HomeMy WebLinkAboutMansard Screen EnclosureDESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS 1. THE 2020 FLORIDA BUILDING CODE, SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CH. 23 WOOD. 2. AA ASM 35 & SPECIFICATIONS FOR ALUMINUM STRUCTURES, PART 1-A OF THE ALUMINUM DESIGN MANUAL PREPARED BY THE ALUMINUM ASSOCIATION, INC. WASHINGTON D.C. 2005 ED. 3. ASCE 7-16 & SE17 4. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 5. AC1318 CONCRETE REFERENCE MANUAL. WIND LOADS 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS ' REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: B 3. WIND LOADS PER FBC TABLE 2002.4 (MWFRS) 4 VULT = 150 MPH & EXPOSURE = B FOR 20 X 20 X 0.013" MESH SCREEN HORIZONTAL PRESSURES ON WINDWARD SURFACES = 31 PSF HORIZONTAL PRESSURES ON LEEWARD SURFACES = 32 PSF VERTICAL PRESSURES ON SCREEN SURFACES = 9 PSF VERTICAL PRESSURES ON SOLID SURFACES = 25 PSF FOR 18 X 14 X 0.013" MESH SCREEN, APPLIED FACTOR = .88 FOR ALLOWABLE STRESS DESIGN, APPLIED FACTOR = •6 FOUNDATION DESIGN FOOTING SIZE EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE -SLAB IS PROVIDED -IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM WxW W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. MISCELLANEOUS 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. FASTENER SPECIFICATIONS 1. FASTENERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG. SPECIFICATIONS) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, FASTENERS AND SCREENS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1 /4" X 3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1 /4" X 2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14 X 2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE # 10 X 1-1 /2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE 1"X2" INSTALLED THROUGHOUT AN "OPEN VIEW' SPACING SHALL BE REDUCED TO 18" O.C. AND 6' FROM ENDS RESPONSIBILITIES 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND ENSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW' MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTURALLY SOUND. 4. CONTRACTOR TO PROVIDE NOA'S & INSTALL ALL MATERIALS AS PER MANUFACTURER'S SPECIFICATIONS. