Loading...
HomeMy WebLinkAboutREVISION, ROOF ATTACHMENTS STRUCTURALT01 01 VICINITY 02 AERIAL LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA PROJECT INFORMATION DISTRICTS DESIGN SPECS GOVERNING CODES SYSTEM COUNTY: ST LUCIE COUNTY JURISDICTION: ST LUCIE COUNTY WIND EXPOSURE: B WIND SPEED (MPH): 160 SNOW LOAD (PSF): 0 BUILDING: FBC 2020/ASCE 7-16 ELECTRICAL: NEC 2017 FIRE: FFPC 2020/NFPA 2018 SIZE (KWDC): 19.76 # PANELS: 52 PANEL: BLK-G9380 INVERTER(S): undefined VOLTAGE (V): 240 PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SHEET INDEX T01COVER S01LAYOUT SF01FIRE SAFETY SP01-SPxxATTACHMENT PLAN SA01-SAxxATTACHMENT DETAIL SD01-SDxxSTRUC DATASHEETS S01 ROOF 1 MEAN HEIGHT:12' MATERIAL: SHINGLE SHAPE: GABLE ATTACHMENT: (148) S5!-S-5-N RAIL: (492') IRONRIDGE-XR100 MAX POINT DEADLOAD: 26 lbs MAX ANCHOR LOAD: -189 lbf MIN SAFETY FACTOR: 8.24 FRAMING RAFTER/TRUSS SIZE: MIN 2X4 RAFTER/TRUSS SPACING: 24" OC ARRAY(S) MODULES: (52) BLK-G9380 ARRAY AREA: 1061 SQFT 01 PLAN VIEW 02 SYSTEM SUMMARY 03 NOTES 04 CERTIFICATION INV -INVERTER/COMBINER PM -POWER METER ACD -AC DISCONNECT MP -MAIN PANEL/DISC -1,2e -OTHER GENERAL 1.1 EXISTING VENTS, SKYLIGHTS OR EXHAUST OUTLETS SHALL NOT BE COVERED BY THE SOLAR PV SYSTEM. 1.2 MODULES SHALL NOT OVERHANG ANY RIDGE, HIP OR ROOF EDGE. 1.3 CONTRACTOR SHALL NOTIFY ENGINEER/DESIGNER OF ANY CHANGES. AN ANALYSIS OF THE ROOF CONSTRUCTION AT THE REFERENCED PROPERTY WAS DONE AND IT HAS BEEN DETERMINED THAT THE STRUCTURE IS ADEQUATE TO SUPPORT THE ADDITIONAL SOLAR PV LOAD. BASED ON OUR REVIEW, THE EXISTING MEMBERS COMPLY WITH FBC 2020/ASCE 7-16 DESIGN SPAN RATINGS WITH SUFFICIENT CAPACITY TO SUPPORT THE NEW LOADS IMPOSED BY THE PROPOSED SOLAR ARRAY. THE SPECIFICATIONS SHOWN IN THIS CONSTRUCTION PLAN WERE DESIGNED PER FBC 2020/ASCE 7-16 FOR A WIND SPEED OF 160 MPH, EXPOSURE CATEGORY B FOR RISK CATEGORY II BUILDING WITH 0 PSF SNOW LOAD. PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SF01 01 FIRE SAFETY OFFSETS NFPA 1 11.12.2.2.2 FOR RESIDENTIAL HOMES .1 PATHWAYS: NOT LESS THAN TWO 36IN WIDE PATHEWAYS ON SEPARATE ROOF PLANES FROM GUTTER TO RIDGE, SHALL BE PROVIDED ON ALL BUILDINGS. ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLANE WITH A PV ARRAY, A 36IN WIDE PATHWAY FROM GUTTER TO RIDGE SHALL BE PROVIDED ON THE SAME ROOF PLANE OR STRADDLING THE SAME AND ADJACENT ROOF ADJACENT ROOF PLANES. PATHWAYS SHALL BE LOCATED IN AREAS WITH MINIMAL OBSTRUCTIONS SHUCH AS VENT PIPES, CONDUIT, OR MECHANICAL EQUIPMENT. .2 33 PERCENT RULE: FOR PV ARRAYS OCCUPYING UP TO 33 PERCENT OF THE PLAN VIEW ROOF AREA, A MINIMUM 18IN PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. FOR PV ARRAYS OCCUPYING MORE THAN 33 PWECENT OF THE PLAN VIEW AREA, A MINIMUM OF 36IN PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SP01 01 ATTACHMENT PLAN (SHINGLE ROOF) PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 LEGEND PARAMETERS ARRAY MODULE:(52) BLK-G9380 TOTAL AREA:1061.46 SQFT HARDWARE RAIL: ATTACHMENT: ANCHORAGE: 492' IRONRIDGE-XR100 (148) S5!-S-5-N RIB/SEAM FRAMING SIZE:MIN. 2X4 SPACING:24" OC ROOF MEAN HEIGHT:12' MATERIAL:SHINGLE SHAPE:GABLE GEOGRAPHY EXPOSURE CAT:B WIND SPEED:160 MPH SNOW LOAD:0 LBS LOAD CALCS PER ASCE 7-16 & SEAOC PV2-2017 DEAD LOAD CALC LOADS: Panel = 43lbs Anchors = 1.2lbs Rail = 0.72lbs/ft Misc = 1.6lbs/panel DEADLOAD PER ROW, Fdr: Fdr = (lbs/panel*#panels/row) + (lbs/ft-rail*ft-rail/row)*2 + (lbs/anchor*#anchors/row) + (misc-lbs/panel*#panels/row) (lbf) DIST DEADLOAD, Fdd: Fdd = Fdr/(area/panel*#panels/row) (psf) DEADLOAD PER ANCHOR, Fda: Fda = Fdr/(#anchors/row) (lbs) FLUSH MOUNTED PANELS ON ANY ROOF CRITERIA: - Panels parallel to roof surface (within 2 deg) - Max height of