HomeMy WebLinkAboutAPPROVED engineering plansDIRECTORY OF PAGES PV-1 PROJECT SUMMARY PV-2 SITE PLAN PV-3 SINGLE-LINE DIAGRAM PV-4 SAFETY LABELS PV-5.1 ATTACHMENT PLAN 5.1 PV-5.2 ATTACHMENT PLAN 5.2 PV-6 ATTACHMENT DETAILS PV-7 FIRE SAFETY PLAN APPENDIXMODULE DATASHEET INVERTER DATASHEET MOUNTING SYSTEM DATASHEET UL 2703 GROUND AND BONDING CERTIFICATION ANCHOR DATASHEET PROJECT DETAILS PROPERTY ADDRESS 5231 OAKLAND LAKE CIR, FORT PIERCE, FL 34951 US ZONING RESIDENTIAL USE AND OCCUPANCY CLASSIFICATION ONE- OR TWO-FAMILY DWELLING GROUP (GROUP R3) UTILITY COMPANY FLORIDA POWER & LIGHT CO ELECTRICAL CODE 2017 NEC (NFPA 70) FIRE CODE 2018 NFPA 1 OTHER BUILDING CODES 2020 FL BUILDING CODE CONTRACTOR INFORMATION CONTRACTOR SIGNATURE SCOPE OF WORK THIS PROJECT INVOLVES THE INSTALLATION OF A GRID- INTERACTIVE PV SYSTEM. PV MODULES WILL BE MOUNTED USING A PREENGINEERED MOUNTING SYSTEM. THE MODULES WILL BE ELECTRICALLY CONNECTED WITH DC TO AC POWER INVERTERS AND INTERCONNECTED TO THE LOCAL UTILITY USING MEANS AND METHODS CONSISTENT WITH THE RULES ENFORCED BY THE LOCAL UTILITY AND PERMITTING JURISDICTION. THIS DOCUMENT HAS BEEN PREPARED FOR THE PURPOSE OF DESCRIBING THE DESIGN OF A PROPOSED PV SYSTEM WITH ENOUGH DETAIL TO DEMONSTRATE COMPLIANCE WITH APPLICABLE CODES AND REGULATIONS. THE DOCUMENT SHALL NOT BE RELIED UPON AS A SUBSTITUTE FOR FOLLOWING MANUFACTURER INSTALLATION INSTRUCTIONS. THE SYSTEM SHALL COMPLY WITH ALL MANUFACTURERS LISTING AND INSTALLATION INSTRUCTIONS, AS WELL AS ALL APPLICABLE CODES. NOTHING IN THIS DOCUMENT SHALL BE INTERPRETED IN A WAY THAT OVERRIDES THEM. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL CONDITIONS, DIMENSIONS, AND DETAILS IN THIS DOCUMENT. SYSTEM DETAILS DESCRIPTION NEW GRID-INTERACTIVE PV SYSTEM WITH NO ENERGY STORAGE DC RATING OF SYSTEM 9.57KW AC RATING OF SYSTEM 8.41KW AC OUTPUT CURRENT 35.1A INVERTER(S)29 X ENPHASE IQ7PLUS-72-2-US MODULE APTOS SOLAR DNA-120 330 ARRAY WIRING (1) BRANCH OF 3 IQ7PLUS-72-2-US MICROINVERTERS (2) BRANCH OF 13 IQ7PLUS-72-2-US MICROINVERTERS INTERCONNECTION DETAILS POINT OF CONNECTION NEW LOAD-SIDE AC CONNECTION PER NEC 705.12(B)(2)(3)(A) AT MSP UTILITY SERVICE 120/240V 1Φ LOCATION MAIN SERVICE PANEL W/200A BUSBAR 150A MCB SITE DETAILS ASHRAE EXTREME LOW 0°C (32°F) ASHRAE 2% HIGH 33°C (91°F) CLIMATE DATA SOURCE VERO BEACH MUNICIPAL AIRPORT (KVRB) WIND SPEED 160 MPH (ASCE7-10) RISK CATEGORY II WIND EXPOSURE CATEGORY B P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951PROJECT SUMMARY DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-1 GENERAL NOTES 1 EQUIPMENT LIKELY TO BE WORKED UPON WHILE ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT SATISFY MINIMUM WORKING CLEARANCES PER NEC 110.26. 