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. SHEET NO. DRAWING INDEX S/01 GENERAL NOTES S/02 PLAN/ ELEVATIONS S/03 DETAILS S/04 DETAILS S/05 DETAILS PROPOSED MANSARD SCREEN ENCLOSURE SEE FOUNDATION DESIGN SHEET-01 _N oco ago __ 4/ o O ''co _ a W � Fw- Q _ o m W Q Z co 0 ui �///111111111\\\\ .2 U Q p USN J O Ln 00 o J r" co I— ccei za Z�// E Lu O V U wJOaoCD W<LLLo.E _I CA Z �-- L1J m N z III _ N GENERALIZEF'LE CO 'ROPOSED 2l0 0 0-7 4 REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC &,� Q 2 _ Oro J CL L CD M CV O CV J `L w w F- W n a� 0 Z� Q F-. o Z(�U) Z kx F- O U) oQ = bra Y ' O a DESIGN DATE: 02/16/2021 REVISION 1: DATE REVISION 2: DATE SHEET: 01 DRAWN BY: TCP SCALE: NTS -81-911 1X2 0 2X4 PB ORSMB N N N XI N N 3X3X.125 DJ r1I N 2X2 DJ O 2X4SMB N N X a —II N N N O + IV N L" 2X4SM8 r -I I N O 2X4SMB c-I I N 0 Z 1X2 81-6" 25% O/H OF LAST PANEL WIDTH ALONG SIDES, TYP. HOST 12" O/H -,- -------------------------------------------- TI f 3" x .024"x1LB c'6 iir INSULATED ROOF m I 3105-1-114 V) "-1' SLOPE (MIN.) N (FL21443.1-R4) 2X8SMB C.B. W/S.G. 4'-C 2X6TIED INTO FASCIA W/ (2) 1/4" X 3" GALV. LAG SCREWS @ 12" O.C. (INTERNAL) HOST 12" O/H STRUC. GUTTER ALUMINUM SPECIFICATIONS 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE NOTED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. #10 SCREW 6" FROM ENDS & 12" CENTER TO CENETER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. 7. 1"X2" & 1"X3" NON STRUCTURAL MEMBERS MAY BE USED INTERCHANGEABLY. 8. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. HOST 12" O/H STRUC. GUTTER 2X2 TYP. - co m m 2X2 TYP. m m m 2 2 2 2 X X X X X X N N N N N N N 2X2 TYP. 2X2 TYP. 45'-0" ;�--------- ---------------------- T----------------T---------------- MAX. \ ` ra m m 1X2 + 2X2 m m m // cV ` x X X X x N N ; by ` \\ N N `"I N 2X2 TYP. i / 1X2 TYP. i , --7'-0"--i�-7'-0" 7'-0" I t 7'-0"------7'-O"-5'-W— 4-5-0"~ I 1X2 j2X2 DJ 2X2 DJ o 2X4SMB a-i I N 0 2X4SMB N N X X N x N N + `� cilN N X O 2X4SMB L" ri I N O 2X4SMI3 ;' LIn c-I I N o 1X2 j 1 8'-6"�i .Q CD C%J Z�[/ N 00 LL. W 00 0v� w CD . ......PROF \\�,; LU /////111111111111 5" OR T'x6" WIDTHx0.250" EXTRUDED GUTTER BRACKET @ EA. BEAM W/ (4) #120/4" S.M.S. INTO GUTTER LIP 1"x2"x0.045" OPEN BACK W/ (2) #12x2" INTO GUTTER & (1) #12x 2" @ 24" O.C. 0BEAM O 2"x2"x1/8" X ALUMINUM ANGLE W/ (2) #14x3/4" S.M.S. INTO BEAM ON EA SIDE (4) INTO GUTTER OPTIONAL: 2"x2"x0.062" -RECEIVING CHANNEL W/ (2) #10x3/4" EA SIDE TO COVER EXPOSED BEAM NOTE: 2x4 SMB BEAM ONLY REQUIRES 4" WIDTH GUTTER BRACKET W/ (2) 3/9-1 A S (4) 3l8" LAG SCREWS @ 1-1/2- SPACING @ EA GUTTER BRACKET & (1) @ 12 O.C. MAX -MIN EMBEDMENT SHALL BE 2" `THE HOST STRUCTURE SHALL HAVE AT LEAST A 2"x4" FASCIA AND ROOF TRUSS SYSTEM. CONTRACTOR SHALL S.M.S.4" VERIFY THIS AND IF {4) #14x3SMALLER CONTRACTOR INTO GUTTER -EA SHALL BRING STRUCTURE UP TO A 2"x4" FASCIA AND ENSURE LESS THAN A 2'-0- OVERHANG GUTTER BRACKET & BEAM ATTACHMENT DETAIL SCALE:NTS NOTES 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (4) #104/8" S.M.S. MINIMUM. 