HomeMy WebLinkAboutBuilding PlansTHESE DOCUMENTS HAVE BEEN PREPARED ACCORDING TO THE FOLLOWING REQUIREMENTS— FLORIDA BUILDING CODE 7th EDITION 2020 OCCUPANCY WAREHOUSE STORAGE TYPE IIIA CONSTRUCTION ALTERATION LEVEL 2 GENERAL NOTES- - CONTRACTOR AND SUB CONTRACTORS SHALL VISIT SITE AND VERIFY ALL CONDITIONS BEFORE PROCEEDING NTH ANY COMMENCEMENT OF WORK OR ANY MATERIAL ORDERING. NOTIFY THIS ARCHITECT AND ENGINEERS OF ANY ERRORS, OMISSIONS OR CHANGES BEFORE COMMENCEMENT OF PROJECT. — CONTRACTOR SHALL NOTIFY ALL APPROPRIATE UTILITY COMPANIES BEFORE ANY EXCAVATION HAS COMMENCED AND TO VERIFY EXISTING SERVICE LINES AND POSSIBLE HAZARDS, — COORDINATE ELECTRICAL SERVICE, TELEPHONE, TELEVISION (CABLE), COMPUTER SYSTEM REQUIREMENTS AND LOCATIONS AND AVAILABILITY WITH SERVICE PROVIDERS. — BATHROOM, RESTROOM FLOORS, BASE TUB AND SHOWER ENCLOSURES SHALL BE IMPERVIOUS MATERIAL ( CERAMIC TILE) UNLESS SPECIFIED OTHERWISE. PROVIDE CERAMIC TILE BASE AND WAINSCOT FINISH Min. 5ft AFF (WALLS) INTERIOR PARTITIONS (NON —BEARING) SHALL BE 1/2" GYPSUM WALLBOARD ON EACH SIDE OF 2"x 4" WOOD STUDS or 25 go METAL"C" SHAPED STUDS SPACED 24" ON CENTER, UNLESS OTHERWISE SPECIFIED.. — ALL WOOD IN CONTACT WITH CONCRETE SHALL BE TREATED OR OTHERWISE PROTECTED WITH TYPE: 30 FELT MEMBRANE BARRIER. — WOOD GRADE FOR STUDS AND TOP PLATES SHALL BE SOUTHERN PINE — STANDARD GRADE. BASE PLATES SHALL BE No. 2 SOUTHERN PINE TREATED SURFACE DRY USED AT MAX. 19% MOISTURE CONTENT. — STRUCTURAL GRADE LUMBER SHALL BE MIN. Fb = 1,200 PSI UNLESS OTHERWISE SPECIFIED. — NAILS FOR — STUD TO STUD PLATE — (2) 16d STUD TO SOLE PLATE / TOE NAIL- (2) 8d DOUBLE TOP PLATE— (2) ted NAIL 0 12"o.c. — TOP PLATES IN BEARING WALLS SHALL BE DOUBLED AND LAPPED AT INTERSECTION OF WALLS AND PARTITIONS. JOINTS SHALL BE LAPPED NOT LESS THAN (4) FEET — CORNER OF STUD WALLS SHALL BE FRAMED SOLID BY NOT LESS THAN 3 STUDS WITH 16d NAILS 0 12" o.c.. CORNER STUD SECURED TO (3). MEMBER STUDS 2 16d NAILS 0 6"o.c.. —TOP PLATES IN NON —BEARING PARTITIONS SHALL BE SINGLE — SOLE PLATES IN NON —BEARING PARTITIONS SECURE TO CONCRETE SLAB WITH TAPCON FASTENER 1/4"x 1-1/2" EMBED or HILTI POWDER ACTUATED FASTENER PIN DN 72 P08 x 0.145 SHANK Diu. SPACE FASTENERS AT 32"o.c.. — CEILING FURRING STRIPS SHALL BE SOUTHERN .PINE 1"x 3" WOOD SECURED TO WOOD JOISTS, TRUSSES SPACED 16"o.c. WITH (2) 8d NAILS COMMON. — WALL