2 CONTRACTOR SHALL USE ONLY COMPONENTS LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY FOR THE INTENDED USE. 3 CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL EQUIPMENT, CABLES, ADDITIONAL CONDUITS, RACEWAYS, AND OTHER ACCESSORIES NECESSARY FOR A COMPLETE AND OPERATIONAL PV SYSTEM. (E) MAIN SERVICE PANEL (MSP), OUTDOOR (E) UTILITY METER, OUTDOOR (N) VISIBLE, LOCKABLE, READILY-ACCESSIBLE AC DISCONNECT LOCATED WITHIN 10 FT OF UTILITY METER, OUTDOOR (N) AC COMBINER, OUTDOOR , OUTPUT CIRCUIT CONDUCTORS SHALL BE RUN IN PVC-40 CONDUIT OVER ROOF NO CLOSER THAN 0.5" ABOVE ROOF SURFACE (N) TRANSITION BOX, OUTDOOR , OUTPUT CIRCUIT CONDUCTORS SHALL BE RUN IN LFMC CONDUIT THROUGH THE INTERIOR OF THE BUILDING (N) PROPOSED ROOF-MOUNTED PHOTOVOLTAIC ARRAY. 6:12 (27°) SLOPED ROOF, 13 PV MODULES (BLACK FRAME, BLACK BACKSHEET), 270° AZIMUTH ROADWAY (N) TRANSITION BOX, OUTDOOR , OUTPUT CIRCUIT CONDUCTORS SHALL BE RUN IN LFMC CONDUIT THROUGH THE INTERIOR OF THE BUILDING (N) PROPOSED ROOF-MOUNTED PHOTOVOLTAIC ARRAY. 6:12 (27°) SLOPED ROOF, 16 PV MODULES (BLACK FRAME, BLACK BACKSHEET), 180° AZIMUTH ALL ARRAY CIRCUITS SHALL BE ROUTED THROUGH THE INTERIOR OF THE BUILDING, AND WHERE POSSIBLE, ALONG THE BOTTOM OF LOAD BEARING MEMBERS. NO CONDUIT SHALL BE INSTALLED ABOVE THE ROOF. P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951SITE PLAN DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-2 PV MODULE MICRO- INVERTER PM1-29 330W 13 IN BRANCH 3 IN BRANCH 13 IN BRANCH 1 2 3 4 5 6 7 JUNCTION BOXES JB1-2 31 2 AC COMBINER CB2 25A CB1 20A 4 CB3 20A C1 8 PV DISCONNECT SW1 60A 5 LOADS MAIN SERVICE PANEL AC GEC KWHR LOAD LINE KWHR LOAD LINE UTILITY METER (E) 240/120V 1ɸ, 3W 200A BUSBAR 150A MAIN BREAKER (E) 150A CB4 50A 9 10 MODULES REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING PM1-29 29 APTOS SOLAR DNA-120 330 330W 304W 10.51A 10.02A 40.3V 32.9V -0.123V/°C (-0.31%/°C)20A INVERTERS REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1-29 29 ENPHASE IQ7PLUS-72-2-US 240V NOT SOLIDLY GROUNDED 290W 1.2A 15.0A 60V 97.0% DISCONNECTS REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE SW1 1 EATON DG222URB OR EQUIV.60A 240VAC OCPDS REF.QTY.RATED CURRENT MAX VOLTAGE CB1,3 2 20A 240VAC CB2 1 25A 240VAC CB4 1 50A 240VAC SYSTEM SUMMARY BRANCH 1 BRANCH 2 BRANCH 3 INVERTERS PER BRANCH 13 3 13 MAX AC CURRENT 15.73A 3.63A 15.73A MAX AC OUTPUT 3,770W 870W 3,770W ARRAY STC POWER 9,570W ARRAY PTC POWER 8,825W MAX AC CURRENT 35A MAX AC POWER OUTPUT 8,410W DERATED AC POWER OUTPUT 8,410W NOTES THE DC AND AC CONNECTORS OF THE ENPHASE IQ7PLUS-72-2-US AND ARE LISTED TO MEET REQUIREMENTS AS A DISCONNECT MEANS AS ALLOWED BY NEC 690.15(D). MATING CONNECTORS SHALL COMPLY WITH NEC 690.33. 