HomeMy WebLinkAboutProject InformationBuilding Analysis Job: John Paul Edgar Date: Entire House By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Project• • For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (T) 70 75 Elevation: 30 ft Design TD ('F) 27 16 Latitude: 28'N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (°F) 43 91 Infiltration: Daily range (°F) - 16 (L ) Method Simplified Wet bulb (F - 78 Construction quality Semi -tight Wind speed mph) 15.0 7.5 Fireplaces 0 Heating Component Btuh/ft2 Btuh % of load Walls 2.4 1542 20.9 Glazing 12.6 540 7.3 Doors 10.5 214 2.9 Ceilings 0.7 416 5.6 Floors 3.4 2049 27.7 Infiltration 1.6 1082 14.7 Ducts 1097 14.9 Piping 0 0 Humidification 0 0 Ventilation 443 6.0 Adjustments 0 Total 7383 100.0 Cooling Component Btuh/ft2 Btuh % of load Walls 2.2 1387 19.8 Glazing 30.7 1313 18.7 Doors 11.4 232 3.3 Ceilings 1.4 815 11.6 Floors 0 0 0 Infiltration 0.5 334 4.8 Ducts 1448 20.6 Ventilation 255 3.6 Internal gains 1230 17.5 Blower 0 0 Adjustments 0 Total 7016 100.0 Latent Cooling Load = 1999 Btuh Overall U-value = 0.094 Btuh/ftz-°F Data entries checked. Glazing I Gains ;ts wr1gt•tsoft- 2020-Nov-20 11:17:23 Right -Suite® Universal 2018 18.0.16 RS000268 Page 1 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N r tom. _.:,.. :.,,-�• ._ � r Component Constructions Job: John Paul Edgar ' Date: Entire House By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Project• • For: John Paul Edgar 5512 Pine'Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (T) 70 75 Elevation: 30 ft Design TD (T) 27 16 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (T) 43 91 Infiltration: Daily range (T) - 16 (L ) Method Simplified Wet bulb (T) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft?°F f2-°F/3tuh BtuhM Btuh Btuh/ft' Stu Walls 12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2" n 72 0.091 13.0 2.45 176 2.20 159 gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud a 122 0.091 13.0 2.45 299 2.20 269 s 289 0.091 13.0 2.45 706 2.20 635 w 147 0.091 13.0 2.45 360 2.20 324 all 630 0.091 13.0 2.45 1542 2.20 1387 Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4" a 11 0.470 0 12.6 133 50.5 531 gap, 1/4" thk; 6.67 ft head ht s 27 0.470 0 12.6 335 18.6 492 w 6 0.470 0 12.6 73 50.5 291 all 43 0.470 0 12.6 540 30.7 1313 Doors 11 DO: Door, wd sc type a 20 0.390 0 10.5 214 11.4 232 Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 595 0.026 38.0 0.70 416 1.37 815 gypsum board intfnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth, tile flr fnsh 77 0.989 0 26.6 2049 0 0 wrightsoft' 2020-Nov-20 11:17:23 aa,..-..„..,a..P Right -Suite® Universal 2018 18.0.16 RS000268 Page 1 ..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Component Constructions Job: John Paul Edgar Date: BathRoom By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature ff) 70 75 Elevation: 30 ft Design TD (T) 27 16 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (T) 43 91 Infiltration: Daily range (T) - 16 ( L ) Method Simplified Wet bulb (T) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft? °F ft'-°F/Btuh Btuh/ft' Btu BWh/ft' Btu Walls 12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2" n 72 0.091 13.0 2.45 176 2.20 159 gypsum board int fnsh, 2'•x4" wood frm, 16" o.c. stud s 72 0.091 13.0 2.45 176 2.20 159 w 147 0.091 13.0 2.45 360 2.20 324 all 291 0.091 13.0 2.45 713 2.20 641 Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4" w 6 0.470 gap, 1/4" thk; 6.67 ft head ht Doors (none) Ceilings f 