Loading...
HomeMy WebLinkAboutAPPROVED, MANUAL Jv-7 wrlgn1 project Summary Jo Date AHU 1 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: TINDALL RESIDENCE 11652 ORANGE AVENUE, FORT PIERCE, FL Notes: Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 °F Inside db 70 °F Design TD 28 °F Heating Summary Structure 27647 Btuh Ducts 7493 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 35141 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ft2) 2493 2493 Volume (ft3) 32886 32886 Air changes/hour 0.24 0.13 Equiv. AVF (cfm) 134 72 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 9.3 kW 31844 Btuh 21 °F 1400 cfm 0.040 cfm/Btuh 1.00 in H2O Dec 08, 2020 Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 20424 Btuh Ducts 10869 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipmenf sensible load 29728 Btuh Latent Cooling Equipment Load Sizing Structure 4201 Btuh Ducts 2962 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 7162 Btuh Equipment Total Load (Sen+Lat) 36891 Btuh Req. total capacity at 0.70 SHR 3.5 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond CA16NA04200GOBO Coil FX4DNF049L AHRI ref 202024777 Efficiency 13.0 EER, 16 SEER Sensible cooling 29400 Btuh Latent cooling 12600 Btuh Total cooling 42000 Btuh Actual air flow 1400 cfm Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 30ft—ord- W riigl 2020-Dec-08 11:36:29 _ Right -Suite® Universal 2019 19.0.08 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S v-7 wrlgn1 project Summary Jo Date AHU 2 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: TINDALL RESIDENCE 11652 ORANGE AVENUE, FORT PIERCE, FL Notes: Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 °F Inside db 70 °F Design TD 28 °F Heating Summary Structure 16005 Btuh Ducts 2552 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 18556 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heatingg Coolingg Area (ft2) 1217 1217 Volume (ft3) 12170 12170 Air changes/hour 0.38 0.20 Equiv. AVF (cfm) 76 41 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 5.2 kW 17593 Btuh 27 °F 590 cfm 0.032 cfm/Btuh 1.00 in H2O Dec 08, 2020 Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 9968 Btuh Ducts 3578 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipmenf sensible load 12869 Btuh Latent Cooling Equipment Load Sizing Structure 1905 Btuh Ducts 935 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 2840 Btuh Equipment Total Load (Sen+Lat) 15709 Btuh Req. total capacity at 0.70 SHR 1.5 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond CA16NW01800GOA0 Coil FX4DNF019L AHRI ref 9200856 Efficiency 13.5 EER, 16 SEER Sensible cooling 12390 Btuh Latent cooling 5310 Btuh Total cooling 17700 Btuh Actual air flow 590 cfm Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 30ft—ord- W riigl 2020-Dec-08 11:36:29 _ Right -Suite® Universal 2019 19.0.08 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU 1 MUDROOM 2 Exposed wall 180.0 ft 0 ft 3 Room height 13.2 ft 10.0 ft heat/cool 4 Room dimensions 1.0 x 175.0 ft 5 Room area 2493.0 ft2 175.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-Ofcs 0.183 n 5.12 3.18 778 631 3233 2009 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 36 0 312 311 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 48 0 417 414 0 0 0 0 11 2 glazing, clr low-e 0.310 n 8.68 8.63 16 0 139 138 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 32 0 278 276 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 15 0 130 99 0 0 0 0 W G 13AB-Ofcs 0.183 e 5.12 3.18 156 156 799 497 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 s 5.12 3.18 899 719 3682 2288 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 20 20 174 173 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 32 32 278 276 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 128 128 1111 1105 0 0 0 0 t-G2 13AB-Ofcs 0.183 w 5.12 3.18 403 373 1911 1188 0 0 0 0 glazing, clr low-e 0.310 w 8.68 16.82 30 0 260 505 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 