FURRING AND CONTINOUS FIRE STOP FOR CONCRETE, MASONRY WALLS SHALL BE 1"x 2" TREATED PINE SPACED 24"o.c. HORIZONTAL AND MAX. 8ft HIGH VERTICAL PROVIDE FIRE STOP ABOVE 8ft. SECURE TO CONCRETE WITH CUT NAILS OR "T' NAILS SPACED 0 16"o.c. — WHERE VERTICAL PIPES POSITIONS NECESSITATE THE CUTTING OF PLATES, A METAL TIE 1"x 1/8' SHALL BE PLACED EACH SIDE OF WOOD PLATE ACROSS THE OPENING 6" PAST AND NAILED WITH (2) 16d ad 8d COMMON NAILS AT EACH END. — HEADERS OR LINTELS OVER STUD WALL OPENINGS SHALL BEAR NOT LESS THAN (3) 2x JACK STUDS or HANGER SECURED TO NOT LESS THAN (3) KING STUDS. — WALLBOARD SHALL BE ASTM C36-85 REGULAR 1/2" / ASTM C36-85 TYPE "X" FIRE RATED / ASTM C117 (MOISTURE RESIISTANT) UNLESS SPECIFIED OTHERWISE — JOINT TREATMENT SHALL BE COMPOUND AND TAPE (READY MIX) ASTM C475-88 CORNER BEAD ASTM C1047-85 PANEL ADHESIVE SHALL BE STA—STUCK SS-200, ASTM C-557-73 — PROVIDE MIN. 1/2" AIR GAP BETWEEN FLOOR AND WALLBOARD BOTTOM — ATTACHMENTS FOR WALLBOARD TO SUPPORTS SHALL BE — METAL STUDS— TYPE W 1-1/4' DRYWALL SCREWS SPACED 0 12"o.c. WOOD STUDS & FURRING— NAILS GWB-54 ANNUAL RING 1/4" HEAD, .098 Dio SHANK ATTACHMENT SPACING J CEILING— 7' o.c. / WALLS— 8" o.c. SCREW STUD TRACK— .0179" BASE STEEL x 3-5/8" MADE STUDS— "C" SHAPED SCREW STUDS, ASTM C645 x .0179" BASE STEEL SCREWS— TYPES-12 LOW PROFILE (2) SCREWS PER ATTACHMENT (METAL to METAL) HILT] SHOT THROUGH BASE TRACK TO CONCRETE— PIN DN 19 POB x .145" Dia. SHANK CEILING METAL TRACK TO. WOOD FURRING—. TYPE —W SCREW x 1-1/4" SPACED.0 24"o.c. METAL FURRING— ASTM C645 / 7/8" x .179" BASE STEEL ROOM FINISH SCHEDULE AREA FLOOR BASE WALLS CEILING CEILING HEIGHT REMARKS RESTROOMS TILE .TILE PAINT * PAINT * 8'-0" WAINSCOT 5ft HIGH AFF TILE STORAGE CONCRETE L PAINT PAINT 8'-0. VESTIBULE CONCRETE TILE 8'-0" NOTES — ALL DOORS SHALL BE PAINTED WITH SEMI —GLOSS ENAMEL **EGG SHELL LATEX PAINT O SCHEDULE / DOOR MARK SIZE TYPE DOOR MATERIAL FRAME THRESHOLD REMARKS A 3'-O' x 7'-0 FLUSH HOLLOW WOOD NONE LEVER HANDLES METAL SELF CLOSER B S-O" x 7'-0 FLUSH HOLLOW WOOD NONE LEVER HANDLES METAL NOTE-. UNLESS OTHERWISE INDICATED ALL DOORS AND FRAMES SHALL BE PAINT GRADE AND FINISHED WITH APPROPRIATE TYPE PANT FOR INTERIOR AND EXTERIOR APPLICATION- ENAMEL PAINT PAINT COLORS SHALL BE OWNER SELECTED DOOR HARDWARE SHALL BE OWNER SELECTED FASTENERS to TOP PLATE 3/4"PLYWOOD SHEATHING SIMJOIST