Loading...
HomeMy WebLinkAboutBuilding PlansINSTALLATION NOTES AND SPECIFICATIONS 1. DESIGN IS FOR MAXIMUM 30'-0" WIDE X 16'-0" EAVE HEIGHT UTILITY STRUCTURES. 2, DESIGN WAS DONE IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE (FBC) 7TH EDITION. _ 3. DESIGN LOADS ARE AS FOLLOWS: A) DEAD LOAD =15 PSF B) LOVE LOAD =12 PSF C) GROUND SNOW LOAD = 0 PSF (24'-0" WITH U-CHANNEL RAFTER TIE) 4. ULTIMATE WIND SPEED 180 MPH (NOMINAL WIND SPEED 140 MPH) MAXIMUM RAFTER / POST AND END POST SPACING = 4'4' (UNLESS NOTED OTHERWISE). 5. RISK CATEGORY:1 6. WIND EXPOSURE CATEGORY: B 7. SPECIFICATIONS APPLICABLE TO 26 GAUGE METAL PANELS FASTENED DIRECTLY TO 3" x3"x3/16" TUBE STEEL (TS) (UNLESS NOTED OTHERWISE). 8. AVERAGE FASTENER SPACING ON -CENTERS ALONG RAFTERS OR HAT CHANNELS, AND COLUMNS (INTERIOR OR END) = 6" O.C. (MAX). 9. FASTENERS CONSIST OF Y4" X 3/a' SELF DRILLING FASTENER (SDF), USE CONTROL SEAL WASHER WITH EXTERIOR FASTENERS SPECIFICATIONS APPLICABLE ONLY FOR MEAN ROOF HEIGHT OF 20'-0" OR LESS, AND ROOF SLOPES OF 14" (3:12 PITCH) OR LESS SPACING REQUIREMENTS FOR OTHER ROOF HEIGHTS AND / OR SLOPES MAY VARY. 10. WIND FORCES GOVERN OVER SEISMIC FORCES SEISMIC PARAMETERS ANALYZED ARE: SOIL SITE CLASS = D RISK CATEGORY IAI/111 R= 3.25 ID=1.0 BIDS = TBD V = CSW SDI = TBD FRAMING MEMBER NOTES: 1. ROOF RAFTERS TO BE 3"x3"x3/16" TUBE STEEL (MIN.) 2. KICKERS TO MATCH ROOF RAFTER 3. FASTEN RAFTER TO COLUMN W/ 1/2" THRU-BOLT 4. FASTEN KICKER TO RAFTER/COLUMN W/ 1/2" THRU-BOLT 5. COLUMN TO BE 3"x3"x1/4" TUBE STEEL (MIN.) 6. BASE -RAIL TO MATCH COLUMN 7. COLUMN TO BE WELDED TO BASE -RAIL 8. GROUND ANCHOR SIZE TO BE 1/2"x4" EMBEDMENT (MIN.) TABLE 1 RAFTER / POST OR END POST SPACING WIND SPEED X 5 150 5'-0" O.C. 150 < X 5 180 ,PRODUCT APPROVAL: 1 ROOF PANEL APPROVAL CODE 17031.1 2 WALL PANEL APPROVAL CODE 17021.1 3 ELIXIR DOOR APPROVAL CODE 17996.3 4 ASTA FL APPROVAL CODE FL7074.2 5- KINRO-WINDOW _ _ _ _ APPROVAL CODE 993.7 PANELS APPROVAL CODE 14024.1 j9GA LAP SIDINGEEEEE APPROVAL CODE 31737.1 NOTE: PRODUCT APPROVAL CODES PROVIDED BY OTHERS FOR SITE SPECIFIC PLANS ONLY 3 2 O O O 2 O O 2 O3 2 WINDOW AND DOOR NOTE EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING LABORATORY, AND BEAR AN AAMA OR WDMA OR OTHER APPROVED LABEL INDENTIFYING THE MANUFACTURER, PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT EVALUATION ENTITY TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF THE FOLLOWING SPECIFICATION. ANSI/AAMA/NWWDA 101/1S 2/97 THE CONSTRUCTION SHALL BE TESTED IN ACCORDANCE WITH ASTM E 330, STANDARD TEST METHODS FOR STRUCTURAL PERFORMANCE OF EXTERIOR WINDOWS, CURTAIN WALLS, AND DOORS BY UNIFORM STATIC AIR PRESSURE. DESIGN WAS DONE IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE 7TH ED. (FBC) WITH 2O12 SUPPLEMENT AMENDMENTS 2006 INTERNATIONAL BUILDING CODE (IBC), 2009 IBC AND 2012 IBC. GENERAL NOTES: 1, ALL STEEL SHALL BE 50 KSI STEEL. 