Loading...
HomeMy WebLinkAboutAPPROVED M Heat Load CalculationsBeachfront Mann Realty HVAC Load Analysis for Beachfront Mann Realty 10525 South Ocean Drive Jensen Beach, Florida Prepared By: Eric J. Svoboda, PE Fort Pierce Engineering, Inc. 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Tuesday, January 12, 2021 Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 2 General Project Data Input General Project Information Project file name:Mann Realty Heat Load.CH8 Project title:Beachfront Mann Realty Designed by:Eric J. Svoboda, PE Project date:Monday, July 07, 2008 Weather reference city:WEST PALM BEACH, FLORIDA, USA Client name:Beachfront Mann Realty Client address:10525 South Ocean Drive Client city:Jensen Beach, Florida Company name:Fort Pierce Engineering, Inc. Company representative:Eric J. Svoboda, PE Company address:315 South 7th Street Company city:Fort Pierce, FL 34950 Company phone:772-672-4636 Company fax:772-672-4637 Barometric pressure:29.905 in.Hg. Altitude:15 feet Latitude:27 Degrees Mean daily temperature range:15 Degrees Starting & ending time for HVAC load calculations:7am - 10pm Number of unique rooms in this project:14 Building Default Values Calculations performed:Both heating and cooling loads Lighting requirements:2.00 Watts per square foot Equipment requirements:1.00 Watts per square foot People sensible load multiplier:250 Btuh per person People latent load multiplier:200 Btuh per person Room sensible safety factor:0 % Room latent safety factor:0 % Room heating safety factor:0 % People diversity factor:100 % Lighting profile number:0 Equipment profile number:0 People profile number:0 Building default ceiling height:10.00 feet Building default wall height:12.00 feet Internal Operating Load Profiles (C = 100) hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 C C C C C C C C C C C C C C C C C C C C C C C C 2 C C C C C C C C C C C C C C C C C C C C C C C C 3 C C C C C C C C C C C C C C C C C C C C C C C C 4 C C C C C C C C C C C C C C C C C C C C C C C C 5 C C C C C C C C C C C C C C C C C C C C C C C C 6 C C C C C C C C C C C C C C C C C C C C C C C C 7 C C C C C C C C C C C C C C C C C C C C C C C C 8 C C C C C C C C C C C C C C C C C C C C C C C C 9 C C C C C C C C C C C C C C C C C C C C C C C C 10 C C C C C C C C C C C C C C C C C C C C C C C C Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 3 General Project Data Input (cont'd) Building-Level Design Conditions Design Month Outdoor Dry Bulb Outdoor Wet Bulb Indoor Rel.Hum Indoor Dry Bulb Grains Diff In/Outdoor Correction August 95 80 50%75 66.29 6 Winter 41 75 Master Roofs Roof No. ASHRAE Roof# Roof U-Fac Dark Color Susp. Ceil 1 1 0.033 No No Roof #1 Description: Wood Roof, R-30 Master Walls Wall No. ASHRAE Group Wall U-Fac Wall Color 1 C 0.095 D Wall #1 Description: Block wall, 8" sand & gravel, hollow core, siding exterior, interior finish, 1" extruded poly, R-5.0 Master Glass Glass No. Summer U-Factor Winter U-Factor Glass Shd.Coef. Interior Shading Interior Shd.Coef 1 0.810 0.830 1.000 1 0.550 Glass #1 Description: Default Glass Master Shading Devices Shade No. Dist Horiz Overh Projects Dist Beyond Right W.Edge Dist Beyond Left W.Edge Dist Overh Above Wind Dist Right Fin Proj Dist R-Fin Beyond W.Edge Ht Of Right Fin Dist Left Fin Proj Dist L-Fin Beyond W.Edge Ht Of Left Fin 1 5.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00 0.00 2 4.50 5.00 5.