HomeMy WebLinkAboutM Manual JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Load Short Form Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACX-047-230* AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259382 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.7 Sensible cooling Btuh32900 Heating output Btuh36400 Latent cooling Btuh14100 Temperature rise °F21 Total cooling Btuh47000 Actual air flow cfm1567 Actual air flow cfm1567 Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.053 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.74 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 138 3371 2389 135 127 Storage 16 0 0 0 0 Lin 7 0 0 0 0 Guest Bath 63 925 645 37 34 Back Hall 75 0 0 0 0 Bed 2 209 4444 2357 178 126 Hallway 141 0 0 0 0 Pantry 82 218 158 9 8 Foyer 71 2645 1358 106 72 Great Room 641 6912 6288 277 335 Bed 3 226 3529 2756 142 147 Rec Room 275 6883 4211 276 224 Cabana Bath 69 1833 988 74 53 Vestibule 81 2262 1892 91 101 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S Kit/Dining 566 6043 6347 242 338 A/H 1 d 2661 39065 29388 1567 1567 Other equip loads 1804 958 Equip. @ 0.95 RSM 28950 Latent cooling 10628 TOTALS 2661 40869 39578 1567 1567 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 3 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Load Short Form Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 0 cfmPressure / AVF1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS018-230A** AHRI ref Coil CBA25UH-018-230-** AHRI ref 202540456 Efficiency 100 EFF Efficiency 12.2 EER, 14 SEER Heating input kW4.6 Sensible cooling Btuh12600 Heating output Btuh15544 Latent cooling Btuh5400 Temperature rise °F24 Total cooling Btuh18000 Actual air flow cfm600 Actual air flow cfm600 Air flow factor cfm/Btuh0.035 Air flow factor cfm/Btuh0.058 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.69 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Master Bath 212 3850 1846 133 107 Wtr Clst 41 954 646 33 38 Master Bedroom 432 7727 4697 268 273 M Lin 11 0 0 0 0 His 70 125 96 4 6 Hers 77 1393 841 48 49 Office 209 3274 2206 113 128 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 4 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S A/H 2 d 1052 17323 10331 600 600 Other equip loads 813 432 Equip. @ 0.95 RSM 10268 Latent cooling 4907 TOTALS 1052 18137 15176 600 600 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Building Analysis Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 14.760053.1Walls 21.9896918.4Glazing 000Doors 10.342211.6Ceilings 15.462882.42.4Floors 18.676123.4Infiltration 14.65969Ducts 00Piping 00Humidification 4.41804Ventilation0Adjustments 100.040869Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 12.537791.9Walls 33.61019720.9Glazing 000Doors 10.732521.2Ceilings 000Floors 7.522671.0Infiltration 13.13974Ducts 3.2958Ventilation 19.55920Internal gains 00Blower 0Adjustments 100.030346Total Latent Cooling Load = 10628 Btuh Overall U-value = 0.233 Btuh/ft²-°F Data entries checked. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Building Analysis Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.834113.2Walls 14.8268214.3Glazing 000Doors 9.216691.6Ceilings 18.733843.23.2Floors 23.642863.4Infiltration 10.41891Ducts 00Piping 00Humidification 4.5813Ventilation0Adjustments 100.018137Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 20.321822.0Walls 28.0301516.1Glazing 000Doors 11.912851.2Ceilings 000Floors 11.912761.0Infiltration 11.51243Ducts 4.0432Ventilation 12.41330Internal gains 00Blower 0Adjustments 100.010763Total Latent Cooling Load = 4907 Btuh Overall U-value = 0.223 Btuh/ft²-°F Data entries checked. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Component Constructions Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh 12613.155.10.109400n 8062.02 2452.023833.155.10.109121ne 6192.029683.155.10.109307e 4852.027583.155.10.109241s 452.02713.155.10.10922sw 12962.0220263.155.10.109643w 682.021073.155.10.10934nw 35652.0255733.155.10.1091769all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-13 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x6" Wd Frm, 16" OC Stud 2141.164322.3313.00.080185 Windows Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (2 ft window ht, 2 ft sep.); 8.6 ft head ht 1839.1323211.600.40020n Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 20 