU, i -n 1 D nr -n 1 D91:v aeiP a:e - - a-e — .... h :a -..�.._ _':�'-aa.. : •t�"��'�'�w ,:���:v gh �:.,. d7:'� 5:7�Si6...��{.er .. -u.. .A.... L.S6 c,. �:r L:9�.�`> ._€i•�'- nti Wit- ,e,C -t :i i•ciiie %ccu�a w'sa ire r•i, vccew� . ;Lip",,. i zfR•4 Lr1_•.! eeq G•4r 6 �-�-G4 �•4•. _•G.�:a -•y'a ..-Z ... ii. INaTALLATMN7 6.i Polyglass Roof Underiayments shall be installeu in accoruan%2 rr'Ith PolygliiSS published installation requirements subject to the Limitations set fOlth in Section 5 herein and the cnPrifirr noted hPinw 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 PolvProtector UDL: A 1 Shall hP inctallPri in rmmniianrP with the rPniiirPmPnte for ASTM r)77(; TvnP TT FindprlavmPnt in FBC Sections 1507 for the type of prepared roof covering to be installed. 6.3.2 For use in non -tile applications: F,.1_7-1 ThP minimum slrinP -,hall hi- 7ei7_ WhPrP t_hP_ s_InnP_ ic_ 7e17 tin to 4-17, t_hP_ F_Fnr_iP_rla_vmP_nt_ shall be installed in two layers. 6.3.2.2 The underiayment shall be laid horizontally (parallel 'to eave) starring at the lowest point, printed side up, with ninimurn 3-inch horizontal (head) laps and 6-Inch vertical (end) laps. tiverlLFPa :ii?d-ll tilt] uviih INLI HUIN Jf W_Fier if; :_i 4:ii m"i"19 manner. The underlayment shall be ati:aiileu c roof i'7ecn 'i.!',y!!.4 plastic or nietal cap nails havirig rain-muni 1-Inch, ]lead rliamPtPr cnarP_ri A-in_rh_ n r at head anti Pnrl lane anti 17-inrh n r vPri-iraliv anti hnri:nntally in a ..tom c maered pwt`.rrF- s V•✓•L•✓ V.LLi✓FyisUFiy4� Vc- .,l j6F�n Ji-iU-C CO\e- U FViv 5 t i s=.r,f us if: ]yin nniica tion£_ in Mane fn ^ inn£ :n LVnJL1![!+t!J!! '±1iUh 1 i1.Jdnl�l v.! V!J� i)/ -L:J i1,Jtt!ll4l.iVl� Manual, Fourth Ldition, and I4tIiV L 6_4 Fla,;tnha:P or FlactrhacP Pnlv- --------- - -------- - - !:Zh! Pik ii f?-:i.i}Ia_i0 i:F ;7i rG Ulu E-F FG�.'-'F "e4i G-i rirL3G4•v i_iF ra _tip icy 'fk--kf i£iiS= 11 Lii ni4FSbr-i,ii6G :8 LF r,+... ..... t.,. L" FF •' [ •-•• t � LLB[ LF .'L •....v _ y. �..[ f -�. •• [ •-• I -or n7r, in non-r innHrAtinns- 6,ti, J_1 v-4 r_ii_7 Ylia`T i'_: :72=i:1E_' iUl Uj2 i_7irr U;ii i_e'iii it , rif irw, NIZ ,.i­-j j1 F'i5li-'jtij1:_ :t00mi(i jti_a0il:3i ,alifi HWMA F-4.7-7 FlactnhasP nr Fiactnha-P Pniv may hP rnvPrP.d with a lAvPr of Pnlvctirk_ PnlyflPY SAP_ -. ..... =Ui v.]C [FF M, tip 4Sll f3u!lLLiV!! d`ieA, a Dr.Z y'•Ilai iii ��s�vf lQ TIT' it SJSLl11a6i lfi ! 1UfluUl, ! VUl ll! LL�llli Vll, 0-nW 11�1U1C 2 Exterior Research and Desican. LLC. Evaluation Re_aci d P12060.02.09 ,- l �I TRINITY I ERD 6.5 Polystick MTS. IR-Xe. TU. TU P and TU Plus. and Polyflex SAP: 6.5.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Sections 1507 for the type of prepared roof covering to be installed. 6.5.2 For non -tile applications: 6.5.2.1 All Polystick materials, with the exception of Polystick TU Plus, should be back -nailed in selvage edge seam as per Polyglass Back Nailing Guide published at www2.polyglass. Nails shall be corrosion. resistant, 11 gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area i-nark—ed "riaii area; died aacd clavar" on the face of membrane. The head lap membrane is to cover the area being back: nailed b..`,.2.t Aii Se -al :ter 5c-Wlris Isei'V ge lar-s Ini:s` virmy rr_ilZw ;A;;vh rCli4Uito C'11- =- ::ilk Contact. 6.5.2.3 All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyglass Polyplus 55 Premium Modified Flashing Cement, Polyglass Polyplus 50 Premium MB Flashing Leir ellL, !