1 THE ENPHASE IQ7PLUS-72-2-US HAS A CLASS II DOUBLE-INSULATED RATING AND DOES NOT REQUIRE GROUNDING ELECTRODE CONDUCTORS (GEC) OR EQUIPMENT GROUNDING CONDUCTORS (EGC). THE RATING INCLUDES GROUND FAULT PROTECTION (GFP). TO SUPPORT GFP, USE ONLY PV MODULES EQUIPPED WITH DC CABLES LABELED PV WIRE OR PV CABLE. 2 ENPHASE SYSTEM MEETS REQUIREMENTS FOR PHOTOVOLTAIC RAPID SHUTDOWN SYSTEM (PVRSS), AS PER NEC 690.12(B).3 MICROINVERTER BRANCH CIRCUIT CONDUCTORS ARE MANUFACTURED ENPHASE Q CABLES LISTED FOR USE IN 20A OR LESS CIRCUITS OF ENPHASE IQ MICROINVERTERS. THEY ARE ROHS, OIL RESISTANT, AND UV RESISTANT. THEY CONTAIN TWO 12 AWG CONDUCTORS OF TYPE THHN/THWN-2 DRY/WET AND CERTIFIED TO UL3003 AND UL 9703. 4 DC PV CONDUCTORS ARE NOT SOLIDLY-GROUNDED. NO DC PV CONDUCTOR SHALL BE WHITE- OR GRAY-COLORED5 ALL METAL ENCLOSURES, RACEWAYS, CABLES AND EXPOSED NONCURRENT-CARRYING METAL PARTS OF EQUIPMENT SHALL BE GROUNDED TO EARTH AS REQUIRED BY NEC 250.4(A) AND PART III OF ARTICLE 250 AND EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45. THE GROUNDING ELECTRODE SYSTEM SHALL ADHERE TO NEC 690.47(A) AND NEC 250.169. THE DC GROUNDING ELECTRODE SHALL BE SIZED ACCORDING TO NEC 250.166 AND INSTALLED IN COMPLIANCE WITH NEC 250.64. 6 MAX DC VOLTAGE OF PV MODULE IS 43.3V AT 0°C (0°C - 25°C) X -0.123V/C + 40.27V = 43.3V).7 AC AGGREGATION PANEL BUSBAR AND THE OVERCURRENT PROTECTION PROTECTING THE BUSBAR SHALL BE SIZED IN ACCORDANCE WITH NEC 705.12(B)(2)(3)(C)8 POINT-OF-CONNECTION IS ON LOAD SIDE OF SERVICE DISCONNECT, IN COMPLIANCE WITH NEC 705.12(B)(2)(3)(A). OUTPUT IS BACKFED THROUGH BREAKER IN MAIN PANEL.9 PV SYSTEM DISCONNECT SHALL BE A VISIBLE KNIFE-BLADE TYPE DISCONNECT THAT IS ACCESSIBLE AND LOCKABLE BY THE UTILITY. THE DISCONNECT SHALL BE LOCATED WITHIN 10 FT OF UTILITY METER. DISCONNECT SHALL BE GROUPED IN ACCORDANCE WITH NEC 230.72. 10 CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS ID TYPICAL CONDUCTOR CONDUIT / CABLE CURRENT-CARRYING CONDUCTORS IN CONDUIT / CABLE OCPD EGC TEMP. CORR. FACTOR FILL FACTOR CONT. CURRENT MAX. CURRENT (125%) BASE AMP.DERATED AMP. TERM. TEMP. RATING AMP. @ TERM. TEMP. RATING 1 1 10 AWG THWN-2, COPPER 0.75" DIA. LFMC 4 20A 10 AWG THWN-2, COPPER 0.76 (53°C)0.8 15.73A 19.66A 40A 24.32A 90°C 40A 2 1 10 AWG THWN-2, COPPER 0.75" DIA. LFMC 4 25A 10 AWG THWN-2, COPPER 0.76 (53°C)0.8 3.63A 4.54A 40A 24.32A 90°C 40A 3 1 10 AWG THWN-2, COPPER 0.5" DIA. LFMC 2 20A 10 AWG THWN-2, COPPER 0.76 (53°C)1.0 15.73A 19.66A 40A 30.4A 90°C 40A 4 1 6 AWG