HomeMy WebLinkAboutSARKAR engineeringArchitectonic Inc
April 2, 2021
St. Lucie County Building Department
2300 Virginia Ave.
Fort Pierce, FL
Re: Roofing specification prepared for the St. Lucie County Building Department for the
structure located at, 7830 US 1, Port St. Lucie, FL
Manufacturer:
Profiles:
Code:
Wind Speed:
Exposure:
Mean Roof Height:
Pitch:
Required Design Pressure:
Maximum Uplift Pressure:
Fasteners:
Underlayment:
Roof Decking:
JA TAYLOR ROOFING
5-V Crimp 24 ga. Steel, FL# 17443.1
FBC 2020; Section R 905.10
165MPH; Ultimate Design Wind Speeds
C
30' Maximum
5 / 12 Minimum
Zonal:-65.7 Zone 2:-82.84 Zone3: -97.8
Zone 1-69.25, Zone 2 & 3-129.25
#9-15 Woodtite Fasteners @ Zone 1 @ 16" o.c. Zone 2 & 3 @ 6" o.c.,
with sealing washer through panel rib with M" minimum penetration
through plywood
Owen's Corning Weatherlock Specialty Metal and Tile Underlayment,
FL# 9777.7 (self -adhering)
Existing 5/8" plywood sheathing to be nailed w/8d x 2" ring shank
@ 6" O.C. thru out zone 1, 4" O.C. perimeter, and 6" O.C. field zone 2,
and 4" D.C. thru out zone 3.
The above approved, as per Florida Building Code Compliance acceptances, 2020 Florida Building Code,
and the Manufacturer's recommendations.
Respectfully submitted,
Michael Seal
Inc.
806 Delaware Avenue Tel: 7724607751 www.architectonlcinc.com
Fort Pierce, Florida 34950 Fax: 772 4604244 FL Reg #AA26003348 1 of 1