HomeMy WebLinkAboutGuba gas regulator specs 1 22H, R222H, R222, R232A and R232E Series
LP-Gas egulators
VENT POINTED DOWN �•�m _ 71r
r}
T14446-A2
Figure 2.Regulator with Vent Pointed Down
Table 1. Relief Valve Specifications
TYPICAL SETPOINT
NOMINAL RELIEF VALVE MAXIMUM OUTLET PRESSURE WITH DISC REMOVED
START-TO-DISCHARGE
TYPE Inlet Pressure Maximum Outlet Pressure
psi bar psi bar psig bar psig bar
R122H 10 0.69 16 1.10 250 17.2 Not Applicable
5 0.35 9 0.62
R222H 10 0.69 16 1.10 250 17.2 Not Applicable
R222 11 in.w.c. 27 mbar 1 0.07 30 2.07 2.0 0.14
R232At1) 11 in.w.c. 27 mbar 1 0.07 2.0 0.14
250 17.2
R232110) 2 0.14 3.5 0.24 5.0 0.35
1.For integral two-stage regulators,the second stage disc is removed.
Table 2. Capacity, Connection Sizes and Vent Orientation _
REGULATOR TYPE CAPACITY INLET OUTLET OUTLET 3/8 IN.FNPT SCREENED VENT
APPLICATION NUMBER BTU/HR CONNECTION CONNECTION PRESSURE STANDARD LOCATION
PROPANEM SETTING
First Stage R122H-AAJ 1,100,000 1/4 in.FNPT 1/2 in.FNPT 10 psig/0.69 bar Over Outlet')
R222H-BGK 1,700,000 1/2 in.FNPT 1/2 in.FNPT
R222H-DGK 2,000,000 3/4 in.FNPT 3/4 in.FNPT
/
R222H-HGK 1,700,000 FPOL 1!2 in.FNPT 5 psig 0.35 bar
R222H-JGK 1,875,000 FPOL 3/4 in.FNPT
First Stage Over Outlet
R222H-BGJ 1,800,000 1/2 in.FNPT 1/2 in.FNPT
R222H-DGJ 2,000,000 3/4 in.FNPT 3/4 in.FNPT
(
R222H-HGJ 1,800,000 FPOL 1/2 in.FNPT 10 psig 0.69 bar
R222H-JGJ 1,875,000 FPOL 3/4 in.FNPT
R222-BAF Over Inlet
Second Stage 650,000 1/2 in.FNPT 1/2 in.FNPT
R222-BAFXA Over Outlet
R232A-BBF 550,000 1/2 in.FNPT 1/4 in.FNPT 11 in.w.c./ First Stage(3):Down
Integral R232A-HBF FPOL 27 mbar Second Stage:Over Outlet
Two-Stage R232A-BBFXA 550,000 1/2 in.FNPT 1/4 in.FNPT First Stage:Opposite Gauge Taps
R232A-HBFXA FPOL Second Stage:Opposite Gauge Taps
Integral Two psig R232E-BBH 1/4 in.FNPT First Staget3):Down
Service 500,000 1/2 in.FNPT 2 psig/0.14 bar
R232E-HBH FPOL Second Stage:Over Outlet
1.Capacities Based on:
Second Stage:10 psig/0.69 bar with 2 in.w.c./5 mbar droop.
Integral Two Stage:30 psig/2.07 bar and 2 in.w.c./5 mbar droop.
Integral Two psig Service Regulator:30 psig/2.07 bar inlet pressure and 20%droop.
First Stage:30 psig/2.07 bar inlet pressure and 20%droop.
2.Also available with vent apposite gauge taps.
3.Integral First Stage Vent size:7/16-24 UN thread for 1/4 in.OD copper tube inverted flare fitting.