ft overhang (6 ft window ht, 2 ft sep.); 8.6 ft head ht 2199.1327811.600.40024n Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (6 ft window ht, 2 ft sep.); 8.6 ft head ht 41613.955718.600.64030s 144226.7100218.600.64054w 185822.1155918.600.64084all Impact: Impact; NFRC rated (SHGC=0.37); foreground = green grass (0.23); 15 ft overhang (10 ft window ht, 2 ft sep.); 8.6 ft head ht 242820.2281923.500.810120n Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 14 ft overhang (6 ft window ht, 2 ft sep.); 8.6 ft head ht 84820.747611.600.40041ne Impact: Impact; NFRC rated (SHGC=0.31); foreground = green grass (0.23); 16.6 ft overhang (6.5 ft window ht, 2 ft sep.); 8.6 ft head ht 71035.445922.900.79020ne 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5 ft window ht, 2 ft sep.); 8.6 ft head ht 66026.429011.600.40025w Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (4 ft window ht, 2 ft sep.); 8.6 ft head ht 30326.721018.600.64011e 30326.721018.600.64011w 60526.742118.600.64023all Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 18 ft overhang (4 ft window ht, 2 ft sep.); 8.6 ft head ht 16713.922318.600.64012e Impact: Impact; NFRC rated (SHGC=0.25); foreground = green grass (0.23); 2 ft overhang (2 ft window ht, 2 ft sep.); 8.6 ft head ht 13413.411611.600.40010s Impact: Impact; NFRC rated (SHGC=0.25); foreground = green grass (0.23); 10 ft overhang (2 ft window ht, 2 ft sep.); 8.6 ft head ht 16113.413911.600.40012s Impact: Impact; NFRC rated (SHGC=0.31); foreground = green grass (0.23); 10 ft overhang (8 ft window ht, 2 ft sep.); 8.6 ft head ht 72315.1110022.900.79048s Impact: Impact; NFRC rated (SHGC=0.31); foreground = green grass (0.23); 6 ft overhang (6.5 ft window ht, 2 ft sep.); 8.6 ft head ht 41420.745922.900.79020sw Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (4 ft window ht, 2 ft sep.); 8.6 ft head ht 52826.423211.600.40020w Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (3 ft window ht, 2 ft sep.); 8.6 ft head ht 24026.716718.600.6409w Doors (none) Ceilings DftCathCeil: Attic, Metal Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh 1.2242211.5921.00.4052661 3252 Floors DftFlor: On Grade Depth, Tile Flr Fnsh 00628828.700.989219 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 3 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Component Constructions Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 0 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8" Thk, 1/2" Gyp Bd Int Fnsh 4143.155.10.109132n 2652.02 10172.0215893.155.10.109504e 5042.027883.155.10.109250s 3962.026193.155.10.109197w 21822.0234113.155.10.1091083all Partitions (none) Windows Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (2 ft window ht, 2 ft sep.); 8.6 ft head ht 52826.423211.600.40020e Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (6 ft window ht, 2 ft sep.); 8.6 ft head ht 3069.1338911.600.40034n Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (6 ft window ht, 2 ft sep.); 8.6 ft head ht 36811.957518.600.64031n 41613.955718.600.64030s 78512.9113218.600.64061all Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5 ft window ht, 2 ft sep.); 8.6 ft head ht 66026.429011.600.40025e Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (4 ft window ht, 2 ft sep.); 8.6 ft head ht 30326.721018.600.64011e Impact: Impact; NFRC rated (SHGC=0.25); foreground = green grass (0.23); 2 ft overhang (2 ft window ht, 2 ft sep.); 8.6 ft head ht 13413.411611.600.40010s Impact: Impact; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (3 ft window ht, 2 ft sep.); 8.6 ft head ht 30011.131311.600.40027s Doors (none) 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 4 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S Ceilings DftCathCeil: Attic, Metal Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh 1.2216691.5921.00.4051052 1285 Floors DftFlor: On Grade Depth, Tile Flr Fnsh 00338428.700.989118 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Project Summary Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor:TBD Noble Oaks Ln, Port St Lucie, FL 34952 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh33095 Structure Btuh25414 Ducts Btuh5969 Ducts Btuh3974Central vent (57 cfm) 1804 Btuh Central vent (57 cfm) Btuh958 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh40869 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh28950 