UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS
208/230 Volt, 1−phase, 60 Hz
REFRIGERATION CIRCUIT
•Environmentally balanced R-410A refrigerant
•Liquid refrigerant filter driers
•Copper tube/aluminum fin condenser and evaporator coils
EASY TO INSTALL AND SERVICE
•Light weight, compact construction ideal for manufactured housing and residential applications
•Hand holds built into the unit base pan
•Compact, fully self-contained, electric cooling unit with horizontal supply and return ducts
•Easy panel accessibility for maintenance and installation
•Accessory electric heaters with single point connections
•Designed to be serviced from both the side and front
•Cabinet air leakage less than 2.0% at 1.0 inch W.C. and cabinet air leakage less than 1.4%
at 0.5 in. W.C., when tested in accordance with ASHRAE Standard 193
BUILT TO LAST
•Vibration isolation provides quiet operation. Compressors have internal over current protection
•Direct-drive multi-speed, blower motor standard on all models
•No-rust base pan with integrated drain pan standard on all units
•Durable pre-painted steel cabinet
•Louvered coil enclosure for protection against vandalism and hail damage
•Aerodynamic fan blade design reduces the overall sound
•All models have factory installed tin-coated copper evaporator coil.
(identified with letters TP in the 11th and 12th positions in the model numbers)
LIMITED WARRANTY*
• 10 year parts limited warranty (including compressor and coils)
* 5 years parts limited warranty if not registered within 90 days of original installation. See warranty certificate
for complete details and restrictions.
UNIT PERFORMANCE DATA
Model
Number
Nominal
Tons
COOLING
Unit Dimensions
Height x Width x Depth
inches (mm)
Operating
Weight
lbs (kg)
Net Capacity
BTU/h @
95°F(35°C)SEER EER
PAJ424000KTP0B 2 22,400 14 11.5 30-1/8 x 51 x 32
(765 x 1295 x 813)217 (98)
PAJ430000KTP0B 2.5 28,600 14 11.5 30-1/8 x 51 x 32
(765 x 1295 x 813)234 (106)
PAJ436000KTP0B 3 34,200 14 11.5 30-1/8 x 51 x 32
(765 x 1295 x 813)255 (116)
PAJ442000KTP0A 3.5 41,000 14.5 11.5 34-1/8 x 51 x 32
(867 x 1295 x 813)275 (125)
PAJ448000KTP0A 4 47,000 14 11.5 42-1/8 x 51 x 32
(1070 x 1295 x 813)318 (144)
PAJ460000KTP0A 5 54,000 14 11.3 42-1/8 x 51 x 32
(1070 x 1295 x 813)344 (156)
PAJ4
Product Specifications
As an Energy Star® Partner,
International Comfort Products has
determined that this product meets
the ENERGY STAR® guidelines for
energy efficiency.
Use of the AHRI Certified TM Mark in-
dicates a manufacturer’s participation
in the program. For verification of certi-
fication for individual products, go to
www.ahridirectory.org .
2 426 41 1707 05Specifications subject to change without notice.
MODEL NOMENCLATURE
MODEL SERIES 1 2, 3 4 5,6 7,8,9 10 11,12 13 14 15
P AJ 4 36 000 K TP 0 A 1
P = Package
AJ = Air Conditioner
4 = 14 SEER
24 = 2 Tons
30 = 2.5 Tons
36 = 3 Tons
42 = 3.5 Tons
48 = 4 Tons
60 = 5 Tons NOMINAL COOLINGCAPACITY
000 = no factory heat NOMINAL HEATING BTUH (input)
K = 208/230−1−60 VOLTAGE
TP − Tin Plated Copper Evaporator Main Tubes FACTORY INSTALLED
0 = Standard FEATURE CODE
Sales Model Digit
Engineering Digit
AHRI* CAPACITY RATINGS
Cooling Capacities and Efficiencies
UNIT SIZE NOMINAL TONS STANDARD CFM
NET COOLING
CAPACITY
AT 95°F (35°c)
(Btuh)
EER†SEER**
24 2 800 22400 11.5 14
30 2.5 1000 28600 11.5 14
36 3 1200 34200 11.5 14
42 3.5 1400 41000 11.5 14.5
48 4 1600 47000 11.5 14
60 5 1850 54000 11.3 14
LEGEND
dB---Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning Heating & Refrigeration Institute
† At "A" conditions--80°F (26.7°C) indoor db/67°F
(19.4°C) indoor wb & 95°F (35°C) outdoor db.
** Rated in accordance with U.S. Government DOE
Department of Energy) test procedures and/or AHRI
Standards 210/240---08, 270-1995.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7°C) db, 67°F wb (19.4°C) indoor entering---air
temperature and 95°F db (35°C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
A−Weighted Sound Power Level (dBA) − AHRI STANDARDS 270−1995
UNIT SIZE STANDARD RATING (dBA)TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
125 250 500 1000 2000 4000 8000
24 71 51.7 55.2 58.2 62.0 55.6 49.4 44.0
30 73 60.4 56.6 61.7 64.0 57.4 54.9 46.4
36 75 57.7 61.6 63.9 65.5 60.0 54.4 49.5
42 77 64.8 68.3 72.9 72.2 68.2 62.6 53.1
48 76 58.4 61.9 65.3 65.5 59.7 55.0 47.4
60 80 72.9 65.4 68.8 70.5 65.2 60.5 50.9
426 41 1707 05 3Specifications subject to change without notice.
