HomeMy WebLinkAboutAPPROVED M-3VERTICAL AHU DETAILFLEX DUCT CONNECTION DETAILS CEILING CABINET EXHAUST FAN DETAILAIR COOLED CONDENSING UNIT DETAIL SCALE = (N.T.S.)C DAB SCALE = (N.T.S.)SCALE = (N.T.S.)SCALE = (N.T.S.)
F SCALE = (N.T.S.)E REFRIGERANT PIPING SCHEMATIC SCALE = (N.T.S.)NO.DATEDRREVISIONSCKAPP315 South 7th Street
Phone: 772 672-4636
Fort Pierce, FL. 34950
Fort Pierce
Dependable Mechanical, Electrical
& Plumbing Design
Fax: 772 672-4637
Reg. No. 28173
Engineering, Inc.BEACH FRONT MANN REALTYBRENT A. WOOD ARCHITECTURECONDENSATE DRAIN TRAP DETAIL
NOTE:
1.FILL TRAP MANUALLY ON INITIAL START-UP.
2.PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE.
3.A = 1" + FAN SUCTION S.P.
B = A / 2
4.ALL CONDENSATE PIPING TO BE PVC.
5.INSULATE ALL DRAIN LINES WITH 1 2" ARMAFLEXBASLOPE TO
DRAIN
DRAIN PAN
CASING SLEEVE
AIR
HANDLER
UNIT
UNION
THREADED CAP WITH 1 2"Ø
HOLE DRILLED IN TOP,
HAND TIGHTENED.
THREADED CAP,
HAND TIGHTENED
J.ER IC SVOB
O
D
REENIGNELANOIS
S
EFORP L I C E NS
E
F
LO R I D A
No. 60982
STATE OF ATYPE 'B'
TYPE 'A'
NOTE:
8'-0" MAX HANGER SPACING
30 TO 60 B
19 TO 30 A/B
UP TO 18 A
INCHES
DUCT DIMENSIONS
HANGER
TYPE
DUCT SCHEDULE
DUCT SUPPORT DETAILSG SCALE = (N.T.S.)