a Y a FL# FL30310-R1
Application Type Revision
z. Code Version 2020
s:.
Application Status Approved
w
ru
k�
Comments
Archived
Product Manufacturer IKO Industries Ltd
Address/Phone/Email 40 Hansen Road South
Brampton, NON-US L6W 3H4
(905)457-2880 Ext4581
william.liu@iko.com
, Authorized Signature William Liu
william.liu@iko.com
Technical Representative William Liu
Address/Phone/Email 40
Y;. Hansen Road South
Brampton, FL L6W 3H4
6 (416) 525-3740
william.liu@iko.com
Quality Assurance Representative
Address/Phone/Email
Category Roofing
;g Subcategory Asphalt Shingles
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report- Hardcopy Received
r:
r`'+ Florida Engineer or Architect Name who developed the Zachary R. Priest
t Evaluation Report
k : . Florida License PE-74021
Quality Assurance Entity PRI Construction Materials Technologies, LLC
Quality Assurance Contract Expiration Date 12/31/2024
Validated By Steven M. Urich, PE
Validation Checklist- Hardcopy Received
Certificate of Independence FL30310 R1 COI IK019002.2 2020 FBC Eval Shingles final.pdf
Referenced Standard and Year(of Standard) Standard Year
ASTM D 3018 1990
ASTM D 3161 2016
ASTM D 3462 2010
ASTM E 108 2016
TAS 100 1995
TAS 107 2020
hfps://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvH%2bffZfjjpUCSn6k7lpZ96MbxnNUZe3Q76B4ygcSbcE8w%3d%3d 1/2
1/14/2021 Florida Building Code Online
Equivalence of Product Standards
Certified By
Sections from the Code
e
Product Approval Method Method 1 Option D
Date Submitted 10/16/2019
Date Validated 10/23/2020
Date Pending FBC Approval 10/28/2020
��'-- Date Approved v 12/16/2020
FL# Model,Number or Name Description;
30310.1 IKO Shingles ASTM D 3161, Class F asphalt shingles, hip and ridge shingles,
starter strip&shingle strip
Limits of Use Installation Instructions
Approved for use in HVHZ:Yes FL30310 RI II IKO19002.2 2020 FBC Eval Shingles final.pdf
Approved for use outside HVHZ:Yes Verified By: Zachary R. Priest PE-74021
Impact Resistant: N/A Created by Independent Third Party: Yes
Design Pressure: N/A Evaluation Reports
Other: See evaluation report for limits of use. FL30310 R1 AE IK019002.2 2020 FBC Eval Shingles final.pdf
Created by Independent Third Party: Yes
Contact Us::2601 Blair Stone Road,Tallahassee FL 32399 Phone:850-487-1824
R=:
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
x
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to apublic-records request,do not send electronic
mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.*Pursuant to Section 455.275(1),
`s Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if they have one.The emails
provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply a personal address,please
provide the Department with an email address which can be made available to the public.To determine if you are a licensee under Chapter 455,F.S.,please click here.