2493 2493 3953 3411 175 175 277 239 F 22A-tph 1.358 38.02 0.00 2493 180 6844 0 175 0 0 0 6 c) AED excursion 0 -16 Envelope loss/gain 23521 12689 277 224 12 a) Infiltration 4126 1184 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 6550 500 Subtotal (lines 6 to 13) 27647 20424 277 724 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 27647 20424 277 724 15 Duct loads 27% 53% 7493 10869 27% 53% 75 385 FFTotal room load 35141 31293 353 1109 Air required (cfm) 14001 1400 14 50 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 1 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name UTILITY RM POWDER RM 2 Exposed wall 8.0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 10.0 x 10.0 ft 4.0 x 9.0 ft 5 Room area 100.0 ft2 36.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.68 3.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 01 0 0 0 0 0 t-G2 13A6-Ofcs 0.183 w 5.12 3.18 80 65 333 207 0 0 0 0 glazing, clr low-e 0.310 w 8.68 16.82 15 0 1301 252 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 100 100 159 137 36 36 57 49 F 22A-tph 1.358 38.02 0.00 100 8 304 0 36 0 0 0 6 c) AED excursion 126 -1 Envelope loss/gain 926 722 57 48 12 a) Infiltration 148 42 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1074 764 57 48 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1074 764 57 48 15 Duct loads 27% 53% 291 407 27% 53% 15 26 Total room load 1365 1171 773 74 Air required (cfm) 54 52 3 3 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 2 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 1 M WIC 2 2 Exposed wall 0 ft 20.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 14.0 x 9.0 ft 9.0 x 11.0 ft 5 Room area 126.0 ft2 99.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-Ofcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 0 0 0 0 W G 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13AB-Ofcs 0.183 s 5.12 3.18 0 0 0 0 90 90 461 287 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 110 110 564 350 2 glazing, clr low-e 0.310 w 8.68 16.82 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 126 126 200 172 99 99 157 135 F 22A-tph 1.358 38.02 0.00 126 0 0 0 99 20 760 0 6 c) AED excursion -14 -19 Envelope loss/gain 200 158 1942 754 12 a) Infiltration 0 0 369 106 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13) 200 658 2311 860 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 200 658 2311 860 15 Duct loads 27% 53% 54 350 27% 53% 626 457 FFTotal room load 254 1008 2938 1317 Air required (cfm) 10 45 117 59 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 3 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET M BATH 2 Exposed wall 12.0 ft 20.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 5.0 x 7.0 ft 1.0 x 220.0 ft 5 Room area 35.0 ft2 220.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 50 50 256 159 120 105 538 334 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 15 0 130 99 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.68 3.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 01 0 0 0 0 0 13A6-Ofcs 0.183 w 5.12 3.18 70 70 359 223 80 65 333 207 2 glazing, clr low-e 0.310 w 8.68 16.82 0 0 0 0 15 0 130 252 C 16X19-0md 0.408 1.59 1.37 35 35 55 48 220 220 349 301 F 22A-tph 1.358 38.02 0.00 35 12 456 0 220 20 760 0 6 c) AED excursion -10 92 Envelope loss/gain 1127 419 2241 1285 12 a) Infiltration 221 64 369 106 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1348 483 2610 1391 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1348 483 2610 1391 15 Duct loads 27% 53% 365 257 27% 53% 707 740 FFTotal room load 7 1714 740 3317 2131 Air required (cfm) 1 168 33 1 132 95 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 4 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM KITCHEN 2 Exposed wall 27.0 ft 16.0 ft 3 Room height 10.0 ft heat/cool 16.5 ft heat/cool 4 Room dimensions 15.0 x 18.0 ft 1.0 x 334.0 ft 5 Room area 270.0 ft2 334.