3
andRegulators
Table 2. Capacity, Connection Sizes, and Vent Orientation
CAPACITY OUTLET 3/4-INCH NPT
REGULATOR TYPE BTU/HR INLET OUTLET PRESSURE SCREENED
APPLICATION NUMBER PROP ViR CONNECTION CONNECTION SETTING VENT STANDARD
LOCATION
R622-BCF 875,000 1/2-inch FNPT 1/2-inch FNPT
R642-DFF 900,000
3/4-inch FNPT '11 inches w.c./
R652-DFF 1,000,000 27 mbar
3/4-inch FNPT
R622-CFF 1/2-inch FNPT
Second P.622-DFF 3/4-inch FNPT Stage 1,400,000 Over Inlet
R622-CFGXA 1,125,000 1/2-inch FNPT 18 inches w.c./
3/4-inch FNPT 45 mbar
HSRL-BFCtzI 3/4-inch FNPT 11 inches w.c./
2,100,000 27 mbar
HSRL-CFCtzI 1-inch FNPT 1-inch FNPT
R632A-BCF 850,000 1/2-inch FNPT 114-inch FNPT First Stage(`):R632A-I-ICF FPOL 11 inches w.c.! Down
R632A-CFF 950,000 114-inch FNPT 27 mbar Second Stage:
3/4-inch FNPT Over Outlet
Integral R632A-JFF 850,000 FPOL
Two-Stage R632A-BCFXA 114-inch FNPT t,t.
850,000 1/2-inch FNPT First Stage
R632A-HCFXA FPOL 11 inches w.c/ Opposite gauge taps
R632A-CFFXA 950,000 1/4-inch FNPT 27 mbar Second Stage:
R632A-JFFY.A 850,000 FPOL 3/4-inch FNPT Opposite gauge taps
R632E-BCH 850,000 1/4-inch FNPT First Stage('):
Integral 1/2-inch FNPT Down
9 R632E-HCH 900,000 FPOL
2 psig/0.14 bar 2 psig/0.14 bar
Service R632E-CFH 1/4-inch FNPT Second Stage:
R632E-JFH
850,000 FPOL 3/4-inch FNPT Over Outlet
R622E-BCH 1,250,000 1/2-inch FNPT 1/2-inch FNPT
2 psig/0.14 bar R622E-DCH 1.500.000 2 psig/0.14 bar Ovgr Inlet
Service 3/4-inch FNPT 314-inch FNPT
R652E-DFH 1,400,000
R622H-BGK 2,000,000 1/2-inch FNPT 5 psig/0.35 bar
R622H-BGJ
1/2-inch FNPT
R622FI-HGJ 2.100,000 10 psig/0.69 bar
First Stage R622Fl-1-IGJKA FPOL Over Outlet
R622H-JGI< 5 psig/0.35 bar
2,250,000
R622H-JGJ 3/4-inch FNPT
10 psig/0.69 bar
R622H-DGJ 2,400,000 3/4-inch FNPT
1. Capacities Based on:
Second Stage:10 psig/0.69 bar inlet pressure and 2 inches w.c./5 mbar droop.
Integral Two-stage:30 psig 12.1 bar and 2 inches w.c./5 mbar droop.
Integral Two psig Service:30 psig/2.07 bar and 20%droop.
2 psig/0,14 bar Service:10 psig/0.69 bar inlet pressure and 20%droop.
First Stage:30 psig/2.1 bar inlet pressure and 20%droop.
2. Straight globe valve body configuration.
3. Integral First Stage Vent size:7/16-24 UN thread for 1/4-inch OD copper tube inverted flare fitting.
Replace old pigtails. Blow out any debris,dirt or copper Installation Location
sulfate in the copper tubing and the pipeline.
® Apply pipe compound to the male threads of the pipe ® The installed regulator should be adequately
before installing the regulator. protected from vehicular traffic and damage from
other external sources.
Make sure gas flow through the regulator is in the same
direction as the arrow on the body. "inlet"and"Outlet" a Install the regulator with the vent pointed vertically
connections are clearly marked. down, see Figure 2. If the vent cannot be installed
in a vertically down position,the regulator must be
installed under a separate protective cover. Installing
4