HomeMy WebLinkAbout213180-1d Compaction - signedHeadquarters 11345 U.S. Highway 1 Sebastian, FL. 32958 Orlando 723 Progress Way Sanford, FL. 32771 April 29, 2021 CONTRACTOR: JOB LOCATION: PERMIT #: To Whom it may concern, tl 10 1 t ENGINEERING i11.7jVi AND TESTING James Trefelner 1760 Copenhaver Road Ft. Pierce, Florida 34945 5785 Hickory Drive Fort Pierce, Florida 2102-0679 As requested, we tested the compacted fill for the Pad. Mailing PO Box 78-1377 Sebastian, FL. 32978 Phone: 772-589-0712 C.A.# 5693 KSMengineering.net KSM JOB # : 213180-1d/JM/bm To determine if the fill was properly compacted on the pad to a depth of 3 feet, we performed nucleardensity tests on the top two feet. To estimate the soil density below a depth of 2 feet we used a Static Cone Penetrometer. During the tests, a shaft with a conical point is pushed through soil and the soil resistance measured on a calibrated gauge. After the soil resistance is measured, the hole is advanced with a hand -auger in 1-foot increments to permit a continuation of measurement of density versus depth. Test Results: Nuclear density tests performed on the top 2 feet indicates the compaction exceeds the project specifications of 95% (ASTM 1557). Static Cone Penetrometer readings indicate the compacted backfill below 2 feet are generally well compacted to a depth of 3 feet. Based on the nuclear density tests and Static Cone Penetrometer readings, it appears the fill on the house pad was properly compacted. Should you have any questions, please feel free to contact our office. Respectfully, This item has been electronically signed and sealed by Bryan E. Dahlke, PE FL. Lic. 81439 on the date stated directly to the right using a digital signature. Printed copies of this documents are not considered signed and sealed and the signature must be verified on any electronic copies. Bryan E. Dahlke, P.E. V.P. of Engineering PE# 81439 04/29/21 Email: TrefelnerJ@bellsouth.net Digitally signed by Bryan E Dahlke Date: 2021.04.29 13:27:03 Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting Proudly Serving Florida since 1990 Certified Women Owned Business - WBE Headquarters 1W C IL � ENGINEERING Mailing 11345 U.S. Highway 1 PO Box 78-1377 Sebastian, FL. 32958 &J XW% AND TESTING Sebastian, FL. 32978 Orlando Phone: 772-589-0712 723 Progress Way SOIL COMPACTION REPORT C.A.# 5693 Sanford, FL. 32771 ASTM D 1557 and ASTM D 6938 KSMengineering.net DATE TESTED: April 28, 2021 KSM JOB #: 213180-1d/JM/bm NUC # 215 PERMIT #: 2102-0679 Nuc Model: MC-IDR-P Nuc Serial #: MD80404215 CONTRACTOR: James Trefelner JOB LOCATION: 5785 Hickory Drive Fort Pierce, Florida ITEM TESTED: Compacted Foundation Fill - Pad TEST LOCATION PEN DRY MAX. DRY PERCENT DEPTH OF SAMPLE READ DENSITY PROCTOR VALUE (P.C.F) COMPACTION 1 S. E. 0" - 12" 17D 117.3 119.7 98.0% 2 Center 18D 118.8 99.2% 3 N.W. 17D 117.8 98.4% 4 S.W. 16D 116.1 97.0% 5 N.E. 18D 119.0 99.4% 6 S.W. 12" - 24" 18D 118.0 98.6% 7 N.E. 17D 117.9 98.5% Soil Description: 121.0 I I I I I I I 1 Clayed Brown Sand with W Traces of Shell Fragments E 120.0 I I I I I I I I In Place Moisture: I I I I I I I I G I I I I I I I I I I I I I I I Proctor Optimum Moisture: T 118.0—..1..—I..—.I.—.. 1..—I..—. _..L_.._ 10.7% P I I I I I I I I Proctor Max. Dry Density: P.C.F. 117.0..+..-1..—.—..�..+..-1._.—..�.._ 1. 119.7 C I I I I I I I I @ Test Locations the Density & Frt.._ .—.1.—..r..rt..-1.._.1._..r.._ 116.0 Penetrometer readings indicate the I I I I I I I I Degree of Compaction Meets 115.0 Minimum Requirement D 1 1 1 I I for Staked Foundation R I I I I I 114.0—..rt..—;..—.;.—..�..�..—;.._.;.—..�..� I I I Respectfully Submitted: Y 5 6 7 8 9 10 11 12 13 14 Moisture - % of Dry Weight Disclaimer: Contractor is responsible to maintain the tested area in the condition that KSM completed the indicated passed compaction test. KSM is not responsible if the tested area has been altered from the approved inspected condition. Bryan E. Dahlke, P.E. V.P. of Engineering PE # 81439 4/29/2021 Email to: TrefelnerJ@bellsouth.net Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting Proudly Serving Florida since 1990 Certified Women Owned Business - WBE