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh5975 Ducts Btuh2466Central vent (57 cfm) Btuh2187 CoolingHeating Outside air26612661Area (ft²) Equipment latent load Btuh10628 3085930859Volume (ft³)Air changes/hour 0.260.46 Equipment Total Load (Sen+Lat)Btuh39578 Equiv. AVF (cfm) 134239 Req. total capacity at 0.70 SHR ton3.4 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACX-047-230*AHRI ref Coil CBA27UHE-048-230*++TDR AHRI ref 10259382Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.7 Sensible cooling Btuh32900Heating output Btuh36400 Latent cooling Btuh14100 Temperature rise °F21 Total cooling Btuh47000Actual air flow cfm1567 Actual air flow cfm1567 Air flow factor cfm/Btuh0.040 Air flow factor cfm/Btuh0.053Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.74 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Project Summary Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor:TBD Noble Oaks Ln, Port St Lucie, FL 34952 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh15432 Structure Btuh9089 Ducts Btuh1891 Ducts Btuh1243Central vent (26 cfm) 813 Btuh Central vent (26 cfm) Btuh432 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh18137 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh10268 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 150 Pa / 0 cfmPressure / AVF Structure Btuh3114 Ducts Btuh808Central vent (26 cfm) Btuh986 CoolingHeating Outside air10521052Area (ft²) Equipment latent load Btuh4907 1137211372Volume (ft³)Air changes/hour 0.400.71 Equipment Total Load (Sen+Lat)Btuh15176 Equiv. AVF (cfm) 75134 Req. total capacity at 0.70 SHR ton1.2 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACXS018-230A**AHRI ref Coil CBA25UH-018-230-** AHRI ref 202540456Efficiency 100 EFF Efficiency 12.2 EER, 14 SEER Heating input kW4.6 Sensible cooling Btuh12600Heating output Btuh15544 Latent cooling Btuh5400 Temperature rise °F24 Total cooling Btuh18000Actual air flow cfm600 Actual air flow cfm600 Air flow factor cfm/Btuh0.035 Air flow factor cfm/Btuh0.058Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name A/H 1 Laundry 2 Exposed wall 219.3 ft 25.5 ft 3 Room height 11.6 dft 10.0 heat/coolft 4 Room dimensions ft138.3x1.0 5 Room area 2660.6 ft²138.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 564 400 1261 806 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 20 0 232 183 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 24 0 278 219 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 120 0 2819 2428 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 182 121 383 245 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 41 0 476 848 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 20 0 459 710 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 331 307 968 619 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 11 0 210 303 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 12 12 223 167 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 341 241 758 485 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 10 10 116 134 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 12 12 139 161 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 30 30 557 416 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 48 48 1100 723 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 42 22 71 45 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 20 20 459 414 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 762 643 2026 1296 115 97 306 196 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 20 0 232 528 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 25 0 290 660 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 9 0 167 240 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 11 0 210 303 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 54 0 1002 1442 18 0 334 481 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 34 34 107 68 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 185 185 432 214 140 140 327 162 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 2661 2661 4221 3252 138 138 219 169 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 2661 219 6288 0 138 26 731 0 6 c) AED excursion 320 115 Envelope loss/gain 25484 17228 1917 1122 12 a) Infiltration 7612 2267 388 116 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 5000 500 Subtotal (lines 6 to 13)33095 25414 2306 1738 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 550 328 14 Subtotal 33095 25414 2856 2066 15 Duct loads 18%16%5969 3974 18%16%515 323 Total room load 39065 29388 3371 2389 Air required (cfm)Air required (cfm)1567 1567 135 127 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Storage Lin 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft3.5x4.5 ft3.5x2.0 5 Room area 15.8 ft²7.