2. DOOR SHALL BE ATTACHED TO ENCLOSURE W/ (2) HINGES MINIMUM. 3. HINGS SHALL BE ATTACHED TO DOOR WITH (4) #104/9' S.M.S. FASTEN A 1x2"4.044" TO UPRIGHT W/#12xl" S.M.S. @ 12" O.C. AND WITHIN 3" FROM END OF THE UPRIGHT. TYPICAL SCREEN DOOR CONNECTION DETAIL SCALE:NTS BEAM SCREWS 2"x4" SMB 6 2"x5" SMB 6 2"x6" SMB 8 2"x7" SMB 8 2"x8" SMB 10 2"x9" SMB 10 2"x10" SMB 12 2"x PURLINS (SEE A-1 FOR SIZE) ATTACHED TO BEAM W/ MIN. (4) #10x1 1/2" BEAM "B" "N" "S1" "S2" "S3" "S4,• 2X4 12 4 34' 11/2" 16" 3.75" 2X5 12 4 3/4" 11/2" 16" 4.75" 2x6 16 5 1" 11/2" 19" 5.75" 2X7 20 6 1" 11/2" 22" 1 6.75" 2X8 24 7 1" 13/8" 23" 7.75" [j2X�924 7 1"13l8" 23" 8.75" 28 8 1" 11/4" 24" 9.75" 3/16" ALUMINUM GUSSET PLATE ,-B #14 SMS NOTES: 1. "N" NUMBER OF SCREWS IN ANY DIRECTION. 2. TOTAL NUMBER OF SCREWS PER JOINT EQUALS 4 TIMES "B". 3. PLATE WIDTH SHALL BE DETERMINED FROM ANGLE OF BEAM AND MIN SPACE REQUIRED. 4. GUSSET PLATES MAY BE INTERNAL OR EXTERNAL.- -- - - 5. INTERNAL SCREWS FOR PURLIN CONNECTION MAY BE INCLUDED IN TOTAL NUMBER OF SCREWS. 6. GABLE SPLICE WILL HAVE THE SAME PATTERN. BEAM SPLICE GUSSET DETAIL TYPICAL SCALE:NTS MAINTAIN MIN, OF 5/8" SEPERATION FROM EDGE OF BEAM SMS O.C. SELF -MATING BEAM SHALL BE NOTCHED FOR SLOPED BEAMS FOR UPRIGHT MAINTAIN ALL SCREW SPACING FROM EDGE OF BEAM 5/8" 2"x2" EAVE RAIL SECTION (UNLESS OTHERWISE SHOWN ON S-2) ATTACHED TO BEAM W/ O O (4) 10x2" SMS INTO SCREW O O BOSS a O O 1"x2" OPEN BACK EAVE 0 RAIL ATTACHED TO UPRIGHT W/ (2) #10xl 1/2" SMS INTO SCREW BOSS #10x1 1/2" SMS 24" C/C " (MIN) UPRIGHT #14x3/4" SCREWS (SEE TABLE ABOVE) UPRIGHT TO BEAM CONNECTION - ALL WIND ZONES SCALE:NTS ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: Tx 2" x 0.050" 2x3:2"x3"x0.050" 2 x 4: 2" x 4" x 0.050" 2 x 5: Tx 5" x 0.059' OPEN BACK SECTIONS 1 x2: 1"x2"x0.044" 1 x3: 1"x3"x0.045" SNAP SECTIONS 2X2SNAP: 2"x2"x0.045" 2X3SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2" x 4" x 0.045" SELF MATING (SMB) 2X4SMB: Tx4"x0.046"x0.100" 2X5SMB: 2"x5"x0.050"x0.116" 2x6SMB: 2"x6"x0.050"x0.120" 2X7SMB: Tx 7" x 0.055" x 0. 