Fire Alarm Plan; TPH-FA DS
SUBSCRIPT AT STROBES AND HORN/STROBES DENOTES CANDELA PER NFPA 72 2016 AND UL 1971. ALL WIRING, & INITIATING DEVICES, SHALL BE SUPERVISED TO THE POINT OF ANNUNCIATION (F/A PANEL TO SUPERVISE THE ANNUNCIATOR PANEL ALL CIRCUITS AND INITIATING DEVICES). WIRING SHALL NOT BE LOOPED THROUGH DEVICES: WIRE MUST BE CUT FOR IN AND OUT. ALL DEVICES IN THE FIRE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURERS SPECIFICATION. 5. AREAS HAVING MORE THAN ONE VISUAL NOTIFICATION APPLIANCE WITHIN 55' OF EACH OTHER & WITH THE SAME FIELD OF VIEW SHALL BE SYNCHRONIZED. 6. SUBSCRIPT SHOWN NEXT TO INITIATING DEVICES DENOTES THAT DEVICE'S ADDRESS ON THE SIGNALING LINE CIRCUIT (SLC). 7. FOR ALL SHIELDED CABLES USED IN THE INSTALLATION OF THE SYSTEM, THE SHIELDS MUST BE SPLICED THROUGH FROM CABLE TO CABLE AND BE INSULATED/ISOLATED FROM GROUND AND CLEAR OF GROUND FAULTS. 8. INSTALLATION SHALL COMPLY WITH NFPA 72, 2016, APPLICABLE CHAPTERS. 9. INSTALLATION SHALL COMPLY WITH NEC 2017 APPLICABLE CHAPTERS. 10. THE DESIGN INSTALLATION COMPLIES WITH THE FLORIDA BUILDING CODE (F.B.C.) 7TH EDITION. 11. THE DESIGN INSTALLATION COMPLIES WITH THE FLORIDA FIRE PREVENTION CODE (FFPC) 7TH EDITION. 12. RACEWAYS TO BE EMT, WIREMOLD, PVC & FREEWIRE (FISHED) WHERE CODE PERMITS. MINIMUM RACEWAY 3/4". 40% CONDUIT FILL MAXIMUM. 13. SYSTEM SHALL BE GROUNDED PER MANUFACTURES SPECIFICATIONS. 14. WIRE RUNS ARE NOT EXACT ROUTE OF CONDUIT OR FREEWIRE. 15. ALL SPACES SHALL MEET THE AUDIBILITY CHARACTERISTICS OF NFPA 72 & NFPA 101. 16. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN OR BATHROOM DOORS. 17. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10'-0" +/— ON SMOOTH FLAT CEILING UNLESS OTHERWISE NOTED. 18. THIS IS A BATTERY BACKUP SYSTEM, WITH 24 HOURS OF BACKUP & 5 MINUTES ALARM. SHOULD LOSS OF NORMAL 120 VAC OPERATING POWER OCCUR, THE FACP WILL AUTOMATICALLY TRANSFER TO STANDBY BATTERY. 19. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE FED BY A 120 VAC, SINGLE PHASE, 20 AMP, DEDICATED BREAKER. 20. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. 21. ALL EQUIPMENT, FIRE CAULK TO BE U.L. LISTED. 28. THIS IS A REMOTE STATION SERVICE FIRE ALARM SYSTEM. 29. FBO — FURBISHED BY OTHERS 30. EX — EXISTING TO REMAIN AS IS. 31. PATHWAY SURVIVABILITY LEVEL 1 — (12.4.2) LEVEL 1 PATHWAYS SHALL CONSIST OF PATHWAYS IN BUILDINGS THAT ARE FULLY PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. 