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 150 114 584 363 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 36 0 312 311 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 90 90 461 287 33 33 169 105 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13AB-0fcs 0.183 s 5.12 3.18 0 0 0 0 231 211 1081 672 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 20 20 174 173 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 01 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 30 30 154 96 0 0 0 0 2 glazing, clr low-e 0.310 w 8.68 16.82 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 270 270 428 369 334 334 530 457 F 22A-tph 1.358 38.02 0.00 270 27 1027 0 334 16 608 0 6 c) AED excursion -63 -44 Envelope loss/gain 2966 1362 2562 1363 12 a) Infiltration 498 143 487 140 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1400 1200 Subtotal (lines 6 to 13) 3465 2905 3049 2703 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3465 2905 3049 2703 15 Duct loads 27% 53% 9391 1546 27% 53% 826 1438 Total room load 4404 4451 3875 4141 Air required (cfm) 1175 1991 1 11541185 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 5 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING/DINING PANTRY 2 Exposed wall 35.0 ft 13.0 ft 3 Room height 16.5 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 35.0 x 22.0 ft 13.0 x 8.0 ft 5 Room area 770.0 ft2 104.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 130 106 543 338 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 24 0 208 207 11 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13AB-0fcs 0.183 s 5.12 3.18 578 418 2139 1329 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 32 32 278 276 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 128 128 1111 1105 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 w 8.68 16.82 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 770 770 1221 1053 104 104 165 142 F 22A-tph 1.358 38.02 0.00 770 35 1331 0 104 13 494 0 6 c) AED excursion 28 -16 Envelope loss/gain 6080 3792 1411 671 12 a) Infiltration 1066 306 240 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2200 0 Subtotal (lines 6 to 13) 7146 6298 1651 740 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 7146 6298 1651 740 15 Duct loads 27% 53% 1937 3352 27% 53% 447 394 Total room load 9082 9650 2098 1134 Air required (cfm) 13621 4321 1841 51 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 6 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 1 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER DEN 2 Exposed wall 16.0 ft 13.0 ft 3 Room height 16.5 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 12.0 x 10.0 ft 13.0 x 8.0 ft 5 Room area 120.0 ft2 104.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 198 150 769 478 130 106 543 338 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 24 0 208 207 11 2 glazing, clr low-e 0.310 n 8.68 8.63 16 0 139 138 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 32 0 278 276 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 6.59 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 33 33 169 105 0 0 0 0 2 glazing, clr low-e 0.310 a 0.00 0.00 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.68 3.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 8.68 8.63 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 33 33 169 105 0 0 0 0 2 glazing, clr low-e 0.310 w 8.68 16.82 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 120 120 190 164 104 104 165 142 F 22A-tph 1.358 38.02 0.00 120 16 608 0 104 13 494 0 6 c) AED excursion -30 -32 Envelope loss/gain 2322 1236 1411 655 12 a) Infiltration 487 140 240 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 750 Subtotal (lines 6 to 13) 2809 1376 1651 1474 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2809 1376 1651 1474 15 Duct loads 27% 53% 761 732 27% 53% 447 784 Total room load 3571 2109 2098 2258 Air required (cfm) 142 94184 101 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 7 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU 2 BEDROOM 4 2 Exposed wall 127.0 ft 30.0 ft 3 Room height 10.0 ft 10.0 ft heat/cool 4 Room dimensions 15.0 x 15.0 ft 5 Room area 1217.0 ft2 225.