HomeMy WebLinkAboutProject InformationBuilding Analysis Job: John Paul Edgar
Date:
Entire House By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Project• •
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Design
Conditions
Location:
Indoor:
Heating
Cooling
Vero Beach Municipal AP, FL, US
Indoor temperature (T)
70
75
Elevation: 30 ft
Design TD ('F)
27
16
Latitude: 28'N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (°F) 43
91
Infiltration:
Daily range (°F) -
16 (L
) Method
Simplified
Wet bulb (F -
78
Construction quality
Semi -tight
Wind speed mph) 15.0
7.5
Fireplaces
0
Heating
Component
Btuh/ft2
Btuh
% of load
Walls
2.4
1542
20.9
Glazing
12.6
540
7.3
Doors
10.5
214
2.9
Ceilings
0.7
416
5.6
Floors
3.4
2049
27.7
Infiltration
1.6
1082
14.7
Ducts
1097
14.9
Piping
0
0
Humidification
0
0
Ventilation
443
6.0
Adjustments
0
Total
7383
100.0
Cooling
Component
Btuh/ft2
Btuh
% of load
Walls
2.2
1387
19.8
Glazing
30.7
1313
18.7
Doors
11.4
232
3.3
Ceilings
1.4
815
11.6
Floors
0
0
0
Infiltration
0.5
334
4.8
Ducts
1448
20.6
Ventilation
255
3.6
Internal gains
1230
17.5
Blower
0
0
Adjustments
0
Total
7016
100.0
Latent Cooling Load = 1999 Btuh
Overall U-value = 0.094 Btuh/ftz-°F
Data entries checked.
Glazing
I Gains
;ts
wr1gt•tsoft- 2020-Nov-20 11:17:23
Right -Suite® Universal 2018 18.0.16 RS000268 Page 1
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N r
tom. _.:,.. :.,,-�• ._ � r
Component Constructions Job: John Paul Edgar
' Date:
Entire House By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Project• •
For: John Paul Edgar
5512 Pine'Tree Drive, Ft. Pierce, FL 34982
Design
Conditions
Location:
Indoor:
Heating
Cooling
Vero Beach Municipal AP, FL, US
Indoor temperature (T)
70
75
Elevation: 30 ft
Design TD (T)
27
16
Latitude: 28°N
Relative humidity (%)
30
50
Outdoor: Heating Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (T) 43 91
Infiltration:
Daily range (T) - 16 (L
)
Method
Simplified
Wet bulb (T) - 78
Construction quality
Semi -tight
Wind speed (mph) 15.0 7.5
Fireplaces
0
Construction descriptions
or
Area U-value Insul R
Htg HTM
Loss Clg HTM
Gain
ft' Btuh/ft?°F f2-°F/3tuh
BtuhM
Btuh
Btuh/ft'
Stu
Walls
12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2"
n
72 0.091 13.0
2.45
176
2.20
159
gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud
a
122 0.091 13.0
2.45
299
2.20
269
s
289 0.091 13.0
2.45
706
2.20
635
w
147 0.091 13.0
2.45
360
2.20
324
all
630 0.091 13.0
2.45
1542
2.20
1387
Partitions
(none)
Windows
4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4"
a
11 0.470 0
12.6
133
50.5
531
gap, 1/4" thk; 6.67 ft head ht
s
27 0.470 0
12.6
335
18.6
492
w
6 0.470 0
12.6
73
50.5
291
all
43 0.470 0
12.6
540
30.7
1313
Doors
11 DO: Door, wd sc type
a
20 0.390 0
10.5
214
11.4
232
Ceilings
16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2"
595 0.026 38.0
0.70
416
1.37
815
gypsum board intfnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth, tile flr fnsh
77 0.989 0
26.6
2049
0
0
wrightsoft' 2020-Nov-20 11:17:23
aa,..-..„..,a..P Right -Suite® Universal 2018 18.0.16 RS000268 Page 1
..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Component Constructions Job: John Paul Edgar
Date:
BathRoom By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533
5512 Pine Tree Drive, Ft.
Pierce, FL 34982
Design
Conditions
Location:
indoor:
Heating
Cooling
Vero Beach Municipal AP, FL, US
Indoor temperature ff)
70
75
Elevation: 30 ft
Design TD (T)
27
16
Latitude: 28°N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (T) 43
91
Infiltration:
Daily range (T) -
16
( L ) Method
Simplified
Wet bulb (T) -
78
Construction quality
Semi -tight
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions
Or Area U-value Insul R
Htg HTM
Loss Clg HTM Gain
ft' Btuh/ft? °F ft'-°F/Btuh
Btuh/ft'
Btu
BWh/ft'
Btu
Walls
12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2"
n 72 0.091 13.0
2.45
176
2.20
159
gypsum board int fnsh, 2'•x4" wood frm, 16" o.c. stud
s 72 0.091 13.0
2.45
176
2.20
159
w 147 0.091 13.0
2.45
360
2.20
324
all 291 0.091 13.0
2.45
713
2.20
641
Partitions
(none)
Windows
4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4" w 6 0.470
gap, 1/4" thk; 6.67 ft head ht
Doors
(none)
Ceilings f
16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 136 0.026
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth, the fir fnsh 33 0.989
0 12.6 73 50.5 291
38.0
0.70
95
1.37
186
0
26.6
878
0
0
I
Wriightsc)ft- 2020-Nov-20 11:17:23
.M-II I-- mPm Right -Suite® Universal 2018 18.0.16 RS000268 Page 2
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Component Constructions Job: John Paul Edgar
Date:
Hall By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Location:
Vero Beach Municipal AP, FL, US
Elevation: 30 ft
Latitude: 28°N
Outdoor: Heating
Dry bulb (T) 43
Daily range (7) -
Wet bulb (T) -
Wind speed (mph) 15.0
Indoor:
Indoor temperature (T)
Design TD (T)
Relative humidity (%)
Cooling
Moisture difference (gr/lb)
91
Infiltration:
16 ( L )
Method
78
Construction quality
7.5
Fireplaces
Construction descriptions or Area u-value
ft' BWh/ft' `F
Walls
(none)
Partitions
(none)
Windows
(none)
Doors
(none)
Ceilings
16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 30 0.026
gypsum board intfnsh
Floors
(none)
Heating Cooling
70
75
27
16
30
50
-0.2
58.7
Simplified
Semi -tight
0
Insul R Htg HTM Loss Clg HTM Gain
ft'-°FBtuh Btuh/ft' Btu Btu hflN Btu
38.0 0.70 21 1.37 41
wrightsoftg 2020-Nov-20 11:17:23
Right -Suite® Universal 2018 18.0.16 RS000268 Page 3
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Component Constructions Job: John Paul Edgar
Date:
Pantry By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Design
Conditions
Location:
Indoor:
Heating
Cooling
Vero Beach Municipal AP, FL, US
Indoor temperature ff)
70
75
Elevation: 30 ft
Design TD (°F)
27
16
Latitude: 28°N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (T) 43
91
Infiltration:
Daily range (T) -
16 ( L
) Method
Simplified
Wet bulb (T) -
78
Construction quality
Semi -tight
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
it, Btuh/ft"F ft'-°F/Btuh Btuh/ft' Btu Btuh/ft' Btu
Walls
(none)
Partitions
(none)
Windows
(none)
Doors
(none)
Ceilings
16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 43 0.026 38.0 0.70 30 1.37 58
gypsum board intfnsh
Floors
(none)
4 wriightsoftl 2020-Nov-20 11:17:23