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 16 16 25 19 7 7 11 9 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 16 0 0 0 7 0 0 0 6 c) AED excursion -1 0 Envelope loss/gain 25 18 11 8 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)25 18 11 8 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -25 -18 -11 -8 14 Subtotal 0 0 0 0 15 Duct loads 18%16%0 0 18%16%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 3...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Guest Bath Back Hall 2 Exposed wall 5.5 ft 10.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft5.5x11.5 ft11.5x6.5 5 Room area 63.3 ft²74.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 35 24 75 48 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 11 0 210 303 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 20 20 63 40 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 55 46 145 93 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 9 0 167 240 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 45 45 105 52 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 63 63 100 77 75 75 119 91 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 63 6 158 0 75 10 287 0 6 c) AED excursion 71 25 Envelope loss/gain 570 482 858 559 12 a) Infiltration 186 55 186 55 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)756 537 1044 614 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 28 21 -1044 -614 14 Subtotal 784 558 0 0 15 Duct loads 18%16%141 87 18%16%0 0 Total room load 925 645 0 0 Air required (cfm)Air required (cfm)37 34 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 4...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Hallway 2 Exposed wall 21.5 ft 0 ft 3 Room height 12.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft15.5x13.5 ft141.0x1.0 5 Room area 209.3 ft²141.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 96 96 302 193 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 162 122 384 246 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 10 10 116 134 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 30 30 557 416 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 209 209 332 256 141 141 224 172 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 209 22 617 0 141 0 0 0 6 c) AED excursion -70 -7 Envelope loss/gain 2308 1175 224 165 12 a) Infiltration 870 259 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)3179 1684 224 165 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 586 354 -224 -165 14 Subtotal 3765 2039 0 0 15 Duct loads 18%16%679 319 18%16%0 0 Total room load 4444 2357 0 0 Air required (cfm)Air required (cfm)178 126 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 5...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Pantry Foyer 2 Exposed wall 0 ft 9.5 ft 3 Room height 10.0 heat/coolft 13.0 heat/coolft 4 Room dimensions ft81.6x1.0 ft7.5x9.5 5 Room area 81.6 ft²71.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 124 64 200 128 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 12 12 139 161 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 48 48 1100 723 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 82 82 129 100 71 71 113 87 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 82 0 0 0 71 10 272 0 6 c) AED excursion -4 -49 Envelope loss/gain 129 96 1824 1050 12 a) Infiltration 0 0 417 124 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)129 96 2241 1174 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 55 41 0 0 14 Subtotal 185 136 2241 1174 15 Duct loads 18%16%33 21 18%16%404 184 Total room load 218 158 2645 1358 Air required (cfm)Air required (cfm)9 8 106 72 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 6...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Great Room Bed 3 2 Exposed wall 21.0 ft 21.5 ft 3 Room height 13.