N STRONG 2x6 WOOD JOISTS SPACED 24" O.C. x. N (4) 8d x 1-1/2" NAILS (4) 8d . EACH LEG EXTERIOR WALL H3 24 WOOD JOISTS H3 2 "X" 1J2" TYPE GYPSUM WALLBOARD 9 2-2x4 WOOD TOP PLATE DRYWALL CEILING 2x4 WOOD STUDS ON FURRING SPACED AT 16" O.C. SPACED AT 16" O.C. PROVIDE 1/2" SPACE BETWEEN DRYWALL AND SLAB Typical 2x4 WOOD STUDS SPACED AT 16" O.C. oQ' F4' \OQ-OJci' ,hQ'10 2x4 4ft ABOVE SLAB 2�Q4- to JO FLOORS, BASE and WAINSCOT 5ft HIGH BE. MPERVIOUS MATERIAL— TILE 111 BASE 24 W00 TREATED BASE PLATE J3 1" EMBED TAPCON SCREW SPACED ON CENTER CONCRETE SLAB U d I a a. a. CONCRETE SLAB `..• Grade FOUNDATION a . •' < . '.. e SECTION S-1 INTERIOR PARTITION AREA of WORK EXISTING ELECTRIC SERVICE METER/ DISC n- n f_J — Lt_—,-1 — — — — — — — — — — JB EXIT PANEL ,,A„ PANEL „B,, EXISTING ELECTRIC REMOVE EXISTING RESTROOM L�-�=J1 AREA of WORK Existing Existing Vest. Warehouse Warehouse Counter Lev RESTROOM Service wa AREA of WORK Sink 7 — — — — — — — — — — — — — — — — — — — — — — — — 7 NEW we SCOPE OF WORK ALTERATION LEVEL 2 INTERIOR _ 1 PARTITIONS - INTERIOR DRYWALL PARTITIONS ENCLOSURES forI RESTROOM RESTROOMS, VESTIBULE and STORAGE AREA 1 -INTERIOR DOORS and FINISHES Lav -ELECTRIC, PLUMBING and EXHAUST FANS I L_ _------------=-----------I STORAGE Existing Office — — — — — — — — — — ---- ----- EXIT I EXIT EXISTING METAL BUILDING, EXTERIOR WALL 62'-4" Existina Exis ing ---Doo EXISTING METAL 6 EXTERIOF G RECEIVED FEB 2 3 202f REVIEWED FOIE Permitting Department CODE COMPLIANCE St. LUcle Counirf ST. LUCIE COUNTY SOCC FLOOR PLAN = Date 2/8/2021 Rev' O ry LLJ z� LIJ O Q I = O Q (<�/ LL. Cn U LJ 0 LLB V)z - O a_ r1r) I O O nl� O El- N 11 Date `? 2ozi ROBERT I HMAN Q ~ a- '., O U o Z Q LL! M (n morn — 00 MOm (� N OEM U w 3orn H WV) a z10 =3LO m.Q IiZJ^J� O o �o PROJECT No. Sc 3/16"= 1'-0" S H E E T A-1 of 2 ELECTRIC NOTES. ALL ELECTRIC WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE. — MOUNT ALL SWITCHES 42" A.F.F. ANDALL RECEPTACLES 18" A.F.F. MOUNT WALL HUNG FIXTURES NOT LOWER THAN 80" A.F.E. TO BOTTOM OF FIXTURE. — OWNER / CONTRACTOR SHALL SELECT LIGHT FIXTURES TYPE AND SUBMIT TO ARCHITECT FOR APPROVAL FOR LOCATION USAGE. — ALL EXTERIOR RECEPTACLES ( WEATHER PROOF) FOR GENERAL PURPOSE AND BATHROOM / RESTROOM SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER. — SMOKE DETECTORS SHALL BE 110 Volt WITH BATTERY BACK UP