Product Approval Accepts:
Credit Card
Safe
https://www.floHdabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvH%2bffZfjpUCSn6k71pZ96MbxnNUZe3Q76B4ygcSbcE8w%3d%3d 212
Certificate of Authorization No. 29824
CREEK17520 Edinburgh Dr
Tampa, FL 33647
TECHNICAL SERVICES, LLC (813)480-3421
EVALUATION REPORT FLORIDA BUILDING CODE,fH EDITION(2020)
Manufacturer: IKO INDUSTRIES, LTD Issued October22, 2020
40 Hansen Rd S
Brampton,ON L6W 3H4
Canada
(905)457-2880
www.iko.com
Manufacturing Plants: Calgary,Alberta
Hawkesbury, Ontario
Hillsboro,TX
Kankakee, IL
Sumas,WA
Sylacauga,AL
Toronto, Ontario
Wilmington, DE
Quality Assurance: PRI Construction Materials Technologies(QUA9110)
SCOPE
Category: Roofing
Subcategory: Asphalt Shingles
Code Edition: Florida Building Code,7`"Edition(2020)including High-Velocity Hurricane Zones(HVHZ)
Code Sections: 1504.1.1, 1507.2.5, 1507.2.7.1, 1523.5.1, 1523.6.5.1
Properties: Physical properties,Wind Resistance,Wind Driven Rain
REFERENCES
E02Y Resort No. Standard Year
FM Approvals(TST1867) 3036971 FM 4475 2010
FM Approvals(TST1867) 3040947 FM 4475 2010
ASTM E 108 2016
FM Approvals(TST1867) 3041689 FM 4475 2010
FM Approvals(TST1867) 3044376 FM 4475 2010
FM Approvals(TST1867) 3045254 FM 4475 2010
FM Approvals(TST1867) 3046191 FM 4475 2010
PRI Construction Materials Technologies(TST5878) IKO-050-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-051-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-053-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-067-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-071-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-072-02-02 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-076-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-077-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-088-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-095-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-096-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-099-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-100-02-01 TAS 107 2020
PRI Construction Materials Technologies(TST5878) IKO-114-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-115-02-01 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-117-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-120-02-01 ASTM D 3462 2010A
IKO19002.2 FL30310-R2 Page 1 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES, LLC
Enti Report No. Standard Year
PRI Construction Materials Technologies(TST5878) IKO-121-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-123-02-01 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-125-02-01 TAS 107 2020
ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-126-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-127-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-128-02-01 TAS 107 2020
ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-129-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-130-02-01 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-131-02-01 TAS 107 2020
ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-140-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-148-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-153-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-171-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) I KO-1 71-02-02 TAS 107 2020
ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-171-02-03 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-198-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-198-02-02 TAS 100 2020
PRI Construction Materials Technologies(TST5878) IKO-198-02-03 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-199-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-199-02-02 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-199-02-03 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-201-02-01 ASTM D 3462 2010A
ASTM E 108 2016
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) IKO-201-02-02 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-201-02-07 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-202-02-01 ASTM D 3462 2010A
ASTM E 108 2011
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) IKO-202-02-02 TAS 107 2020
ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-202-02-07 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-203-02-01 ASTM D 3462 2010A
ASTM E 108 2011
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) IKO-203-02-02 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-203-02-07 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-205-02-01 ASTM D 3462 2010A
ASTM E 108 2016
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) IKO-205-02-02 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-205-02-07 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-206-02-01 ASTM D 3462 2010A
ASTM E 108 2016
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) IKO-206-02-02 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) IKO-206-02-07 TAS 100 1995
PRI Construction Materials Technologies(TST5878) IKO-208-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-217-02-01 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) IKO-218-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) 476C0017.1 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476C0017.2 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) 476C0017.3 ASTM E 108 2016
PRI Construction Materials Technologies(TST5878) 476C0020.1 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476C0020.2 ASTM D 3161 2016
IK019002.2 FL30310-R2 Page 2 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES, LLC
Ea!Lty Report No. Standard Year
PRI Construction Materials Technologies(TST5878) 476C0020.3 ASTM E 108 2016
PRI Construction Materials Technologies(TST5878) 476C0033.1 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476C0033.2 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) 476C0033.3 ASTM E 108 2016
PRI Construction Materials Technologies(TST5878) 476T0002 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476T0003 TAS 100 1995
PRI Construction Materials Technologies(TST5878) 476T0004 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) 476T0O12 ASTM D 3462 2010A
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) 476T0013 ASTM D 3161 2016
TAS 107 2020
PRI Construction Materials Technologies(TST5878) 476T0021 ASTM D 3462 2010A
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) 476T0O22 ASTM D 3161 2016
TAS 107 2020
PRI Construction Materials Technologies(TST5878) 476T0023 ASTM E 108 2016
PRI Construction Materials Technologies(TST5878) 476T0034 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476T0039 ASTM D 3462 2010A
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) 476T0O40 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) 476T0041 TAS 100 1995
PRI Construction Materials Technologies(TST5878) 476T0042 ASTM D 3462 2010A
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) 476T0O43 TAS 100 1995
PRI Construction Materials Technologies(TST5878) 476T0044 ASTM D 3462 2010A
ASTM D 3018 1990(R94)E1
PRI Construction Materials Technologies(TST5878) 476T0045 ASTM D 3161 2016
PRI Construction Materials'Technologies(TST5878) 476T0O46 TAS 100 1995
PRI Construction Materials Technologies(TST5878) 476T0057 ASTM D 3462 2010A
PRI Construction Materials Technologies(TST5878) 476T0058 ASTM E 108 2016
PRI Construction Materials Technologies(TST5878) 476T0059 ASTM D 3161 2016
PRI Construction Materials Technologies(TST5878) 476T0O61 ASTM D 7158 2019ael
PRODUCT DESCRIPTION
Roofshake"m HW 13-3/4" x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Sumas) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Shingles shall be used in the non-HVHZ only.