2, FASTEN METAL ROOF AND WALL PANELS TO FRAMING WITH 1/4" X 3/4" SELF DRILLING FASTENERS WITH CONTROL SEAL WASHER @ 4" O.C. AVERAGE. 3, ALL FIELD CONNECTIONS SHALL BE 1/4" X 3/4" SELF DRILLING SCREWS. 4. ALL SHOP CONNECTIONS SHALL BE WELDED. 5, CONCRETE EXPANSION ANCHORS SHALL BE WEJ-IT ANKR-TITE MODEL AT 1252, OR SLEEVE ANCHOR MODEL HSA 1260, OR EQUIVELENT. GROUND ANCHOR REQUIREMENTS ARE 1@ EACH CORNER & ONE EVERY -INTERIOR RAFTER POST LOCATION: -- - - AT A MAXIMUM 4'-0" O.C., AND BOTH SIDES OF OPENINGS WHERE BASE RAIL IS ABSENT. GROUND ANCHORS ARE NOT REQUIRED FOR CONCRETE FOOTING AND/OR CONCRETE SLAB CONSTRUCTION. 6, POST/RAFTER BRACING: BRACE ON EVERY POST/RAFTER CONNECTION, EXCEPT FOR END WALLS. HELIX ANCHOR NOTES: 1. FOR VERY DENSE AND! OR CEMENTED SANDS, COARSE GRAVEL AND COBBLES, CALICHE, PRELOADED SILTS AND CLAYS, USE MINIMUM (2) 4" HELICES WITH MINIMUM 30" EMBEDMENT OR SINGLE 6' HELIX WITH MINIMUM 50" EMBEDMENT. 2. FOR CORAL USE MINIMUM (2) 4" HELICES WITH MINIMUM 30" EMBEDMENT OR SINGLE 6" HELIX WITH MINIMUM 50. EMBEDMENT. 3. FOR MEDIUM DENSE COARSE SANDS, SANDY GRAVELS, VERY �/ EMBEDMENT. SILTS, AND CLAYS USE MINIMUM (2) 4" HELICES WITH T-0" (TI P) 50N G MBEDMENTORSINGLE HELIXWITHMINIMUM 4. FOR LOOSE TO MEDIUM DENSE SANDS, FIRM TO STIFF CLAYS AND SILTS ALLUVIAL FILL, USE MINIMUM (2) S' HELICES WITH MINIMUM 50" EMBEDMENT. 5. FOR VERY LOOSE TO MEDIUM DENSE SANDS FIRM TO STIFFER CLAYS AND SILTS, ALLUVIAL FILL US MINIMUM (2) S" HELICES WITH MINIMUM 60" EMBEDMENT. ,,b 9COPY 9�02 �' REvrOw U k=Un CODE COMPLIANCE Sio LVCIE BOC Gc�N TY �ALN WIND PRESSURES ZONE DESIGN PRESSURE (PSF) POSITIVE NEGATIVE 1 25.7 54.6 2e 25.7 -64.6 2n 25.7 79.0 2r 25.7 -79.0 3e 25.7 -79.0 3r 25.7 -91.4 q 36.7 -40.0 5 36.7 -48.0 Engineer: Kent Bice FL License #: 50421 COM 30468 02/23/21 U Z U) Z J_ m J Lu LLI CD Z W O CD 'Q V w z 0 9H y a o o o� � O N w " €� co �E ) o w � aE Z w U �I zTE m +' al o o LU .� of a U J sir 1 of 5 0 Z VARIES 26 GA R-PANEL SIDE OR END 26 GA AG PANEL PANELS METAL DECK SEE TABIEt SEE TABLET II SEE TABlE1 SEE JT�A�LETABIEt TYP SIDE ELEVATION NOT TO SCALE �G GROUND ANCHORS @ EACH END BOW POST AND EVERY OTHER INTERIOR BOW POST LOCATION (SEE DETAIL 4 SHEET 3) SIDE ELEVATION NOT TO SCALE . GALVANIZED METAL ROOF _S FASTENED TO RAFTERS 3'x3"xt/4" TS BASE RAIL TYPICAL BOW