panel above roof, h1 & h2 OF 10" - Min panel gap of 0.25" - Min edge distance 2*h2 - Max panel chord length of 6.7' UPLIFT ON ONE PANEL, Fup = P*A (lbf) Per ASCE 2.4, 26.10.2 & 29.4.4 P = pasd = 0.6*p = 0.6*qh*(GCp)*(YE)*(Ya), A = load area UPLIFT PER ROW, Fur = SUM(Fup(0):Fup(n)) (lbf) Where Fup(0):Fup(n) = loads from first to last panel in row UPLIFT PER ANCHOR, Fua = Fur/(#ANCHORS/ROW) (lbf) LOAD PER ANCHOR, Fa = 0.6*Fda + Fua (lbf) SAFETY FACTOR, SF = Ftest/Fa VELOCITY PRESSURE qh = 0.00256*Kz*Kzt*Kd*Ke*V^2 = 32 (lb/sqft) Where Kz = 0.57, Kzt = 1, Kd = 0.85, Ke = 1, V = 160 EXT PRESSURE COEFFICIENT, GCp: GCp varies per roof & zone, 30.3-2A-I to 30.3.7: Aeff = 5.1 sqft EXPOSURE FACTOR, YE: YE = 1.5 for uplift loads on panels that are exposed and within a distance 1.5Lp from the end of a row at an exposed edge of the array; YE = 1.0 elsewhere for uplift loads and for all downward loads, as illustrated in Fig. 29.4-7. A panel is defined as exposed if d1 to the roof edge > 0.5h and one of the following applies: 1. d1 to the adjacent array > max (4h2, 4 ft (1.2m) or 2. d2 to the next adjacent panel > max (4h2, 4 ft (1.2m). Per SEAOC 5.3.3 2*h2 may be used instead of 1.5Lp for flush mounted panels. PRESSURE EQUALIZATION FACTOR, Ya: Ya is given as 0.7 per SEAOC 5.3.5 with h2 = 6" & panel gap = 0.37" ZONES f0: 1' (Flat) f1: 1 (Flat) f2: 2 (Flat) f3: 3 (Flat) g1: 1 (Gable) g2e: 2e (Gable) g2n: 2n (Gable) g2r: 2r (Gable) g3r: 3r (Gable) g3e: 3e (Gable) h1: 1 (Hip) h2r: 2r (Hip) h2e: 2e (Hip) h3: 3 (Hip) ROW: 0 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 16.54 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 00 16.6" ROW: 1 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -817 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 10 Z: g1 P: -20 psf Fup: -408 lbf 11 23.75" ROW: 2 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 16.54 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 20 16.6" ROW: 3 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 30 Z: g1 P: -20 psf Fup: -408 lbf 31 Z: g1 P: -20 psf Fup: -408 lbf 32 23.75" ROW: 4 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -2042 lbf #ANCHORS: 16 LOAD/ANCHOR, Fa: -117 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 13.29 DIST LOAD, Fdd: 2.8 psf POINT LOAD, Fda: 17.86 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 40 Z: g1 P: -20 psf Fup: -408 lbf 41 Z: g1 P: -20 psf Fup: -408 lbf 42 Z: g1 P: -20 psf Fup: -408 lbf 43 Z: g1 P: -20 psf Fup: -408 lbf 44 23.75" ROW: 5 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1633 lbf #ANCHORS: 14 LOAD/ANCHOR, Fa: -107 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 14.55 DIST LOAD, Fdd: 2.82 psf POINT LOAD, Fda: 16.43 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 50 Z: g1 P: -20 psf Fup: -408 lbf 51 Z: g1 P: -20 psf Fup: -408 lbf 52 Z: g1 P: -20 psf Fup: -408 lbf 53 2.35" ROW: 6 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 10 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 13.85 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 60 Z: g1 P: -20 psf Fup: -408 lbf 61 Z: g1 P: -20 psf Fup: -408 lbf 62 23.75" ROW: 7 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 10 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 13.85 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 70 Z: g1 P: -20 psf Fup: -408 lbf 71 Z: g1 P: -20 psf Fup: -408 lbf 72 23.75" ROW: 8 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 16.54 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 80 16.6" ROW: 9 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 90 Z: g1 P: -20 psf Fup: -408 lbf 91 Z: g1 P: -20 psf Fup: -408 lbf 92 23.75" ROW: 10 