aw ,�, •aw ,...,� „� Right -Suite® Universal 2018 18.0.16 RS000268 Page 4
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
i
Component Constructions
Job: John Paul EdgarDate:
Play Room
By: Jimmy
Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651. Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Project•
•
For:
John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Design
Conditions
Location:
Indoor:
Heating
Cooling
Vero Beach Municipal
AP, FL, US
Indoor temperature (T)
70
75
Elevation: 30 ft
Design TD (T)
27
16
Latitude: 28'N
Relative humidity (%)
30
50
Outdoor:
Heating Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (T)
43 91
Infiltration:
Daily range (T)
- 16 ( L
) Method
Simplified
Wet bulb ff)
- 78
Construction quality
Semi -tight
Wind speed (mph)
15.0 7.5
Fireplaces
0
Construction descriptions or Area U-value
ft' Btu hffl'F
Walls
12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2" s 110 0.091
gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud
Partitions
(none)
Windows
4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4" s 21 0.470
gap, 1/4" thk; 6.67 ft head ht
Doors
(none)
Ceilings
1613-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 174 0.026
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth, tile flr fnsh 15 0.989
Insul R Htg HTM Loss Clg HTM Gain
ft'-°F/Btuh Btuhtft' Btu Btuh/ft' Btu
13.0
0
38.0
0
2.45 268 2.20 241
12.6 266 18.6 390
0.70 122 1.37 238
26.6 386 0 0
" wrightsoft- 2020-Nov-20 11:17:23
�m„o�• ,o,v,.... e.,� M Right -Suite® Universal 2018 18.0.16 RS000268 Page 5
..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Corn onent Constructions Job: John Paul Edgar
P Date:
Utility By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Design
Conditions
Location:
Indoor:
Heating
Cooling
Vero Beach Municipal AP, FL, US
Indoor temperature (T)
70
75
Elevation: 30 ft
Design TD (T)
27
16
Latitude: 28°N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
-0.2
58.7
Dry bulb (T) 43
91
Infiltration:
Daily range (T) -
16 (L
) Method
Simplified
Wet bulb (T) -
78
Construction quality
Semi -tight
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions
or
Area
U-value
Insul R
Htg HTM
Loss Clg HTM
Gain
ft'
Btuh/ft'--°F
f'-°FBtuh
Btu h/ft'
BWh
Btuh/ft'
Btuh
Walls
12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2"
a
122
0.091
13.0
2.45
299
2.20
269
gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud
s
107
0.091
13.0
2.45
262
2.20
236
all
229
0.091
13.0
2.45
561
2.20
505
Partitions
(none)
Windows
4A4-2ov: 2 glazing, clr, outr, argon gas, vnl frm mat, clr low-e innr, 1/4" e 11 0.470 0 12.6 133 50.5 531
gap, 1/4" thk; 6.67 ft head ht s 6 0.470 0 12.6 70 18.6 102
all 16 0.470 0 12.6 202 39.5 633
Doors
11 DO: Door, wd sc type a 20 0.390 0 10.5 214 11.4 232
Ceilings
16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 213 0.026 38.0 0.70 149 1.37 291
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth, file fir fnsh 30 0.989 0 26.6 785 0 0
1 _rk wrightsoft- 2020-Nov-20 11:17:23
Right -Suite® Universal 2018 18.0.16 RS000268 Page 6
ACCK ..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Project Summary
Entire House
Ace Air Conditioning
Job: John Paul Edgar
Date:
By: Jimmy Evans