SECTION NOT TO SCALE TYP END ELEVATION NOT TO SCALE VARIES TYPICAL SIDE WALLS NOT TO SCALE 26 GA. GALVANIZED METAL ROOF PANELS FASTENED TO RAFTERS 3'xni/4' TS COLUMN 6" C®DE COMPLIANCL Sie LUCIE//1C/�OUNTY BOCC 30'-0" RAFTER SPAN TYPICAL END WALLS NOT TO SCALE 16 GA U-CHANNEL BRACE FASTENED RAFTER. POSITIONED AT 4S" W/ 2-114"xl" SDF'S AT EACH END (4 PER BRACE) 26 GA GALVANIZED METAL SIDE PANELS. SECURE WALL PANELS TO RAFTER/BOW AND END POST WITH 114" X 314" SDF'S W/CONTROL SEAL WASHER (SEE TABLE 1 FOR FASTENER SPACING) U 3'x3"x114" TS BASE RAIL STANDARD LEAN-TO OPTION MAIN STRUCTURE STANDARD LEAN-TO OPTION TYPICAL HORSE BARN SECTION NOT TO SCALE ci uxl N O Z igpi � Pit gg :o Engineer: Kent Bice >si FL License #: 50421 w' COA# 30468 OOf N I O 2 M � Z=O Z �'' *g l i ao � SHEET 2 5 Z 02/23/21 r INSTALL 1/2' X4" EXPANSION ANCHOR THROUGH BASE RAIL WITHIN 6' OF EACH BOW ALONG SIDES OR INSIDE EVERY END WALLS POST ALONG END WALL SECTIONS e 12" 16" MONOLITHIC CON . FOOTING NOTE: (3000 PSI MIN.) 6 X 6 X #10 W.W. MESH REINF. OR REINFORCED WITH 2i/4's 6 MIL PLASTIC MEMBRANE CONTINUOUS WELL COMPACTED EARTH FILL 95% PROCTOR CONCRETE BASE RAIL ANCHORAGE �_SCALE: NTS DRILL 5/8"HOLE THROUGH THE BASE RAIL & SECURE TO ANCHOR W/ 1/2" DIA THROUGH BOLT 2" WASHERS TOPOFASPHAULT PAVEMENT OR STABLE \ GROUND SURFACE 48" 16 GA U-CHANNEL BRACE NOTE: BRACE NOT REQUIRED IF END ENCLOSED NIPPLE TO 3/16 RAFTER 3/18 2 x3"xi/4" TS RAFTER POST FASTENED TO KICKER W/ 1!I THRU BOLTS 3'k3'x3/16" TS RAFTER 3"x3'x3/16' TS KICKER FASTENED TO RAFTER W/ 1/Z' THRU BOLTS 6' LONG TS 12 GA NIPPLE SECURE POST TO NIPPLE WITH 41/4" X 1 3/4" SDFs. BOX EAVE RAFTER/CORNER POST DETAIL L SCALE: NTS TS CONT. BASE RAIL SIZE TO MATCH COLUMN F�l I 3-1l8" FOR 16 GA U-CHANNEL BRACE 1/4"FRAMING FASTENED TO THE POST AND RAFTER, POSITIONED @ 45' W/ 2-1/4" X 1' SDF's AT EACH END (4 PER BRACE) BRACE SECTION COLUMN TO 3/16 BASE RAIL 3/16 TS POST TS CONTINUOUS BASE RAIL - SIZE TO MATCH COLUMN POST/BASE RAIL CONN. DETAIL �,SCALE: NTS 3"x3*x3/16°-TS,TRUSSED RAFTER CHORD. OR NONSTRUCTURAL HEADER COLUMN TO BASE RAIL 3/18 3"x3"x1/4° TS DOUBLE POST MINIMUM 6" LONG. MINIMUM 14 GA CONNECTOR SLEEVE SECURE WITH (4) SDFS 2"X2"X2"14 GA CLIP ANGLE SECURE TO RAFTER COLUMN AND BASE RAIL WITH (4) SDFS TS CONTINUOUS BASE RAIL -SIZE TO MATCH COLUMN COLUMN/BASE RAIL CONN. DETAIL -. SCALE: NTS -%C V 3 t "N'r-0 I'Un -ODE COMPLIANCE �;T- LUCIE COUNTY OCC EYE ANCHOR W. 5/8' ROD 30" LONG SCALE: NTS WITH DEL 3" HELIX 3" TSS POST 2"X2"X2"16GA.ANGLE BASE RAIL ANCHORAGE "ND " COLUMN HLEADER WITH 11 dX3/4ASDDFS. OF 3'k3"x1/4" TS COLUMN i A O ND COLUMN 3R