PHYSICAL DATA
UNIT SIZE 24 30 36 42 48 60
NOMINAL CAPACITY (ton)2 2.5 3 3.5 4 5
SHIPPING WEIGHT (lb)
(kg)
286
130
298
136
329
150
352
160
368
167
402
183
COMPRESSOR TYPE SCROLL
REFRIGERANT R410A
REFRIGERANT QUANTITY (lb)
QUANTITY (kg)
4.5
2.0
4.8
2.1
6.8
3.0
5.7
2.6
6.3
2.9
7.5
3.4
METERING DEVICE ID Piston TXV
ORIFICE OD (in.)
(mm)
0.057
1.45
0.063
1.60
0.073
1.85
0.076
1.93
0.080
2.03 N/A
OUTDOOR COIL
ROWS...FINS/in.
FACE AREA (sq. ft)
1...20
9.1
1...20
9.1
2...20
9.1
2...20
10.2
2...20
13.0
2...20
15.5
OUTDOOR FAN
NOMINAL AIRFLOW (CFM)
DIAMETER (in.)
DIAMETER (mm)
MOTOR HP (RPM)
2400
20
508
1/8 (825)
2400
20
508
1/8 (825)
2700
20
508
1/4 (1100)
2700
20
508
1/4 (1100)
2700
20
508
1/4 (1100)
3000
20
508
1/3 (1110)
INDOOR COIL
ROWS...FINS/in.
FACE AREA (sq. ft)
2...12
4.3
3...12
4.3
3...12
4.3
3...12
4.9
3...15
4.9
3...15
6.1
INDOOR BLOWER
NOMINAL COOLING AIRFLOW (CFM)
NOMINAL SIZE W x D (in.)
(mm)
MOTOR (HP)
800
8 x 11
254 x 203
1/3
1000
8 x 11
254 x 203
1/3
1200
9 x 12
279 x 229
1/2
1400
9 x 12
279 x 229
1/2
1600
11 x 12
279 x 229
3/4
1850
11 x 12
267 x 305
1
HIGHPRESSURE SWITCH (psig)
CUTOUT
RESET (AUTO)
650 +/ 15
420 +/ 25
RETURNAIR FILTERS
THROWAWAY (in.)
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
*Required filter sizes shown are based on the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated airflow at a velocity
of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1−in. (25.4 mm) thick.
Multiplication Factors
HEATER kW RATING VOLTAGE DISTRIBUTION MULTIPLICATION FACTOR
240
200 .69
208 .75
230 .92
240 1.00
Example: 15.0 kW (at 240v) heater on 208v
= 15.0 (.75 mult factor)
= 11.25 capacity at 208v
4 426 41 1707 05Specifications subject to change without notice.
DIMENSIONAL DRAWINGS — 24−36
A180299
426 41 1707 05 5Specifications subject to change without notice.
DIMENSIONAL DRAWINGS — 42−60
A180309
6 426 41 1707 05Specifications subject to change without notice.
SELECTION PROCEDURE
A. DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS.
Given:
Required Cooling Capacity (TC) 34,000 Btuh.......
Sensible Heat Capacity (SHC) 25,000 Btuh........
Required Heating Capacity 15,000 Btuh...........
Outdoor Entering−Air Temperature 95°F (35°C).....
Indoor Entering−Air Temperature 80°F edb (26.7°C);
67°F (19.4°C) ewb
Indoor−Air Quantity 1200 CFM....................
External Static Pressure 0.20 IN. W.C..............
Electrical Characteristics (V−Ph−Hz) 230−1−60.....
B. SELECT UNIT BASED ON REQUIRED COOLING CAPACITY (3−TON EXAMPLE)
Enter Cooling Capacities table at condenser entering temperature of 95°F (35°C), indoor air entering at 1200 CFM and 67°F
(19.4°C) ewb. The 36 unit provides a total cooling capacity of 34,500 Btuh and a sensible heat capacity of 26,040 Btuh.
For indoor−air temperature other than 80°F (26.7°C) edb, calculate sensible heat capacity correction, as required, using the formula
found following the Cooling Capacities tables.
NOTE: Unit ratings are net capacities.
C. SELECT ELECTRIC HEAT.
The required heating capacity is 15,000 Btuh (given).
Determine the electric heat capacity in kW.
15,000 Btuh
3414 Btuh/kW = 3.8 kW of heat required
Enter the Accessory Electric Heater table on page 4 for 208/230, single−phase, 036 unit. The 5−kW heater at 240v most closely
satisfies the heating required. To calculate kW at 230 V, multiply the heater kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 4.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh
D. DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total static pressure required. From the given, Filter Pressure Drop table, and the
Accessory Electric Heat Pressure Drop table find:
External static pressure 0.20 IN. W.C.
