Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutRevisions OFFICE USE ONLY:
'DATE FILED:
REVISION FEE: RECEIPT# 1
PLANNING&DEVELOPMENT SERVICES
BUILDING&CODE REGULATION DIVISION
C
py 2300 VIRGINIA AVENUE
FORT PIERCE,FL 34982.5652
'� (772)462-1553
APPLICATION FOR BUILDING PERMIT REVISIONS
PROJECT INFORMATION
LOCATION/SITE
ADDRESS: / Q�
5307 Myrtle Drive Fort Pierce, FL 34982 ST.LUCIE COUNk
FOR COMPLI
-DETAILED DESCRIPTION OF PROJECT REVIEWED BY
DATE >�
REVISIONS: LANS AND PE On Site Modifications-See attached Manual J,D&S MUST BE KEPT O JON WILL B
CONTRACTOR INFORMATION:
STATE of FL REG./CERT. #: CAC055550 ST.LUCIE CO CERT.#:
BUSINESS NAME: Service Star Air Conditioning And Heating, Inc
QUALIFIERS NAME: Robert Noeker
ADDRESS: 18735 E Colonial Dr#100
CITY: Orlando STATE: FL ZIP: 32820
PHONE(DAYTIME): 407-568-4688 FAX: 407-568-2766
ONVNER/BUILDER INFORMATION:
NAW: Michael Lalonde
ADDRESS:5307 Myrtle Drive
CITY: Fort Pierce STATE: FL ZIp: 34982
PHONE(DAYTIME: 518478-3850 FAX:
ARCHITECT/ENGINEER INFORMATION:
NAME:
ADDRESS:
CITY: STATE: ZIP:
PHONE(DAYTIME): FAX:
SLCCC: 9123109
Revised 06130/17
r
'.\ N -FILE COPY
HVAC Layout
�11112'-0" �
- Strg
25'-0"
Kitchen
Mwic Master Bath
RA over doot
12x4
Dining
10x6 10x6 10x6 10x6
25 cfm 34 cfm 90 cfm
90 cfm
4" 4 6" 6"
era, 24 x 0 8 x 4 Bath2
RA overdoot ah located inattic793 CM 16 cfm 10 x 6
12x4
p 20 x 12 4" 178 cfm
24'-0" 8" 24'-0"
M ® 64 cfm
6" Enclosed Garage
10x6 10x6
135 cfm 161 cfm RA overdoos
6° 8" 12x4
Living Rm
Master Bedroom Bedroom
r 38'-0" 12'-0" ►�
r� r+r ?e�` `` Y U� � ➢ i i�
Job#: R0218054 Service Star Cooling and Heating Scale: 1/8" = TO"
Performed by JND/TMN for: Page 1
Lalonde Residence RightSuite®Universal 2018
5307 Myrtle Dr 18.0.11 RSU07440
Fort Pierce,FL 34982 2018-Apr-13 15:12:38
...R0218054-Lalonde\R0218054c.rup
wrightsoft. Duct System Summary Job: R0218054
Date: 02-07-18104/13/18
Entire House By: JNDITMN
Service Star Cooling and Heating
Project Information
M.V
For: Lalonde Residence
5307 Myrtle Dr, Fort Pierce, FL 34982
FIR
K.
."Al 31 -11
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0.17 In H2O 0.17 in H2O
Available static pressure 0.33 in H2O 0.33 in H2O
Supply/return available pressure 0.240 0.090 in H2O 0.240 0.090 in H2O
Lowest friction rate 0.147 in/100ft 0.147 in/100ft
Actual air flow 0 cfm 793 cfm
Total effective length(TEL) 224 ft
Supply Branch Detail Table
Design Htg Cig Design Diarn H x W Duct Actual Ftg.Eqv
Name (13tuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk
Bath2 c 352 0 16 0.164 4.0 Ox 0 VIFx 15.9 130.0 stl
Bedroom C 1393 0 64 0.171 6.0 OX0 VIFx 14.8 125.0 stl
Enclosed Garage C 3877 0 178 0.153 8.0 Ox 0 VIFx 26.5 130.0 stl
Kitchen C 1958 0 90 0.170 6.0 Ox 0 VIFx 15.6 125.0 stl
Kitchen-A C 1958 0 90 0.189 6.0 ox 0 VIFx 6.9 120.0 stl
Living Rm c 3512 0 161 0.178 8.0 ox 0 VIFx 10.0 125.0 stl
Master Bath G 752 0 34 0.150 4.0 Ox 0 VIFx 19.5 140.0 st2
Master Bedroom C 2946 0 135 0.149 6.0 Ox 0 VIFx 20.5 140.0 st2
I Mwic I G 536 1 0 1 25 1 0.147 1 4.0 1 OX0 VIFx 1 22.8 1 140.0 1 st2
Supply Trunk Detail Table
Trunk Htg Cig Design Veloc Diarn H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
stl Peak AVF 0 793 0.147 476 12.8 12 x 20 VinIFIx
st2 Peak AVF 0 194 0.147 247 12.0 0 x 0 VinIFIx st'l
Return Branch DetaJi Table
Grille Htg CIg TEL Design Veloc; Diarn H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb2 ox 0 0 793 61.3 0.147 568 16.0 ox 0 VIFx
F LE COPY
wrightsoft- 201 B-Apr-1 3 15:05:46