TYPE, INTERCONNECTED HARDWIRED TO NON SWITCHABLE INDIVIDUAL CIRCUIT. LOCATE ON OR NEAR CEILING IN THE IMMEDIATE VICINITY OUTSIDE AND INSIDE BEDROOMS AT DOORWAY AND AT STAIRWAY LANDINGS. LOCATE NO CLOSER THAN 3 Feet TO A/C DIFFUSER GRILL. — THE ELECTRICAL CONTRACTOR SHALL NOTIFY ARCHITECT OF ANY CHANGES TO EQUIPMENT LOADS DIFFERENT THAN SCHEDULE PANEL LOADS. — GROUNDING ELECTRODES SHALL BE COPPER THW IN ON CONTINOUS LENGTH OR SPLICES IN BUSBARS SHALL BE PERMITTED AND SHALL BE ENCLOSED IN CONDUIT ENCLOSURE SECURELY FASTENED TO THE SURFACE ON WHICH IT IS CARRIED TO EXPOSED CONNECTIONS FOR GROUNDING. METHODS FOR SECURING GROUND SHALL. BE PERMANENT. PROVIDE GROUNDING ELECTRODES FROM ALL SERVICE EQUIPMENT ORSEPERATLEY DERIVED SYSTEM TO WATER PIPE OR STRUCTURAL METAL BUILDING MEMBER AND FROM THAT POINT TO ONE OF THE ELECTRODES SHOWN FOR GROUNDING. — BONDING SHALL BE PROVIDED WHERE NECESSARY TO ASSURE ELECTRICAL CONTINUITY AND THE CAPACITY TO CONDUCT SAFELY ANF FAULT CURRENT LIKELY TO BE IMPOSED. .ALL NON —CURRENT CARRYING METAL PARTS OF SERVICE EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. AN ACCESSIBLE MEANS EXTERNAL TO ENCLOSURES FOR CONNECTING INTER —SYSTEM BONDING AND GROUNDING CONDUCTORS SHALL BE PROVIDED AT THE SERVICE BY EITHER EXPOSED METALLIC SERVICE RACEWAYS, EXPOSED GROUNDING ELECTRODES CONDUCTOR OR APPROVED MEANS FOR THE EXTERNAL CONNECTION OF A BONDING, OR GROUNDING CONDUCTOR TO THE SERVICE RACEWAY OR. EQUIPMENT. METHODS OF BONDING SHALL BE BY SCREWS, CLIPS, THREADED COUPLING AND CONNECTORS, BONDING JUMPERS OR OTHER DEVICES SUCH AS BONDING TYPE LOCKNUTS AND BUSHINGS. — TESTING— ALL WIRING SHALL BE FREE FROM SHORT CIRCUITS AND GROUNDS AND SHALL BE TESTED FOR THESE DEFECTS PRIOR TO BEING CONNECTED TO THE CIRCUITS. — GROUNDING CONDUCTOR MATERIAL TYPE AND SIZE AS PER PANEL SCHEDULE AND RISER. PROTECTION OF CONDUCTORS SHALL BE BY CONDUIT, BOXES AND COVERS STUD PLATES AND SLEEVES, RACEWAY ETC.TO INSURE ADEQUATE PROTECTION OF CONDUCTORS AGAINST DAMAGE. — SEPARATE GROUNDING SYSTEM SHALL BE INSTALLED AND PROPERLY BONDED AS PER CODE AND USAGE REQUIREMENTS. — ROMEX TYPE WIRING ( 2CONDUCTOR WITH. GROUND) COPPER MAY BE USED FOR LOCATIONS IN PLACE OF CONDUIT, ( UNLESS OTHERWISE SPECIFIED ) " ARC —FAULT CIRCUIT INTERRUPTER) BREAKERS, N.E.C. Art 210-12 PROVIDE ALL 120—VOLTS, SINGLE PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS OR SIMILAR ROOMS OR AREAS SPECIFIED IN N.E.C. 2008 ARTICLE 210.12 TO BE PROTECTED BY A LISTED ARC -FAULT CIRCUIT INTERRUPTER, COMBINATION TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. TO COMPLY WITH ARTICLE N.E.C. 2008 ARTICLE 406.11 PROVIDE ALL RECEPTACLE OUTLETS, 125— VOLTS, 15 AND 20 AMPERE INSTALLED IN DWELLING UNITS AREAS SPECIFIED IN N.E.C. 2008 ARTICLE 210.52 TO BE LISTED TAMPER RESISTANT RECEPTACLES. PROVIDE CARBON MONOXIDE TYPE SMOKE DETECTOR WITHIN 10 Feet OF THE BEDROOM AREA. F.B.C. 907.2.10 ELECTRIC LEGEND RECEPTACLE 110 Volt SINGLE DUPLEX FOUR PLEX ® RECEPTACLE 240 Volt SINGLE AFCI ARC FAULT CIRCUIT INTERRUPTER GFCI GROUND FAULT CIRCUIT INTERRUPTER WP WEATHER PROOF JUNCTION BOX d JUNCTION BOX FUSED (Yl LIGHT FIXTURE WALL MOUNT (wri CEILING MOUNT (cm) RECESSED SPOT HIGH HAT (hh) RECESSED SPOT HIGH HAT LOW VOLTAGE (Iv) v} SWITCH SINGLE THREE WAY ELECTRICAL PANEL (x) ELECTRICAL( ETER /DISCONNECT of EXHAUST FAN CEILING BROAN MODEL 679. 70 CFM (INTERMITTENTLY) 4" Dia. METAL EXH. DUCT to EXTERIOR 24 go C-1 CIRCUIT NUMBER Q� EMERGENCY LIGHT LED WALL MOUNT 80" AFF EL—RW, 120v, 3w 0-0 (x) F—EX—ITJ EXISTING. (x) AREA of WORK PROVIDE FOR THE FOLLOWING NEW CIRCUITS ON EXISTING PANEL "B" 200A C-1 LIGHTING 3 # 12 in 1/2"m-20A CB' C-2 RECEPTACLES GFCI 3 # 12 in 1/2"EP-20A CB „ EXISTINGELECTRIC SERVICE METER/ DISC M M 0 0 EXIT JB PANEL "A" PANEL '' B" EXISTING ELECTRIC AREA of WORK I— I Vest GFCI ,� C-1 ¢ 2 Couri C-1 REST Odd EF crr Servicel n C-1 C-,3E�ENL�U`ATS 3 # 12 in 1 2 QP-20A CB Q� �P FLOOR PLAN ELECTRIC EF c-1 .. RESTR00 cm —t GFCI C-2@ —1 Cm, St. C-1 , Existing Office 7,-8„ PLUMBING NOTES— Grab bar PLUMBING CONTRACTOR, SHALL VERIFY SEPTIC TANK, SEWER AND WATER SERVICE LINES AND ELEVATIONS TO INSURE PROPER FLOW AND ADEQUATE REQUIREMENTS FOR THE DRYWALL INTENDED PROJECT. NOTIFY THIS ARCHITECT OF ANY CHANGES TO FLOOR ELEVATIONS I30"X 48" PRIOR TO COMMENCEMENT OF WORK OR MATERIAL ORDERING. Access GRAEBAR S,S. ALL WASTE WATER PIPING UNDER THE SLAB SHALL BE SCH 40 PVC WITH A MINIMUM -1/2"BAR SLOPE OF 1/8"/ FT AND BE PROPERLY SUPPORTED IN CLEAN SAND FILL. I-)/42" ,I ALL SANITARY AND DOMESTIC WATER PIPING SHALL BE PROPERLY SUPPORTED ON TOILET RM. o WALLS AND CEILINGS. - THE PLUMBER' SHALL INSTALL ALL FIXTURES WITH REQUIRED CLEARANCES 00 — ALL DOMESTIC WATER LINES SHALL BE INSULATED Door — ALL