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 320 269 1378 857 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 15 0 130 130 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 36 0 312 311 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 520 460 2357 1465 150 120 615 382 2 glazing, clr low-e 0.310 a 8.68 22.91 60 0 521 1374 30 0 260 687 W 13AB-0fcs 0.183 s 5.12 3.18 210 210 1076 669 150 150 769 478 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 220 220 1127 701 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 1217 1217 1930 1665 225 225 357 308 F 22A-tph 1.358 38.02 0.00 1217 127 4829 0 225 30 1141 0 6 c) AED excursion 0 43 Envelope loss/gain 13661 7170 3141 1897 12 a) Infiltration 2344 673 554 159 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2125 250 Subtotal (lines 6 to 13) 16005 9968 3695 2306 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 230 94 14 Subtotal 16005 9968 3925 2400 15 Duct loads 16% 36% 2552 3578 16% 36% 626 861 Total room load 18556 13546 4550 3261 Air required (cfm) 590 5901145 142 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 8 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 4 HALL 4 2 Exposed wall 15.0 ft 4.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 9.0 ft 6.0 x 7.0 ft 5 Room area 54.0 ft2 42.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 0 0 0 0 W 13AB-0fcs 0.183 s 5.12 3.18 60 60 307 191 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 01 0 0 0 0 0 13A6-Ofcs 0.183 w 5.12 3.18 90 90 461 287 40 40 205 127 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 54 54 86 74 42 42 67 57 F 22A-tph 1.358 38.02 0.00 54 15 570 0 42 4 152 0 6 c) AED excursion -13 -3 Envelope loss/gain 1425 538 424 182 12 a) Infiltration 277 79 74 21 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13) 1701 818 497 203 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 230 94 -497 -203 14 Subtotal 1931 912 0 0 15 Duct loads 16% 36% 308 327 16% 36% 0 0 FFTotal room load 2239 1239-7 0 0 Air required (cfm) 71 54 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 9 '� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU CLST TOILET 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 3.0 ft 6.0 x 4.0 ft 5 Room area 18.0 ft2 24.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.00 3.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 18 18 29 25 24 24 38 33 F 22A-tph 1.358 38.02 0.00 18 0 0 0 24 0 0 0 6 c) AED excursion 0 -6 Envelope loss/gain 29 24 38 27 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 350 Subtotal (lines 6 to 13) 29 24 38 377 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -29 -24 38 32 14 Subtotal 0 0 76 409 15 Duct loads 16% 36% 0 0 16% 36% 12 147 FFTotal room load � _T 0 0 88 556 Air required (cfm) 0 0 3 24 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 10 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL CLST HALL 3 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 3.0 ft 6.0 x 12.0 ft 5 Room area 18.0 ft2 72.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.00 3.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 18 18 29 25 72 72 114 99 F 22A-tph 1.358 38.02 0.00 18 0 0 0 72 0 0 0 6 c) AED excursion 0 -2 Envelope loss/gain 29 24 114 97 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 29 24 114 97 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -29 -24 -114 -97 14 Subtotal 0 0 0 0 15 Duct loads 16% 36% 0 0 16% 36% 0 0 Total room load FT 0 0F7T 0 0 Air required (cfm) 0 0 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 11 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name SINKS 4 BATH 4 2 Exposed wall 0 ft 6.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 12.0 ft 9.0 x 6.0 ft 5 Room area 72.0 ft2 54.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 0 0 0 0 60 60 307 191 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.00 3.