120" 2X8SMB: 2"x8"x0.072"x0.224" 2 x 9 SMB: 2"x9"x0.072"x0.224" 2 x 9 (H) SMB: 2" x 9" x 0.082" x 0.306" 2 x 10 SMB: 2" x 10" x 0.092" x 0.374" DETAIL A 1"x2" FASTENED TO COLUMN WITH (2) #10x1 1/2" SMS INTO SCREW BOSSES FOR SMB OR SNAP COLUMN \�11111111111111a/////// \O\v N .. .. . .. o O C o =�'•v LU ¢ O' = E2 W - v =% L9 uj gm ju<1 ////I111111111111 UPRIGHT WEB LAPPED OVER PURLIN W! (2) #12x3/4"-SMS EACH SIDE THRU UPRIGHT & PURLIN 2"x2" EDGE BEAM ATTACHED TO UPRIGHT W! (3) #10x1-1/2" SMS INTO SCREW BOSS 1"x2"x.045" OPEN BACK ATTACHED TO PURLIN W/ (2) #10x1-1/2" SMS INTO SCREW BOSS 1"x2"x.045" OPEN BACK ATTACHED TO 2"x2"x.050" EAVE RAIL MEMBER W! 910xl-1/2" SMS 24" O.C. NOTE: A RECEIVING CHANNEL (1/16" THICKNESS) WITH (4) #10x3/4" SMS AT EACH CONNECTION MAY BE USED IN PLACE OF THE (2) #10x3" SCREW BOSS CONNECTION. ECONDARY ANGLE MIN 0.125" THICK (NOT (4) #10x3/4" SMS REQUIRED FOR 2x3 FASTENING SECONDARY MEMBER) ANGLE TO COLUMN (TYP EACH SIDE) RIMARY 2"x2" (B) 3/8" 0 CONCRETE SCREW x0.125" ANGLE ANCHOR INTO SECONDARY 2) #10x3/4" SMS FASTENING ANGLE COLUMN TO PRIMARY ANGLE OPTION #1 (TYP EACH SIDE) O cr (TYP EACH SIDE) (SEE TABLE) D O O "x2" BASE MEMBER I ANCHOR SPA (TYP EACH SIDE) (4) #10x1 1/2" SMS INTO SCREW BOSSES OPTION #2 (MIN) (TYP) (SEE TABLE) 1) 3/8" 0 CONCRETE SCREW COLUMN SIZE 3/8" 0 CONCRETE SCREW ANCHOR B MIN SPA 2X3 0 0 2X4 1 3 2X5 1 3 2X6 1 4 2X7 1 5 2X8 - --2 3- 2X9 2 4 0010 1 2 4.5 ANCHOR INTO PRIMARY ANGLE AND @ 1/4" 0 CONCRETE �T'MIN. SCREW ANCHOR @ 24" O.C. BETWEEN COLUMNS NOTES: (TYP EACH SIDE) 1. NUMBER OF ANCHORS "B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE 1X2. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2 3X' AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTH AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED ON S-1, D. FASTENERS, OTHER BRAND & TYPE SHALL BE APPROVED BY ENGINEER. 4.2X3 W/ 1X2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. _ 5. IF FOR AN IN -FILL, TOP OF COLUMN CONNECTIONS SIMILAR IF CONCRETE LINTEL IF WOOD LINTEL SUBSTITUTE 1/4" OX3" LAG SCREW FOR 318" 0 LDT FOR BOTH PRIMARY & SECONDARY ANGLES. 6.2X2X.045 DOOR JAMB MEMBER SHALL CONNECT SIMILAR TO 2X3 MEMBER. 