16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 136 0.026 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth, the fir fnsh 33 0.989 0 12.6 73 50.5 291 38.0 0.70 95 1.37 186 0 26.6 878 0 0 I Wriightsc)ft- 2020-Nov-20 11:17:23 .M-II I-- mPm Right -Suite® Universal 2018 18.0.16 RS000268 Page 2 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Component Constructions Job: John Paul Edgar Date: Hall By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533 For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Location: Vero Beach Municipal AP, FL, US Elevation: 30 ft Latitude: 28°N Outdoor: Heating Dry bulb (T) 43 Daily range (7) - Wet bulb (T) - Wind speed (mph) 15.0 Indoor: Indoor temperature (T) Design TD (T) Relative humidity (%) Cooling Moisture difference (gr/lb) 91 Infiltration: 16 ( L ) Method 78 Construction quality 7.5 Fireplaces Construction descriptions or Area u-value ft' BWh/ft' `F Walls (none) Partitions (none) Windows (none) Doors (none) Ceilings 16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 30 0.026 gypsum board intfnsh Floors (none) Heating Cooling 70 75 27 16 30 50 -0.2 58.7 Simplified Semi -tight 0 Insul R Htg HTM Loss Clg HTM Gain ft'-°FBtuh Btuh/ft' Btu Btu hflN Btu 38.0 0.70 21 1.37 41 wrightsoftg 2020-Nov-20 11:17:23 Right -Suite® Universal 2018 18.0.16 RS000268 Page 3 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Component Constructions Job: John Paul Edgar Date: Pantry By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533 For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature ff) 70 75 Elevation: 30 ft Design TD (°F) 27 16 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (T) 43 91 Infiltration: Daily range (T) - 16 ( L ) Method Simplified Wet bulb (T) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain it, Btuh/ft"F ft'-°F/Btuh Btuh/ft' Btu Btuh/ft' Btu Walls (none) Partitions (none) Windows (none) Doors (none) Ceilings 16B-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 43 0.026 38.0 0.70 30 1.37 58 gypsum board intfnsh Floors (none) 4 wriightsoftl 2020-Nov-20 11:17:23 aw ,�, •aw ,...,� „� Right -Suite® Universal 2018 18.0.16 RS000268 Page 4 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N i Component Constructions Job: John Paul EdgarDate: Play Room By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651. Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Project• • For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (T) 70 75 Elevation: 30 ft Design TD (T) 27 16 Latitude: 28'N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (T) 43 91 Infiltration: Daily range (T) - 16 ( L ) Method Simplified Wet bulb ff) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value ft' Btu hffl'F Walls 12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2" s 110 0.091 gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud Partitions (none) Windows 4A4-2ov: 2 glazing, clr outr, argon gas, vnl frm mat, clr low-e innr, 1/4" s 21 0.470 gap, 1/4" thk; 6.67 ft head ht Doors (none) Ceilings 1613-38ad:Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 174 0.026 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth, tile flr fnsh 15 0.989 Insul R Htg HTM Loss Clg HTM Gain ft'-°F/Btuh Btuhtft' Btu Btuh/ft' Btu 13.0 0 38.0 0 2.45 268 2.20 241 12.6 266 18.6 390 0.70 122 1.37 238 26.6 386 0 0 " wrightsoft- 2020-Nov-20 11:17:23 �m„o�• ,o,v,.... e.,� M Right -Suite® Universal 2018 18.0.16 RS000268 Page 5 ..