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -2042 lbf #ANCHORS: 10 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 100 Z: g1 P: -20 psf Fup: -408 lbf 101 Z: g1 P: -20 psf Fup: -408 lbf 102 Z: g1 P: -20 psf Fup: -408 lbf 103 Z: g1 P: -20 psf Fup: -408 lbf 104 12" ROW: 11 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1633 lbf #ANCHORS: 8 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 110 Z: g1 P: -20 psf Fup: -408 lbf 111 Z: g1 P: -20 psf Fup: -408 lbf 112 Z: g1 P: -20 psf Fup: -408 lbf 113 19.15" PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SP02 ROW: 12 Z: g1 P: -20 psf Fup: -408 lbf 120 Z: g1 P: -20 psf Fup: -408 lbf 121 Z: g1 P: -20 psf Fup: -408 lbf 122 23.75" ROW: 13 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 130 Z: g1 P: -20 psf Fup: -408 lbf 131 Z: g1 P: -20 psf Fup: -408 lbf 132 23.75" ROW: 14 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 10 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 13.85 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 140 Z: g1 P: -20 psf Fup: -408 lbf 141 Z: g1 P: -20 psf Fup: -408 lbf 142 23.75" NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 8.24 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg ROW: 15 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1429 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -133 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 11.72 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -30 psf Fup: -613 lbf 150 Z: g1 P: -20 psf Fup: -408 lbf 151 Z: g1 P: -20 psf Fup: -408 lbf 152 23.75" ROW: 16 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -1429 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -133 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 11.72 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -30 psf Fup: -613 lbf 160 Z: g1 P: -20 psf Fup: -408 lbf 161 Z: g1 P: -20 psf Fup: -408 lbf 162 23.75" ROW: 17 NOM SPAN: 48" MAX SPAN: 48" MAX CANTILEVER: 24" UPLIFT/ROW, Fur: -817 lbf #ANCHORS: 8 LOAD/ANCHOR, Fa: -93 lbf TEST LOAD/ANCHOR: -1554 lbf SF: 16.64 DIST LOAD, Fdd: 2.85 psf POINT LOAD, Fda: 14.53 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0-2 deg Z: g1 P: -20 psf Fup: -408 lbf 170 Z: g1 P: -20 psf Fup: -408 lbf 171 1.05" SA01 BLK-G9380 72.4 IN 40.6 IN 5.9-17.7 IN 0-21.7 IN GENERAL 1.1 DESIGNED PER FBC 2020/ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES. 1.2 CONTRACTOR IS RESPONSIBLE FOR INSTALLING PV MODULES, RACKING & RACKING SUPPORTS IN ACCORDANCE WITH THE MANUFACTURER INSTALLATION INSTRUCTIONS NOT SHOWN IN THIS PLAN. 1.3 WITHDRAWAL VALUES GIVEN PER NDS 2015 BASED ON SG OF 0.5 OR MANUFACTURER SUPPLIED 3RD PARTY UPLIFT TESTING REPORTS WITH APPLICABLE SAFETY FACTORS. 1.4 ALL PENETRATIONS SHALL BE FLASHED OR SEALED IN A MANNER THAT PREVENTS MOISTURE FROM ENTERING THE WALL AND ROOF USING ASTM C920 COMPLAINT SEALANT IN PILOT HOLES AND AROUND FASTENERS. 1.5 THE SUPPORTING ROOF STRUCTURE SHALL BE CONVENTIONAL WOOD FRAMED CONSTRUCTION WITH PRE-ENGINEERED TRUSSES OR ROOF FRAMING MEMBERS AT A SPACING OF 24 IN MAXIMUM ON CENTER. 1.6 EXISTING STRUCTURE IS ASSUMED TO BE IN COMPLIANCE WITH APPLICABLE BUILDING CODES AT THE TIME OF CONSTRUCTION. 1.7 CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION CHANGES. 01 ANCHORAGE DETAIL 02 NOTES 03 ANCHOR DETAIL 04 RAIL & CLAMPS DETAIL 05 MODULE DETAILS PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SD01 PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SD02 PROJECT ID: CONTRACTOR:DESCRIPTIONDATEVERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN 04.21.21 RG 02 UPDATED ATTACHMENTS UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609 CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840