2"x3" OR LARGER UPRIGHT TO CONCRETE W/WO PAVER DETAILS SCALE:NTS 2"x2" OR Z x&' J MEMBER i i .062" ALUMINUM INTERNAL OR I i EXTERNAL RECEIVING CHANNEL W/ (4) #10x3X' INTO BEAM OR UPRIGHT (2) #14x3/4" EA LEG INTO GIRT OR PURLIN (0.062" ANGLE 1 CLIPS W/ (2) #14x3/4" SMS EA LEG) PRIGHT OR BEAM - SNAP OR SELF MATING OR HOLLOW PURLIN OR GIRT TO BEAM OR POST DETAIL SCALE:NTS PTION #1 - A-36 STEEL "x2"x1/8" ANGLE I.f J� CLIP MAY BY PLACED ON TOP OR SIDE OF DECK W/ " SLEEVE 4) #12x3/4" SMS TOP OF ANCHOR A O O (TYP TOP AND SIDE) CONCRETE O O NOTE: WHEN USING OPTION #2 DOUBLE COMPRESSION SLEEVES /8" DIA STAINLESS CONNECTION CABLE MUST BE d O a STEEL CABLE WITHIN 6" OF CORNER OR 4" NOMINAL SLAB c ° d ae de PRIMARY MEMBER. MINIMUM 3/8" WELDED STAINLESS STEEL EYE BOLT 3/8" 0X3" MASONRY OPTION #1 (8) #14x3/4 SMS ANCHOR (MIN 3 3/4" 2500 PSI CONCRETE W/ EMBEDMENT 4" SLAB ONLY WELDED WIRE OR SIDE VIEW FIBERMESH 0 (MIN) WASHER HENEATH NUT-- �-= .125" STAINLESS STEEL CABLE 2500 PSI CONCRETE W/ O O - -- = _ --- WELDED WIRE OR O O TOP OF FIBERMESH O O O CONCRETE --- ----------- ° 0 ° ° TOP VIEW i O 1 0 ADJUSTABLE EYE d O I BOLT FOR CABLE TENSION 4" NOMINAL SLAB O d O MINIMUM ° cOPTION #2 ° 110 i /8" 0 STAINLESS I I STEEL CABLE 11/2"X51/2"ALUMINUM OPTION #2 I I I STRAP W/ (2) 31W 0X3" USE WITH FOOTING MASONRY ANCHOR (MIN 3 3/4" EMBEDMENT) 2"x2"x1/8" EXTRUDED ANGLE ON45°ANGLE SIDE VIEW CABLE TO FOUNDATION CONNECTION DETAIL OPTION #1 SCALE:NTS CABLE CONNECTION AT CORNER SCALE:NTS BEAM BRACE (2) #10x3" SMS CROSS SCREWING BRACE TO BEAM OR EAVE MEMBER (.125" BACKING PLATE USED) 125" FLAT YP.) 3/8" DIA. THRU BOLT NYLON LOCKING NUT THREAD LOCKING TERIAL APPLIED MEMBER JRLIN ROOF BRACING CONNECTION DETAIL SCALE:NTS o N p �\\\�0O\vzJ�= uj j o o= c w ��i�I�'' ......pp••'.O� LLI .. \�� U ra 14i EXISTING RAFTER OR TRUSS C # 14x I /7' S.M.S. W/ INTEGRAL 3/4"0 O O C WASHER AND NEOPRENE GASKET @ 12' O.C., TOP & BOTTOM EXTRUDED OR BRAKE -FORMED ROOF HEADER OR RECEIVING CHANNEL (0.044" MIN. THICKNESS) SECURE FASCIA TO EACH WITH MIN. 1-1 /2' BEARING LEG. RAFTER TAIL W/ (1) 1 /4" 0 x 4" LONG PAN HEAD LAG SCREWS (1) 1 /4" 0 x 2' LAG SCREW @ 24" O.C. BEFORE ATTACHING REC. CHANNEL ENTIRE LENGTH OF RECEIVING CHANNEL ROOF PANEL ATTACHMENT - WOOD FRAME SCALE: N.T.S. (2) 3/8" DIA. MACHINE BOLTS THRU CARRIER CARRIER BEAM BEAM & POST PER PLAN 3X3 OR 4X4 POST PER PLAN BEAM TO POST CONNECTION #1 DETAIL SCALE: N.T.S. (2) 3/8" DIA. MACHINE CARRIER BEAM BOLTS THRU CARRIER PER PLAN BEAM & POST 3X3 OR 4X4 POST PER PLAN BEAM TO POST CONNECTION #2 DETAIL SCALE: N.T.S. 024 FLASHING SEALED TO WALL (TYP.) ° • n° #14xl /7' S.M.S. W/ INTEGRAL 3/4"0 WASHER AND NEOPRENE GASKET @ 17' O.C., TOP & BOTTOM. O O IF CLEARANCE PROHIBITS INSTALLATION OF TOP