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Corn onent Constructions Job: John Paul Edgar P Date: Utility By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Design Conditions Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (T) 70 75 Elevation: 30 ft Design TD (T) 27 16 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (T) 43 91 Infiltration: Daily range (T) - 16 (L ) Method Simplified Wet bulb (T) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ft'--°F f'-°FBtuh Btu h/ft' BWh Btuh/ft' Btuh Walls 12C-Osw: Frm wall, stucco ext, 5/8" wood shth, r-13 cav ins, 1/2" a 122 0.091 13.0 2.45 299 2.20 269 gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud s 107 0.091 13.0 2.45 262 2.20 236 all 229 0.091 13.0 2.45 561 2.20 505 Partitions (none) Windows 4A4-2ov: 2 glazing, clr, outr, argon gas, vnl frm mat, clr low-e innr, 1/4" e 11 0.470 0 12.6 133 50.5 531 gap, 1/4" thk; 6.67 ft head ht s 6 0.470 0 12.6 70 18.6 102 all 16 0.470 0 12.6 202 39.5 633 Doors 11 DO: Door, wd sc type a 20 0.390 0 10.5 214 11.4 232 Ceilings 16B-38ad: Attic ceiling, asphalt shingles roof mat, r-38 ceil ins, 1/2" 213 0.026 38.0 0.70 149 1.37 291 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth, file fir fnsh 30 0.989 0 26.6 785 0 0 1 _rk wrightsoft- 2020-Nov-20 11:17:23 Right -Suite® Universal 2018 18.0.16 RS000268 Page 6 ACCK ..Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Project Summary Entire House Ace Air Conditioning Job: John Paul Edgar Date: By: Jimmy Evans 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Uffe7lect Intormation For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Notes: Weather: Vero Beach Municipal AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 43 °F Outside db 91 °F Inside db 70 °F Inside db 75 °F Design TD 27 °F Design TD 16 °F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Structure 6286 Btuh Ducts 1097 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 7383 Btuh Infiltration Method Construction quality Fireplaces Simplified Semi -tight 0 Heating cooling Area (ft2) 595 595 Volume (ft3) 5355 5355 Air changes/hour 0.41 0.22 Equiv. AVF (cfm) 37 20 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacity balance point = 5 °F Backup: 8.2 HSPF 33800 Btuh @ 47°F 77 °F 400 cfm 0.054 cfm/Btuh 0.50 in H2O Sensible Cooling Equipment Load Sizing Structure 5568 Btuh Ducts 1448 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data Rate/swing multiplier n 0.95 Equipment sensible load 6701 Btuh Latent Cooling Equipment Load Sizing Structure 1581 Btuh Ducts 418 Btuh Central vent (0 cfm) 0 Btuh (pone) Equipment latent load 1999 Btuh Equipment Total Load (Sen+Lat) 8699 Btuh Req. total capacity at 0.80 SHR 0.7 ton Cooling Equipment Summary Make Trade Cond Coil AHRI ref Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 11.5 EER, 14 SEER 26400 Btuh 6600 Btuh 33000 Btuh 400 cfm 0.057 cfm/Btuh 0.50 in H2O 0.78 Input = 3 kW, Output = 9735 Btuh, 100 AFUE Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -rk- wriohtsoft- 2020-Nov-20 11:17:23 -- Right -Suite® Universal 2018 18.0.16 RS000268 Page 1 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Job M John Paul Edgar Performed by Jimmy Evans for: John Paul Edgar 5512 Pine Tree Drive Ft. Pierce, FL 34982 Sheet 1 Ace Air Conditioning 2985 Enterprise Rd. Debary, FL 32713 Phone:386-668-8651 Fax:386-668-7758 www.aceac.com jevans@aceac.com Scale: 1 : 107 Page 1 Right -Suite® Universal 2018 18.0.16 RS000268 2020-Nov-20 11:17:27 ...tailed Enterprises\John Paul.rup Duct System Summary Jo e: John Paul Edgar Entire House By: Jimmy Evans 9-1 Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Project