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Uffe7lect Intormation
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Notes:
Weather: Vero Beach Municipal AP, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 43 °F Outside db 91 °F
Inside db 70 °F Inside db 75 °F
Design TD 27 °F Design TD 16 °F
Daily range L
Relative humidity 50 %
Moisture difference 59 gr/lb
Heating Summary
Structure 6286 Btuh
Ducts 1097 Btuh
Central vent (0 cfm) 0 Btuh
(none)
Humidification 0 Btuh
Piping 0 Btuh
Equipment load 7383 Btuh
Infiltration
Method
Construction quality
Fireplaces
Simplified
Semi -tight
0
Heating
cooling
Area (ft2)
595
595
Volume (ft3)
5355
5355
Air changes/hour
0.41
0.22
Equiv. AVF (cfm)
37
20
Heating Equipment Summary
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
Capacity balance point = 5 °F
Backup:
8.2 HSPF
33800
Btuh @ 47°F
77
°F
400
cfm
0.054
cfm/Btuh
0.50
in H2O
Sensible Cooling Equipment Load Sizing
Structure
5568
Btuh
Ducts
1448
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
Rate/swing multiplier
n
0.95
Equipment sensible load
6701
Btuh
Latent Cooling Equipment Load Sizing
Structure
1581
Btuh
Ducts
418
Btuh
Central vent (0 cfm)
0
Btuh
(pone)
Equipment latent load
1999
Btuh
Equipment Total Load (Sen+Lat)
8699
Btuh
Req. total capacity at 0.80 SHR
0.7
ton
Cooling Equipment Summary
Make
Trade
Cond
Coil
AHRI ref
Efficiency
Sensible cooling
Latent cooling
Total cooling
Actual air flow
Air flow factor
Static pressure
Load sensible heat ratio
11.5 EER, 14 SEER
26400
Btuh
6600
Btuh
33000
Btuh
400
cfm
0.057
cfm/Btuh
0.50
in H2O
0.78
Input = 3 kW, Output = 9735 Btuh, 100 AFUE
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-rk- wriohtsoft- 2020-Nov-20 11:17:23
-- Right -Suite® Universal 2018 18.0.16 RS000268 Page 1
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Job M John Paul Edgar
Performed by Jimmy Evans for:
John Paul Edgar
5512 Pine Tree Drive
Ft. Pierce, FL 34982
Sheet 1
Ace Air Conditioning
2985 Enterprise Rd.
Debary, FL 32713
Phone:386-668-8651 Fax:386-668-7758
www.aceac.com jevans@aceac.com
Scale: 1 : 107
Page 1
Right -Suite® Universal 2018
18.0.16 RS000268
2020-Nov-20 11:17:27
...tailed Enterprises\John Paul.rup
Duct System Summary Jo e: John Paul Edgar
Entire House By: Jimmy Evans
9-1 Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Project Information
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.50
in H2O
0.18
in H2O
0.32
in H2O
0.183 / 0.137
in H2O
0.165
in/100ft
400
cfm
Cooling
0.50
in H2O
0.18
in H2O
0.32
in H2O
0.183 / 0.137
in H2O
0.165
in/100ft
400
cfm
194 ft
Supply Branch Detail Table
Design
Htg
Clg
Design
Diam
H x W
Duct
Actual
Ftg.Egv
Name
(13tuh)
(cfm)
(cfm)
FIR
(in)
(in)
Mat]
Ln (ft)
Ln (ft)
Trunk
BathRoom
h 2754
149
103
0.168
7.0
Ox0
VIFx
9.0
100.0
Pantry
h 179
10
10
0.171
4.0
Ox0
VIFx
7.2
100.0
Play Room
c 2203
87
126
0.179
7.0
Ox 0
VIFx
2.1
100.0
Utility
c 2846
154
162
0.165
8.0
Ox0
VIFx
10.7
100.0
Return Branch Detail Table
Grille
Htg
Clg
TEL
Design
Veloc
Diam
H x W
Stud/Joist
Duct
Name
Size (in)
(cfm)
(cfm)
(ft)
FIR
(fpm)
(in)
(in)
Opening (in)
Mat]
Trunk
rb2
Ox 0
163
172
83.1
0.165
315
10.0
0x 0
VIFx
rb1
Ox 0
237
228
74.0
0.185
434