Armourshake"m 18-1/2" x 37-3/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Sumas) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Royal EstateTm 13-1/4" x 40", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Toronto) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Crowne Slate 13-1/4" x 39-1/2", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Toronto) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Shingles shall be used in the non-HVHZ only.
DynastyTm 13-3/4" x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Calgary,Hawkesbury, architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Hillsboro,Kankakee& Shingles manufactured in Calgary and Sumas shall be used in the non-HVHZ only.
Sumas)
Nordic""° 13-3/4" x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Hillsboro&Kankakee) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
IKO19002.2 FL30310-R2 Page 3 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES, LLC
CambridgeTTM 13-3/4" x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Calgary, Hawkesbury, architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Hillsboro,Kankakee, Shingles manufactured in Calgary and Toronto shall be used in the non-HVHZ only.
Sumas,Sylacauga,
Toronto&Wilmington)
CRC Biltmore® 13-3/4"x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Calgary, Hawkesbury, architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Sumas& Toronto) Shingles manufactured in Calgary and Toronto shall be used in the non-HVHZ only.
CRC Regency® 13-3/4" x 40-7/8", ASTM D 3161, Class F self-sealing, fiberglass reinforced, laminated
(Calgary&Hawkesbury) architectural asphalt shingle surfaced with granules complying with ASTM D 3462.
Shingles manufactured in Calgary shall be used in the non-HVHZ only.
CRC Superglass® 13-1/4" x 39-3/8", ASTM D 3161, Class F self-sealing, 3-tab asphalt shingle with
(Calgary,Hawkesbury& fiberglass mat coated on both sides with asphalt and surfaced with granules complying
Toronto) with ASTM D 3462. Shingles manufactured in Calgary and Toronto shall be used in the
non-HVHZ only.
MarathonTTM Plus AR 13-1/4" x 39-3/8", ASTM D 3161, Class F self-sealing, 3-tab asphalt shingle with
(Calgary,Hawkesbury, fiberglass mat coated on both sides with asphalt and surfaced with granules complying
Hillsboro, Kankakee, with ASTM D 3462. Shingles manufactured in Calgary, Sumas and Toronto shall be
Sumas,Sylacauga& used in the non-HVHZ only.
Toronto)
.� Hip&RidgeTTM 12 13-1/4"x 36", ASTM D 3161, Class F fiberglass reinforced, monolayer asphalt hip and
(Kankakee&Sylacauga) ridge shingle surfaced with granules and perforated every 12-inches complying with
ASTM D 3462.
Hip&Ridge Plusih° 13414: x 39-3/8", ASTM D 3161, Class F fiberglass reinforced, monolayer asphalt hip
(Calgary) and ridge shingle surfaced with granules and perforated every 13-inches complying with
ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Hip and RidgeTTM 13-1/4" x 39-3/8", ASTM D 3161, Class F fiberglass reinforced, monolayer asphalt hip
(Sumas) and ridge shingle surfaced with granules and perforated every 10-inches complying with
ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Armour StarterTm 13-1/4"x 39-3/8", ASTM D 3161, Class F fiberglass reinforced asphalt strip embedded
(Sumas) with granules complying with ASTM D 3462. For use with ArmourshakeTM shingles.
Leading Edge PlusTM 7-7/8" x 40-7/8", ASTM D 3161, Class F fiberglass reinforced, monolayer asphalt
(Hawkesbury) shingle strip surfaced with granules complying with ASTM D 3462.