32. THE SOUND LEVEL WILL BE AT LEAST 15DBA ABOVE THE EQUIVALENT SOUND LEVEL OF 5DBA ABOVE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FEET ABOVE THE FLOOR IN THE OCCUPIES AREA, INCLUDING RESTROOMS, WALK—IN COOLERS AND STORAGE AREAS. THE CONTRACTOR IS REQUIRED TO CERTIFY THE DBA LEVEL WITH AN APPROVED DBA METER PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. 33. ALL INFORMATION WILL BE ON SITE WHEN THE ST LUCIE COUNTY FIRE DISTRICT IS REQUESTED TO WITNESS THE ACCEPTANCE TEST. 34. THE PLANS MUST INDICATE THE RECORDS OF COMPLETION WILL BE PREPARED Amin A rnov DRfI\/inr_r) Tfl TWIm- rMAINICR AKIF) TWr_ CT 1 1 lr'IC r r)l INITV CIRC r)ICTA1f`T ATION OF AN AREA SPOT SMOKE DETECTOR SHALL ACTIVATE THE AUDIBLE SIGNALING DEVICE IN THE OFFICE. DISPLAY ON THE FIRE ALARM PANEL THE ZONE OF THE ACTIVATED DEVICE AND ILLUMINATE THE ALARM LED. TRANSMIT AN ALARM SIGNAL TO THE REMOTE STATION MONITORING SERVICE. CTIVATION OF ANY FIRE SPRINKLER WATER FLOW SWITCH SHALL: ACTIVATE THE AUDIBLE SIGNALING DEVICE IN THE OFFICE. DISPLAY ON THE FIRE ALARM PANEL THE ZONE OF THE ACTIVATED DEVICE AND ILLUMINATE THE ALARM LED. TRANSMIT AN ALARM SIGNAL TO THE REMOTE STATION MONITORING SERVICE. CTIVATION OF ANY FIRE SPRINKLER SUPERVISORY DEVICE SHALL: DISPLAY ON THE FIRE ALARM PANEL THE ZONE OF THE ACTIVATED DEVICE AND ILLUMINATE THE SUPERVISORY LED. TRANSMIT AN SUPERVISORY SIGNAL TO THE REMOTE STATION MONITORING SERVICE. BNORMAL CONDITIONS SHALL: ANNUNCIATE ON THE FIRE ALARM CONTROL PANEL THE TYPE OF SYSTEM FAULT, LOCATION IF THE DEVICE IS INTELLIGENT AND ILLUMINATE THE TROUBLE LED. TRANSMIT A TROUBLE/ ABNORMAL SIGNAL TO THE REMOTE STATION MONITORTING SERVICE. THE RESTORAL OF ANY TROUBLE CONDITION SHALL AUTOMATICALLY RESTORE THE FIRE ALAR ND TESTING A NEW WATER FLOW SWITCH AND TAMPER SWITCH. DEVICES TO BE INSTALLED IN CCORDANCE WITH FLORIDA FIRE PREVENTION CODE 7TH EDITION WITH FLORIDA CHANGES REFERENCE MOUNTING REQUIREMENTS ED. D 3 MIN. ACCEPTED HERE IDN ?ry m IJ ACCEPTED .ERE ❑a �O^ w AU010 VISUAL J ®mo^ NEVER HERE 0. DOOR WIDTH LE55 0' ad- wan sp =��o n Tlc OE WALL �46� �$��� N SIDE WALL WITHIN 5' DM DOOR z g m PER NRPA J] 2U16 17.14.8.6 FlNI H ROOR HHE ALARM SYMB= SYMBOL ODES IDESCRIETION1 IQUAN 0 FACP 52071 FFEE ALARM CONTROL PANE 0 EX SMOKE DETECTOR EBO WATER FLOW © m] 11AMPLE SW17=H Jeff,Key,P,,,, a