10.0
Ox 0
VIFx
Bold/italic values have been manually overridden
wrightsoft, 2020-Nov-20 11:17:23
Right-SuiteO Universal 2018 18.0.16 RS000268 Page 1
JCCK ... Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Duct system multi orientation report
Entire House
Ace Air Conditioning
Job: John Paul Edgar
Date:
By: Jimmy Evans
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533
Project• •
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Group 1: (N, NE, S) Group 2: (E, SE, SW, W, NW)
dO ttNacne
i : i
eg CFM eg�Li� tict Srie
ir;NE}
egvCFM eg Siae iict Size eg�IC eg Slag uct Size
969E
eg CFM eg Siaa uct Sim
I. Branches
BathRoom
149 h
12x6
7
149 h
12x6 7
149 h
12x6
7
149 h
12x6
7
Pantry10
h
8x4
4
10 h
8x4
4
10 h
8x4
4
10 h
8x4
4
PlayRoom
182 c,
12x6
8
157 c''
12x6
8
126 c
12x6
7
149 c
12x6
7
U tility
154 h
14x8
8
154 h
14x8
8
162 c
148
8
154 h
148
8
eturtn Branches
rb2
12x12
10
163 h
12x12
10
172 c
12x12
10
163 h
12x12
10
b1
;63
12x12
10
244 c
12x12
10
237 h
12x12
10
238 c
12x12
10
0.165
0.165
0.165
Heatin FR
Cooling FIR
0.165
1
1 0.165
0.165
0.165
- * wrightsoft, 2020-Nov-20 11:17:23
,rti Right -Suite@ Universal 2018 18.0.16 RS000268 Page 1
J+CK ... Calculations\DetailedaEnterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Project Information
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
WAR==
t aMUMMOMF
OF
egs
uct Size,
eg�CFM
S
uci Sizes
CPM
eg Sim
ct Sis
GSM
eg+Sb
ct Size
h,GfiGi3S,Mal
MEW
MMMOM
WMEMIMAM
BathRoom
149 h
12x6
7
149 h
12x6
7
149 h
12x6
7
149 h
12x6
7
Pantry
10 h
8x4
4
10 h
8x4
4 '
10 h
8x4
4
10 h
8x4
4
PlayRoom
Ta`171,=c<:
1M
8
146 c
12x6
7
118 c
12x6
7 °'°'
4154 c"
12x6
7-'-,
Alit
154 h",
14z8
8
I58 c
14x8
8
'177c
14x8
8
158'c
148
8
etBcancties
�187
rb2
163 h
12x12
10
167 c
12x12
10
c
12x12
10
167 c
12x12
10
rb1
248 c
12x12
10
237 h
12x12
10
237 h
12x12
10
237 h
12x12
10
-
.
;
x
�
,
Heating FIR0.165
0.165
0.165.
0.165
Cooling FIR0.165
0.165
0.165
0.165
wrightsoft, 2020-Nov-20 11:17:23
,rt . -1.., ,,... , Right -Suite® Universat201818.0.16 RS000268 Paget
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Project Inf• •
For: John Paul Edgar
5512 Pine;Tree Drive, Ft. Pierce, FL 34982
4 MIName
ll.ar r '"t
lSrnaiest
®RecllSiza ,t7u"ctiSizH� eg CFM �,. ear® tLiuctlSlm
12x6 7 149 h 12x6 7
Rea1GFM
R55. Branches
BathRoom
149 h
Pantry
10 h
8x4
4
10 h
8x4
4
Play Room
182 c
12x6
8
.118 c
12x6
7,
Utility
177 c
148
8
154 h
148
8
x:eturn BrLanches
163 h
12x12
10
rb2
187 c
12x12
10
rb1
253 c
12x12
10
237 h
12x12
10
riction F2ates
Heating FR
.165
0.165
Cooling FR
P.165
0.165
wrightSoft`° 2020-Nov-20 11:17:23
Right -Suite@ Universal 2018 18.0.16 RS000268 Page 3
...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Static Pressure and Friction Rate Job: John Paul Edgar
Date:
Entire House By: Jimmy Evans
Ace Air Conditioning
2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533
iwroject inTormation
For: John Paul Edgar
5512 Pine Tree Drive, Ft. Pierce, FL 34982
Available Static Pressure
Heating
Cooling
(in H2O)
(in H2O)
External static pressure
0.50
0.50
Pressure losses
Coil
0
0
Heat exchanger
0
0
Supply diffusers
0.04
0.04
Return grilles
0.04
0.04
Filter
0.10
0.10
Humidifier
0
0