FASTENERS USE #14x4" S.M.S. W/ 1-1 WO FENDER WASHER AND NEOPRENE GASKET @ 12" O.C. EXTRUDED OR BRAKE -FORMED ROOF HEADER OR RECEIVING CHANNEL (0.044" MIN. THICKNESS) WITH MIN. 1-1 /7BEARING LEG. HOST STRUCTURE 1/4" 0 x 2-1/7' LONG WOOD LAG SCREW OR MASONRY OR WOOD 1 /4" 0 x 2-1 /4" LONG MASONRY ANCHORS @ 24" O.C. MAX. ROOF PANEL ATTACHMENT - MASONRY SCALE: N.T.S. 25(7k.063"- DIM. TO MATCH PURLIN SIZE RECEIVING CHANNEL (2) # 12 SMS INTERNAL TO EAVE E�PER 1-1 /4' 0 FENDER WASHER RAIL (3) # 12 EACH SIDE INTO PURLIN GASKET @ 12' O.C. Sp�RUN S o o uM PURLIN TO CARRIER BEAM + SOLID ROOF CONNECTION SCALE: N.T.S. 1'kSk7' WIDTH EXTRUDED GUTTER BRACKET # 144" S.M.S. w/ 1-114- 0 FENDER WASHER (THICKNESS OF LEG @ C.B. SCREW SHALL BE AND NEO-PRENE GASKET @ 17O.C. 0.125' MIN., LONG LEG SHALL BE 0.072' MIN.) @ EACH BEAM w/(2) # 12x3/4" SMS @ 1" SPACING #12 X 9/16" W/ 5/8" NEO-WASHER INTO GUTTER LIP. (2) #14 SMS OT TEK SCREWS @ 1" (3) PER PAN FOR PANS SPACING @ EACH GUTTER BRACKET & (1) @ 18" O.C. MAX. (SEE NOTE) NOTE: ROOF PER PLAN FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 7' GUTTER BRACE AT EACH BEAM LOCATION CAGE "FOR 2X9 AND 2X10 -- (2) 3/8" THRU-BOLT BEAM USE #14 INTO BEAM THRU CARRIER BEAM STRUC. i I (NTOO H05OSTAPCON & POSTS GUTTER HOST 2-1/4" MIN. GIRT FASTENED INTERNALLY AT EACH END w/ # l Ox1.5' EACH SCREW GROOVE. FASTEN TO BEAM w/ 7k2"'xl /8" ANGLE (2) # 12 SMS POST INTO BEAM & (2) # 1 Ox1.5 THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH 3X3 OR 4X4 SIDE VIEW ANGLE DIRECTLY TO GUTTER POST PER PLAN FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER INTERNALLYw/(2) #12SMS ALTERNATELY 2x2xl /&'ANGLE BELOW GIRT, (2) #14SMS INTO BEAM & (2) #12SMS INTO GUTTER ROOF PANEL TO CARRIER BEAM W/ GUTTER + ROOF BEAM CONNECTION SCALE: N.T.S. (4) 1 /4'k3-1 /4" TAPCON THRU BOTTOM LEG OF ANGLE INTO CONC. (2) 3/8" DIA. MACHINE BOLTS w/ WASHERS 3-3/4" FROM EDG OF SLAB/FIG. MAY USE (3) #14xl"TEK TOP VIEW IN LIEU OF THRUBOLTS 3k3" POST PER PLAN (2) 3/8" DIA. MACHINE BOLTS w/ WASHERS 1 /8'k7k3" (LENGTH) ANGLE (4) 1 /N'k I /4" TAPCON (INTERNAL) THRU BOTTOM LEG OF ANGLE INTO CONC. 3000 PSI CONC. •, ° SLAB/ FTG. e 6x6-1Ox10 WWM OR FIBERMESH FRONT VIEW YXY POST CONNECTION DETAIL (INTERNAL BASE) SCALE: N.T.S. MAY USE: (2) 3/9'x4" TAPCON IN LIEU OF 3/9' DIA. ANCHORS (2) 3/8" DIA. EXPANSION BOLTS (2) 3/8" DIA. MACHINE SEE NOTE #1 THIS PAGE BOLTS w/ WASHERS FOR BOLT PLACEMENT ® 2' FROM EDGE 7' FROM EDGE