=U'Ycjldss V%_-j3UU mo : id,f::rig :�ivrilf�.i 3L, {ri G3ti�=G�iLL 441 1"r G:iiiiiliri {r;UU4SiL'd L7rSd!.I;Iryi9 Cement, P ule-hide 252. Premium 0.1 �rvi � Cie trornetric Flashing �c ment, or Flule-Hide ` 21 Mod Bit Flashing Adhesive Trowel Grade mastic, applied in between the application of the lap. �...... c..S. �...... ..... ..:S 37:dp .iat LG.. .......... valleys, or exposed roof to wall details 6.5.2.5 Repair of € olystick membranes is to be accomplished by applying Polyglass Polyplus 55 i_ :'C :L°L:i SS 3C: Polyglass OG500 M0 Flashing Cement, Mu16-Hide 24' PI-13MI tM Modified Flashing Cement, Mule -Hide 251 Premium Wet/Dry Elastomeric Flashing Cement, or Mule -bide 421 Mod Bit Flashing Adhesive Trowel Grade mastic to the area in need of repair, followed by a minimum 5 d1. Li SG� .. :sLiL.. 7::cr L...:ci: ... .::,e ;'! �...I di..� .ksi.... iL`:...... ... L•iu'SJC SJVF-7 �..� repair area.. Pate laps,�ii, needed, snail be installed in a water shedding manner 6.5.2.6 All Polystick: membranes shall be installed to ensure full contact with approved subs rates_ Poiygiass reauires a minimum of 40-lb weighted-roiler or, on steep slopes, use of a stiff ;iiux....6te y "U-ius ui .. 5d 31p"Ied :iic- ruiiurs .71.i.,C rJtaVFe iVl fi.F:ill lg of Itc7 F.4iiN.b, i_ip7 Elr 5iii[;Fie r'!'Coiss of CF ii4 iiftl Liaat E7t G fit1C F.1 3 larai? roller or hroom, .- .j r_- V ..e .._> 7 VI CIIG cipail .-f}t11J9iS. 6.5-3.1 Reference is made to Seaipn 6.5-2 herein in conjunction with FRSA/TRI u7321VU-05 ii ....L�i.......... .......�.5:, ...... �.. �L:i...., • Mice. ....Si:� ...... �, :, .:Ski:` U::_ c �tiFca�iiG��. 6.6 Elastnfiex S6G and Poivfiex G. ._...... �. Fb; us ! ik, _...f u'tDfil....r:t.tii.- .... a'-.i:yvk �f.0 i- .. 7331e LV 7':":14 7.7�-,.S CGS .i`sf;L'>, ik:�.�s:.�..S s:. .. �,`��i uiJZlGl:.._, ... conjunction eeitiF a ci_'r-t/ iFti1 U/_o V/xrj-cis iiob aiic,tiv kaki dp:, 10 siFa Ludiiis i, a:Fu iaU. herein. Exterior Research and Lesian. LLC. Evaivation Report ID12060.02.09 ca 2ff..-_- ofAr.: or. 16.7 0-35?3 E_5259-1^5 PuQU 7 or a ' ' s FILECOP�Y�\J'wNinleao 6.7 Tile Staging: 6.7.1 A maximum of 6 tiles per stack are allowed when loading tile directly onto the underlayments. Refer to the Polyglass Tile Loading Guidelines. t = = b y i t_ s mt:—eGc.pfeparedwith: r' POLYSi1CKT Plus. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI 07320/8- 05 must be used on all roof slopes of 7:12 or greater. For roof slopes in excess of 61/4:12, precautions should be taken, such as the use of battens to prevent tile sliding during the loading process. 6.7.3 Note: Polyglass defers to the tile manufacturer on use of tiles directly over its Polystick underlayments 6.7.4 Minimum cure time after membrane installation and before loading of roofing tiles is forty- eight (48) hours. 7. LABELING: Each unit shall bear a permanent label with the manufacturer's name, logo, city, state and logo of the Accredited Quality Assurance Agency noted herein. S. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 9. MANUFACTURING PLANTS: Fernley, NV; Hazelton, PA; Winter Haven, FL 10. QUALITY ASSURANCE ENTITY: Underwriters Laboratories _ QUA1743 Exterior Research and Design, LLC. Certificate of Authorization #9503 - END OF EVALUATION REPORT - Evaluation Report P12060.02.09 FL5259-R5 Date of Issuance: 02/24/2009 Page 8 of 8