IK019002.2 FL30310-R2 Page 4 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES, LLC
-..---._....__.._...__. �.._.._.._..._ _..........._.___...._...........——_._........—._..........—.._........_.—_._.....__�._........_._.._............ -— ........._..._.._
i Dynasty i-Basic Wind Spee.,,.it._ Max. 194 m h
—..._ ......._.—...p..._—.._..........--............--..........
(Calgary(Non-HVHZ), 1 Basic Wind Speed -asd)� Max_ 150 mph ....... ----- --
I—'...__. .._..........._—_..._...................__ i
Oil i Hawkesbury, Kankakee& ; Deck(HVHZ): In accordance with FBC requirements;
Sumas(Non-HVHZ)) Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
and construction.
...................._._.....—_...........---....._
-- --
; Deck Non-HVHZ)_ w.Solidly sheathed in accordance with FBC requirements.
NordicTm
Under--ment: ....�.... In accordance with FBC requirements
(Kankakee) Min.slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
and —� — ' shingles at slopes greater than 21:12. . i
I1....... .. _.__ _..-- -._.._.._........--------
Installation(HVHZ): Installed with 5-7/8 in. exposure in accordance with RAS
CRC Regency® 115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
; below. ...............—......_......... -.--.._....._..---------i
Installation (Non-HVHZ): Installed with 5-7/8 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either"4 Nail
Pattern"or"6 Nail Pattern"detailed below.
_--------._._................_.....---- - ----—--....._.._—_.........-— - --........_. —.__......_...—-...._..__
i
1-1J4" ArmourZone
i ArmourZone -�
Standard Application
Requires 4 Mails/Fasteners :?�:'•\ 3
I Common Bond
j - ------------ ------------ ------------ --
--------------------------------------------
ArmourZone
r7 r7 r7
5-7/6"
I
Figure 7. DynaStyTM and NordicT""
4 Nail Pattern (non-HVHZ on ...........—...........—...............—........._—.....-.........._.....
i ld/4"
! 1-1/4• ArmourZone
!� ArmourZone
i Steep Slope/High Wind Applications ;
Requires 6 Nails/Fasteners
`•\ Common Bond
I E
1 \ \
_- __ \• \.
/--.
___---__-_ -___-_----_
ArmourZone
[17
5-7/8"
I
Figure 8. DynaStyTM and NordicTT°
6 Nail Pattern
IKO19002.2 FL30310-R2 Page 9 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEKIKO INDUSTRIES,LTD
j� Asphalt Shingles
TECHNICAL SERVICES, LLC
_.__...._._..._._—....._..._�__._.._._.. -._...._ ._......_T......_.—._........._._�_.............�.............�_......._._... _...._.._......_ .__........_.-.-_._._.........................._.......--:
Hip&Ridge 12 ; Basic Wind Speed�Vuit) -Max. 194 mph__
✓1 _.. _..—........._......... .................._.........__.._..__,
(Kankakee&Sylacauga) ( Basic Wind Seed Vasd): i Max. 150 mph _
--------------.... -.._........._.__ ...................._...........
Deck(HVHZ): In accordance with FBC requirements; Solidly sheathed
and ! min. 19/32 in. plywood or wood plank for new construction;
j Min_15/32 in_plywood existing construction. i
i............_—._...._..._...
Hip&Ridge PIusTM' ! Deck Non-HVHZ Solidly sheathed in accordance with FBC requirements.
....._._.._�__._......_— I........._ ......._...�y . 9
---------- requirements.
j (Calgary) ...............�..........�... T.__...-- _......._._ ..._.._.........._..........
(non-HVHZ only) Min.slope: i 2:12 and in accordance with FBC requirements j
Installation: I Installed with 5-5/8 inch exposure in accordance with the
FBC and manufacturer's published installation instructions.
I The direction of the exposed end shall be away from the
- --..... P...revailing..wind.
I _....- ----........_ I
[ Perforation Marks
( Direction of prevailing wind
stw
t —
hiceprea-
X!
AUM ,... loom .r. 49M ,...
