Loading...
HomeMy WebLinkAbout03-12-2021 William-Carolyn Harper-final04/06/2021 E-1 1 OF 3GENERATORADDITION RISERDIAGRAMNEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951NTS 1 GENERATOR ADDITION RISER DIAGRAM DATEREVISIONMARKDATE: SHEET DATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911SCOPE OF WORK: ·INSTALL 200AMP NON-SE RATED ATS NEXT TO UTILITY METER/MAIN ON EXTERIOR WALL. ·RE-FEED INTERIOR SUB-PANEL FROM NEW ATS. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANEL IF REQUIRED. ·UTILIZE A PRE-FABRICATED GENERATOR PAD. ·RELOCATE EXISTING A/C UNIT CIRCUIT FROM METER/MAIN TO INTERIOR SUB-PANEL SO IT IS BACKED UP BY THE GENERATOR SYSTEM. ·PROVIDE AND INSTALL (1) 22kW GENERAC GENERATOR. ·PROVIDE AND INSTALL CONDUIT AND CONDUCTORS FROM ATS TO GENERATOR. ·PROVIDE (1) LOAD SHED DEVICES PER SIZING DATA THIS SHEET. ·NEW LP TANK TO BE PROVIDED AND INSTALLED BY FERRELLGAS UNDER A SEPARATE PERMIT. ·NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS SCOPE OF WORK. GENERAL NOTES: 1. 2. LIGHT LINE WORK REPRESENTS EXISTING TO REMAIN. DARK AND RED LINE WORK REPRESENT NEW EQUIPMENT, CONDUIT, AND WIRE. ELECTRICAL LEGEND: SURFACE MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD FLUSH MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD SURFACE MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD FLUSH MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD UTILITY METER CAN OR METER/MAIN COMBO UNIT GENERATOR AND GENERATOR PAD GAS STORAGE TANK SURFACE MOUNT AUTOMATIC TRANSFER SWITCH NON-FUSED DISCONNECT FUSED DISCONNECT 30AR NF 3R FRAME SIZE NEMA RATING NON FUSED 30AR 30AF 3R FRAME SIZE NEMA RATING FUSE SIZE POINT OF NEW CONNECTION AC ALTERNATING CURRENT A/C AIR CONDITIONING AFG ABOVE FINISHED GRADE AL ALUMINUM (CONDUCTOR) AHU AIR HANDLING UNIT ATS AUTOMATIC TRANSFER SWITCH AMP AMPERE AFCI ARC FAULT CIRCUIT INTERRUPTER ANSI AMERICAN NATIONAL STANDARDS INSTITUTE C CONDUIT CU COPPER (CONDUCTOR) COVB CITY OF VERO BEACH DC DIRECT CURRENT DISC DISCONNECT EXIST EXISTING FPL FLORIDA POWER & LIGHT G GROUND GFCI GROUND FAULT CIRCUIT INTERRUPTER IRC INDIAN RIVER COUNTY KVA KILOVOLT AMPERE KW KILOWATT MC METAL CLAD CABLE MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANELBOARD MTS MANUAL TRANSFER SWITCH MSB MAIN SWITCHBOARD MLO MAIN LUGS ONLY NEC NATIONAL ELECTRICAL CODE NIC NOT IN CONTRACT NTS NOT TO SCALE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NFPA NATIONAL FIRE PROTECTION ASSOCIATION NON-SE NON SERVICE ENTRANCE RATED PLCS PLACES (QUANTITY) PNL PANEL PVC POLYVINYL CHLORIDE CONDUIT RMC RIGID METAL CONDUIT RTU ROOF TOP UNIT SE SERVICE ENTRANCE RATED TYP TYPICAL TEMP TEMPORARY TRANS, TX TRANSFORMER UG UNDERGROUND UL UNDERWRITERS LABORATORY UON UNLESS OTHERWISE NOTED V VOLT VA VOLT AMPERE W WATT XFMR TRANSFORMER ABBREVIATIONS: NATURAL GAS METER (SOME SYMBOLS SHOWN MAY NOT PERTAIN TO THIS PROJECT) GROUND ROD EXISTING 200 AMP METER/MAIN 120/240 1Ø NEW 200 AMP GENERAC NON-SE RATED ATS 100AMP BREAKER NEW GENERATOR: AIR COOLED GENERAC 22KW GRADE ATTIC ATTIC GRADE E EXISTING WATER LINE INTERIOR EXTERIOR INTERIOR EXTERIOR EXTERIOR INTERIOR EXTERIOR INTERIOR FINISHED FLOOR B A EXISTING 200 AMP SUB-PANEL BF C D C EXISTING (2) 5/8" X 8' CU GROUND RODS