Filter 0.10 IN. W.C.
Electric Heat 0.04 IN. W.C.
Total static pressure 0.34 IN. W.C.
Enter the table for Dry Coil Air Delivery — Horizontal Discharge. At 0.4 IN. W.C. external static pressure and medium speed, the
motor delivers 1236 CFM.
7426 41 1707 05Specifications subject to change without notice.PERFORMANCE DATA
Cooling Capacities
24
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
700
57 (13.9)21.11 21.11 1.61 20.33 20.33 1.80 19.44 19.44 2.00 18.39 18.39 2.22 16.99 16.99 2.45
62 (16.7)21.97 20.56 1.61 21.01 20.12 1.80 19.92 19.58 2.01 18.62 18.89 2.23 16.85 16.85 2.45
63 (17.2)*22.40 16.82 1.61 21.41 16.39 1.80 20.31 15.89 2.01 18.95 15.25 2.23 17.10 14.40 2.45
67 (19.4)24.12 17.41 1.62 23.11 16.98 1.81 21.98 16.51 2.03 20.69 15.99 2.27 19.08 15.31 2.53
71 (21.7)25.87 14.83 1.64 24.84 14.43 1.83 23.69 13.97 2.04 22.40 13.46 2.29 20.92 12.89 2.56
800
57 (13.9)22.00 22.00 1.62 21.20 21.20 1.81 20.32 20.32 2.03 19.24 19.24 2.26 17.84 17.84 2.49
62 (16.7)22.51 21.92 1.63 21.54 21.49 1.82 20.47 20.95 2.03 19.27 19.27 2.26 17.87 17.87 2.49
63 (17.2)*22.88 17.76 1.63 21.86 17.34 1.82 20.73 16.85 2.03 19.36 16.24 2.26 17.53 15.41 2.48
67 (19.4)24.61 18.36 1.64 23.57 17.97 1.83 22.40 17.50 2.04 21.09 16.99 2.29 19.53 16.40 2.56
71 (21.7)26.33 15.46 1.65 25.29 15.08 1.84 24.10 14.63 2.06 22.78 14.13 2.31 21.28 13.57 2.58
900
57 (13.9)22.74 22.74 1.64 21.92 21.92 1.83 21.01 21.01 2.05 19.95 19.95 2.29 18.58 18.58 2.54
62 (16.7)22.99 23.16 1.64 22.01 22.69 1.83 21.02 21.02 2.05 19.97 19.97 2.29 18.61 18.61 2.54
63 (17.2)*23.26 18.63 1.64 22.21 18.21 1.83 21.06 17.74 2.05 19.70 17.18 2.29 17.88 16.36 2.51
67 (19.4)24.98 19.24 1.65 23.91 18.86 1.84 22.71 18.43 2.06 21.39 17.90 2.30 19.82 17.35 2.58
71 (21.7)26.69 16.04 1.67 25.63 15.67 1.86 24.42 15.24 2.08 23.06 14.74 2.32 21.55 14.19 2.60
30
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
875
57 (13.9)27.60 27.60 1.98 26.50 26.50 2.19 25.24 25.24 2.42 23.71 23.71 2.67 21.76 21.76 2.93
62 (16.7)28.34 26.09 1.98 26.97 25.48 2.19 25.44 24.73 2.43 23.76 23.76 2.67 21.80 21.80 2.93
63 (17.2)*28.82 21.14 1.99 27.42 20.55 2.20 25.85 19.89 2.44 23.90 19.03 2.67 21.30 17.92 2.91
67 (19.4)31.10 21.94 2.00 29.67 21.41 2.22 28.08 20.78 2.46 26.22 20.05 2.73 23.80 19.09 3.00
71 (21.7)33.50 18.60 2.03 32.03 18.06 2.24 30.40 17.48 2.48 28.60 16.81 2.77 26.45 16.02 3.08
1000
57 (13.9)28.80 28.80 2.01 27.65 27.65 2.22 26.38 26.38 2.47 24.84 24.84 2.73 22.85 22.85 2.99
62 (16.7)29.07 27.98 2.01 27.73 27.50 2.22 26.42 26.42 2.47 24.88 24.88 2.73 22.89 22.89 2.99
63 (17.2)*29.43 22.47 2.01 27.98 21.90 2.22 26.39 21.24 2.47 24.44 20.41 2.72 21.82 19.29 2.95
67 (19.4)31.71 23.32 2.03 30.24 22.82 2.24 28.60 22.20 2.49 26.75 21.50 2.76 24.35 20.58 3.05
71 (21.7)34.11 19.53 2.05 32.60 19.03 2.27 30.92 18.43 2.51 29.06 17.77 2.80 26.90 17.01 3.11
1125
57 (13.9)29.76 29.76 2.04 28.59 28.59 2.25 27.28 27.28 2.50 25.75 25.75 2.77 23.78 23.78 3.05
62 (16.7)29.80 29.80 2.04 28.63 28.63 2.25 27.32 27.32 2.50 25.78 25.78 2.78 23.82 23.81 3.05
63 (17.2)*29.89 23.71 2.04 28.42 23.16 2.25 26.81 22.52 2.49 24.85 21.71 2.75 22.25 20.59 2.99
67 (19.4)32.18 24.61 2.06 30.66 24.12 2.27 29.01 23.55 2.51 27.14 22.85 2.79 24.81 21.99 3.09
71 (21.7)34.59 20.40 2.08 33.04 19.89 2.29 31.31 19.33 2.54 29.40 18.68 2.82 27.22 17.94 3.14
See Legend and Notes on page 10.