oF1td� o:w= '> ylited aUvsig�o: y Jeffrey Rn ��e of�lo�•„•" 15:59:42-04'00' N � W o � U o0 M E O •� W (6 N�V c ^, 2lLLW* W N W "" w C J Sc W U E O) 0 c ) 0 = l L U) -O � O 'T N 11 LL U o aw ry Q M p 00 m N N C a N N _0 CN N co N LLnjN C/) 00 Lo x co 0 IL M m a THIS DRAWING AND ITS CONTENTS ARE THE PROPERTY OF ADT COMMERCIAL. IT IS NOT TO BE USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN CONSENT OF ADT COMMERCIAL. IF ANY DOCUMENT PREPARED BY ADT COMMERCIAL IS ALTERED IN ANY MANNER BY OWNER, ITS AGENTS OR BY ANY THIRD PARTY IF CONSTRUCTION IS NOT IN ACCORDANCE WITH UNALTERED DOCUMENTS PREPARED BY ADT COMMERCIAL THEN IT IS UNDERSTOOD THAT ADT COMMERCIAL HAS NO LIABILITY IN WHOLE OR IN PART, RELATED TO THE PROJECT AND THAT THE OWNER AND ITS AGENTS INDEMNIFY AND HOLDS HARMLESS ADT COMMERCIAL FOR ANY AND ALL ACTS RELATED TO THE PROJECT. THIS CONCEPT DRAWING IS FOR INFORMATION ONLY TO POTENTIAL SYSTEM ARRANGEMENT. CONTRACTOR SHALL FIELD VERIFY ALL INFORMATION CONTAINED ON THESE DRAWINGS AND IS RESPONSIBLE FOR DESIGN AND INSTALLATION OF THE SYSTEM IN ACCORDANCE WITH THE SPECIFICATIONS. TO THE BEST OF ADT COMMERCIAL'S KNOWLEDGE THE DRAWINGS AND SPECIFICATIONS SUBMITTED HEREWITH, COMPLY WITH EXISTING INTERPRETATIONS AND PREVISIONS OF THE APPLICABLE N.F.P.A. CODES IN EFFECT AT DATE SHOWN. z w QV w �z L Q m J _j J J LL Q Q O LL ___J = ~i1 LU Q �� w zLL CD rn JURISDICTION: FT. PIERCE DESIGNED BY: FR DATE: 3-7-2021 PROJECT NO: ######### SCALE: 1/8" = 1-0- TITLE: NOTES SHEET: FA-01 Jeffrey P. U::ykSt�teof,� �.�ti= O O O z 0 n n c c s w TOTAL SYSTEM STANDBY 0.121 TOTAL SYSTEM ALARM 0.891 CURRENT (AMPS) CURRENT (AMPS) REQUIRED OPERATION TIME OF SECONDARY SOURCE FROM NFPA 72 2013 ED 10.6.7.2.1 Q LOW TAMPE SYSTEM STANDBY - 24 HOURS ALARM MINUTES S = 0.0833 HRS, 15 = 0.260 HRS QQQQQQQaaa WITCH SWITC ZONE _ N W o E:7777L I• U tnQ alyz 2 lLLWL c ^, W W C C J W N O N W Y :. U c Lu EL d Y�Cm� = u- O ) F1 11 1 _L_ I.O � O � N 11 p lL 0) U o WA A »oo FLOW LOW o m N N C a CV N ©F WF v oNN N LO U x ZONE 5 MliaCO TAMPER TAMPER TAMPER TAMPER TAMPER V V V V V THIS DRAWING AND ITS CONTENTS ARE THE PROPERTY OF ADT COMMERCIAL. IT IS NOT TO BE ZONE 4 ZONE 4 ZONE 4 ZONE 4 ZONE 4 USED OR DUPLICATED BY ANYONE WITHOUT THE WRITTEN CONSENT WATER WATER OF ADT COMMERCIAL. IF ANY ED BY ACT FLOW FLOW COMMERCIAL IS LTEREDENT RIN ANY MANNER WF WF BY OWNER, ITS AGENTS OR BY ANY THIRD PARTY