OR END COLUMN SCALE: NTS " TS END POST OR DOOR/ DOOR 2°X 2" 2" 14 GA ANGLE CLIP TO COLUMN AND X 2" 2" 14 GA ANGLE CLIP ECURE TO COLUMN ANDSECURE ITHER TOP OF HEADER, WINDOWFRAMEPOST2"X2"X2'16GAANGLECUP SECURE TO POST (EACH SIDE)AND RAFTER EITHER TOP OF HEADER, OR OR OTTOM OF WINDOW RAIL jOR CHORD/RAIL WITH 1W X3/4" SDFS 20N BOTTOM OF WINDOW RAIL WITH (4) SOPS TS BASE/WINDOWS RAIL OR BOTTOM AND 2 ON SIDE WITH (4) SOPS NONSTRUCTURAL HEADER NOTE ROLL -UP DOOR OPENINGS, TS STRUCTURAL HEADER POST SHH OULD BE FLUSH WITH RAIL END. CUP POST TO RAIL ONLY ON SIDE OPPOSITE I THE OPENING. TS HEADER OR WINDOW RAIL COLUMN OR WINDOW RAIL TO POST CONN. DETAIL SCALE:NTS DOUBLE TS HEADER O MINIMUM 6" LONG. MINIMUM 14 GA CONNECTOR SLEEVE. SECURE WITH (4) SOPS 0 / 3"x3'k1/4" TS END COLUMN 3118 CONNECTOR SLEEVE TO 3/16 HFAnrR DOUBLE TS HEADER COLUMN OR WINDOW RAIL TO POST 5A CONNV L SCALE 3'k3°xtA4 TS ENDCOLUMN O MINIMUM 6" LONG. MINIMUM 14 GA CONNECTOR SLEEVE. SECURE WITH (4) SDFS O DOUBLE TS HEADER 316 CONNECTOR SLEEVE TO 3/16 HEADER POST TO RAIL, TRUSS CHORD, OR 6 STRUCTURAL HEADER CONN. DETAIL SCALE:NTS (NOTE: PLACE (1) @ CENTER OF DOOR HEADER.) 3'xWx3/16' TS ROOF RAFTER T X 2" A X 2" 14 GANGLE CLIP SECURE TO COLUMN AND RAFTER WITH (4) SDF'S 3"x3"xi/4" TS END COLUMN 3"x3'X3/16'" ROOF RAFTE NON-STRUCTURAL HEADER, WINDOW RAIL, OR GIRT TO POST CONN. DETAIL II SCALE: NTS :ngineer: Kent Bice L License #: 50421 COM 30468 HEADER/COLUMN CONN. DETAIL �� HEADER/COLUMN CONN. DETAIL 9 END COLUMN/RAFTER CONN. DETAIL 10 PEAK BRACE CONN. DETAIL Z��Z-f SCALE:NTS SCALE:NTS SCALE:NTS SCALE:NTS 02/23/21 U Z // `/ Z 0 J M� W J w W V!//i—/� Z Lu D O rQ V a s gal UI N C o �3 M J w P: y� C o a�$ U' 2 O (c fl o � = O 9 o a 0 J �Rk s H 35 0 Z STIFFENE TO POST r 1-12" 18 GA. FURRING CHANNEL FASTENED TO EACH RAFTER WITH (2) 1/4"X3/4"SDF's SPACED NOT MORE THAN 48" O.C. 26 GA. METAL ROOF PANEL —TS RAFTER ROOF PANEL ATTACHMENT ALTERNATE FOR VERTICAL ROOF PANELS SCALE:NTS 2-12'1.<2-12'k14GA TS Double Ladder Post 4'SQ-1/4'm 4GA - 3" long Post ener at 12" D.C. vertically (typ.) DOUBLE LADDER POST ALTERNATE FOR LARGE SINGLE POST SCALE: NTS 1 lwP O.C. CURTAIN 18 GA.21 11 SECTION THROUGH ROLL UP DOOR HEADER SCALE: NTS CURTAIN 24 GA. PBR WITH BAKED ON EPDXY PRIMER & POLYESTER TOP COAT. + TS POST ► NON-STRUCTURAL (2) - (2) - (2) - (2) 1 /4" x 3/4" Fastener pattern @ all end supports (2) - (1) - (2) - (1) 1/4" x 3/4" Fastener pattern @ all Interior supports FASTENED TO POST PER MANUFACTURER'S SPECS. IF SHEATHING IS REQUIRED, MINIMUM 7/16'" OSB FASTENED TO POSTS AT 6" O.C. (typ.) 26 GA. AG panel metal deck 150F125.43 