HomeMy WebLinkAboutAPPROVED , Electrical plan sht 9ELECTRICAL LOAD CALCULATIONS PER NEC
1
1741 S.F. 0 3 VOLT -AMPS
5223 VA
2
2 20A APPLIANCE CIRCUITS
3000
3
LAUNDRY
1500
4
DRYER
5000
5
RANGE
12000
6
1 WATER HEATER
4500
7
DISHWASHER
1200
8
REFRIGERATOR
1200
9
IRRIGATION PUMP OPTION
1800
10
MISC.
5000
TOTAL:
40423 VA
FIRST 10 KW @ 100%
REMAINDER @ 40%
TOTAL:
A/C HEAT @ 100% -
TOTAL:
34169
240 = 142.3717 AMPS USE 200 AMP SERVICE
10000
12169
22169
12000
34169 VA
ELECTRICAL NOTES
ALL 120V RECEPTACLES INSTALLED IN BATHROOMS, GARAGES;
OUTDOORS, IN UNFINISHED BASEMENTS, UNDER FLOOR AREAS,
KITCHEN COUNTER TOPS, KITCHEN ISLAND AND WITHIN 6-FEET
OF A SINK SHALL BE GROUND FAULT CIRCUIT INTERRUPTER
PROTECTED
BATHROOMS RECEPTACLE OUTLETS SHALL BE SUPPLIED BY
AT LEAST ONE 20A BRANCH CIRCUIT, THIS CIRCUIT SHALL
FEED NO OTHER OUTLETS
ALL DWELLING UNIT BEDROOM BRANCH CIRCUITS FEEDING
LIGHTING OR POWER OUTLETS OR SMOKE DETECTORS IN
BEDROOMS SHALL BE PROTECTED, BY AN ARC -FAULT'
CIRCUIT INTERRUPTERS
LIGHTING FIXTURES LOCATED ABOVE SHOWER AND BATHTUB
AREAS SHALL BE MOISTURE RESISTIVE
RECEPTACLE OUTLETS SHALL BE SPACED SUCH THAT ANY
POINT ALONG THE WALL AT THE FLOOR LEVEL IS NOT MORE
THAN 6' FROM A RECEPTACLE WITHOUT CROSSING A
DOORWAY. WALL SPACES GREATER THAN 2' IN WIDTH SHALL
BE PROVIDED WITH A RECEPTACLE. RECEPTACLES IN THE
FLOOR WITHIN 18" OF THE OF THE WALL ALSO MEET THE
REQUIREMENT. THESE RECEPTACLES SHALL BE PROVIDED IN:
KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
DENS, BEDROOMS, OR SIMILAR ROOMS.
ALL SWITCHES ON A MULTIPLE SWITCHED CIRCUIT SHALL BE
CONTROLLED BY THE DIMMER SWITCH ON THAT CIRCUIT.
ALL RECESSEDFIXTURES SHALL BE LABELED AS BEING
CERTIFIED TO HAVE A LEAKAGE RATING OF LESS THAN 2.0 AT
75 PASCAL. _
ALL OUTDOOR LIGHTING MUST BE HIGH EFFICACY OR
i�.r��l t rl� e�i n,nnllTlrlAi ['.rAlt�/1f'f \A/ITtJ IA'ITr/1•]AI -'
VVIY 11\VI�LLv v 1
PHOTOCONTROL.
SMOKE DETECTORS SHALL SOUND AN ALARM AUDIBLE IN ALL
SLEEPING AREAS.
SMOKE DETECTORS SHALL BE "HARD WIRED"/INTERCONNECTED
AND SHALL BE EQUIPPED WITH BATTERY BACKUP.
PROVIDE LIFER OR OTHER APPROVED GROUND.
..PROVIDE TWO DEDICATED 20 AMP SMALL APPLIANCE BRANCH '
CIRCUITS FOR THE KITCHEN, LIMITED TO SUPPLYING WALL AND
COUNTER SPACE OUTLETS ONLY.
LIGHT FIXTURES LOCATED IN TUB OR SHOWER ENCLOSURES.