Information For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in H2O 0.18 in H2O 0.32 in H2O 0.183 / 0.137 in H2O 0.165 in/100ft 400 cfm Cooling 0.50 in H2O 0.18 in H2O 0.32 in H2O 0.183 / 0.137 in H2O 0.165 in/100ft 400 cfm 194 ft Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (13tuh) (cfm) (cfm) FIR (in) (in) Mat] Ln (ft) Ln (ft) Trunk BathRoom h 2754 149 103 0.168 7.0 Ox0 VIFx 9.0 100.0 Pantry h 179 10 10 0.171 4.0 Ox0 VIFx 7.2 100.0 Play Room c 2203 87 126 0.179 7.0 Ox 0 VIFx 2.1 100.0 Utility c 2846 154 162 0.165 8.0 Ox0 VIFx 10.7 100.0 Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Mat] Trunk rb2 Ox 0 163 172 83.1 0.165 315 10.0 0x 0 VIFx rb1 Ox 0 237 228 74.0 0.185 434 10.0 Ox 0 VIFx Bold/italic values have been manually overridden wrightsoft, 2020-Nov-20 11:17:23 Right-SuiteO Universal 2018 18.0.16 RS000268 Page 1 JCCK ... Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Duct system multi orientation report Entire House Ace Air Conditioning Job: John Paul Edgar Date: By: Jimmy Evans 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: jevans@aceac.com Web: www.aceac.com License: CAC1813533 Project• • For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Group 1: (N, NE, S) Group 2: (E, SE, SW, W, NW) dO ttNacne i : i eg CFM eg�Li� tict Srie ir;NE} egvCFM eg Siae iict Size eg�IC eg Slag uct Size 969E eg CFM eg Siaa uct Sim I. Branches BathRoom 149 h 12x6 7 149 h 12x6 7 149 h 12x6 7 149 h 12x6 7 Pantry10 h 8x4 4 10 h 8x4 4 10 h 8x4 4 10 h 8x4 4 PlayRoom 182 c, 12x6 8 157 c'' 12x6 8 126 c 12x6 7 149 c 12x6 7 U tility 154 h 14x8 8 154 h 14x8 8 162 c 148 8 154 h 148 8 eturtn Branches rb2 12x12 10 163 h 12x12 10 172 c 12x12 10 163 h 12x12 10 b1 ;63 12x12 10 244 c 12x12 10 237 h 12x12 10 238 c 12x12 10 0.165 0.165 0.165 Heatin FR Cooling FIR 0.165 1 1 0.165 0.165 0.165 - * wrightsoft, 2020-Nov-20 11:17:23 ,rti Right -Suite@ Universal 2018 18.0.16 RS000268 Page 1 J+CK ... Calculations\DetailedaEnterprises\John Paul.rup Calc = MJ8 Front Door faces: N Project Information For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 WAR== t aMUMMOMF OF egs uct Size, eg�CFM S uci Sizes CPM eg Sim ct Sis GSM eg+Sb ct Size h,GfiGi3S,Mal MEW MMMOM WMEMIMAM BathRoom 149 h 12x6 7 149 h 12x6 7 149 h 12x6 7 149 h 12x6 7 Pantry 10 h 8x4 4 10 h 8x4 4 ' 10 h 8x4 4 10 h 8x4 4 PlayRoom Ta`171,=c<: 1M 8 146 c 12x6 7 118 c 12x6 7 °'°' 4154 c" 12x6 7-'-, Alit 154 h", 14z8 8 I58 c 14x8 8 '177c 14x8 8 158'c 148 8 etBcancties �187 rb2 163 h 12x12 10 167 c 12x12 10 c 12x12 10 167 c 12x12 10 rb1 248 c 12x12 10 237 h 12x12 10 237 h 12x12 10 237 h 12x12 10 - . ; x � , Heating FIR0.165 0.165 0.165. 0.165 Cooling FIR0.165 0.165 0.165 0.165 wrightsoft, 2020-Nov-20 11:17:23 ,rt . -1.., ,,... ­, Right -Suite® Universat201818.0.16 RS000268 Paget ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Project Inf• • For: John Paul Edgar 5512 Pine;Tree Drive, Ft. Pierce, FL 34982 4 MIName ll.ar r '"t lSrnaiest ®RecllSiza ,t7u"ctiSizH� eg CFM �,. ear® tLiuctlSlm 12x6 7 149 h 12x6 7 Rea1GFM R55. Branches BathRoom 149 h Pantry 10 h 8x4 4 10 h 8x4 4 Play Room 182 c 12x6 8 .118 c 12x6 7, Utility 177 c 148 8 154 h 148 8 x:eturn BrLanches 163 h 12x12 10 rb2 187 c 12x12 10 rb1 253 c 12x12 10 237 h 12x12 10 riction F2ates Heating FR .165 0.165 Cooling FR P.165 0.165 wrightSoft`° 2020-Nov-20 11:17:23 Right -Suite@ Universal 2018 18.0.16 RS000268 Page 3 ...Calculations\Detailed Enterprises\John Paul.rup Calc = MJ8 Front Door faces: N Static Pressure and Friction Rate Job: John Paul Edgar Date: Entire House By: Jimmy Evans Ace Air Conditioning 2985 Enterprise Rd., Debary, FL 32713 Phone: 386-668-8651 Fax: 386-668-7758 Email: ievans@aceac.com Web: www.aceac.com License: CAC1813533 iwroject inTormation For: John Paul Edgar 5512 Pine Tree Drive, Ft. Pierce, FL 34982 Available Static Pressure Heating Cooling (in H2O) (in H2O) External static pressure 0.50 0.50 Pressure losses Coil 0 0 Heat exchanger 0 0 Supply diffusers 0.04 0.04 Return grilles 0.04 0.04 Filter 0.10 0.10 Humidifier 0 0 Balancing damper 0 0 Other device 0 0 Available static pressure 0.32 0.32 Total Effective Length Supply Return (ft) (ft) Measured length of run -out 11 13 Measured length of trunk 0 0 Equivalent length of fittings 100 70 Total length 111 83 Total effective length 194• Supply Ducts Return Ducts Friction Rate Heating (in/100ft) 0.165 OK 0.165 OK Cooling (in/100ft) 0.165 OK 0.165 OK Fitting Equivalent Length Details Supply.• 1A=35, 11G=5: TotalEL=100 Return 5D=40, 6M=20, 11 G=5, 11 G=5: TotalEL=70 .t wrightsott`° 2020-Nov-2011:17:24 Right -Suite® Universal 2018 18.0.16 RS000268 Page 1 +� ... Calculations\DetailedsEnterprises\John Paul.rup Calc = MJ8 Front Door faces: N Prepared By: Ace Air Conditioning Jimmy Evans FORMS HVAC/Mechanical License; CAC1813533 FLORIDA BUILDING CODE, ENERGY CONSERVATION FORIVI R402-2017 Residential Building Thermal Envelope Approach Climate Zone 0 Scope: Compliance with Section R401.2(1) of the Florida Building Code, Energy Conservation, shall be demonstrated by the use of Form R402 for single- and multiple -family residences of three stories or less in height, additions to existing residential buildings, alterations, renovations and building systems in existing buildings, as applicable. To comply, a building must meet or exceed all of the energy efficiency requirements on Table R402A and all applicable mandatory requirements summarized in Table R402B of this form. If a building does not comply with this method, or by the UA Alternative method, it may still comply under Section R405 of the Florida Buliding Code, Energy Conservation. PROJECT NAME John Paul Edgar ANDADDRESS:5512 Pine Tree Dr. Ft Peirce BUILDER: OWNER: John Paul Edgar PERMITTING OFFICE: JURISDICTION NUMBER: General instructions: PERMIT NUMBER: 1. Fill in all the applicable spaces of the 'To Be Installed" column on Table R402A with the information requested. All "To Be Installed" values must be equal to or more efficient than the required levels. 2. Complete page 1 based on the "To Be Installed" column information. 3. Read the requirements of Table R402B and check each box to Indicate your intent to comply with all applicable Items. 4. Read, sign and date the "Prepared By" certification statement at the bottom of page 1. The owner or owner's agent must also sign and date the form. 1. New construction, addition, or existing building 1. Addition 2. Single-family detached or multiple -family attached 3. If multiple -family, number of units covered by this submission 2 -- 4. Is this a worst case? (yes/no) 3. -- 4. No _ 5. Conditioned floor area (sq. ft.) 5. 595 S. Windows, type and area a) U-factor: Ba. .40 b) Solar Heat Gain Coefficient (SHGC) 6b - 2 5 c) Area 7. Skylights sc• -43- a) U-factor: 7a b) Solar Heat Gain Coefficient (SHGC) 7b - 8. Floor type, area or perimeter, and insulation: a) Slab -on -grade (R-value) 8a 595 + b) Wood, raised (R-value) 8b. c) Wood, common (R-value) 80.- d) Concrete, raised (R-value) 8d i e) Concrete, common (R-value) 8e 9. Wall type and insulation: a) Exterior: 1. Wood frame (Insulation R-value) gat, i 2. Masonry (insulation R-value) 9a2. 