Balancing damper
0
0
Other device
0
0
Available static pressure
0.32
0.32
Total Effective Length
Supply
Return
(ft)
(ft)
Measured length of run -out
11
13
Measured length of trunk
0
0
Equivalent length of fittings
100
70
Total length
111
83
Total effective length
194•
Supply Ducts
Return Ducts
Friction Rate
Heating
(in/100ft)
0.165 OK
0.165 OK
Cooling
(in/100ft)
0.165 OK
0.165 OK
Fitting Equivalent Length Details
Supply.• 1A=35, 11G=5: TotalEL=100
Return 5D=40, 6M=20, 11 G=5, 11 G=5: TotalEL=70
.t wrightsott`° 2020-Nov-2011:17:24
Right -Suite® Universal 2018 18.0.16 RS000268 Page 1
+� ... Calculations\DetailedsEnterprises\John Paul.rup Calc = MJ8 Front Door faces: N
Prepared By:
Ace Air Conditioning
Jimmy Evans FORMS
HVAC/Mechanical License;
CAC1813533
FLORIDA BUILDING CODE, ENERGY CONSERVATION
FORIVI R402-2017
Residential Building Thermal Envelope Approach
Climate Zone 0
Scope: Compliance with Section R401.2(1) of the Florida Building Code, Energy Conservation, shall be demonstrated by the use of Form
R402 for single- and multiple -family residences of three stories or less in height, additions to existing residential buildings, alterations,
renovations and building systems in existing buildings, as applicable. To comply, a building must meet or exceed all of the energy efficiency
requirements on Table R402A and all applicable mandatory requirements summarized in Table R402B of this form. If a building does not
comply with this method, or by the UA Alternative method, it may still comply under Section R405 of the Florida Buliding Code, Energy
Conservation.
PROJECT NAME John Paul Edgar
ANDADDRESS:5512 Pine Tree Dr. Ft Peirce BUILDER:
OWNER: John Paul Edgar
PERMITTING OFFICE:
JURISDICTION NUMBER:
General instructions: PERMIT NUMBER:
1. Fill in all the applicable spaces of the 'To Be Installed" column on Table R402A with the information requested. All "To Be Installed" values must be
equal to or more efficient than the required levels.
2. Complete page 1 based on the "To Be Installed" column information.
3. Read the requirements of Table R402B and check each box to Indicate your intent to comply with all applicable Items.
4. Read, sign and date the "Prepared By" certification statement at the bottom of page 1. The owner or owner's agent must also sign and date the form.
1. New construction, addition, or existing building 1. Addition
2. Single-family detached or multiple -family attached
3. If multiple -family, number of units covered by this submission 2 --
4. Is this a worst case? (yes/no) 3. --
4. No _
5. Conditioned floor area (sq. ft.) 5. 595
S. Windows, type and area
a) U-factor: Ba. .40
b) Solar Heat Gain Coefficient (SHGC) 6b - 2 5
c) Area
7. Skylights sc• -43-
a) U-factor: 7a
b) Solar Heat Gain Coefficient (SHGC) 7b -
8. Floor type, area or perimeter, and insulation:
a) Slab -on -grade (R-value) 8a 595
+
b) Wood, raised (R-value) 8b.
c) Wood, common (R-value) 80.-
d) Concrete, raised (R-value) 8d i
e) Concrete, common (R-value) 8e
9. Wall type and insulation:
a) Exterior: 1. Wood frame (Insulation R-value) gat, i
2. Masonry (insulation R-value) 9a2. 6
b) Adjacent: 1. Wood frame (Insulation R-value) 9bl.