THWN-2, COPPER 0.75" DIA. PVC-40 3 50A 8 AWG THWN-2, COPPER 0.96 (33°C)1.0 35.09A 43.86A 75A 72A 75°C 65A 5 1 6 AWG THWN-2, COPPER 0.75" DIA. PVC-40 3 50A 8 AWG THWN-2, COPPER 0.96 (33°C)1.0 35.09A 43.86A 75A 72A 75°C 65A REVISIONS PROJECT ID: CREATED BY: CHECKED BY: DATE: SCALE:GRID-TIED SOLAR POWER SYSTEMFORT PIERCE, FL 349515231 OAKLAND LAKE CIRPV-3 P-158037 04/23/21 SDT 158037 SINGLE-LINE DIAGRAM 1 PV-3 SINGLE-LINE DIAGRAM NTS GROUNDING NOTES 1 ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690 2 PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED BY LOCAL JURISDICTION. ALL OTHER EXPOSED METAL PARTS SHALL BE GROUNDED USING UL-LISTED LAY-IN LUGS. 3 INSTALLER SHALL CONFIRM THAT MOUNTING SYSTEM HAS BEEN EVALUATED FOR COMPLIANCE WITH UL 2703 "GROUNDING AND BONDING" WHEN USED WITH PROPOSED PV MODULE. 4 IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. 5 AC SYSTEM GROUNDING ELECTRODE CONDUCTOR (GEC) SHALL BE A MINIMUM SIZE #8AWG WHEN INSULATED, #6AWG IF BARE WIRE. 6 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE, AND #6AWG SHALL BE USED WHEN EXPOSED TO DAMAGE 7 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN, OR MARKED GREEN IF #4AWG OR LARGER GENERAL ELECTRICAL NOTES 1 UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE. 2 CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE 310.10 (D). 3 CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C). C1 - AC COMBINER (ENPHASE IQ COMBINER+) SW1 - DISCONNECT (EATON DG222URB ) MSP - MAIN SERVICE PANEL SEE NOTE NO. 4 (MSP) EMERGENCY RESPONDER THIS SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE 'OFF' POSITION TO SHUT DOWN THE ENTIRE PV SYSTEM. NFPA 111.12.2.1.1.1.1,11.12.2.1.4 AND NEC690.56(C)(1) AC COMBINER PANEL (C1) ! WARNING ! THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR. NEC705.12(B)(2)(3)(C) EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (SW1) ! WARNING ! ELECTRIC SHOCK HAZARD. TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. NEC690.13(B) AC SOLAR DISCONNECT (SW1, CB4 IN MSP) PV SYSTEM DISCONNECT NEC690.13(B) AC DISCONNECT (SW1, CB4 IN MSP) MAXIMUM AC OPERATING CURRENT: 35.1A MAXIMUM AC OPERATING VOLTAGE: 240V NEC690.54 ANY AC ELECTRICAL PANEL THAT IS FED BY BOTH THE UTILITY AND THE PHOTOVOLTAIC SYSTEM (MSP) ! WARNING ! DUAL POWER SOURCE. SECOND SOURCE IS PHOTOVOLTAIC SYSTEM. NEC705.12(B)(3) LABELING NOTES 1 ALL PLAQUES AND SIGNAGE REQUIRED BY 2017 NEC AND 2018 NFPA 1 WILL BE INSTALLED AS REQUIRED. 2 LABELS, WARNING(S) AND MARKING SHALL COMPLY WITH ANSI Z535.4, WHICH REQUIRES THAT DANGER, WARNING, AND CAUTION SIGNS USED THE STANDARD HEADER COLORS, HEADER TEXT, AND SAFETY ALERT SYMBOL ON EACH LABEL. THE ANSI STANDARD REQUIRES A HEADING THAT IS AT LEAST 50% TALLER THAN THE BODY TEXT, IN ACCORDANCE WITH NEC 110.21(B). 