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 4 Building Summary Loads Building peaks in August at 3pm. Bldg Load Descriptions Area Quan Sen Loss %Tot Loss Lat Gain Sen Gain Net Gain %Net Gain Roof 2,172 2,437 6.28 0 3,140 3,140 3.42 Wall 1,967 6,353 16.36 0 4,247 4,247 4.63 Glass 397 11,210 28.87 0 17,105 17,105 18.64 Floor Slab 197 4,153 10.69 0 0 0 0.00 Skin Loads 24,153 62.20 0 24,492 24,492 26.69 Lighting 4,344 0 0.00 0 14,822 14,822 16.15 Equipment 2,172 0 0.00 0 7,411 7,411 8.08 Pool Latent 0 0 0.00 0 0 0 0.00 People 40 0 0.00 7,640 9,960 17,600 19.18 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret.0 0 0.00 0 0 0 0.00 Heat. Pret.0 0 0.00 0 0 0 0.00 Cool. Vent.400 0 0.00 18,024 8,795 26,820 29.23 Heat. Vent.400 14,680 37.80 0 0 0 0.00 Cool. Infil.0 0 0.00 0 0 0 0.00 Heat. Infil.0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 619 619 0.67 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap.0 0 0.00 0 0 0 0.00 Reheat Cap.0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 38,833 100.00 25,664 66,099 91,764 100.00 Building Summary Sen Loss %Tot Loss Lat Gain Sen Gain Net Gain %Net Gain Ventilation 14,680 37.80 18,024 8,795 26,820 29.23 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Room Loads 24,153 62.20 7,640 56,685 64,325 70.10 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 0 0.00 0 619 619 0.67 Building Totals 38,833 100.00 25,664 66,099 91,764 100.00 Check Figures Total Building Supply Air (based on a 21° TD):2,584 CFM Total Building Vent. Air (15.48% of Supply):400 CFM Total Conditioned Air Space:2,172 Sq.ft Supply Air Per Unit Area:1.1898 CFM/Sq.ft Area Per Cooling Capacity:284.0 Sq.ft/Ton Cooling Capacity Per Area:0.0035 Tons/Sq.ft Heating Capacity Per Area:17.88 Btuh/Sq.ft Total Heating Required With Outside Air:38,833 Btuh Total Cooling Required With Outside Air:7.65 Tons Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 5 Air Handler #1 - AHU 1 - Summary Loads Rm No Description Room Peak Time Area People Volume Htg.Loss Htg.CFM CFM/Sqft Sen.Gain Clg.CFM CFM/Sqft Lat.Gain S.Exh W.Exh Htg.O.A. Req.CFM Act.CFM Clg.O.A. Req.CFM Act.CFM 1 Mechanical Room 9pm August 48 0 480 1,011 47 0.98 1,148 48 1.00 0 0 0 Direct 8 12 Direct 8 6 2 Conference Room 3pm August 192 8 1,920 2,272 105 0.55 5,842 244 1.27 1,240 0 0 Direct 34 26 Direct 34 31 3 Waiting 8am August 108 2 1,296 5,626 261 2.41 10,759 449 4.15 400 0 0 Direct 23 65 Direct 23 57 4 Reception 7am August 126 1 1,260 1,935 90 0.71 4,245 177 1.40 200 0 0 Direct 22 22 Direct 22 22 5 RR 109 2pm August 48 1 480 54 2 0.05 812 34 0.71 200 0 0 Direct 8 1 Direct 8 4 6 RR 110 2pm August 48 1 480 54 2 0.05 812 34 0.71 200 0 0 Direct 8 1 Direct 8 4 7 Hall 2pm August 110 1 1,100 123 6 0.05 1,539 64 0.58 200 0 0 Direct 19 1 Direct 19 8 8 Office 103 3pm August 140 1 1,400 1,332 62 0.44 2,890 121 0.86 200 0 0 Direct 25 15 Direct 25 15 9 Small Conference 7am August 110 2 1,100 1,513 70 0.64 3,723 155 1.41 400 0 0 Direct 19 17 Direct 19 20 10 Office 105 7am August 90 1 900 1,202 56 0.62 2,796 117 1.30 200 0 0 Direct 16 14 Direct 16 15 11 Office 106 1pm August 90 1 900 2,256 105 1.16 3,501 146 1.62 200 0 0 Direct 16 26 Direct 16 18 Room Peak Totals: Total Rooms: 11 Unique Rooms: 11 1,110 19 11,316 17,379 805 0.73 38,067 1,587 1.43 3,440 0 0 200 200 200 200 Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 6 Air Handler #1 - AHU 1 - Total Load Summary Air Handler Description:AHU 1 Constant Volume - Proportion Supply Air Fan:Draw-Thru with program estimated horsepower of 0.15 HP Fan Input:0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio:0.91 --- This system occurs 1 time(s) in the building. --- Air System Peak Time:1pm in August. Outdoor Conditions:Clg: 93° DB, 80° WB, 133.69 grains, Htg: 41° DB Indoor Conditions:Clg: 75° DB, 50% RH, Htg: 75° DB Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at 7am is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 36,268. Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss:17,379 Btuh Infiltration sensible loss:0 Btuh 0 CFM Outside Air sensible loss: 7,340 Btuh 200 CFM Supply Duct sensible loss:0 Btuh Return Duct sensible loss:0 Btuh Return Plenum sensible loss:0 Btuh Total System sensible loss:24,719 Btuh Heating Supply Air: 17,379 / (.999 X 1.08 X 20) =805 CFM Winter Vent Outside Air (24.8% of supply) =200 CFM Room space sensible gain:33,752 Btuh Infiltration sensible gain:0 Btuh Draw-thru fan sensible gain:380 Btuh Supply duct sensible gain:0 Btuh Reserve sensible gain:0 Btuh Total sensible gain on supply side of coil:34,132 Btuh Cooling Supply Air: 36,648 / (.999 X 1.1 X 21) =1,587 CFM Summer Vent Outside Air (12.6% of supply) =200 CFM Return duct sensible gain:0 Btuh Return plenum sensible gain:0 Btuh Outside air sensible gain:3,958 Btuh 200 CFM Blow-thru fan sensible gain:0 Btuh Total sensible gain on return side of coil:3,958 Btuh Total sensible gain on air handling system:38,090 Btuh Room space latent gain:3,440 Btuh Infiltration latent gain:0 Btuh Outside air latent gain:9,459 Btuh Total latent gain on air handling system:12,899 Btuh Total system sensible and latent gain:50,989 Btuh Check Figures Total Air Handler Supply Air (based on a 21° TD):1,587 CFM Total Air Handler Vent. Air (12.60% of Supply):200 CFM Total Conditioned Air Space:1,110 Sq.ft Supply Air Per Unit Area:1.4300 CFM/Sq.ft Area Per Cooling Capacity:261.2 Sq.ft/Ton Cooling Capacity Per Area:0.0038 Tons/Sq.ft Heating Capacity Per Area:22.27 Btuh/Sq.ft Total Heating Required With Outside Air:24,719 Btuh Total Cooling Required With Outside Air:4.25 Tons Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 7 Air Handler #2 - AHU 2 - Summary Loads Rm No Description Room Peak Time Area People Volume Htg.Loss Htg.CFM CFM/Sqft Sen.Gain Clg.CFM CFM/Sqft Lat.Gain S.Exh W.Exh Htg.O.A. Req.CFM Act.CFM Clg.O.A. Req.CFM Act.CFM 12 Janitor 9pm August 32 1 320 275 13 0.40 771 32 1.00 200 0 0 Direct 6 8 Direct 6 6 13 Break Room 9pm August 80 2 800 688 32 0.40 1,803 75 0.93 400 0 0 Direct 15 20 Direct 15 15 14 Work Area 4pm August 950 18 9,500 5,810 269 0.28 21,485 890 0.94 3,600 0 0 Direct 179 172 Direct 179 179 Room Peak Totals: Total Rooms: 3 Unique Rooms: 3 1,062 21 10,620 6,774 314 0.30 24,060 997 0.94 4,200 0 0 200 200 200 200 Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Beachfront Mann Realty Fort Pierce, FL 34950 Page 8 Air Handler #2 - AHU 2 - Total Load Summary Air Handler Description:AHU 2 Constant Volume - Proportion Supply Air Fan:Draw-Thru with program estimated horsepower of 0.09 HP Fan Input:0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio:0.85 --- This system occurs 1 time(s) in the building. --- Air System Peak Time:5pm in August. Outdoor Conditions:Clg: 94° DB, 80° WB, 133.44 grains, Htg: 41° DB Indoor Conditions:Clg: 75° DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss:6,774 Btuh Infiltration sensible loss:0 Btuh 0 CFM Outside Air sensible loss: 7,340 Btuh 200 CFM Supply Duct sensible loss:0 Btuh Return Duct sensible loss:0 Btuh Return Plenum sensible loss:0 Btuh Total System sensible loss:14,114 Btuh Heating Supply Air: 6,774 / (.999 X 1.08 X 20) =314 CFM Winter Vent Outside Air (63.7% of supply) =200 CFM Room space sensible gain:23,871 Btuh Infiltration sensible gain:0 Btuh Draw-thru fan sensible gain:239 Btuh Supply duct sensible gain:0 Btuh Reserve sensible gain:0 Btuh Total sensible gain on supply side of coil:24,110 Btuh Cooling Supply Air: 24,110 / (.999 X 1.1 X 22) =997 CFM Summer Vent Outside Air (20.1% of supply) =200 CFM Return duct sensible gain:0 Btuh Return plenum sensible gain:0 Btuh Outside air sensible gain:4,178 Btuh 200 CFM Blow-thru fan sensible gain:0 Btuh Total sensible gain on return side of coil:4,178 Btuh Total sensible gain on air handling system:28,288 Btuh Room space latent gain:4,200 Btuh Infiltration latent gain:0 Btuh Outside air latent gain:9,236 Btuh Total latent gain on air handling system:13,436 Btuh Total system sensible and latent gain:41,723 Btuh Check Figures Total Air Handler Supply Air (based on a 22° TD):997 CFM Total Air Handler Vent. Air (20.06% of Supply):200 CFM Total Conditioned Air Space:1,062 Sq.ft Supply Air Per Unit Area:0.9386 CFM/Sq.ft Area Per Cooling Capacity:305.4 Sq.ft/Ton Cooling Capacity Per Area:0.0033 Tons/Sq.ft Heating Capacity Per Area:13.29 Btuh/Sq.ft Total Heating Required With Outside Air:14,114 Btuh Total Cooling Required With Outside Air:3.48 Tons Z:\ ...\Mann Realty Heat Load.CH8 Tuesday, January 12, 2021, 11:05 AM