Right-Suite®Universal=8 18.0.11 RSUD7440 Page i
ACCA ...vAc\awork FilMR0218054-Lalande\R0218054c.rup Calc=MJ8 Front Door faces: N
Manual S Compliance Report Job: R0218054
- wrightsoft9 Date: 02-07-18/04113118
Entire House By: JND/TMN
Service Star Cooling and Heating
Project Information
For: Lalonde Residence
5307 Myrtle Dr, Fort Pierce, FL 34982
Cooling Equipment
Design Conditions
Outdoor design DB: 90.0°F Sensible gain: 17284 Btuh Entering coil DB: 77.6°F
Outdoor design WB: 78.0°F Latent gain: 4562 Btuh Entering coil WB: 63.9°F
Indoor design DB: 75.0°F Total gain: 21847 Btuh
Indoor RH: 50% Estimated airflow: 793 cfm
Manufacturer's Performance Data at Actual Design Conditions 104
Equipment type: Split ASHP y ��! 4� sr '
Manufacturer:' Rheem Model: RP1424AJ1NA+RH1T2417S ,A + V. r k-,
V . l:ee P
L.w`' .!�4 r r T a a d
Actual airflow: 793 cfm ? � a4 E ° fi.
s � f
Sensible capacity: 17374 Btuh 101% of load
/°
Latent capacity: 6426 Btuh 141 of load ' 6
,h 4 si
Total capacity: 23800 Btuh 109%of load SHR: 73%
Heating Equipment
Design Conditions
Outdoor design DB: 42.0°F Heat loss: 14582 Btuh Entering coil DB: 70.0°F
Indoor design DB: 70.0°F
FI 'L�' E COPY
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Rheem Model: RP1424AJ1NA+RH1T2417STANJA
Actual airflow: 0 cfm
Output capacity: 22800 Btuh 156%of load Capacity balance: 30 of
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 0 cfm
Output capacity: 5.0 kW 117% of load Temp. rise: 20 °F
Meets all requirements of ACCA Manual S.
- wrightsoft- 2018-Apr-1315:05:19
Right-Suite®Universal 2018 18.0.11 RSU07440 Page 1
ACCA...VAC\.Work File\R0218054-Lalonde\R0218054c.rup Calc=MJ8 Front Door faces: N
Job: R0218064
ft wrightso - Project Summary Date: 02-07-18104/13118
Entire House By: JNDrrMN
Service Star Cooling and Heating
IRA
Project Information
1_7
For: Lalonde Residence 1
5307 Myrtle Dr, Fort Pierce, FL 34982
W-1 a
Notes: Load calculation was obtained from an electro aidd�4'
Des,ign Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 *F Outside db 90 'F
Inside db 70 'F Inside db 75 'F
Design TD 28 'F Design TD 15 'F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 11739 Btuh Structure 12674 Btuh
Ducts 1596 Btuh Ducts 4611 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0. Btuh
Piping 0 Btuh
Equipment load 13335 Btuh Use manufacturer's data y
Ratelswing multiplier 1.00
Infiltration Equipment sensible load 17284 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 3193 Btuh
Ducts 1369 Btuh
Central vent(0 cfm) 0 Btuh
He tin Cool' (none)
a]Area(ft2) 1229 1226 Equipment latent load 4562 Btuh
Volume(ft3) 9808 9808
Air changes/hour 0.31 0.16 Equipment Total Load (Sen+Lat) 21847 Btuh
Equiv.AVF(cfm) 51 26 Req,total capacity at 0.76 SHR 1.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Rheem Make Rheern
Trade Split HP Trade Split HP
Model RP1424AJlNA Cond RP1424AJlNA
AHRI ref 7489174 Coll RHIT2417STANJA
AHRI ref 7489174
Efficiency 8.2 HSPF Efficiency 11.5 EER, 14 SEER
Heating input Sensible cooling 18088 Btuh
Heating output 22800 Btuh @ 47°F Latent cooling 5712 Btuh
Temperature rise 0 'F Total cooling 23800 Btuh
Actual air flow 0 cfm Actual air flow 793 cfm
Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.79
Capacity balance point= 30'F
Backup: Aux Heat
Input= 5 kW, Output= 17061 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-Fid-
'0
Z_
Right-Suite(D Universal 2018 18.0.11 RSU07440 Roe I
ACCK...VAC\aWork Fi(e\R0218054-Lalonde\R02180W.rup Cato=MJ8 Front Door faces: N
E