HomeMy WebLinkAboutREVIEWED, 2020 CODE- MANUAL JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Project Summary FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information WETMILLER ADDITION, COMPLETE CONSTRUCTION OF THE TREASURE COAST, LLC.For: 4811 TREE TOP TRAIL, FORT PIERCE, FL 34951 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh12023 Struc ture Btuh14066 Ducts Btuh2790 Ducts Btuh4052 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh14813 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh17212 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3085 Ducts Btuh1062 Central vent (0 cfm)Btuh0 CoolingHeating (none) 10591059Area (ft²)Equipment latent load Btuh4147 99009900Volume (ft³) Air changes/hour 0.230.45 Equipment Total Load (Sen+Lat)Btuh21359 Equiv. AVF (cfm)3874 Req. total capacity at 0.70 SHR ton2.0 Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1624AJ1NA AHRI ref Coil RH1T2417STANJA AHRI ref 7940891 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW4.6 Sensible cooling Btuh16800 Heating output Btuh15656 Latent cooling Btuh7200 Temperature rise °F18 Total cooling Btuh24000 Actual air flow cfm800 Actual air flow cfm800 Air flow factor cfm/Btuh0.054 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.81 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House CABANA 2 Exposed wall 113.0 ft 22.0 ft 3 Room height 9.3 ft 8.0 heat/coolft 4 Room dimensions ft55.0x1.0 5 Room area 1059.0 ft²55.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 1.901.90 1.181.18 88 71 136 84 48 31 60 37 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 17 17 183 173 17 17 183 173 .WW 12E-0sw12E-0sw 0.0680.068 ee 1.901.90 1.181.18 308 248 472 293 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 60 0 1092 2026 0 0 0 0 11 WW 12E-0sw12E-0sw 0.0680.068 ss 1.901.90 1.181.18 320 304 579 360 48 40 76 47 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 16 16 291 240 8 8 146 120 WW 12E-0sw12E-0sw 0.0680.068 ww 1.901.90 1.181.18 284 210 401 249 80 80 152 95 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 6 0 109 203 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 27 0 488 905 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 41 0 742 1377 0 0 0 0 CC 16B-30md16B-30md 0.0320.032 --0.900.90 1.601.60 1059 1059 949 1694 55 55 49 88 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1059 113 4297 0 55 22 837 0 6 c) AED excursion 86 -81 Envelope loss/gain 9738 7690 1502 479 12 a) Infiltration 2285 626 402 110 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 5750 500 Subtotal (lines 6 to 13)12023 14066 1904 1089 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 12023 14066 1904 1089 15 Duct loads 23%29%2790 4052 23%29%442 314 Total room load 14813 18118 2346 1402 Air required (cfm)Air required (cfm)800 800 127 62 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name TOILET M BATH 2 Exposed wall 5.0 ft 11.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft5.0x4.0 ft172.0x1.0 5 Room area 20.0 ft²172.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 1.901.90 1.181.18 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12E-0sw12E-0sw 0.0680.068 ee 1.901.90 1.181.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 11 WW 12E-0sw12E-0sw 0.0680.068 ss 1.901.90 1.181.18 40 40 76 47 40 32 61 38 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 8 8 146 120 WW 12E-0sw12E-0sw 0.0680.068 ww 1.901.90 1.181.18 0 0 0 0 48 42 80 50 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 6 0 109 203 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16B-30md16B-30md 0.0320.032 --0.900.90 1.601.60 20 20 18 32 172 172 154 275 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 20 5 190 0 172 11 418 0 6 c) AED excursion -28 -6 Envelope loss/gain 284 51 968 679 12 a) Infiltration 91 25 201 55 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 300 Subtotal (lines 6 to 13)376 376 1169 1034 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 376 376 1169 1034 15 Duct loads 23%29%87 108 23%29%271 298 Total room load 463 485 1440 1332 Air required (cfm)Air required (cfm)25 21 78 59 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 1 M WIC 2 2 Exposed wall 8.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft8.0x6.0 ft8.0x6.0 5 Room area 48.0 ft²48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 1.901.90 1.181.18 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12E-0sw12E-0sw 0.0680.068 ee 1.901.90 1.181.18 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 11 WW 12E-0sw12E-0sw 0.0680.068 ss 1.901.90 1.181.18 64 64 122 76 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 1.901.90 1.181.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16B-30md16B-30md 0.0320.032 --0.900.90 1.601.60 48 48 43 77 48 48 43 77 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 48 8 304 0 48 0 0 0 6 c) AED excursion -13 -5 Envelope loss/gain 469 139 43 71 12 a) Infiltration 146 40 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)615 179 43 71 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 615 179 43 71 15 Duct loads 23%29%143 52 23%29%10 21 Total room load 758 231 53 92 Air required (cfm)Air required (cfm)41 10 3 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM KITCHEN 2 Exposed wall 37.0 ft 9.0 ft 3 Room height 8.