426 41 1707 058Specifications subject to change without notice.COOLING CAPACITIES (CONT)
36
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
57 (13.9)33.44 33.44 2.35 31.96 31.96 2.59 29.97 29.97 2.84 27.67 27.67 3.12 25.22 25.22 3.45
62 (16.7)34.22 31.29 2.36 32.42 30.45 2.60 30.12 29.15 2.84 27.72 27.72 3.12 25.24 25.24 3.45
63 (17.2)*34.84 25.34 2.36 32.94 24.51 2.60 30.42 23.42 2.85 27.34 22.11 3.11 24.16 20.79 3.42
1050 67 (19.4)37.73 26.43 2.41 35.79 25.64 2.66 33.57 24.74 2.93 30.40 23.49 3.18 27.11 22.21 3.49
71 (21.7)40.85 22.45 2.44 38.88 21.72 2.71 36.70 20.91 3.00 33.78 19.82 3.27 30.28 18.55 3.57
57 (13.9)34.88 34.88 2.40 33.34 33.34 2.65 31.45 31.45 2.91 28.98 28.98 3.18 26.41 26.41 3.51
62 (16.7)35.12 33.55 2.40 33.20 33.20 2.64 31.51 31.51 2.91 29.02 29.02 3.18 26.46 26.46 3.51
1200 63 (17.2)*35.55 26.89 2.40 33.61 26.06 2.65 31.13 25.01 2.90 28.00 23.71 3.16 24.74 22.34 3.47
67 (19.4)38.47 28.10 2.45 36.47 27.30 2.70 34.20 26.40 2.97 31.08 25.20 3.23 27.68 23.88 3.54
71 (21.7)41.59 23.57 2.48 39.58 22.87 2.75 37.38 22.07 3.04 34.48 21.01 3.33 30.86 19.72 3.62
57 (13.9)36.08 36.08 2.45 34.48 34.48 2.70 32.64 32.64 2.97 30.06 30.06 3.24 27.39 27.39 3.56
62 (16.7)36.12 36.12 2.45 34.54 34.54 2.70 32.69 32.69 2.97 30.11 30.11 3.24 27.44 27.44 3.56
1350 63 (17.2)*36.10 28.35 2.44 34.12 27.53 2.69 31.76 26.55 2.95 28.50 25.18 3.20 25.21 23.76 3.51
67 (19.4)39.04 29.64 2.48 36.98 28.88 2.74 34.70 27.99 3.02 31.57 26.78 3.27 28.16 25.44 3.58
71 (21.7)42.15 24.61 2.51 40.11 23.92 2.78 37.87 23.13 3.08 35.02 22.12 3.38 31.28 20.82 3.67
See Legend and Notes on page 10.
42
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
1225
57 (14)41.68 41.68 2.75 38.94 38.94 3.11 35.98 35.98 3.49 32.25 32.25 3.87 28.66 28.66 4.32
62 (17)42.95 38.93 2.75 39.78 36.79 3.12 36.43 34.57 3.50 32.28 32.28 3.87 28.71 28.71 4.32
63 (17)43.70 31.61 2.75 40.44 29.72 3.12 36.99 27.79 3.51 32.43 25.38 3.87 27.98 23.06 4.30
67 (19)47.16 32.78 2.77 43.74 30.91 3.13 40.27 29.04 3.52 36.10 26.97 3.96 31.37 24.61 4.39
71 (22)51.59 26.51 2.78 47.98 24.89 3.15 44.33 23.26 3.55 40.57 21.60 3.99 36.10 19.78 4.49
1400
57 (14)43.43 43.43 2.79 40.56 40.56 3.15 37.56 37.56 3.55 33.84 33.84 3.94 30.06 30.06 4.39
62 (17)44.02 41.66 2.79 40.84 39.39 3.16 37.60 37.60 3.55 33.90 33.90 3.94 30.11 30.11 4.40
63 (17)44.60 33.50 2.79 41.26 31.57 3.16 37.77 29.61 3.55 33.24 27.21 3.92 28.66 24.78 4.36
67 (19)48.06 34.74 2.81 44.57 32.83 3.17 41.00 30.90 3.56 37.08 28.93 4.01 32.09 26.48 4.45
71 (22)52.46 27.65 2.82 48.78 26.00 3.19 45.03 24.35 3.59 41.21 22.67 4.03 36.86 20.91 4.53
1575
57 (14)44.86 44.86 2.83 41.89 41.89 3.19 38.82 38.82 3.59 35.20 35.20 4.02 31.25 31.25 4.47
62 (17)45.00 44.04 2.83 41.94 41.94 3.20 38.88 38.88 3.59 35.25 35.25 4.02 31.28 31.28 4.47
63 (17)45.28 35.25 2.83 41.88 33.29 3.20 38.36 31.31 3.59 33.90 28.93 3.98 29.21 26.39 4.41
67 (19)48.74 36.57 2.84 45.17 34.62 3.21 41.56 32.62 3.60 37.71 30.65 4.05 32.66 28.22 4.50
71 (22)53.13 28.71 2.86 49.38 27.04 3.23 45.55 25.35 3.63 41.66 23.65 4.07 37.49 21.93 4.58
See Legend and Notes on page 10.