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft641.4x1.0 ft226.4x1.0 5 Room area 641.4 ft²226.4 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 273 153 482 308 60 60 189 121 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 120 0 2819 2428 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 155 119 375 240 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 36 0 668 961 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 641 641 1018 784 226 226 359 277 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 641 21 602 0 226 22 617 0 6 c) AED excursion -227 277 Envelope loss/gain 4921 3293 2209 1876 12 a) Infiltration 921 274 726 216 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1400 250 Subtotal (lines 6 to 13)5842 5427 2935 2342 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 14 11 55 41 14 Subtotal 5856 5438 2990 2383 15 Duct loads 18%16%1056 850 18%16%539 373 Total room load 6912 6288 3529 2756 Air required (cfm)Air required (cfm)277 335 142 147 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 7...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Rec Room Cabana Bath 2 Exposed wall 48.5 ft 13.5 ft 3 Room height 11.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft275.1x1.0 ft69.0x1.0 5 Room area 275.1 ft²69.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 165 145 457 292 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 20 0 232 183 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 182 170 534 342 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 12 12 223 167 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 35 35 110 71 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 187 167 526 337 100 89 280 179 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 20 0 232 528 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 11 0 210 303 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 275 275 436 336 69 69 109 84 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 275 49 1391 0 69 14 387 0 6 c) AED excursion 22 82 Envelope loss/gain 4031 2206 1097 719 12 a) Infiltration 1800 536 456 136 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)5831 3642 1553 855 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 5831 3642 1553 855 15 Duct loads 18%16%1052 569 18%16%280 134 Total room load 6883 4211 1833 988 Air required (cfm)Air required (cfm)276 224 74 53 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 8...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Vestibule Kit/Dining 2 Exposed wall 10.6 ft 32.2 ft 3 Room height 10.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft81.0x1.0 ft565.6x1.0 5 Room area 81.0 ft²565.6 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 66 42 132 85 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 24 0 278 219 11 GG ImpactImpact 0.6400.640 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 23.4923.49 20.2320.23 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 64 44 138 88 119 78 245 157 GG ImpactImpact 0.4000.400 nene 11.6011.60 20.6720.67 0 0 0 0 41 0 476 848 GG ImpactImpact 0.7900.790 nene 22.9122.91 35.4035.40 20 0 459 710 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 18 18 57 36 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 22.9122.91 15.0715.07 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 42 22 71 45 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 22.9122.91 20.6720.67 20 20 459 414 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 150 125 394 252 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 11.6011.60 26.3926.39 0 0 0 0 25 0 290 660 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 34 34 107 68 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --2.332.33 1.161.16 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 81 81 129 99 566 566 897 691 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 81 11 304 0 566 32 923 0 6 c) AED excursion 173 -87 Envelope loss/gain 1559 1529 3799 2929 12 a) Infiltration 358 107 1305 388 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 2 460 Appliances/other 0 1700 Subtotal (lines 6 to 13)1917 1636 5103 5477 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 16 12 14 Subtotal 1917 1636 5119 5489 15 Duct loads 18%16%346 256 18%16%923 858 Total room load 2262 1892 6043 6347 Air required (cfm)Air required (cfm)91 101 242 338 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 9...