6 b) Adjacent: 1. Wood frame (Insulation R-value) 9bl. 2. Masonry (Insulation R-value) 9b2 10. Ceiling type and insulation a) Attic (Insulation R-value) 10a. R-38 ' b) Single assembly (Insulation R-value) 10b. 11. Air distribution system: ' a) Duct location, insulation 11a Attic, R-8 ' b) AHU location 11b. Attic c) Total duct leakage. Test report attached. 11c. - cfm/100 s.f. Yes ❑ No ❑ 12. Cooling system: a) type 12a. Central ' b) efficiency 12b. 14 -- ' 13. Heating system: a) type 13a. Heat Pump - b) efficiency 13b. Egtg- 14. HVAC sizing calculation: attached 14. Yes IN No [I15. Water heating system: a) type 15a. Existin b) erficie 15b. - I hereby certify that the plans and sp ci is s covered by this form are Review of plans and specifications covered by this form indicate i In compliance with the Florida Build de, nergy Conservation. compliance with the Florida Building Code, Energy Conservation. Before PREPARED BY: Jimm Evans Date 6 - 2 4 -2 0 construction is complete, this building will be Inspected for compliance in I hereby certify that this building Is n I ce with the Florida Building accordance with Section 553.908, F.S. Code. Energy Conservation. CODE OFFICIAL: OWNER/AG ENT: Date: Date: FLORIDA BUILDING CODE - ENERGY CONSERVATION, 6th EDITION (2017) R 55 ---------- 1 LF... C.0 FORMS TABLE R402A BUILDING COMPONENT PRESCRIPTIVE REQUIREMENTS' INSTALLED VALUES Climate Zone 1 Climate Zone 2 Windows U-Factor = NR U-Factor = 0.40' U-Factor = SHGC = 0.25 SHGC = 0.25 SHGC = Skylights U-factor = 0.75 U factor = 0.65 U factor = SHGC = 0.30 SHGC = 0.30 SHGC = Doors: Exterior door U-factor = NR U-factor = 0.40' U-factor= Floors: Slab -on -Grade NR NR Over unconditioned spaces° R-13 R-13 R-Value = Walls°: Ext. and Adj. Frame R-13 R-13 R-Value = Mass Insulation on wall interior R-4 R-6 R-Value = Insulation on wall exterior R-3 R-4 R-Value = Ceilings' R=30 R=38 R-Value = Air infiltration Blower door test is required on the building envelope to verify leakage <_ 1 ACH; Total leakage = ACH test report provided to code official. Test rert attached? Yes H No Air distribution systems: Air handling unit Not allowed in,attic Location: Attic Duct R-value R-value>_ R-8 (supply in attics) or>_ R-6 (all other duct locations) R-Value = R-8 Air leakage': Duct test Postconstruction test Total leakage _< 4 cfm/100 s.f. Total leakage = cfm/100s.f. Rough -in test Total leakage <_ 4 cfm/100 s.f. (air handler installed) Test report Attached? Yes ® No ❑ Total leakage <_ 3 cfm/100 s.f. (air handler not installed) Location: Ducts in conditioned space Test not required if all ducts and AHU are in conditioned space Air conditioning system: Minimum federal standard required by NAECA': Central system <_ 65,000 Btu/h SEER 14.0 SEER= Existing Room unit or PTAC EER [from Table C403.2.3(3)] EER = Other: See Tables C403.2.3(1)-(11) Heating system: Minimum federal standard required by NAECA': Heat pump <_ 65,000 Btu/h HSPF 8.2 HSPF = Gas furnace, non -weatherized AFUE80% AFUE= Existing Oil furnace, non -weatherized AFUE 83 % AFUE = Other: Water heating system (storage type): Minimum federal standard required by NAECA': Electrid 40 gal: EF = 0.92 Gallons = 50 gal: EF = 0.90 EF= Existing Gas fired' 40 gal: EF = 0.59 Gallons = 50 gal: EF = 0.58 EF = Other (describe): NR = No requirement. (1) Each component present in the As Proposed home must meet or exceed each of the applicable performance criteria in order to comply with this code