9426 41 1707 05Specifications subject to change without notice.COOLING CAPACITIES (CONT)
48
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
1400
57 (14)46.69 46.69 3.18 43.96 43.96 3.55 41.20 41.20 3.97 38.15 38.15 4.45 34.26 34.26 4.96
62 (17)48.24 40.86 3.19 45.07 40.07 3.56 41.86 39.18 3.99 38.39 38.02 4.46 34.32 34.32 4.97
63 (17)49.13 33.18 3.19 45.86 32.38 3.57 42.55 31.50 4.00 38.89 30.43 4.47 34.04 28.78 4.95
67 (19)53.03 34.45 3.21 49.63 33.69 3.59 46.16 32.87 4.03 42.51 31.94 4.54 38.08 30.67 5.10
71 (22)58.07 27.87 3.25 54.53 27.15 3.63 50.89 26.37 4.07 47.09 25.48 4.58 43.08 24.48 5.17
1600
57 (14)48.69 48.69 3.24 45.86 45.86 3.62 42.97 42.97 4.06 39.87 39.87 4.56 35.98 35.98 5.08
62 (17)49.45 43.78 3.24 46.24 42.96 3.62 43.08 42.83 4.06 39.93 39.93 4.56 36.04 36.04 5.08
63 (17)50.14 35.19 3.25 46.79 34.40 3.62 43.38 33.54 4.06 39.71 32.52 4.55 34.85 30.91 5.04
67 (19)54.04 36.51 3.27 50.57 35.78 3.65 47.00 35.00 4.09 43.31 34.10 4.60 39.07 33.00 5.18
71 (22)59.08 29.08 3.31 55.45 28.38 3.69 51.71 27.61 4.13 47.83 26.75 4.64 43.74 25.74 5.24
1800
57 (14)50.32 50.32 3.30 47.39 47.39 3.68 44.38 44.38 4.12 41.24 41.24 4.63 37.45 37.45 5.19
62 (17)50.52 46.35 3.30 47.46 47.46 3.68 44.44 44.44 4.12 41.29 41.29 4.63 37.50 37.50 5.19
63 (17)50.90 37.05 3.30 47.50 36.30 3.68 44.02 35.46 4.12 40.35 34.49 4.62 35.52 32.90 5.12
67 (19)54.81 38.44 3.33 51.26 37.75 3.70 47.64 36.98 4.14 43.89 36.11 4.65 39.74 35.07 5.24
71 (22)59.83 30.17 3.37 56.13 29.51 3.75 52.32 28.76 4.19 48.35 27.90 4.70 44.21 26.91 5.30
See Legend and Notes on page 10.
60
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C)
75 (24)85 (29)95 (35)105 (41)115 (46)
CFM EWB F
(C)
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KW
Capacity MBtuh Total
Sys
KWTotalSensTotalSensTotalSensTotalSensTotalSens
1500
57 (14)52.95 52.95 3.74 50.23 50.23 4.14 47.43 47.43 4.61 44.47 44.47 5.15 41.30 41.30 5.78
62 (17)55.05 45.97 3.75 51.84 44.39 4.16 48.53 42.78 4.62 45.08 41.06 5.16 41.48 39.18 5.78
63 (17)56.01 37.50 3.76 52.73 36.05 4.17 49.33 34.54 4.63 45.76 32.97 5.17 42.01 31.33 5.79
67 (19)59.99 38.77 3.80 56.43 37.29 4.20 52.75 35.77 4.67 48.90 34.18 5.21 44.88 32.53 5.83
71 (22)65.50 31.45 3.84 61.58 30.06 4.25 57.53 28.62 4.72 53.33 27.13 5.26 48.93 25.58 5.89
1700
57 (14)54.98 54.98 3.81 52.11 52.11 4.21 49.12 49.12 4.68 45.98 45.98 5.23 42.63 42.63 5.85
62 (17)56.20 49.14 3.82 52.89 47.48 4.22 49.49 45.72 4.69 46.04 46.04 5.23 42.69 42.69 5.86
63 (17)57.05 39.66 3.83 53.64 38.16 4.23 50.11 36.61 4.70 46.43 34.99 5.23 42.56 33.29 5.85
67 (19)61.05 41.09 3.86 57.35 39.56 4.26 53.53 37.99 4.73 49.57 36.36 5.27 45.42 34.64 5.89
71 (22)66.61 32.86 3.91 62.53 31.43 4.31 58.37 29.96 4.78 54.02 28.44 5.33 49.49 26.85 5.95
1850
57 (14)56.30 56.30 3.86 53.30 53.30 4.27 50.20 50.20 4.74 46.93 46.93 5.28 43.46 43.46 5.91
62 (17)56.95 51.37 3.87 53.60 49.58 4.27 50.27 50.27 4.74 46.99 46.99 5.28 43.52 43.52 5.91
63 (17)57.68 41.23 3.87 54.17 39.68 4.27 50.58 38.10 4.74 46.82 36.45 5.28 42.89 34.72 5.90
67 (19)61.67 42.77 3.90 57.88 41.20 4.31 54.00 39.60 4.78 49.95 37.93 5.32 45.73 36.18 5.94
71 (22)67.25 33.87 3.95 63.10 32.42 4.36 58.84 30.93 4.83 54.41 29.38 5.37 49.81 27.77 6.00
See Legend and Notes on page 10.
