As requested, we tested the compacted fill for the Pad.
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
KSM JOB # : 213180-1d/JM/bm
To determine if the fill was properly compacted on the pad to a depth of 3 feet, we performed nucleardensity
tests on the top two feet. To estimate the soil density below a depth of 2 feet we used a Static Cone
Penetrometer. During the tests, a shaft with a conical point is pushed through soil and the soil resistance
measured on a calibrated gauge. After the soil resistance is measured, the hole is advanced with a hand -auger in
1-foot increments to permit a continuation of measurement of density versus depth. Test Results:
Nuclear density tests performed on the top 2 feet indicates the compaction exceeds the project specifications of
95% (ASTM 1557). Static Cone Penetrometer readings indicate the compacted backfill
below 2 feet are generally well compacted to a depth of 3 feet.
Based on the nuclear density tests and Static Cone Penetrometer readings, it appears the fill on the house pad
was properly compacted.
Should you have any questions, please feel free to contact our office.
Respectfully,
This item has been electronically signed and
sealed by Bryan E. Dahlke, PE FL. Lic. 81439
on the date stated directly to the right using
a digital signature.
Printed copies of this documents are not
considered signed and sealed and the
signature must be verified on any electronic
copies.
Bryan E. Dahlke, P.E. V.P. of Engineering
PE# 81439 04/29/21
Email: TrefelnerJ@bellsouth.net
Digitally
signed by
Bryan E Dahlke
Date:
2021.04.29
13:27:03
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
Proudly Serving Florida since 1990
Certified Women Owned Business - WBE
Headquarters
1W C IL
� ENGINEERING
Mailing
11345 U.S. Highway 1
PO Box 78-1377
Sebastian, FL. 32958
&J XW% AND TESTING Sebastian, FL. 32978
Orlando
Phone:
772-589-0712
723 Progress Way
SOIL COMPACTION REPORT
C.A.# 5693
Sanford, FL. 32771
ASTM D 1557 and ASTM D 6938 KSMengineering.net
DATE TESTED:
April 28, 2021
KSM JOB #:
213180-1d/JM/bm
NUC #
215
PERMIT #:
2102-0679
Nuc Model:
MC-IDR-P
Nuc Serial #:
MD80404215
CONTRACTOR:
James Trefelner
JOB LOCATION:
5785 Hickory Drive
Fort Pierce, Florida
ITEM TESTED:
Compacted Foundation Fill - Pad
TEST LOCATION
PEN
DRY MAX. DRY
PERCENT
DEPTH
OF SAMPLE
READ
DENSITY PROCTOR VALUE (P.C.F)
COMPACTION
1 S. E.
0" - 12" 17D
117.3 119.7
98.0%
2 Center
18D
118.8
99.2%
3 N.W.
17D
117.8
98.4%
4 S.W.
16D
116.1
97.0%
5 N.E.
18D
119.0
99.4%
6 S.W.
12" - 24" 18D
118.0
98.6%
7 N.E.
17D
117.9
98.5%
Soil Description:
121.0 I I I I I
I I 1
Clayed Brown Sand with
W
Traces of Shell Fragments
E 120.0 I I I I I
I I I
In Place Moisture:
I I I I I I
I I
G I I I I
I I I
I I I I I
I I I
Proctor Optimum Moisture:
T
118.0—..1..—I..—.I.—.. 1..—I..—.
_..L_.._
10.7%
P I I I I I
I I I
Proctor Max. Dry Density: P.C.F.
117.0..+..-1..—.—..�..+..-1._.—..�.._
1.
119.7
C
I I I I I
I I I
@ Test Locations the Density
&
Frt.._ .—.1.—..r..rt..-1.._.1._..r.._
116.0
Penetrometer readings indicate the
I I I I I
I I I
Degree of Compaction Meets
115.0
Minimum Requirement
D 1 1 1
I I
for Staked Foundation
R I I I I I
114.0—..rt..—;..—.;.—..�..�..—;.._.;.—..�..�
I I I
Respectfully Submitted:
Y 5 6 7 8 9 10
11 12 13 14
Moisture - % of Dry
Weight
Disclaimer: Contractor is responsible to maintain the tested area
in the condition that KSM completed the indicated passed
compaction test. KSM is not responsible if the tested area has
been altered from the approved inspected condition.
Bryan E. Dahlke, P.E. V.P. of Engineering
PE # 81439 4/29/2021