HomeMy WebLinkAboutAPPROVED - Out Building Engineer LetterChief Building Official April 19, 2021 St Lucie County Building Department 2300 Virginia Avenue Ft Pierce, FL 34982 Location Out Building 3224 Live Oak Lane Fort Pierce, FL Subject: Metal sloped roof The out building will have a sloped metal roof installed. The metal roof will be a DM Class 1000 with a 1" nailstrip, 26 ga. galvalume coated steel roof panel, 16 wide, with 1" snap seam. The design pressures for the sloped metal roof are 37 psf in zone 1, 62 psf in zone 2 and 93 psf in zone 3 for a "C" exposure, less than 15 foot tall average roof height. These fastening patterns will meet the structural criteria of the 2020 Florida Building code, 71h. Edition, with a "C" exposure during a 170 mph„ i,. 132 mph asd wind event. If you have any questions, please call me at your convenience. Thank you. Dr. Ernest A. Kuonen, 20 President, The Erning Corporation CA-8327 228 Moccasin Trail, West Jupiter, FL 33458 WOLTER.S ENGINEERING ENGINEFiRING. DRAFTING, CONSULTING 15211 971h Road N West Palm Beach, FL 33412 PhlFx: (561) 226-1982 PRODUCT EVALUATION (FOR HVHZ APPROVED PRODUCT) PRODUCT: DM CLASS 1000 26 GA. GALVALUME 1" NAILSTRIP 16" WIDE ROOF PANEL (FLPA# 27499,1) MANUFACTURER: DYNAMIC METALS, LLC 340 PIKE ROAD WEST PALM BEACH, FL 33411 To all concerned, The DM Class 1000 Series 26 Ga. Galvalume 1" Nailstrip 16" Wide Roof Panel, manufactured by Dynamic Metals LLC, is a non-structural galvalume coated Fluropon painted steel roof panel (50 ksi min) that meets the requirements of Sections 1507A and 1518.9 of the 7th Edition (2020) Florida Building Code. The panel has been tested per TAS 100 and TAS 125 by Intertek with results shown in test reports G3443.40-450-44 and G3443.14- 450-44, and per TAS 110 by PRI Construction Materials Technologies, with results shown in test reports VLS-004- 02-01 and VLS-005-02-01. Technical Documentation. Drawing "NSS16-HZ" dated 8/15119, signed and sealed by Scott Wolters, PE. Test Reports listed above by Architectural Testing, Inc. signed and sealed by Vinu Abraham, PE, and by PRI Construction Materials Technologies, signed and sealed by Zachary R Priest, PE. Supplemental Calculations to support "NSS16-HZ" drawing, signed and sealed by Scott Wolters, PE. I have reviewed this submittal per the requirements of FAC Product Approval Rule Chapter 61 G20-3.005 (4). Based on the limitations listed below and those provided in the documents above, this product meets all the requirements of the 7t' Edition (2020) Florida Building Code generally, and chapter 15 specifically, including the HVHZ provisions. Limitations: This panel is approved for use inside and outside of the HVHZ. Overall Limitations: Maximum Panel Width: 16" (nominal) Fastener Spacing across panel: 16" (at Nailstrip) (Panels overlap with male/female snap fit) Min. Slope: HVHZ: 2"/12" Non-HVHZ: ''Y2712" (with Lap Sealant) 3712" (no Lap Sealant in Field Zone) ter , AV ZING IN l irAC I AN" �1'; I A46A V 1�v Field Installation Perimeter & Comer Installation Max. Design Pressure: Fastener S acin : ........_. -116 ssff 3" From Ends, 6" Max. O.C. - -176�sf ___.. 3" From Ends, 6" Max. O.C. Min Panel Fasteners: _. #10x1" Panclip Fasteners ___ #10x1" Panclip Fasteners Panel Sealant: Continuous bead of Geocel 2300 I or 2320 at Nailstrip side of seam Fire Barrier: Where required by code, install an approved fire barrier. Refer to a current fire directory listing for fire ratings of this roofing system assembly as well as the location of the fire barrier within the assembly. (See note #2 below,) Note: Outside of the HVHZ, 1" round plastic caps meeting the requirements of FBC Section 1507.1.1.1, may be used to prevent galvanic reactions. Underlayment: Minimum ASTM D 226 Type 11, installed and anchored per FBC Section 1507.1.1.1 (min). (or) Any undedayment with a valid FLPA or Miami -Dade NOA Note: Outside of the HVHZ, 1" round plastic caps meeting the requirements of FBC Section 1507,1.1.1 may be used to prevent galvanic reactions, Minimum Substrate: 1/2' (15/32" min) 4-ply CDX Plywood or'/4" solid wood planks S.G. = .42 min- nailed to 2x rafters spaced 24' max. on center with 8d ring -shank nails spaced 6' on center. Note: The 1/4" wood planking must be installed as a solid deck and must be nailed or fastened in a manner equal to the deck above, or as specified by a Florida licensed Architect/Engineer Other Limitations: 1. Roof slope must meet requirements of FBC Sections 1507.4.2 or 1515,2. 2. Fire classification is not a part of this evaluation. Refer to a current Approved Roofing Materials Directory for fire ratings of this product. 3. Design of substrate is by others and is not a part of this evaluation