CONDUIT AND WIRE SCHEDULE SYMBOL DESCRIPTION EXISTING 2"PVC UNDERGROUND SERVICE FEEDER EXISTING 1/2"PVC W/ (1) #4 BARE CU EXISTING 2"PVC SLEEVE W/ (1) #4/0 SER AL CABLE EXISTING #4/0 SER AL CABLE 2-1/2"PVC W/ (6) #4/0 THWN AL, (1) #6 THHN CU GROUND 1-1/4"PVC SLEEVE W/ GENERAC CABLE W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND, (5) #14THHN CU 1-1/4"PVC W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND 3/4"PVC W/ (7) #14 THHN CU 1/2"PVC W/ (1) #4 BARE CU A B C D E F G H I NOTE: NOT ALL CONDUIT AND WIRE SHOWN ON THIS SCHEDULE MAY PERTAIN TO THIS PROJECT. LOAD MANAGEMENT "LCM" LOAD SHED LOAD MANAGEMENT TECHNOLOGY ALLOWS THE LOAD CONTROL MODULE TO MONITOR GENERATOR PERFORMANCE AND ONLY SHED LOADS WHEN ABSOLUTELY NECESSARY BY MONITORING GENERATOR CURRENT AND FREQUENCY. BY ONLY SHEDDING THE NONESSENTIAL CIRCUITS, THE ESSENTIAL CIRCUITS ARE ALWAYS POWERED. LOADS ARE SHED THROUGH INTERRUPTION OF INDIVIDUAL CONTROL CIRCUITS (AHU/AC) AND POWER CIRCUITS (RANGE AND WATER HEATER). GENERAL NOTES: ·THE ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL SERVICE ROUGH IN AND INSTALLATION DETAIL WITH THE LOCAL UTILITY POWER COMPANY. ·THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION (2020), LOCAL ORDINANCE, AND THE NATIONAL ELECTRIC CODE NFPA 70 (2017). ·ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A NEAT AND CRAFTSMAN LIKE MANNER BY PERSONS SKILLED IN THE ELECTRICAL TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER ELECTRICIAN LICENSED IN THE STATE OF FLORIDA. ·THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SECURELY SUPPORTED AND FASTENED, WITH WORKING SPACE PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 110.26 SPACES ABOUT ELECTRICAL EQUIPMENT. ·PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, IN OR BELOW CONCRETE AND WHERE EXPOSED NOT SUBJECT TO DAMAGE. PVC SCHEDULE 80 CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE. ·ALL MATERIAL SHALL BE NEW, FREE FROM DEFECT AND SHALL BE LISTED AND BEAR THE LABEL OF A RECOGNIZED TESTING LABORATORY. ·GROUNDING PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 250 GROUNDING AND BONDING. ·STANDBY SYSTEM INSTALLATION PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 702 OPTIONAL STANDBY SYSTEMS, AND MANUFACTURER INSTALLATION INSTRUCTIONS.F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:02 AM GROVE COURTCLAC EXISTING SUB-PANEL EXISTING UTILITY METER NEW ATS 3'-0" 10'-0" 10'-0" NEW GENERATOR AND PAD NEW 500 GAL. LP TANK (BY OTHERS)COVEREDPATIOCOVEREDENTRYPROPERTY LINE 165.00'PROPERTY LINE 50.00'PROPERTY LINE 149.17'PROPERTY LINE 19.01'PROPERTY L INE18.69 'PROPERTY L INE16.80 ' DRIVEWAY GARAGE SINGLE FAMILY RESIDENCE 3604 GROVE COURT FORT PIERCE, FL. 34951 04/06/2021 2 OF 3GENERATORSITE PLANDATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 00019111" = 10'-0" 1 GENERATOR SITE PLAN DATEREVISIONMARKDATE: SHEET N W S E E-2 0'2.5'5'10'20' SCALE: 1" = 10'-0"NEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:42 AM 04/06/2021 3 OF 3 DATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911DATEREVISIONMARKDATE: SHEET E-3PRE-FABRICATEDGENERATORPAD DETAILNO SCALE 1 PRE-FABRICATED GENERATOR PAD DETAIL NEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:55 AM