Loading...
HomeMy WebLinkAboutAPPROVED , Electrical plan sht 9ELECTRICAL LOAD CALCULATIONS PER NEC 1 1741 S.F. 0 3 VOLT -AMPS 5223 VA 2 2 20A APPLIANCE CIRCUITS 3000 3 LAUNDRY 1500 4 DRYER 5000 5 RANGE 12000 6 1 WATER HEATER 4500 7 DISHWASHER 1200 8 REFRIGERATOR 1200 9 IRRIGATION PUMP OPTION 1800 10 MISC. 5000 TOTAL: 40423 VA FIRST 10 KW @ 100% REMAINDER @ 40% TOTAL: A/C HEAT @ 100% - TOTAL: 34169 240 = 142.3717 AMPS USE 200 AMP SERVICE 10000 12169 22169 12000 34169 VA ELECTRICAL NOTES ALL 120V RECEPTACLES INSTALLED IN BATHROOMS, GARAGES; OUTDOORS, IN UNFINISHED BASEMENTS, UNDER FLOOR AREAS, KITCHEN COUNTER TOPS, KITCHEN ISLAND AND WITHIN 6-FEET OF A SINK SHALL BE GROUND FAULT CIRCUIT INTERRUPTER PROTECTED BATHROOMS RECEPTACLE OUTLETS SHALL BE SUPPLIED BY AT LEAST ONE 20A BRANCH CIRCUIT, THIS CIRCUIT SHALL FEED NO OTHER OUTLETS ALL DWELLING UNIT BEDROOM BRANCH CIRCUITS FEEDING LIGHTING OR POWER OUTLETS OR SMOKE DETECTORS IN BEDROOMS SHALL BE PROTECTED, BY AN ARC -FAULT' CIRCUIT INTERRUPTERS LIGHTING FIXTURES LOCATED ABOVE SHOWER AND BATHTUB AREAS SHALL BE MOISTURE RESISTIVE RECEPTACLE OUTLETS SHALL BE SPACED SUCH THAT ANY POINT ALONG THE WALL AT THE FLOOR LEVEL IS NOT MORE THAN 6' FROM A RECEPTACLE WITHOUT CROSSING A DOORWAY. WALL SPACES GREATER THAN 2' IN WIDTH SHALL BE PROVIDED WITH A RECEPTACLE. RECEPTACLES IN THE FLOOR WITHIN 18" OF THE OF THE WALL ALSO MEET THE REQUIREMENT. THESE RECEPTACLES SHALL BE PROVIDED IN: KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, DENS, BEDROOMS, OR SIMILAR ROOMS. ALL SWITCHES ON A MULTIPLE SWITCHED CIRCUIT SHALL BE CONTROLLED BY THE DIMMER SWITCH ON THAT CIRCUIT. ALL RECESSEDFIXTURES SHALL BE LABELED AS BEING CERTIFIED TO HAVE A LEAKAGE RATING OF LESS THAN 2.0 AT 75 PASCAL. _ ALL OUTDOOR LIGHTING MUST BE HIGH EFFICACY OR i�.r��l t rl� e�i n,nnllTlrlAi ['.rAlt�/1f'f \A/ITtJ IA'ITr/1•]AI -' VVIY 11\VI�LLv v 1 PHOTOCONTROL. SMOKE DETECTORS SHALL SOUND AN ALARM AUDIBLE IN ALL SLEEPING AREAS. SMOKE DETECTORS SHALL BE "HARD WIRED"/INTERCONNECTED AND SHALL BE EQUIPPED WITH BATTERY BACKUP. PROVIDE LIFER OR OTHER APPROVED GROUND. ..PROVIDE TWO DEDICATED 20 AMP SMALL APPLIANCE BRANCH ' CIRCUITS FOR THE KITCHEN, LIMITED TO SUPPLYING WALL AND COUNTER SPACE OUTLETS ONLY. LIGHT FIXTURES LOCATED IN TUB OR SHOWER