I -
i 111
's
Nails
1 1
1 i
� t 100
� 1 1
1"Taper Cut �
1 6-1/4"
1
Figure 13. Hip&Ridge TM 12 and 's
Hip&Ridge PIusTM (non-HVHZ only)__ __—..._..........._._._
IK019002.2 FL30310-R2 Page 12 of 15
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES, LLC
_—.......-_�--.............. -- ........... ._..........--..........-....-...............-......................—.._............—.............._—........................-.---
Armour StarterTM' Basic.Wind_Speed (V„i!)-_Max. 194 mph . ......_........... ............ ---------.
(Sumas) i Basic Wind Spee�Vas _ Max. 150 mph _
- ... ..._..............�.................... _._._...................................
_!
l € Deck(HVHZ): In accordance with FBC requirements; Solidly sheathed
1 mina 19/32 in. plywood or wood plank for new construction;
-- ---......... __._._. .._Min. 15/32 in..... I— .. — --_....— _....--......I?-ywood existing construction
Deck(Non—HVHZ)_ Solidly_sheathed in accordance with FBC requirements.
—......_
Underlayment; _ In accordance with FBC requirements ___ _
I f Min.sl .. FBC requirements.—.._._.._—.._._... _ .............
..................
Installation: Installed in accordance with the FBC and manufacturer's
published installation instructions. Shall be attached with
E ; min. 1"x 12 ga�roofng nails with min.3/8-inch head.
Standard Application Requires 4 Nails/Fasteners
i
l
I. Match Color
I STARTER COURSE to Selected
1" and 13" from Each End Armourshake
Shingle
Figure 15.Armour Starter'
F----..-..._..........._.-......--...-.._.............._.__. ......................____-............--...................__..._.—_....................__................—...........--............—..........._....--.........�.y........................_-r.._.._....,
Leading Edge PIUSTM : Basic Wind Speed (V„It : Max.-194 Tph _...._. .-.........—__.._....-.. ..............__.........................._................— ....._ —
(Hawkesbury) Basic Wind Speed (Vasa)__:..Max. 150 mph—.._......_ ..............._._............... — ........-.- _.-..__......... i
_..................�_ T_.�. q y
Deck HVHZ : i In accordance with FBC requirements; Solidi sheathed
U-+
1 t
min. 19/32 in. plywood or wood plank for new construction;
____ Min. 15/32 in. plywood existing construction.
-...-.-. ...
I Dec.
Underlayment: _ In accordance with FBC requirements. i
_ _.. --........ .--.....--
Min.sloped _ 12:12 and in accordance with FBC re_uirements. _
�.._................. __ �.-_....-. --
Installation: ! Installed in accordance with the FBC and manufacturer's j
published installation instructions. Shall be attached with
' min. 1"x 12 ga_roofing nails with min.3/8-inch head.
-_._..............-_._ ._...._—.................... ....
Standard Application
Requires 4 Nails/Fasteners '
1'from Each End
I
i + I
i
I
!
j 3'to 4"from Bottom
Figure 16. Leading Edge Plus'""
__ ........................-.._...----..._....-...._-___._._._ _..- __...-....._ ._.._..---._...__.—_-........._. ---.._. ..................—.--..........
......_
IK019002.2 FL30310-R2 Page 14 of 15
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK IKO INDUSTRIES,LTD
Asphalt Shingles
TECHNICAL SERVICES,LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 ft in the HVHZ.
4) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
5) Shingles shall be installed starting at the eave in horizontal layers such that the laps shed water from the
deck.
6) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
7) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 7t" Edition (2020) including High-Velocity Hurricane Zones(HVHZ)as evidenced in the referenced documents
submitted by the named manufacturer.
t11111111111,,% 2020.10.22
RV R. p
C E N S��FcS�j!��
/ 14:10:00
No 74021
� 7[ � .1. = OkltetlY 9neE bYLW'Yfl PMt..... -04I 001
13 STATE OF :�44/44/
ZacharyR. Priest, P.E.
'iO �,< 0 R O N�,�` Florida Registration No.74021
0NA�E �� Organization No.ANE11669
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire,a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
IKO19002.2 FL30310-R2 Page 15 of 15
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.