426 41 1707 05 10Specifications subject to change without notice.
* At 75°F entering dry bulb - Tennessee Valley Authority (TVA) rating conditions; all others at 80°F dry bulb.
LEGEND
BF — Bypass Factor
Ewb — Entering Wet-Bulb
kW — Total Unit Power Input
SHC — Sensible Heat Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (net)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Sensible capacity (Btuh)
1.10 x cfm
tldb = tedb −
Wet −bulb temperature corresponding to enthalpy
air leaving evaporator coil (hlwb)
tlwb =
total capacity (Btuh)
4.5 x cfm
hlwb = hewb −
Where: hewb = Enthalpy of air entering evaporator coil3. The SHC is based on
80° F (26.7°C) edb temperature of air entering indoor coil.
Below 80° F (26.7°C) edb, subtract (corr factor x cfm) from SHC.
Above 80° F (26.7°C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 - BF) x (edb - 80).
Filter Pressure Drop (IN. W.C.)
FILTER SIZE
in. (mm)
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
20X20X1
(508X508X25)0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 ——————————
20X24X1
(508X610x25)———0.08 0.09 0.10 0.11 0.13 0.14 0.15 0.16 ———————
24X30X1
(610X762x25)———0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.10 ———————
24X36X1
(610X914X25)———————0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14
Accessory Electric Heat Pressure Drop (IN. W.C.)
HEATER kW CFM
800 1000 1200 1400 1600 1800 2000 2200
5−20 0.033 0.037 0.042 0.047 0.052 0.060 0.067 0.075
Wet Coil Delivery*— (Deduct 10% for 208−Volt Operation)
UNIT SIZE SPEED TAP AIR DELIVERY2 EXTERNAL STATIC PRESSURE (in. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
24
1 SCFM 965 818 777 731 670 617 563 489 451 391
2 SCFM 1003 921 890 850 809 756 700 659 597 539
3 SCFM 1103 1068 1034 996 962 930 892 821 791 742
30
1 SCFM 1052 1018 984 943 914 879 833 795 732 678
2 SCFM 1141 1107 1069 1036 1006 974 932 899 856 784
3 SCFM 1246 1213 1181 1144 1108 1078 1043 1015 973 931
36
1 SCFM 1281 1225 1178 1142 1098 1053 1008 935 878 840
2 SCFM 1359 1321 1278 1236 1201 1160 1109 1068 992 941
3 SCFM 1476 1441 1403 1366 1323 1289 1245 1201 1159 1117
42
1 SCFM 1453 1408 1373 1337 1295 1255 1215 1177 1134 1068
2 SCFM 1544 1507 1475 1436 1397 1359 1326 1290 1246 1201
3 SCFM 1614 1575 1542 1509 1467 1430 1395 1358 1323 1267
48
1 SCFM 1657 1625 1590 1554 1517 1486 1448 1417 1381 1340
2 SCFM 1707 1673 1644 1614 1586 1549 1515 1479 1449 1407
3 SCFM 1931 1900 1870 1840 1809 1778 1749 1714 1683 1646
60
1 SCFM 1931 1881 1833 1787 1746 1698 1670 1622 1577 1514
2 SCFM 2038 1994 1935 1894 1851 1811 1774 1738 1691 1648
3 SCFM 2144 2113 2052 2001 1974 1928 1898 1860 1824 1773
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows
below this point.
2. Standard Cubic Feet per Minute.
11 426 41 1707 05Specifications subject to change without notice.
TYPICAL CONNECTION WIRING SCHEMATIC—208/230−1−60, 24−60
A14548
426 41 1707 05 12Specifications subject to change without notice.
TYPICAL LADDER WIRING SCHEMATIC—208/230−1−60, 24−60
A14549
13 426 41 1707 05Specifications subject to change without notice.