IF CONSTRUCTION IS NOT IN ACCORDANCE WITH UNALTERED N E 3 N® ED BY ACT COMMERCIAL THEN IRTISUNDERSTOOD THAT ADT COMMERCIAL HAS NO LIABILITY IN WHOLE OR IN PART, RELATED TO THE PROJECT AND THAT THE OWNER TAMPER AGENTS INDEMNIFY AND HOLDS AND ITS VS HARMLESS ADT COMMERCIAL FOR ANY AND ALL ACTS RELATED TO THE PROJECT. THIS CONCEPT DRAWING IS FOR INFORMATION ONLY TO POTENTIAL ZONE 2 AREA O F WORK SYSTEM ARRANGEMENT. CONTRACTOR SHALL FIELD VERIFY ALL INFORMATION CONTAINED ON THESE DRAWINGS AND IS RESPONSIBLE FOR DESIGN AND INSTALLATI N OF THE SYSTEM IN FLOW ACCORDANCE E WITH THE SPECIFICATIONS. TO THE BEST OF ADT COMMERCIAL'S KNOWLEDGE THE DRAWINGS AND WF p p i n g SPECIFICATIONS SUBMITTED HEREWITH, ZONE 1 _ NOTERPRETMPLY IATIONS AND PREVISIONS OF r l n i n g C e S THE APPLICABLE N.F.P.A. CODES IN i EFFECT AT DATE SHOWN. FA M . E SCOPE OF WORK 1 I . . . 110VAC - z_ Lu QV G (� H- FIRE PANEL AND SURGE J v PROTECTOR GROUND SHALL BE BONDED TO A COMMON BOND POINT. Q n'1 m J ® ® LL QO �U Z J = Ln LU It -�i � uJ o Q [hippinq2 _ z zLL Non onveycbles � w � L.0 m LL � ® ® Non onveycbles CD L L rn Non Conveyables N y N N Non Conveyables ° m _2 m° Oils JURISDICTION: FT. PIERCE Oils DESIGNED BY: FR u` d d DATE: 3-72021 PROJECT NO: ######### Pit SCALE: 1/8" = 1'-0- R e c e i v i n TITLE: Cores Defects LAYOUT SHEET: FA-02 Item Description Standby Current per Device QTY Total Standby Current Alarm Current per Device CITY Total System Alarm Current A SK 5207 0.1200 X 1 = 0.1200 0.7000 X 1 = 0.7000 B 4W-B Smoke 0.0010 X 1 = 0.0010 0.0230 X 1 = 0.0230 C Water Flow 0.0000 X 5 = 0.0000 0.0000 X 5 = 0.0000 D Control Valve 0.0000 X 6 = 0.0000 0.0000 X 6 = 0.0000 E Sys Sens P2R 0.0000 X 1 = 0.0000 0.1680 X 1 = 0.1680 F X - 0.0000 X = 0.0000 G X - 0.0000 X = 0.0000 H X - 0.0000 X = 0.0000 I X = 0.0000 X = 0.0000 J X = 0.0000 X = 0.0000 K X = 0.0000 X = 0.0000 L X = 0.0000 X = 0.0000 M X = 0.0000 X = 0.0000 N X = 0.0000 X = 0.0000 REQUIRED TOTAL SYSTEM REQUIRED REQUIRED ALARM TOTAL SYSTEM REQUIRED ALARM STANDBY TIME STANDBY CURRENT STANDBY CAPACITY TIME (HOURS) ALARM CURRENT (HOUR) (AMPS) (AMP -HOURS) CURRENT (AMP -HOURS) 24 X 0.1210 = 2.9040 0.0833 X 0.8910 = 0.0742 REQUIRED REQUIRED ALARM TOTAL REQUIRED FACTORY OF REQUIRED BATTERY STANDBY CAPACITY CAPACITY SAFETY CAPACITY (AMP -HOURS) (AMP -HOURS) CAPACITY (AMP -HOURS) (AMP -HOURS) 2.9040 + 0.0742 = 2.9782 X 1.2 - 3.5739