PLUMBING FIXTURES SHALL HAVE INDIVIDUAL SHUT—OFF VALVES WITH BACK FLOW Mirr PREVENTORS, DOMESTIC HOT AND COLD WATER LINES. yF I Lav — ALL DOMESTIC WATER LINES SHALL BE COPPER, TYPE "L" FOR BELOW GRADE AND TYPE "M" FOR ABOVE GRADE INSTALLATION. LINES IN AND BELOW SLAB SHALL HAVE MINIMUM 1/32" PLASTIC SLEEVE. HOT WATER LINES SHALL BE INSULATED, — PLUMBING CONTRACTOR SHALL VERIFY ALL EQUIPMENT AND FIXTURE LOCATIONS, HEIGHTS AND INSTALL AS PER MANUFACTURER SPECIFICATIONS. RESTROOM PLAN PROVIDE ALL NECESSARY BACKING IN PARTITIONS WALLS FOR INSTALLATION. — FIXTURE AND HARDWARE TYPE SHALL BE OWNER / CONTRACTOR SELECTED UNLESS UNISEX OTHERWISE INDICATED. — TOILETS SHALL BE WATER SAVING TYPE, 1.6 GPF — SHOWER HEADS SHALL BE 2.5 GPM ® 60 PSIG FLOWING PRESSURE — LAVATORY SHALL BE 2.0 GPM ® 60 PSIG FLOWING PRESSURE I(VTR — WATER FIXTURE SUPPLY LINE = 3/4" / FIXTURES = 1/2" ( UNLESS OTHERWISE SPECIFIED) 3" CONNECT WATER LINES FOR NEW FIXTURES TO EXISTING DOMESTIC WATER LINES IN BUILDING — TUB AND SHOWER VALVES SHALL HAVE IN —LINE STOPS AND SHOWERS SHALL HAVE ANTI —SCALD VALVE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING TYPE. — HORIZONTAL PIPING— PVC SUPPORTS NOT GREATER THAN 4 Feet APART — COPPER PIPING SUPPORTED AT 8 Feet INTERVALS CONNECT TO — EXTEND ROOF VENT MINIMUM 6" ABOVE FINISH ROOF AND PROPERLY FLASH WITH EXISTING SANITARY LINE INTEGRAL PART OF ROOFING SYSTEM. � 3" 1-1/2' TO DRAINFIELD RESTROOM FLOORS, BASE and WAINSCOT 5ft HIGH LAV �—I SHALL BE IMPERVIOUS MATERIAL -TILE 1-1/2" CO3^ SINK CO 3„ TABLE 704.1 FBC 1-1/ " WC WC LAV 2 SLOPE of HORIZONTAL DRAINAGE PIPE SIZE Inches MINIMUM SLOPE Inch per foot 2-1 2 or Less 1 4 3to6 1 8 8 or Larger 1/16 FIXTURE TYPE FIXTURE UNITS TRAP SIZE WATER CLOSET M 3 LAVATORY 1 SINK 2 z„ 3„ 3„ SANITARY RISER RESTROOMS T MIRROR 15N30" DRYWALL m 111111101 mp� �I� Nonni am HANDICAPP RESTR elevations FLOOR PLAN r1.C. LAV. 4FAUCET IN51LILATE WATER PIPE5 VALVES 4 DRAIN / TRAP CERAMIC TILE WAINSCOT 5 ft MIGH COVE EASE REvIEWED FUR CODE COMPLIANCE BOCC 3 .r LINE Date 2/8/2021 Rev 0 of LL I 0 I— Z � LLj Q D > p 0 Q IY S LLI J O - G:f Q LL_ Q Of L p�tY LLJ p W cnz� O 00l2r_ Of Cr) 0 IZ N LL Date Zg� ROBERT G. ISHMAN Q F— a_ 0 00 Z Q LJ M U) d cn _ It mom — Z 00 acm OLL� 0 - U F— of a do) o OY D_ W w 0 3 _ In m<[ cn w ^Jrn O 0 �� v CK zi N 2 F- PROJECT No. sc 1/4" = 1'— 0" S H E E T A — 2 of: 2.