HomeMy WebLinkAboutWind Load Calculation Component & Cladding Wind loads Prepared for Edwing's Unlimited Shutter Services Calculations by Seaside Engineers Project: Meihsner Residence Certificate of Authorization No.32048 Location: 2700 N.HWYAlA,APT408 4265 60th Court Fort Pierce,FL 34949 Vero Beach,Florida 32967 Project ID: (722)202-8008 Info@seasideengineers.com Date: 5/10/2021 w m.seasideenoineers.com Design Information Risk Category II Windspeed 170 mph Exposure D Int.Press.Coef.,GCpi(+/-) 0.18 a 11.00 feet Select the appropriate fastener size and spacing using the pre-engineered attachment schedule for the Florida Approved Product(s)or NOA used on thisjob.The contractor is responsible to ensure the use of the proper material,reinforcement,components,etc.to meet the indicated pressure per the product approval engineering document.The contractor is responsible to verify the component is in the appropriate zone using the"a"dimension shown above and diagrams shown below.The building pressures are calculated using the Allowable Stress Design.Contact Seaside Engineers immediately if the substrate at the attachment locations appears to have deterioration,abnormalities,damage,or other conditions resulting in questionable integrity. Florida Product Area Approval# Building Design Product Design ID Opening Description (sqft) Zone or NOA Manufacturer Model Pressure(PSF) Pressure(PSF) 1 Accordian Shutter 34.7 5 FL389.2 ASSA Bertha HV Blade 1 59.7 106.9 205.0 -190.0 2 Accordian Shutter 73.7 5 FL389.2 ASSA Bertha HV Blade 1 55.6 -96.1 120.0 -100.0 yllP c®p� % PRD K. i �.��O•.9* G E N S�• No.7222 • OF00 ss1ONAL��C���• r►IIIn0� WALL: 16 h Edward K Roske, PE 6 I ® 9 May 10,2021 �� I O