2. Masonry (Insulation R-value) 9b2
10. Ceiling type and insulation
a) Attic (Insulation R-value) 10a. R-38 '
b) Single assembly (Insulation R-value) 10b.
11. Air distribution system: '
a) Duct location, insulation 11a Attic, R-8 '
b) AHU location 11b. Attic
c) Total duct leakage. Test report attached. 11c. -
cfm/100 s.f. Yes ❑ No ❑ 12. Cooling system: a) type 12a. Central '
b) efficiency 12b. 14 -- '
13. Heating system: a) type 13a. Heat Pump -
b) efficiency 13b. Egtg-
14. HVAC sizing calculation: attached 14. Yes IN No [I15. Water heating system: a) type 15a. Existin
b) erficie 15b. -
I hereby certify that the plans and sp ci is s covered by this form are Review of plans and specifications covered by this form indicate i
In compliance with the Florida Build de, nergy Conservation. compliance with the Florida Building Code, Energy Conservation. Before
PREPARED BY: Jimm Evans Date 6 - 2 4 -2 0 construction is complete, this building will be Inspected for compliance in
I hereby certify that this building Is n I ce with the Florida Building accordance with Section 553.908, F.S.
Code. Energy Conservation. CODE OFFICIAL:
OWNER/AG ENT: Date: Date:
FLORIDA BUILDING CODE - ENERGY CONSERVATION, 6th EDITION (2017)
R 55
---------- 1 LF... C.0
FORMS
TABLE R402A
BUILDING COMPONENT
PRESCRIPTIVE REQUIREMENTS'
INSTALLED VALUES
Climate Zone 1
Climate Zone 2
Windows
U-Factor = NR
U-Factor = 0.40'
U-Factor =
SHGC = 0.25
SHGC = 0.25
SHGC =
Skylights
U-factor = 0.75
U factor = 0.65
U factor =
SHGC = 0.30
SHGC = 0.30
SHGC =
Doors: Exterior door
U-factor = NR
U-factor = 0.40'
U-factor=
Floors:
Slab -on -Grade
NR
NR
Over unconditioned spaces°
R-13
R-13
R-Value =
Walls°: Ext. and Adj.
Frame
R-13
R-13
R-Value =
Mass
Insulation on wall interior
R-4
R-6
R-Value =
Insulation on wall exterior
R-3
R-4
R-Value =
Ceilings'
R=30
R=38
R-Value =
Air infiltration
Blower door test is required on the building envelope to verify leakage <_ 1 ACH;
Total leakage = ACH
test report provided to code official.
Test rert attached?
Yes H No
Air distribution systems:
Air handling unit
Not allowed in,attic
Location: Attic
Duct R-value
R-value>_ R-8 (supply in attics) or>_ R-6 (all other duct locations)
R-Value = R-8
Air leakage':
Duct test
Postconstruction test Total leakage _< 4 cfm/100 s.f.
Total leakage = cfm/100s.f.
Rough -in test Total leakage <_ 4 cfm/100 s.f. (air handler installed)
Test report Attached? Yes ® No ❑
Total leakage <_ 3 cfm/100 s.f. (air handler not installed)
Location:
Ducts in conditioned space
Test not required if all ducts and AHU are in conditioned space
Air conditioning system:
Minimum federal standard required by NAECA':
Central system <_ 65,000 Btu/h
SEER 14.0
SEER= Existing
Room unit or PTAC
EER [from Table C403.2.3(3)]
EER =
Other:
See Tables C403.2.3(1)-(11)
Heating system:
Minimum federal standard required by NAECA':
Heat pump <_ 65,000 Btu/h
HSPF 8.2
HSPF =
Gas furnace, non -weatherized
AFUE80%
AFUE= Existing
Oil furnace, non -weatherized
AFUE 83 %
AFUE =
Other:
Water heating system (storage type):
Minimum federal standard required by NAECA':
Electrid
40 gal: EF = 0.92
Gallons =
50 gal: EF = 0.90
EF= Existing
Gas fired'
40 gal: EF = 0.59
Gallons =
50 gal: EF = 0.58
EF =
Other (describe):
NR = No requirement.