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-Omd 0.408 1.59 1.37 72 72 114 99 54 54 86 74 F 22A-tph 1.358 38.02 0.00 72 0 0 0 54 6 228 0 6 c) AED excursion -13 -8 Envelope loss/gain 114 85 621 257 12 a) Infiltration 0 0 111 32 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 750 200 Subtotal (lines 6 to 13) 114 835 732 489 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 64 37 0 0 14 Subtotal 178 872 732 489 15 Duct loads 16% 36% 28 313 16% 36% 117 175 FFTotal room load 206 1185 849 664 Air required (cfm) 7 52 27 29 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 12 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name WIC 3 BEDROOM 3 2 Exposed wall 6.0 ft 14.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 9.0 x 6.0 ft 15.0 x 14.0 ft 5 Room area 54.0 ft2 210.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 60 60 307 191 140 110 564 350 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 30 0 260 687 W 13A 0.310 s 5.00 3.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 13AB-Ofcs 0.183 w 5.12 3.18 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-Omd 0.408 1.59 1.37 54 54 86 74 210 210 333 287 F 22A-tph 1.358 38.02 0.00 54 6 228 0 210 14 532 0 6 c) AED excursion -6 54 Envelope loss/gain 621 259 1689 1378 12 a) Infiltration 111 32 258 74 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 100 175 Subtotal (lines 6 to 13) 732 390 1948 1627 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 70 59 14 Subtotal 732 390 2018 1687 15 Duct loads 16% 36% 1171 140 16% 36% 322 605 Total room load 849 531 2339 2292 Air required (cfm) 27 231 1 1 741 100 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 13 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1111 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 3 BEDROOM 2 2 Exposed wall 23.0 ft 29.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 109.0 ft 1.0 x 232.0 ft 5 Room area 109.0 ft2 232.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-0fcs 0.183 n 5.12 3.18 150 135 692 430 170 134 687 427 2 glazing, clr low-e 0.310 n 8.68 8.63 15 0 130 130 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 36 0 312 311 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 0 0 0 0 W G 13AB-0fcs 0.183 e 5.12 3.18 80 80 410 255 30 30 154 96 2 glazing, clr low-e 0.310 a 8.68 22.91 0 0 0 0 0 0 0 0 W 13A 0.310 s 5.00 3.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e zing, 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 0 0 0 0 I;;-GCCI 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 01 0 0 0 0 0 t-G0.183 13AB-Ofcs w 5.12 3.18 0 0 0 0 90 90 461 287 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0md 0.408 1.59 1.37 109 109 173 149 232 232 368 317 F 22A-tph 1.358 38.02 0.00 109 23 875 0 232 29 1103 0 6 c) AED excursion -17 -27 Envelope loss/gain 2279 946 3085 1410 12 a) Infiltration 425 122 535 154 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 100 Subtotal (lines 6 to 13) 2704 1068 3620 1664 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 90 77 14 Subtotal 2704 1068 3710 1741 15 Duct loads 16% 36% 431 383 16% 36% 591 625 FF Total room load 3135 1451 4302 2366 Air required (cfm) 100 63F7 137 103 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 14 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S IL .r W III I,y111 1 Right-J® Worksheet Job: AHV 2 Date: Dec 08, 2020 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 2 Exposed wall 0 ft 3 Room height 10.0 ft heat/cool 4 Room dimensions 11.0 x 3.0 ft 5 Room area 33.