SAINT LUCIE COUNTY FARE DISTRICT
PLAN REVIEW FOfil','t
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
City ;Vero Beach
Zip 32960
Architect/Engineer !Hans Lundering Telephone
s
Occupancy TypeIndustrial/Business
fonstruction Type ?V3
FMOPermit # jB-21-148
BLDGPermit# 12103-0657
City !Ft. Pierce
Telephone ;(772)564-8008
i
a W Square Feet 10,000
Occupant Load j110perplans NumberofStories i1 +� Y Access Box 'Required Access Key Switch
AFS Permit RegU(red � � FA Permit iReCulred L FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building 4epartment shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteraticn of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
11. Place exit lights over exit doors. Emergency lights are equired.
2. A separate review and permit is required for the installation or alteration of the fire alarm and fire sprinkler systems.
3. Portable fire extinguishers from a licensed contractor .:re required.
4. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfrr; design capacity. Provide a remote test and
inspect appliance equipped with an audible/visuai indicator for each HVAC duct smoke detector. HVAC duct smoke detectors)
shall be tied into the fire alarm system.
s
Page ?? 1 of 1 Reviewed by ; Fpny Jergc r y` Date 04-21-2021