HomeMy WebLinkAbout03-12-2021 William-Carolyn Harper-final04/06/2021
E-1
1 OF 3GENERATORADDITION RISERDIAGRAMNEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951NTS
1 GENERATOR ADDITION RISER DIAGRAM DATEREVISIONMARKDATE:
SHEET DATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911SCOPE OF WORK:
·INSTALL 200AMP NON-SE RATED ATS NEXT TO UTILITY METER/MAIN ON EXTERIOR
WALL.
·RE-FEED INTERIOR SUB-PANEL FROM NEW ATS. SEPARATE NEUTRALS AND
GROUNDS IN SUB-PANEL IF REQUIRED.
·UTILIZE A PRE-FABRICATED GENERATOR PAD.
·RELOCATE EXISTING A/C UNIT CIRCUIT FROM METER/MAIN TO INTERIOR
SUB-PANEL SO IT IS BACKED UP BY THE GENERATOR SYSTEM.
·PROVIDE AND INSTALL (1) 22kW GENERAC GENERATOR.
·PROVIDE AND INSTALL CONDUIT AND CONDUCTORS FROM ATS TO GENERATOR.
·PROVIDE (1) LOAD SHED DEVICES PER SIZING DATA THIS SHEET.
·NEW LP TANK TO BE PROVIDED AND INSTALLED BY FERRELLGAS UNDER A
SEPARATE PERMIT.
·NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS
SCOPE OF WORK.
GENERAL NOTES:
1.
2.
LIGHT LINE WORK REPRESENTS EXISTING TO REMAIN.
DARK AND RED LINE WORK REPRESENT NEW
EQUIPMENT, CONDUIT, AND WIRE.
ELECTRICAL LEGEND:
SURFACE MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD
FLUSH MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD
SURFACE MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD
FLUSH MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD
UTILITY METER CAN OR METER/MAIN COMBO UNIT
GENERATOR AND GENERATOR PAD
GAS STORAGE TANK
SURFACE MOUNT AUTOMATIC TRANSFER SWITCH
NON-FUSED DISCONNECT
FUSED DISCONNECT
30AR
NF 3R
FRAME SIZE
NEMA RATING
NON FUSED
30AR
30AF 3R
FRAME SIZE
NEMA RATING
FUSE SIZE
POINT OF NEW CONNECTION
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AFG ABOVE FINISHED GRADE
AL ALUMINUM (CONDUCTOR)
AHU AIR HANDLING UNIT
ATS AUTOMATIC TRANSFER SWITCH
AMP AMPERE
AFCI ARC FAULT CIRCUIT INTERRUPTER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
C CONDUIT
CU COPPER (CONDUCTOR)
COVB CITY OF VERO BEACH
DC DIRECT CURRENT
DISC DISCONNECT
EXIST EXISTING
FPL FLORIDA POWER & LIGHT
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IRC INDIAN RIVER COUNTY
KVA KILOVOLT AMPERE
KW KILOWATT
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANELBOARD
MTS MANUAL TRANSFER SWITCH
MSB MAIN SWITCHBOARD
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NON-SE NON SERVICE ENTRANCE RATED
PLCS PLACES (QUANTITY)
PNL PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
SE SERVICE ENTRANCE RATED
TYP TYPICAL
TEMP TEMPORARY
TRANS, TX TRANSFORMER
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERE
W WATT
XFMR TRANSFORMER
ABBREVIATIONS:
NATURAL GAS METER
(SOME SYMBOLS SHOWN MAY NOT PERTAIN TO THIS PROJECT)
GROUND ROD
EXISTING
200 AMP
METER/MAIN
120/240 1Ø
NEW
200 AMP
GENERAC
NON-SE
RATED
ATS
100AMP
BREAKER
NEW GENERATOR:
AIR COOLED
GENERAC 22KW
GRADE
ATTIC ATTIC
GRADE
E
EXISTING
WATER LINE
INTERIOR EXTERIOR
INTERIOR EXTERIOR
EXTERIOR INTERIOR
EXTERIOR INTERIOR
FINISHED FLOOR
B A
EXISTING
200 AMP
SUB-PANEL
BF
C
D
C
EXISTING (2) 5/8" X 8'
CU GROUND RODS
CONDUIT AND WIRE SCHEDULE
SYMBOL DESCRIPTION
EXISTING 2"PVC UNDERGROUND SERVICE FEEDER
EXISTING 1/2"PVC W/ (1) #4 BARE CU
EXISTING 2"PVC SLEEVE W/ (1) #4/0 SER AL CABLE
EXISTING #4/0 SER AL CABLE
2-1/2"PVC W/ (6) #4/0 THWN AL, (1) #6 THHN CU GROUND
1-1/4"PVC SLEEVE W/ GENERAC CABLE W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND,
(5) #14THHN CU
1-1/4"PVC W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND
3/4"PVC W/ (7) #14 THHN CU
1/2"PVC W/ (1) #4 BARE CU
A
B
C
D
E
F
G
H
I
NOTE:
NOT ALL CONDUIT AND WIRE SHOWN ON THIS SCHEDULE MAY PERTAIN TO THIS PROJECT.