TYPICAL FIELD WIRING
NOTE: 20kW Heater shown. Smaller heaters have fewer elements and controls
A190069
Single−Phase Accessory Electric Heater Wiring
426 41 1707 05 14Specifications subject to change without notice.
Electrical Data
Model Nominal
VPHHZ
Voltage
Range Compressor OFM IFM Nominal
kW*Heater FLA MCA MOCP**
Min Max RLA LRA FLA FLA 208/240 208 240 208 230 208/230
24 208/230160 197 253 10.3 61.6 0.9 2.8
/16.6 16.6 25
3.8/5 18.0 20.8 26.0 29.5 30/30
5.6/7.5 27.0 31.3 37.3 42.6 40/45
7.5/10 36.1 41.7 48.6 55.6 50/60
30 208/230160 197 253 13.5 72.5 0.9 2.8
/20.6 20.6 30
3.8/5 18.0 20.8 26.0 29.5 30/30
5.6/7.5 27.0 31.3 37.3 42.6 40/45
7.5/10 36.1 41.7 48.6 55.6 50/60
36 208/230160 197 253 14.1 77 1.5 4.1
/23.2 23.2 35
3.8/5 18.0 20.8 27.6 31.1 35/35
5.6/7.5 27.0 31.3 38.9 44.3 40/45
7.5/10 36.1 41.7 50.3 57.3 60/60
11.3/15 54.1 62.5 72.8 83.3 80/90
42 208/230160 197 253 15.9 112.3 1.7 4.1
/25.7 25.7 40
3.8/5 18.0 20.8 27.6 31.1 40/40
5.6/7.5 27.0 31.3 38.9 44.3 40/45
7.5/10 36.1 41.7 50.3 57.3 60/60
11.3/15 54.1 62.5 72.8 83.3 80/90
48 208/230160 197 253 19.6 130 1.7 6.0
/32.2 32.2 50
3.8/5 18.0 20.8 32.2 33.5 50/50
5.6/7.5 27.0 31.3 41.3 46.6 50/50
7.5/10 36.1 41.7 52.6 59.6 60/60
11.3/15 54.1 62.5 75.1 85.6 80/90
15/20 72.1 83.3 97.6 111.6 100/125
60 208/230160 197 253 23.7 152.5 1.9 7.6
/39.1 39.1 60
3.8/5 18.0 20.8 39.1 39.1 60/60
5.6/7.5 27.0 31.3 43.3 48.6 60/60
7.5/10 36.1 41.7 54.6 61.6 60/70
11.3/15 54.1 62.5 77.1 87.6 80/90
15/20 72.1 83.3 99.6 113.6 100/125
** HACR Type Circuit breaker
LEGEND
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
RLA - Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be Power Supply fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
OPERATING SEQUENCE
Cooling Operation
With a call for cooling (Y/G), the contactor is energized which
brings on the compressor and outdoor fan. The indoor fan is also
energized. When the cooling demand is met, Y and G are
de−energized shutting off the contactor. The indoor fan stops
after a 60 second delay.
Heating Operation
With a call for heating (W2), the auxiliary or electric heat
energizes along with the indoor blower. In case of staged
heating, W3 is energized if the demand is not met. The highest
airflow selected is run while the electric heat is in operation.
When heating demand is met, W3 and W2 sequentially
de−energize shutting off the indoor fan and the electric heater.
Continuous Fan
With the continuous indoor fan option selected on the
thermostat, G is continuously energized keeping the indoor fan
running at all times.
APPLICATION DATA
Condensate trap — A 2−in. (51 mm) condensate trap must be
field supplied.
1” (25 mm) MIN.
2” (51 mm) MIN.
TRAP
OUTLET
A08001
Maximum cooling airflow — To minimize the possibility of
condensate blow−off from the evaporator, airflow through the
units should not exceed 450 CFM/ton.
Minimum cooling airflow — The minimum cooling airflow is
350 cfm/ton.
Minimum cooling operating outdoor air temperature — All
standard units have a minimum ambient operating temperature
of 40°F (4.4°C). With accessory low ambient temperature kit,
units can operate at temperatures down to 0°F (−17.8°C).
Maximum operating outdoor air temperature — Maximum
outdoor operating air temperature for cooling is 125°F (51.7°C).
15 426 41 1707 05Specifications subject to change without notice.
TYPICAL INSTALLATION
TOP COVER
INDOOR
THERMOSTAT
DISCONNECT
PER NEC
(UNIT AND
ELECTRIC
HEATER)
FROM
POWER
SOURCE
RETURN
AIR
POWER
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
CONDENSATE
DRAIN
CONNECTION
Power Wiring
Control Wiring
Condenser Airflow
Evaporator Airflow
LOW VOLTAGE
ENTRY
A10135
ENGINEERS’ SPECIFICATION GUIDE
GENERAL
Furnish and install outdoor package, electrically controlled, air
conditioner utilizing a reciprocating or scroll compressor for cooling
duty. Unit shall discharge supply air horizontally as shown on
contract drawings.
Nominal unit electrical characteristics shall be ______ v, ______ ph,
60 Hz. The unit shall be capable of satisfactory operation within
voltage limits of ______ v to ______ v. Unit power wiring shall enter
unit cabinet at a single location.