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft16.0x16.0 ft13.0x9.0 5 Room area 256.0 ft²117.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 1.901.90 1.181.18 40 40 76 47 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12E-0sw12E-0sw 0.0680.068 ee 1.901.90 1.181.18 128 98 187 116 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 30 0 546 1013 0 0 0 0 11 WW 12E-0sw12E-0sw 0.0680.068 ss 1.901.90 1.181.18 128 128 244 151 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 1.901.90 1.181.18 0 0 0 0 108 40 77 48 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 27 0 488 905 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 41 0 742 1377 CC 16B-30md16B-30md 0.0320.032 --0.900.90 1.601.60 256 256 229 410 117 117 105 187 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 256 37 1407 0 117 9 342 0 6 c) AED excursion -196 589 Envelope loss/gain 2689 1542 1754 3106 12 a) Infiltration 676 185 247 68 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1500 2000 Subtotal (lines 6 to 13)3365 3227 2000 5173 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3365 3227 2000 5173 15 Duct loads 23%29%781 930 23%29%464 1490 Total room load 4146 4156 2465 6663 Air required (cfm)Air required (cfm)224 184 133 294 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING LAUNDRY 2 Exposed wall 15.0 ft 6.0 ft 3 Room height 12.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft16.0x15.0 ft13.0x6.0 5 Room area 240.0 ft²78.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12E-0sw12E-0sw 0.0680.068 nn 1.901.90 1.181.18 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12E-0sw12E-0sw 0.0680.068 ee 1.901.90 1.181.18 180 150 286 177 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 30 0 546 1013 0 0 0 0 11 WW 12E-0sw12E-0sw 0.0680.068 ss 1.901.90 1.181.18 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 12E-0sw12E-0sw 0.0680.068 ww 1.901.90 1.181.18 0 0 0 0 48 48 91 57 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 CC 16B-30md16B-30md 0.0320.032 --0.900.90 1.601.60 240 240 215 384 78 78 70 125 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 240 15 570 0 78 6 228 0 6 c) AED excursion -138 -32 Envelope loss/gain 1617 1437 389 149 12 a) Infiltration 411 113 110 30 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 900 250 Subtotal (lines 6 to 13)2028 2450 499 430 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2028 2450 499 430 15 Duct loads 23%29%471 706 23%29%116 124 Total room load 2499 3155 615 553 Air required (cfm)Air required (cfm)135 139 33 24 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-16 14:41:31 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet FEB. 16, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name PANTRY 2 Exposed wall 0 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft5.0x5.0 5 Room area 25.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-0sw 0.068 n 1.90 1.18 0 0 0 0 .D 11D0 0.390 n 10.92 10.34 0 0 0 0 .W 12E-0sw 0.068 e 1.90 1.18 0 0 0 0 .G 2 glazing, clr low-e 0.650 e 18.20 33.77 0 0 0 0 11 W 12E-0sw 0.068 s 1.90 1.18 0 0 0 0 G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 W 12E-0sw 0.068 w 1.90 1.18 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 C 16B-30md 0.032 -0.90 1.60 25 25 22 40 F 22A-tph 1.358 -38.02 0.00 25 0 0 0 6 c) AED excursion -3 Envelope loss/gain 22 37 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)22 37 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 22 37 15 Duct loads 23%29%5 11 Total room load 28 48 Air required (cfm)1 2 2021-Feb-16 14:41:34 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary FEB. 16, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information WETMILLER ADDITION, COMPLETE CONSTRUCTION OF THE TREASURE COAST, LLC.For: 4811 TREE TOP TRAIL, FORT PIERCE, FL 34951 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm800cfm800 Total effective length (TEL)ft165 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st1115.019.8VlFx0x06.01.000621272346hCABANA st3135.025.5VlFx0x08.01.000147673332cKITCHEN st3135.029.5VlFx0x08.01.000147673332cKITCHEN-A st3135.029.1VlFx0x04.01.0002433615hLAUNDRY st2115.017.7VlFx0x08.01.0001391353155cLIVING st1115.014.8VlFx0x06.01.00059781440hM BATH st2115.018.1VlFx0x04.01.0001041758hM WIC 1 st1115.018.3VlFx0x04.01.0004392cM WIC 2 st2115.015.7VlFx0x07.01.000921122073hMASTER BEDROOM st2115.010.7VlFx0x07.01.000921122073hMASTER BEDROOM-A st3135.027.5VlFx0x04.01.0002148cPANTRY st1115.018.8VlFx0x05.01.0002125463hTOILET Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 168 321 1.000 588 10.0 0x0 VinlFlx st1 st1 Peak AVF 400 467 1.000 708 11.0 0x0 VinlFlx st2 Peak AVF 400 333 1.000 733 10.0 0x0 VinlFlx 2021-Feb-16 14:41:34 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...ocumnets\Wrightsoft HVAC\WETMILLER ADDITION.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 8000 800 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������