In-Place Density Test Report
Client:Century Complete Homes UES Technician:Mark Rogers
1155 Malabar Road, NE Suite 8
Palm Bay, FL 32907
Date Tested:04/30/2021
Project:Century Complete Saint Lucie County
Various Locations, Port St. Lucie, St. Lucie County, FL
Type of Test:
Area Tested:7801 James Drive - House Pad Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of lot 0-1 ft 110.2 11.1 106.5 10.6 97 Pass
2 Southwest corner of lot 0-1 ft 110.2 11.1 107.3 10.8 97 Pass
3 Center of lot 0-1 ft 110.2 11.1 106.7 10.8 97 Pass
Remarks:Above stripped surface 1-2’, 2-3’ HCP=60+, > 95 % Compaction, PASS. HCP tests are empirically correlated to the
relative density of the soil.
Reviewed By
GFA International, Inc
FBPE Registry No.4930
John Kent
Senior Project Engineer
STATE OF FLORIDA
Professional Engineer No. 63218
This item has been digitally signed and sealed by John Kent on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.