OF SLAB/ FTG. OF SLAB/ FTG. TOP VIEW (2) 3/8" DIA. MACHINE BOLTS w/ WASHERS (2) 3/8" DIA. EXPANSION BOLTS SEE NOTE # 1 THIS PAGE FOR BOLT PLACEMENT 3'k3" POST (SEE PAGE-2 FOR SIZE) MAY USE (3) #14x1"TEK IN LIEU OFTHRUBOLTS — 3'k3'k0.125 ANGLE 3000 PSI CONC. SLAB/ FTG. ' 6x6-10x10 WWM OR FIBERMESH FRONT VIEW 3"x3' POST CONNECTION DETAIL SCALE: NTS (4) 3/9k4" TAPCON THRU BOTTOM LEG OF ANGLE INTO CONC. (3) 1 /4" DIA. MACHINE BOLTS w/ WASHERS 3-3/4" FROM E OF SLAB/ FTG. 1'S(SkKW WIDTH EXTRUDED GUTTER BRACKET (THICKNESS OF LEG @ #14 SMS OR TEK SHALL BE 0.125' MIN., LONG LEG SHALL BE 0.072' MIN.) @ 24" O.C. w/(2) # 12x3/4" SMS @ 1" SPACING INTO GUTTER LIP. (2) # 14 SMS OR TEK @ 1" SPACING @ EACH GUTTER BRACKET & (1) @ 18" O.C. MAX. ROOF PER PLAN GIRT FASTENED INTERNALLY AT EACH END w/ #10x1.5" EACH SCREW GROOVE. FASTEN TO BEAM w/ 2k7"xl /&' ANGLE (2) # 12 SMS INTO BEAM & (2) #10xl.5THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY T6 GUTTER WR 2X9 AND 2X10 # 14 INTO BEAM CAGE & (3) 1/4-TAPCON BEAM INTO HOST 2-1 /4" MIN. # 14x4" S.MS. w/ 1-1 /4" 0 FENDER WASHER t Q i AND NEC-PRENE GASKET @ 12" O.C. `M ails ns m 5 OR 7 IN. z ed STRUCTURAL uw GUTTER FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL FASTEN CARRIER BEAM TO STRUCTURAL GUTTER PERPLAN SIDEVIEW INTERNALLY w/(2)#12SMS ALTERNATELY 2x20 /&' ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12SMS INTO GUTTER BEAM TO CARRIER BEAM W/ GUTTER + SOLID ROOF CONNECTION SCALE: N.T.S. % '' N ''co O o N CNI.- LL '. y ; ILI co 1 IL Lu c LLJ Q :z= m .,••''La < LLI MAY USE: (4) 3/9'x5" TAPCON IN LIEU OF 1 /2" DIA. ANCHORS 1" (2) 1/7' DIA. EXPANSION BOLTS (3) 1/4" DIA. MACHINE N SEE NOTE #2 THIS PAGE ® r BOLTS w/ WASHERS 2 FOR BOLT PLACEMENT N —[ �El 1„ 3-3/4" FROM EDGE 3-3/4" FROM EDG OF SLAB/ FTG. OF SLAB/ FTG. MAY USE (4) #14x1"TEK TOP VIEW IN LIEU OFTHRUBOLTS (3) 1/4" DIA. MACHINE COLUMN PER PLAN BOLTS w/ WASHERS 1/8 'k2'k7k3-3/4" (LENGTH) ANGLE (4) 3/&' K4"TAPCON (INTERNAL) THRU BOTTOM LEG OF ANGLE INTO CONC. 3000 PSI CONC. e • . . o SLAB/ FTG. ' 6x6-1Ox10 WWM OR FIBERMESH FRONT VIEW 4X4 COLUMN ALT. BASE ATTACHMENT DETAIL SCALE: NTS (3) 1X DIA. MACHINE TOP VIEW BOLTS w/ WASHERS (2) 1 /2' DIA. EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT 3000 PSI CONC. SLAB/ FTG. 6x6-10x10 WWM OR FIBERMESH 4"x4" POST (SEE PAGE-2 FOR SIZE) MAY USE (4) #14x1"TEK IN LIEU OFTHRUBOLTS 2k4k0.125 ANGLE FRONT VIEW 4"M" POST CONNECTION DETAIL SCALE: NTS