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name A/H 2 Master Bath 2 Exposed wall 118.0 ft 29.5 ft 3 Room height 10.8 dft 10.0 heat/coolft 4 Room dimensions ft211.8x1.0 5 Room area 1051.8 ft²211.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 196 132 414 265 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 34 0 389 306 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 18.5618.56 11.8811.88 31 0 575 368 0 0 0 0 GG ImpactImpact 0.8100.810 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 561 504 1589 1017 125 115 363 232 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 20 0 232 528 10 0 116 264 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 25 0 290 660 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 11 0 210 303 0 0 0 0 GG ImpactImpact 0.6400.640 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 317 250 788 504 155 128 404 258 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 10 10 116 134 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 11.1311.13 27 27 313 300 27 27 313 300 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 30 30 557 416 0 0 0 0 GG ImpactImpact 0.7900.790 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 197 197 619 396 15 15 47 30 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 1052 1052 1669 1285 212 212 336 259 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 1052 118 3384 0 212 30 846 0 6 c) AED excursion 0 -23 Envelope loss/gain 11147 6482 2425 1320 12 a) Infiltration 4286 1276 996 297 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 1 230 0 0 Appliances/other 1100 0 Subtotal (lines 6 to 13)15432 9089 3421 1617 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 9 7 14 Subtotal 15432 9089 3430 1624 15 Duct loads 12%14%1891 1243 12%14%420 222 Total room load 17323 10331 3850 1846 Air required (cfm)Air required (cfm)600 600 133 107 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 10...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Wtr Clst Master Bedroom 2 Exposed wall 6.5 ft 52.0 ft 3 Room height 10.0 heat/coolft 11.0 heat/coolft 4 Room dimensions ft4.5x9.0 ft432.0x1.0 5 Room area 40.5 ft²432.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 20 20 63 40 176 112 351 225 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 34 0 389 306 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 18.5618.56 11.8811.88 0 0 0 0 31 0 575 368 GG ImpactImpact 0.8100.810 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 45 34 106 68 281 256 805 515 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 0 0 0 0 25 0 290 660 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 11 0 210 303 0 0 0 0 GG ImpactImpact 0.6400.640 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 11.1311.13 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 116 116 364 233 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 41 41 64 49 432 432 685 528 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 41 7 186 0 432 52 1491 0 6 c) AED excursion 42 -59 Envelope loss/gain 630 503 4951 2775 12 a) Infiltration 219 65 1930 575 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 1 230 Appliances/other 0 550 Subtotal (lines 6 to 13)850 568 6881 4129 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 3 2 14 Subtotal 850 568 6884 4132 15 Duct loads 12%14%104 78 12%14%844 565 Total room load 954 646 7727 4697 Air required (cfm)Air required (cfm)33 38 268 273 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 11...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name M Lin His 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft4.5x2.5 ft14.0x5.0 5 Room area 11.3 ft²70.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 18.5618.56 11.8811.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 11.1311.13 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 11 11 18 14 70 70 111 86 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 11 0 0 0 70 0 0 0 6 c) AED excursion 0 -1 Envelope loss/gain 18 14 111 84 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)18 14 111 84 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -18 -14 0 0 14 Subtotal 0 0 111 84 15 Duct loads 12%14%0 0 12%14%14 12 Total room load 0 0 125 96 Air required (cfm)Air required (cfm)0 0 4 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-12 13:37:53Right-Suite® Universal 2021 21.0.03 RSU27054 Page 12...