3 A PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION IN ACCORDANCE WITH NEC 690.56(B). 4 LABEL(S) WITH MARKING, "TURN RAPID SHUTDOWN SWITCH TO THE 'OFF' POSITION TO SHUT DOWN THE ENTIRE PV SYSTEM," SHALL BE LOCATED WITHIN 3 FT OF SERVICE DISCONNECTING MEANS THE TITLE SHALL UTILIZE CAPITALIZED LETTERS WITH A MINIMUM HEIGHT OF 3/8” IN BLACK ON A RED BACKGROUND, AND REMAINING TEXT SHALL BE CAPITALIZED WITH A MINIMUM HEIGHT OF 3/16” IN BLACK ON WHITE BACKGROUND P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951SAFETY LABELS DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-4 ROOF PROPERTIES ROOF MATERIAL COMPOSITION SHINGLE (1 LAYER) SLOPE 6/12 (26.6°) MEAN ROOF HEIGHT 15.5FT DECK SHEATHING 15/32" OSB CONSTRUCTION RAFTERS (2X4'S), 24IN OC MODULE MECHANICAL PROPERTIES MODEL APTOS SOLAR DNA-120 330 DIMENSIONS (AREA)66.3IN X 39.4IN X 1.4IN (18.2 SQ FT) WEIGHT 41.9LB MOUNTING SYSTEM PROPERTIES RAIL MODEL EVEREST CROSSRAIL 44-X ANCHOR MODEL EVEREST 4000061 (FLASHED), 2.5IN AIR GAP FASTENING METHOD 3.0 INCH EMBEDMENT INTO RAFTERS WITH (1) 5/16IN DIA. FASTENER MAX. ALLOW. RAIL SPAN 48.0IN (ZONES 1, 2, AND 3) MAX. MOUNT SPACING 48.0IN (ZONES 1, 2, AND 3) MAX. ALLOW. CANTILEVER 16.0IN (ZONES 1, 2, AND 3) GROUNDING AND BONDING INTEGRAL GROUNDING CERTIFIED TO UL 2703 REQUIREMENTS DEAD LOAD CALCULATIONS LOAD QTY LBS TOTAL LBS MODULES 16 41.9 670.2 MICROINVERTERS 16 1.1 17.3 LINEAR FEET OF RAIL 112 FT 0.5 52.7 ANCHORS 41 1.2 51.2 MISC. HARDWARE 9.0 9.0 TOTAL ARRAY WEIGHT 800.4 LBS AREA NAME QTY SQFT TOTAL SQFT MODULES 16 18.2 291.2 POINT LOAD (800.4 LBS / 41 ATTACHMENTS)19.5 LBS DIST. LOAD (800.4 LBS / 291.2 SQFT)2.75 PSF NOTES 1 RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE MOUNT SPACING EXCEED "MAX. MOUNT SPACING" 2 PER ENGINEERING, CANTILEVER ("RAIL END OVERHANG") "IS NOT TO EXCEED 33% OF ACCEPTABLE RAIL SPAN" DEFINED IN THIS DOCUMENT AS "MAX. ALLOW. RAIL SPAN". WIND ZONE I WIND ZONE II WIND ZONE III DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7- 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES. α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0.04 * LEAST HORIZONTAL DIMENSION, 3 FT) 4.8 FT = MAX(MIN(0.4 * 15.5 FT, 0.1 * 48.0 FT), 0.04 * 48.0 FT, 3 FT) P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951ATTACHMENT PLAN DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-5.1 ROOF PROPERTIES ROOF MATERIAL COMPOSITION SHINGLE (1 LAYER) SLOPE 6/12 (26.6°) MEAN ROOF HEIGHT 15.5FT DECK SHEATHING 15/32" OSB CONSTRUCTION