ENCLOSURES. SHALL BE LABLED "SUITABLE FOR WET LOCATIONS" OR "SUITABLE FOR DAMP LOCATIONS. INCANDESCENT LIGHTING FIXTURES RECESSED INTO INSULATED. CEILINGS SHALL BE I.C. RATED BY UL OR OTHER APPROVED AGENCY. ELECTRICAL WITHIN 6 FEET OF ATTIC ACCESS SHALL BE PROTECTED. NON-METALLIC SHEATHED CABLE SHALL BE SECURED BY STAPLES, CABLE TIES, STRAPS, HANGERS, OR SIMILAR AT INTERVALS NOT EXCEEDING 4-1/2 FEET AND WITHIN 12 INCHES I I OF EVERY CABINET, BOX OR FITTING. FLAT CABLES SHALL NOT ' > j� / ra^ VENT LECTRICAL PLAN NOTES > E BE STAPLED ON EDGE. _____ __ 00 j j j I i I I_ / I g�N 1: ARC FAULTS ARE RE URED EVERYWHERE ST�OR VENT Q `L \ GFI \I I X ( SPECIFIED IN NEC 2014 210.12. _ f \ 2. ALL RECEPTACLES MUST BE TAMPER RESISTANT y -�- \• \M 3 sw NEC 2014 406.11 NOTE TO ELECTRICIAN. ELECTRICAL PLAN KEY NOTES a ALL BEDROOM OUTLETS MUST BE ARC FAULT PROTECTION El- \ II SD WASHER _ / r\ OUTLETS PER NEC 210 12(b) - [j / ,, / LIB �, , , \, � I ,'\ j I _ / v I \ T ACCESS WITH LIGHT & SWITCH r `IJ I I ILK 1 AT IC w ,/ jj — —s^ " l T RS ARE TO BE IN H w rl I =NTR I / 3 I SMOKE &CARBON MONOXIDE DETEC O EAC cn \, iu � � ,� .� ` : � / ^ V 3 VENT MASTER — _ _ _ ¢�/' J I I z BEDROOM; COMMON AREA NEAR BEDROOMS, ON EACH STORY, LAv \ I E O STAIRS GOING UP. �-------- I I DINING ROOM. � _ � AND CLOSE T 1 � B E D RHO■��///����#3 � ^ I \ < ^ ( M I . I 3 VEN BATH ROO o .. _ y I w r SMOKE & CARBON MONOXIDE DETECTORS SHALL BE WIRED TO y L _:— J i \ I .. � � I � ,� �� -' BLOCK & a VP 13 y ^ we COMPLY W/ NFPA 72. > i <>, { l)FOR.y 3 C WIRE �� � ," �� /,.� HWR .r Kxxxxxxx <k \ r r ,, v <. I y t , i / . , FILING FAN T BOX FOR ALL FAN PREWIRE$. � � ,- a^ USE UL LISTED SUPPORT . Y � --..., � _ g" TUB SHWR ,� 1 J GFI a WP GF �. LAU N �R S SHALL BE VENTED THROUGH THE ROOF. �i GD x . I s ALL EXHAUST FAN y WH \ % t� vvc >. _ J. L J Cry WITH E EDITION HE i ELECTRICAL DESIGN SHALL COMPLY THE O OF T Y 3 w j VP VP s j \ NECS ADOPTED BY THE FLORIDA BUILDING CODE. I- Xr r _ � � k / EC w W _ it ;�, - j _ _ ��.. c to ,> z 1 ... .>x7 0. J 1 _ \ I 1 I \ _ ,, _ — — — — — — - — — i3T— — — _. -_ _ — — — ___ \ v_v.1 :, `✓ �--i. r.rwrr\ \ mr.lr e%" A 1 1 MC! l/CAITCI-1 TLJ�lII InU TLJC �!'1!'1C /lam SCALE: SCALE: 1 /4"=V-0" (UNLESS OTHERWISE NOTED) JOB #: 21.0012—PAC DRAWN BY: CDE CHECKED -BY: CDE-JM