using this method. (2) For impact rated fenestration complying with Section R301.2.1.2 of the Florida Building Code, Residential or Section 1609.1.2 of the Florida Building Code, Building, the maximum U-factor shall be 0.65 -in Climate Zone 2. An area -weighted average of U-factor and SHGC shall be accepted to meet the requirements, or up to 15 square feet of glazed ;fenestration area are exempted from the U-factor and SHGC requirement based on Sections R402.3.1, R402.3.2 and R402.3.3. (3) One side -hinged opaque door assembly up to 24 square feet is exempted from this U-factor requirement. (4) R-values are for insulation material only as applied in accordance with manufacturer's installation instructions. For mass walls, the "interior of wall' requirement must be met except if at least 50 percent of the insulation required for the "exterior of wall" is installed exterior of, or integral to, the wall. (5) Ducts & AHU installed "substantially leak free" per Section R403.3.2. Test required by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. The total leakage test is not required for ducts and air handlers located entirely within the building thermal envelope. (6) Minimum efficiencies are those set by the National Appliance Energy Conservation Act of 1987 for typical residential equipment and are subject to NAECA rules and regulations. For other types of equipment, see Tables C403.2.3(1-11) of the Commercial Provisions of the Florida Building Code, Energy Conservation. (7) For other electric storage volumes, minimum EF = 0.97 - (0:00132 * volume). (8) For other natural gas storage volumes, minimum EF = 0.67 - (0.0019 * volume). R-56 FLORIDA BUILDING CODE — ENERGY CONSERVATION, 6th EDITION (2017) FORMS TABLE R402B MANDATORY REQUIREMENTS, Component Section I Summary of Requirement(s) Check Air leakage R402.4 To be caulked, gasketed, weatherstripped or otherwise sealed per Table R402.4.1.1. Recessed lighting: IC -rated as having <_ 2.0 cfm tested to ASTM E 283. Windows and doors: 0.3 cfm/sq. ft. (swinging doors: 0.5 cfm/sf) when tested to NFRC 400 or AAMAIWDMA/CSA 101/I.S. 2/A440. Fireplaces: Tight -fitting flue dampers & outdoor combustion air. Programmable R403.1.2 A programmable thermostat is required for the primary heating or cooling system. thermostat Ducts shall The tested as per Section R403.3.2 by either individuals as defined in Section 553.993(5) or (7), Florida Air distribution system R403.3.2 Statutes, or, individuals licensed as set forth in Section 489.105(3) (f), (g) or (i), Florida Statutes. Air handling units R403.3.4 are not,allowed in attics. Water heaters R403.5 Comply with efficiencies in Table C404.2. Hot water pipes insulated to >_ R-3 to kitchen outlets, other cases. Circulating systems to have an automatic or accessible manual OFF switch. Heat trap required for vertical pipe risers. Swimming pools & spas R403.10 Spas and heated pools must have vapor -retardant covers or a liquid cover or other means proven to reduce heat loss except'if 70 % of heat from site -recovered energy. Off/timer switch required. Gas heaters minimum thermal efficiency is 82 % . Heat pump pool heaters minimum COP is 4.0. Cooling/heating R403.7 Sizing calculation performed & attached. Special occasion cooling or heating capacity requires separate system or equipment variable capacity system. Lighting equipment R404.1 At least 75 % of permanently installed lighting fixtures shall be high -efficacy lamps. FLORIDA BUILDING CODE — ENERGY CONSERVATION, 6th EDITION (2017) R-57