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Right-J® Worksheet Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers Office 2 Exposed wall 11.0 ft 19.0 ft 3 Room height 10.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft11.0x7.0 ft15.5x13.5 5 Room area 77.0 ft²209.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nn 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 11.6011.60 9.139.13 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.4000.400 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 11 GG ImpactImpact 0.6400.640 nn 18.5618.56 11.8811.88 0 0 0 0 0 0 0 0 GG ImpactImpact 0.8100.810 nn 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 nene 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ee 3.153.15 2.022.02 110 100 315 202 0 0 0 0 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 10 0 116 264 0 0 0 0 GG ImpactImpact 0.4000.400 ee 11.6011.60 26.3926.39 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 18.5618.56 26.7026.70 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ss 3.153.15 2.022.02 0 0 0 0 162 122 384 246 GG ImpactImpact 0.4000.400 ss 11.6011.60 13.4013.40 0 0 0 0 10 10 116 134 GG ImpactImpact 0.4000.400 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ss 11.6011.60 11.1311.13 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ss 18.5618.56 13.8813.88 0 0 0 0 30 30 557 416 GG ImpactImpact 0.7900.790 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.7900.790 swsw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 ww 3.153.15 2.022.02 0 0 0 0 66 66 208 133 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.4000.400 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 GG ImpactImpact 0.6400.640 ww 0.000.00 0.000.00 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 0.000.00 0.000.00 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.080Frm Wall, 1/2" Gyp B 0.080 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC DftCathCeilDftCathCeil 0.4050.405 --1.591.59 1.221.22 77 77 122 94 209 209 332 256 FF DftFlorDftFlor 0.9890.989 --28.6828.68 0.000.00 77 11 315 0 209 19 545 0 6 c) AED excursion 69 -28 Envelope loss/gain 869 629 2142 1157 12 a) Infiltration 371 111 769 229 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 550 Subtotal (lines 6 to 13)1241 740 2911 1936 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 6 4 14 Subtotal 1241 740 2917 1941 15 Duct loads 12%14%152 101 12%14%357 265 Total room load 1393 841 3274 2206 Air required (cfm)Air required (cfm)48 49 113 128 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Duct System Summary Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.528 / 0.172 in H2O in H2O0.528 / 0.172 Lowest friction rate in/100ft0.133in/100ft0.133 Actual air flow cfm1567cfm1567 Total effective length (TEL) ft524 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3205.024.6VlFx0x08.00.2301512144444hBed 2 st2210.056.3VlFx0x08.00.1981761702756cBed 3 st5310.079.0VlFx0x06.00.13663881833hCabana Bath st6315.075.7VlFx0x07.00.135871272645hFoyer st6315.080.3VlFx0x09.00.1332011663144cGreat Room-A st6315.067.6VlFx0x09.00.1382011663144cGreat Room-B st3205.022.5VlFx0x04.00.2324145925hGuest Bath st2210.047.4VlFx0x08.00.2052031453173cKit/Dining st2210.055.0VlFx0x08.00.1992031453173cKit/Dining-A st3205.017.5VlFx0x07.00.2371531623371hLaundry st2210.045.1VlFx0x04.00.2071010218hPantry st5310.074.2VlFx0x08.00.1371351663441hRec Room st5310.083.7VlFx0x08.00.1341351663441hRec Room-A st5310.076.2VlFx0x07.00.1371211091892cVestibule Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 528 454 0.134 673 12.0 0x0 VinlFlx st2 st6 Peak AVF 460 489 0.133 623 12.0 0x0 VinlFlx st2 st2 Peak AVF 1459 1535 0.133 869 18.0 0x0 VinlFlx st3 Peak AVF 421 345 0.230 771 10.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb7 0x 3310 269 129.1 0.133 422 12.0 x0 0 VlFx rt2 rb1 0x 1700 176 90.3 0.191 505 8.0 x0 0 VlFx rt2 rb2 0x 2140 151 93.1 0.185 484 9.0 x0 0 VlFx rt2 rb4 0x 11650 1284 89.4 0.193 588 20.0 x0 0 VlFx rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 1880 1880 0.133 862 20.0 0x0 VinlFlx 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 3 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Duct System Summary Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.465 / 0.235 in H2O in H2O0.465 / 0.235 Lowest friction rate in/100ft0.117in/100ft0.117 Actual air flow cfm600cfm600 Total effective length (TEL) ft597 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4325.065.1VlFx0x05.00.1195958841cHers st4325.066.4VlFx0x04.00.1197596cHis st1220.033.6VlFx0x08.00.1831291603850hMaster Bath st4325.071.3VlFx0x07.00.1171091071566cMaster Bedroom st4325.063.4VlFx0x07.00.1201091071566cMaster Bedroom-A st1220.042.6VlFx0x07.00.1771091071566cMaster Bedroom-B st1220.033.9VlFx0x07.00.1831541362206cOffice st1220.034.0VlFx0x04.00.1834540646cWtr Clst Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 277 284 0.117 520 10.0 0x0 VinlFlx st1 st1 Peak AVF 720 720 0.117 674 14.