LOAD MANAGEMENT
"LCM" LOAD SHED
LOAD MANAGEMENT TECHNOLOGY ALLOWS THE LOAD CONTROL MODULE TO MONITOR GENERATOR PERFORMANCE AND
ONLY SHED LOADS WHEN ABSOLUTELY NECESSARY BY MONITORING GENERATOR CURRENT AND FREQUENCY. BY ONLY
SHEDDING THE NONESSENTIAL CIRCUITS, THE ESSENTIAL CIRCUITS ARE ALWAYS POWERED. LOADS ARE SHED THROUGH
INTERRUPTION OF INDIVIDUAL CONTROL CIRCUITS (AHU/AC) AND POWER CIRCUITS (RANGE AND WATER HEATER).
GENERAL NOTES:
·THE ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL SERVICE ROUGH IN AND INSTALLATION
DETAIL WITH THE LOCAL UTILITY POWER COMPANY.
·THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION (2020), LOCAL
ORDINANCE, AND THE NATIONAL ELECTRIC CODE NFPA 70 (2017).
·ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A NEAT AND CRAFTSMAN LIKE MANNER BY
PERSONS SKILLED IN THE ELECTRICAL TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER ELECTRICIAN
LICENSED IN THE STATE OF FLORIDA.
·THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SECURELY SUPPORTED AND
FASTENED, WITH WORKING SPACE PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 110.26 SPACES ABOUT ELECTRICAL
EQUIPMENT.
·PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, IN OR BELOW CONCRETE AND WHERE EXPOSED NOT
SUBJECT TO DAMAGE. PVC SCHEDULE 80 CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE.
·ALL MATERIAL SHALL BE NEW, FREE FROM DEFECT AND SHALL BE LISTED AND BEAR THE LABEL OF A RECOGNIZED
TESTING LABORATORY.
·GROUNDING PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 250 GROUNDING AND BONDING.
·STANDBY SYSTEM INSTALLATION PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 702 OPTIONAL STANDBY SYSTEMS,
AND MANUFACTURER INSTALLATION INSTRUCTIONS.F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:02 AM
GROVE COURTCLAC
EXISTING
SUB-PANEL
EXISTING UTILITY
METER
NEW ATS
3'-0"
10'-0"
10'-0"
NEW GENERATOR
AND PAD
NEW 500 GAL.
LP TANK
(BY OTHERS)COVEREDPATIOCOVEREDENTRYPROPERTY LINE 165.00'PROPERTY LINE 50.00'PROPERTY LINE 149.17'PROPERTY LINE 19.01'PROPERTY L
INE18.69
'PROPERTY L
INE16.80
'
DRIVEWAY
GARAGE
SINGLE FAMILY
RESIDENCE
3604 GROVE COURT
FORT PIERCE, FL. 34951
04/06/2021
2 OF 3GENERATORSITE PLANDATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 00019111" = 10'-0"
1 GENERATOR SITE PLAN DATEREVISIONMARKDATE:
SHEET
N
W
S
E
E-2
0'2.5'5'10'20'
SCALE: 1" = 10'-0"NEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:42 AM
04/06/2021
3 OF 3 DATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911DATEREVISIONMARKDATE:
SHEET
E-3PRE-FABRICATEDGENERATORPAD DETAILNO SCALE
1 PRE-FABRICATED GENERATOR PAD DETAIL NEW GENERATOR FOR:WILLIAM & CAROLYN HARPER3604 GROVE COURTFORT PIERCE, FL. 34951F:\GENERATOR DRAWINGS\03-12-2021 William-Carolyn Harper\03-12-2021 William-Carolyn Harper.dwg, 4/6/2021 9:19:55 AM