Hat channel s4� PANEL DETAIL SCALE: N.T.S. TUBING OPTIONS: 2X3 OUBLEI OOR OF 26 GAL INTERIOR SIDE A SECTION SCALE: NTS CODE COMPLIANCE. S`I® LUCIE COUNTY 30Ca- C SIDING INSTALLED PER MANUFACTURER'S SPECIFICATIONS ii a z ��G TWIN aR FQ Q$ 'lag o $n� _ s �15 1/4" X SDF @120.C..C. ffi Engineer: Kent Bice $a� FL License #: 50421 W COM 30468 N F ° SHE o of b Q O W Z C ag � � Z —23-2 ¢ U 0 m �. ca o iLL r'� D U _J SHEET � � Q 02/23/21 4 °F 5 0 Z a U) w F— I I I I I I I L_ 4" CONC. SLAB 6 X 6 #10 W.W. MESH REINF. - FIBERMESH OPTIONAL 6 MIL PLASTIC MEMBRANE WELL COMPACTED EARTH FILL 95% PROCTOR TREAT SOIL FOR TERMITES 30'-0" MAXIMUM 4' PAD 3.5" II ..:.' ¢�: ir' MONOLITIIC CON . FOOTING NOTE (3000 PSI MIN.) 6X 6 X010 W.W. MESH REINF. OR REINFORCED WITH 2 NSs 6 MIL PLASTIC MEMBRANE CONTINUOUS WELL COMPACTED EARTH FILL 96%PROCTOR MONOLITHIC FOOTER (TYP.) SCALE:NTS C®IDE COMPLIANCE ST. LUCIE COUNTY BOCC CONCRETE: CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. COVER OVER REINFORCING STEEL FOR FOUNDATIONS, MINIMUM CONCRETE COVER OVER REINFORCING BARS SHALL BE: 3 INCHES IN FOUNDATIONS WHERE THE CONCRETE IS CAST AGAINSTAND PREMANENTLY IN CONTACT WITH EARCH OR EXPOSED TO THE EARTH OR WEATHER AND 1 1/2" ELSEWHERE. REINFORCING BARS EMBEDDED IN GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF 1/4" FOR FINE GROUT OR 1/2" FOR COURSE GROUT BETWEEN REINFORCING BARS AND ANY FACE OF A CELL. REINFORCING BARS USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO EARTH OR WEATHER 1 1/2" FOR MASONRY UNITS NOT EXPOSED TO EARCH OR WEATHER. REINFORCING STEEL: THE REINFORCING STEEL SHALL BE MINIMUM GRADE 40 GALVANIZATION: METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION NOT DIRECTLY EXPOSED TO THE WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153, CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS AND NAILS EXPOSED DIRECTLY TO THE WEATHER SHALL BE IN STAINLESS STEEL OR HOT DIPPED GALVANIZED. REINFORCEMENT MAY BE BENT IN THE SHOP OR THE FIELD PROVIDED: 1. ALL REINFORCEMENT IS BENT COLD 2. THE DIAMETER OF THE BEND, MEASURED ON THE INSIDE OF THE BAR, IS NOT LESS THAN 6-BAR DIAMETERS AND 3. REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT. EXCEPTION: WHERE BENDING IS NECESSARY TO ALIGN BARS WITH A VERTICAL CELL, BARS PARTIALLY EMBEDDED IN CONCRETE SHALL BE PERMITTED TO BE BENT AT A SLOPE NOT MORE THAN 1" OF THE HORIZONTAL DISPLACEMENT TO 6" OF VERTICAL BAR LENGTH. Engineer: Kent Bice FL License #: 50421 COA# 30468 2-23-2f 02/23/21 U Z U) (V _Z J_ MD W J W W U) Z w W F— D O Q 1 o� o CV O 5� C) (n �5 W o a z w U C o z U aV -J sir 5�F5 �3 0 z