(1) Each component present in the As Proposed home must meet or exceed each of the applicable performance criteria in order to comply with this code using
this method.
(2) For impact rated fenestration complying with Section R301.2.1.2 of the Florida Building Code, Residential or Section 1609.1.2 of the Florida Building Code,
Building, the maximum U-factor shall be 0.65 -in Climate Zone 2. An area -weighted average of U-factor and SHGC shall be accepted to meet the
requirements, or up to 15 square feet of glazed ;fenestration area are exempted from the U-factor and SHGC requirement based on Sections R402.3.1,
R402.3.2 and R402.3.3.
(3) One side -hinged opaque door assembly up to 24 square feet is exempted from this U-factor requirement.
(4) R-values are for insulation material only as applied in accordance with manufacturer's installation instructions. For mass walls, the "interior of wall'
requirement must be met except if at least 50 percent of the insulation required for the "exterior of wall" is installed exterior of, or integral to, the wall.
(5) Ducts & AHU installed "substantially leak free" per Section R403.3.2. Test required by either individuals as defined in Section 553.993(5) or (7), Florida
Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. The total leakage test is not required for ducts and air
handlers located entirely within the building thermal envelope.
(6) Minimum efficiencies are those set by the National Appliance Energy Conservation Act of 1987 for typical residential equipment and are subject to NAECA
rules and regulations. For other types of equipment, see Tables C403.2.3(1-11) of the Commercial Provisions of the Florida Building Code, Energy
Conservation.
(7) For other electric storage volumes, minimum EF = 0.97 - (0:00132 * volume).
(8) For other natural gas storage volumes, minimum EF = 0.67 - (0.0019 * volume).
R-56 FLORIDA BUILDING CODE — ENERGY CONSERVATION, 6th EDITION (2017)
FORMS
TABLE R402B MANDATORY REQUIREMENTS,
Component
Section I
Summary of Requirement(s)
Check
Air leakage
R402.4
To be caulked, gasketed, weatherstripped or otherwise sealed per Table R402.4.1.1. Recessed lighting: IC -rated as
having <_ 2.0 cfm tested to ASTM E 283.
Windows and doors: 0.3 cfm/sq. ft. (swinging doors: 0.5 cfm/sf) when tested to NFRC 400 or
AAMAIWDMA/CSA 101/I.S. 2/A440.
Fireplaces: Tight -fitting flue dampers & outdoor combustion air.
Programmable
R403.1.2
A programmable thermostat is required for the primary heating or cooling system.
thermostat
Ducts shall The tested as per Section R403.3.2 by either individuals as defined in Section 553.993(5) or (7), Florida
Air distribution system
R403.3.2
Statutes, or, individuals licensed as set forth in Section 489.105(3) (f), (g) or (i), Florida Statutes. Air handling units
R403.3.4
are not,allowed in attics.
Water heaters
R403.5
Comply with efficiencies in Table C404.2. Hot water pipes insulated to >_ R-3 to kitchen outlets, other cases.
Circulating systems to have an automatic or accessible manual OFF switch. Heat trap required for vertical pipe
risers.
Swimming pools & spas
R403.10
Spas and heated pools must have vapor -retardant covers or a liquid cover or other means proven to reduce heat
loss except'if 70 % of heat from site -recovered energy. Off/timer switch required. Gas heaters minimum thermal
efficiency is 82 % . Heat pump pool heaters minimum COP is 4.0.
Cooling/heating
R403.7
Sizing calculation performed & attached. Special occasion cooling or heating capacity requires separate system or
equipment
variable capacity system.
Lighting equipment
R404.1
At least 75 % of permanently installed lighting fixtures shall be high -efficacy lamps.
FLORIDA BUILDING CODE — ENERGY CONSERVATION, 6th EDITION (2017) R-57