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb6 0x 4770 457 200.3 0.117 446 14.0 x0 0 VlFx rt1 rb3 0x 2430 263 178.1 0.132 482 10.0 x0 0 VlFx rt1 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 4 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 720 720 0.117 516 16.0 0x0 VinlFlx 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Manual S Compliance Report Sep 29, 2020Date:A/H 1 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Cooling Equipment Design Conditions °F75.7Entering coil DB:Btuh30346Sensible gain:°F90.4Outdoor design DB: °F63.6Entering coil WB:Btuh10628Latent gain:°F77.4Outdoor design WB: Btuh40974Total gain:°F75.0Indoor design DB: cfm1567Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACX-047-230*+CBA27UHE-048-230*++TDRModel:LennoxManufacturer: cfm1567Actual airflow: % of load108Btuh32900Sensible capacity: % of load133Btuh14100Latent capacity: %70SHR:% of load115Btuh47000Total capacity: Heating Equipment Design Conditions °F68.7Entering coil DB:Btuh40869Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1567Actual airflow: °F50Temp. rise:% of load89kW10.7Output capacity: Meets all requirements of ACCA Manual S. 2021-Feb-12 13:37:55 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...t HVAC\TBD Noble Oaks Ln - Pereira Res -VCC.rup Calc = MJ8 Front Door faces: S 1336Job:Manual S Compliance Report Sep 29, 2020Date:A/H 2 Vicki Lynne NisaBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Pereira Residence, Villadelta Construction Corp, LLCFor: TBD Noble Oaks Ln, Port St Lucie, FL 34952 Cooling Equipment Design Conditions °F75.8Entering coil DB:Btuh10763Sensible gain:°F90.4Outdoor design DB: °F63.6Entering coil WB:Btuh4907Latent gain:°F77.4Outdoor design WB: Btuh15671Total gain:°F75.0Indoor design DB: cfm600Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACXS018-230A**+CBA25UH-018-230-**Model:LennoxManufacturer: cfm600Actual airflow: % of load117Btuh12600Sensible capacity: % of load110Btuh5400Latent capacity: %70SHR:% of load115Btuh18000Total capacity: Heating Equipment Design Conditions °F68.6Entering coil DB:Btuh18137Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm600Actual airflow: °F50Temp. rise:% of load86kW4.6Output capacity: Meets all requirements of ACCA Manual S. Job #: 1336 Performed by Vicki Lynne Nisa for: Pereira Residence TBD Noble Oaks Ln Port St Lucie, FL 34952 Air Calcs, LLC 7550 Hidden Hammock Ln Vero Beach, FL 32966 Phone: 772.800.8413 vickilynne@aircalcs.com Scale: 1 : 211 Page 1 Right-Suite® Universal 2021 21.0.03 RSU27054 2021-Feb-12 13:38:18 ...e Oaks Ln - Pereira Res -VCC.rup N Level 1 Garage 1 Garage 2 Laundry Storage Lin Guest Bath Back Hall Bed 2 Hallway Pantry Foyer Office Great Room Master Bedroom His Hers M Lin Wtr Clst Master Bath Bed 3 Rec Room Cabana Bath Vestibule Kit/Dining 12 x 12 176 cfm 12 x 8 162 cfm 12 x 8 176 cfm 8 x 4 45 cfm 12 x 12 214 cfm 12 x 8 214 cfm 8 x 4 10 cfm 12 x 12 203 cfm 12 x 12 203 cfm 8 x 4 7 cfm 10 x 6 59 cfm 10 x 10 160 cfm 12 x 8 127 cfm 12 x 12 263 cfm 12 x 8 154 cfm 12 x 8 109 cfm 12 x 8 109 cfm 8 x 4 45 cfm 10 x 6 88 cfm 10 x 10 166 cfm 10 x 10 166 cfm 12 x 12 201 cfm 12 x 12 201 cfm 12 x 12 331 cfm 10 x 6 121 cfm 7 " 4 "8 " 8 " 4 " 8 " 8 " 7 " 9 " 9 " 7 " 8 " 8 " 6 " 10 " 14 " 16 " 18 " 10 " 14 " 8 "7 " 4 " 12 " 12 " 10 " 4 " 5 " 7 " 7 " 24 x 18 477 cfm 36 x 18 1284 cfm 20 " 9 "8 " 12 " 10 x 6 109 cfm 7 " Ducts Penetrating the walls or ceiling separting the dwelling from the garage shall be construted of a min no. 26 gage sheet steel or other approved material Ducts penetrating the walls or ceiling separating the dwelling from the garage shall be constructed of a min no. 26 gage sheet steel or other approved material 4 " 80 CFM 4" Duct 4" Exhaust 4 " 80 CFM 4" Duct 4" Exhaust 6 " 120 CFM 6" Duct 6" Exhaust 6 " 120 CFM 6" Duct 6" Exhaust