Separate power supply shall not be required for electric heat.
COOLING CAPACITY
Total cooling capacity of the unit shall be _____ Btuh or greater, and
sensible capacity shall be ______ Btuh or greater at conditions of
______ cfm indoor air entering unit at ______F dry bulb, _____ F wet
bulb and outdoor entering air of ______F dry bulb. Total design
conditions shall be a minimum of ______ Btuh/Watt. The unit shall be
capable of cooling operation down to 40 F (4.4 C) as shipped from
the factory.
CABINET
Unit cabinet shall be constructed of phosphated, bonderized,
zinc−coated, prepainted steel. Basepan shall be made of a
single−piece non−corrosive, composite material.
Evaporator−fan compartment interior cabinet surfaces shall be
insulated with a minimum 1/2−in. (12.7 mm) thick, flexible fiberglass
insulation, coated on the air side with aluminum foil.
Cabinet panels shall be easily removable for servicing.
Outdoor coil shall be protected by metal louvered panels.
COMPRESSOR
Compressor shall be fully hermetic type with external vibration
isolation.
CONDENSER SECTION
Condenser fan shall be of the direct−driven propeller type blades,
riveted to corrosion−resistant spiders, and shall be dynamically
balanced and discharge air vertically upwards.
Condenser coils shall have aluminum−plate fins mechanically bonded
to copper tubes with all joints brazed.
Tube sheet openings shall be belled to prevent tube wear.
EVAPORATOR SECTION
Fan shall be multi−speed with direct drive motor as shown on the
equipment drawings.
Fan wheel shall be made from steel, be double−inlet type with
forward−curved blades with a corrosion−resistant finish and
dynamically balanced.
Evaporator coils shall have aluminum−plate fins mechanically
bonded to copper tubes with all joints brazed.
Tube sheet openings shall be belled to prevent tube wear.
MOTORS
Compressor motors shall be of the refrigerant cooled type with line
break thermal and current overload protection.
All fan motors shall have permanently lubricated bearings, and
inherent automatic reset thermal overload protection.
Condenser fan motor shall be totally enclosed.
REFRIGERANT SYSTEM
Refrigerant system shall include fixed orifice or TXV metering
system.
CONTROLS
Unit shall be complete with self−contained low voltage control circuit.
APPROVALS
Unit shall be UL listed as a total package for safety requirements. All
wiring shall be in accordance with NEC.
Unit shall be rated in accordance with AHRI Standards 210/240.
Cabinet insulation shall conform to ASHRAE Standard 62.2
Insulation and adhesive shall meet NFPA 90A requirements for flame
spread and smoke generation.
Unit shall have a sloped drain pan that conforms to ASHRAE
Standard 62.2.
ACCESSORIES
Field−installed accessories shall include solid−state compressor
short−cycle device, outdoor thermostat, room thermostats, electric
heaters with single−point connection, crankcase heater, and
low−ambient kit.
426 41 1707 05 16Specifications subject to change without notice.
OPTIONS AND ACCESSORIES
PART NUMBER
ITEM DESCRIPTION
FIELD
INSTALLED
ACCESSORY
CPHSTART002A00 Compressor Start Kit Compressor Start Kit assists compressor start-up by providing additional
starting torque on sing phase units only.X
CPCRKHTR008A00 Crankcase Heater Crankcase Heater provides anti-floodback protection for low-load cooling
applications.
24 - 36
CPCRKHTR004A00 42 - 60
CPLOWAMB001A00 Low Ambient Kit Low Ambient Kit (Motormaster II Control) allows the use of mechanical cooling
down to outdoor temperatures as low as 0°F (-18°C) when properly installed.X
NRTIMEGD001A00 Time Guard II
Automatically prevents the compressor from restarting for at least 4 minutes
and 45 seconds after shutdown of the compressor. Not required when a
corporate programmable thermostat is applied.
X
Accessory Electric Heaters
CATALOG
ORDERING NO.
NOMINAL
CAPACITY
(kW)
USED WITH SIZES
CIRCUIT
BREAKER
(Yes/No)
STAGES 24 30 36 42 48 60
ELECTRIC HEATERS (208/230-SINGLE PHASE-60Hz)
CPHEATER125A0*3.8 / 5.0 No 1 √√√√√√
CPHEATER126A0*3.8 / 5.0 Yes 1 √√√√√√
CPHEATER127A0*5.6 / 7.5 No 2 √√√√√√
CPHEATER128A0*5.6 / 7.5 Yes 2 √√√√√√
CPHEATER129A0*7.5 / 10.0 No 2 √√√√√
CPHEATER130A0*7.5 / 10.0 Yes 2 √√√√√√
CPHEATER131A0*11.3 / 15.0 Yes 2 √√√√
CPHEATER132A0*15.0 / 20.0 Yes 2 √√
√ =Approved combination
Copyright 2019 International Comfort ProductsLewisburg, Tennessee 37091 USAwww.GoComfortmaker.com