SHALL BE LABLED "SUITABLE FOR WET LOCATIONS" OR
"SUITABLE FOR DAMP LOCATIONS.
INCANDESCENT LIGHTING FIXTURES RECESSED INTO INSULATED.
CEILINGS SHALL BE I.C. RATED BY UL OR OTHER APPROVED
AGENCY.
ELECTRICAL WITHIN 6 FEET OF ATTIC ACCESS SHALL BE
PROTECTED.
NON-METALLIC SHEATHED CABLE SHALL BE SECURED BY
STAPLES, CABLE TIES, STRAPS, HANGERS, OR SIMILAR AT
INTERVALS NOT EXCEEDING 4-1/2 FEET AND WITHIN 12 INCHES
I I OF EVERY CABINET, BOX OR FITTING. FLAT CABLES SHALL NOT
' > j� / ra^ VENT LECTRICAL PLAN NOTES
> E BE STAPLED ON EDGE.
_____ __
00 j j j I i
I I_ / I g�N 1: ARC FAULTS ARE RE URED EVERYWHERE
ST�OR VENT Q
`L \ GFI \I I X ( SPECIFIED IN NEC 2014 210.12.
_ f \
2. ALL RECEPTACLES MUST BE TAMPER RESISTANT
y -�- \• \M 3
sw NEC 2014 406.11 NOTE TO ELECTRICIAN.
ELECTRICAL PLAN KEY NOTES
a ALL BEDROOM OUTLETS MUST BE ARC FAULT PROTECTION
El-
\ II SD WASHER
_ / r\ OUTLETS PER NEC 210 12(b)
- [j / ,, / LIB �, , , \, �
I ,'\ j I _ / v I \ T ACCESS WITH LIGHT & SWITCH
r `IJ I I ILK
1 AT IC
w ,/
jj
— —s^ " l T RS ARE TO BE IN H
w rl I =NTR I / 3 I SMOKE &CARBON MONOXIDE DETEC O EAC
cn
\, iu � � ,� .� ` : � / ^ V 3 VENT
MASTER
— _ _ _ ¢�/' J I I z BEDROOM; COMMON AREA NEAR BEDROOMS, ON EACH STORY,
LAv \ I E O STAIRS GOING UP.
�-------- I I DINING ROOM. � _ � AND CLOSE T
1 � B E D RHO■��///����#3 � ^ I \
< ^ (
M I . I 3 VEN
BATH ROO o .. _ y
I w r SMOKE & CARBON MONOXIDE DETECTORS SHALL BE WIRED TO
y L _:— J i \ I
..
� � I � ,� �� -' BLOCK & a
VP 13 y ^ we COMPLY W/ NFPA 72.
> i <>, {
l)FOR.y 3
C WIRE �� � ," �� /,.� HWR
.r
Kxxxxxxx
<k
\ r
r ,, v <. I
y t , i
/ . , FILING FAN
T BOX FOR ALL FAN PREWIRE$.
� � ,- a^ USE UL LISTED SUPPORT
. Y � --..., � _ g" TUB SHWR
,� 1 J
GFI a WP GF �.
LAU N �R
S SHALL BE VENTED THROUGH THE ROOF.
�i GD x . I s ALL EXHAUST FAN
y WH \ % t� vvc
>. _
J. L J Cry
WITH E EDITION HE
i ELECTRICAL DESIGN SHALL COMPLY THE O OF T
Y 3
w j VP VP s
j \ NECS ADOPTED BY THE FLORIDA BUILDING CODE.
I- Xr r _ � � k / EC
w
W _ it ;�, - j _ _ ��..
c to ,> z 1
... .>x7 0. J 1 _ \ I 1 I \ _ ,, _ — — — — — — - — — i3T— — — _. -_ _ — — — ___ \ v_v.1 :, `✓ �--i. r.rwrr\ \ mr.lr e%" A 1 1 MC! l/CAITCI-1 TLJ�lII InU TLJC �!'1!'1C /lam
SCALE:
SCALE: 1 /4"=V-0"
(UNLESS OTHERWISE NOTED)
JOB #:
21.0012—PAC
DRAWN BY:
CDE
CHECKED -BY:
CDE-JM