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AB-OFcs 0.183 n 5.12 3.18 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 2 glazing, clr low-e 0.310 n 8.68 8.63 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 11 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 2 glazing, clr low-e 0.310 n 0.00 0.00 0 0 0 0 W T CG 13AB-Ofcs 0.183 e 5.12 3.18 0 0 0 0 2 glazinq, clr low-e 0.310 e 8.68 22.91 0 0 0 0 0.310 s 5.00 3.00 0 0 0 0 2 glazing, clr low-e 2 glazi g, 0.310 s 0.00 0.00 0 0 0 0 TE� 2 glazing, clr low-e 0.310 s 0.00 0.00 0 0 0 0 2 glazing, clr low-e 0.3101 s 0.00 0.00 0 0 0 0 V�J VLCG 13AB-9fcs 0.183 w 5.12 3.18 0 0 0 0 2 glazing, clr low-e 0.310 w 0.00 0.00 0 0 0 0 C 16X19-Omd 0.408 1.59 1.37 33 33 52 45 F 22A-tph 1.358 38.02 0.00 33 0 0 0 6 c) AED excursion -1 Envelope loss/gain 52 44 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 52 44 Less external load 0 0 Less transfer 0 0 Redistribution -52 -44 14 Subtotal 0 0 15 Duct loads 16% 36% 0 0 Total room load 0 0 Air required (cfm) 0 0 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. - >fit' -Ill wrigl 2020-Dec-0811:36:29 Right -Suite® Universal 201919.0.08 RSU08101 Page 15 �� E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S t-T wrignI Duct System Summary Job: Date AHU 1 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: TINDALL RESIDENCE 11652 ORANGE AVENUE, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 1400 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 1400 cfm 191 ft Dec 08, 2020 Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk DEN c 2258 84 101 1.000 7.0 Ox0 VIFx 45.2 135.0 st6 FOYER h 3571 142 94 1.000 7.0 Ox0 VIFx 47.1 135.0 st6 KITCHEN c 2070 77 93 1.000 7.0 Ox0 VIFx 26.8 115.0 st2 KITCHEN -A c 2070 77 93 1.000 7.0 Ox0 VIFx 20.2 115.0 st2 LIVING/DINING c 3217 121 144 1.000 8.0 Ox0 VIFx 55.7 135.0 st6 LIVING/DINING-A c 3217 121 144 1.000 8.0 Ox0 VIFx 44.3 135.0 st6 LIVING/DINING-B c 3217 121 144 1.000 8.0 Ox0 VIFx 48.7 135.0 st6 M BATH h 3317 132 95 1.000 7.0 Ox0 VIFx 31.4 135.0 st5 M TOILET h 1714 68 33 1.000 5.0 Ox0 VIFx 39.7 135.0 st5 M WIC 1 c 1008 10 45 1.000 6.0 Ox 0 VIFx 17.0 115.0 st 1 M W I C 2 h 2938 117 59 1.000 6.0 Ox 0 VIFx 36.5 135.0 st5 MASTER BEDROOM c 2226 88 100 1.000 7.0 Ox0 VIFx 35.4 135.0 st5 MASTER BEDROOM -A C 2226 88 100 1.000 7.0 Ox0 VIFx 40.6 135.0 st5 MUDROOM c 1109 14 50 1.000 6.0 Ox0 VIFx 14.7 115.0 st1 PANTRY h 2098 84 51 1.000 6.0 Ox0 VIFx 25.9 115.0 st2 POWDER RM c 74 3 3 1.000 4.0 Ox0 VIFx 12.7 115.0 st1 UTILITY R M h 1365 54 52 1.000 6.0 Ox 0 VIFx 13.7 115.0 st 1 - - - - - ift-f"1111111- wrigl 2020-Dec-08 11:36:39 Right-Suite(g) Universal 2019 19.0.08 RSU08101 Page 1 �� ✓ E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st6 Peak AVF 588 627 1.000 798 12.0 0 x 0 VinlFlx st2 st2 Peak AVF 826 863 1.000 807 14.0 0 x 0 VinlFlx st5 Peak AVF 493 387 1.000 904 10.0 0 x 0 VinlFlx st1 st1 Peak AVF 574 537 1.000 731 12.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox0 1400 1400 0 0 0 0 Ox 0 VIFx - -- )ft-1"11111F wrigl ,..,�. � Right-Suite(g) Universal 2019 19.0.08 RSU08101 �� ✓ E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S fz4Pz1E.Z all -I ffiiI WORD Page 2 t-T wrignI Duct System Summary Job: Date AHU 2 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: TINDALL RESIDENCE 11652 ORANGE AVENUE, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 590 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 590 cfm 145 ft Dec 08, 2020 Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 3 h 3135 100 63 1.000 6.0 Ox 0 VIFx 26.0 115.0 st4 BATH 4 c 664 27 29 1.000 5.0 Ox 0 VIFx 15.7 115.0 st3 BEDROOM 2 h 4302 137 103 1.000 7.0 Ox0 VIFx 26.4 115.0 st4 BEDROOM 3 c 2292 74 100 1.000 7.0 Ox0 VIFx 18.4 115.0 st4 BEDROOM 4 h 4550 145 142 1.000 8.0 Ox0 VIFx 11.7 115.0 st3 SINKS 4 c 1185 7 52 1.000 6.0 Ox 0 VIFx 14.2 115.0 st3 TOILET c 556 3 24 1.000 5.0 Ox0 VIFx 14.2 115.0 st3 WIC 3 h 849 27 23 1.000 5.0 Ox0 VIFx 29.6 115.0 st4 WIC h 2239 71 54 1.000 6.0 Ox0 VIFx 13.5 115.0 st3 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st4 Peak AVF 338 289 1.000 765 9.0 0 x 0 VinlFlx st3 Peak AVF 252 301 1.000 681 9.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb 1 Ox 0 590 590 0 0 0 0 Ox 0 VIFx - -- ift-f"1111111- wrigl 2020-Dec-08 11:36:39 .,..,�.,q,,.H.� Right-Suite(g) Universal 201919.0.08 RSU08101 Page 3 �� ✓ E:\Documnets\Wrightsoft HVAC\TINDALL RESIDENCE.rup Calc = MJ8 Front Door faces: S This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.