RAFTERS (2X4'S), 24IN OC MODULE MECHANICAL PROPERTIES MODEL APTOS SOLAR DNA-120 330 DIMENSIONS (AREA)66.3IN X 39.4IN X 1.4IN (18.2 SQ FT) WEIGHT 41.9LB MOUNTING SYSTEM PROPERTIES RAIL MODEL EVEREST CROSSRAIL 44-X ANCHOR MODEL EVEREST 4000061 (FLASHED), 2.5IN AIR GAP FASTENING METHOD 3.0 INCH EMBEDMENT INTO RAFTERS WITH (1) 5/16IN DIA. FASTENER MAX. ALLOW. RAIL SPAN 48.0IN (ZONES 1, 2, AND 3) MAX. MOUNT SPACING 48.0IN (ZONES 1, 2, AND 3) MAX. ALLOW. CANTILEVER 16.0IN (ZONES 1, 2, AND 3) GROUNDING AND BONDING INTEGRAL GROUNDING CERTIFIED TO UL 2703 REQUIREMENTS DEAD LOAD CALCULATIONS LOAD QTY LBS TOTAL LBS MODULES 13 41.9 544.5 MICROINVERTERS 13 1.1 14.0 LINEAR FEET OF RAIL 90 FT 0.5 42.1 ANCHORS 32 1.2 40.0 MISC. HARDWARE 7.3 7.3 TOTAL ARRAY WEIGHT 648.0 LBS AREA NAME QTY SQFT TOTAL SQFT MODULES 13 18.2 236.6 POINT LOAD (648.0 LBS / 32 ATTACHMENTS)20.2 LBS DIST. LOAD (648.0 LBS / 236.6 SQFT)2.74 PSF NOTES 1 RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE MOUNT SPACING EXCEED "MAX. MOUNT SPACING" 2 PER ENGINEERING, CANTILEVER ("RAIL END OVERHANG") "IS NOT TO EXCEED 33% OF ACCEPTABLE RAIL SPAN" DEFINED IN THIS DOCUMENT AS "MAX. ALLOW. RAIL SPAN". WIND ZONE I WIND ZONE II WIND ZONE III DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7- 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES. α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0.04 * LEAST HORIZONTAL DIMENSION, 3 FT) 4.8 FT = MAX(MIN(0.4 * 15.5 FT, 0.1 * 48.0 FT), 0.04 * 48.0 FT, 3 FT) P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951ATTACHMENT PLAN DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-5.2 P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951ATTACHMENT DETAILS DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-6 GENERAL NOTES 1 ACCESS AND SPACING REQUIREMENTS SHALL BE REQUIRED TO PROVIDE EMERGENCY ACCESS TO THE ROOF, PROVIDE PATHWAYS TO SPECIFIC AREAS OF THE ROOF, PROVIDE FOR SMOKE VENTILATION OPPORTUNITY AREAS, AND TO PROVIDE EMERGENCY EGRESSION FROM THE ROOF. THE AHJ SHALL BE PERMITTED TO REDUCED OR MODIFY ROOF ACCESS BASED UPON FIRE DEPARTMENT VENTILATION PROCEDURES OR ALTNERATIVE METHODS THAT ENSURE ADEQUATE FIRE DEPARTMENT ACCESS, PATWAYS, AND SMOKE VENTILATION. (NFPA 1 11.12.2.2.1) 2 NOT LESS THAN TWO 36 IN. (914 MM) WIDE PATHWAYS ON SEPARATE ROOF PLANES, FROM GUTTER TO RIDGE, SHALL BE PROVIDED ON ALL BUILDINGS. ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLAN WITH A PV ARRAY, A 36 IN. (914 MM) WIDE PATHWAY FROM GUTTER TO RIDGE SHALL BE PROVIDED ON THE SAME ROOF PLANE AS THE PV ARRAY, ON AN ADJACENT ROOF PLANE OR STRADDLING THE SAME AND ADJACENT ROOF PLANES. PATHWAYS SHALL BE LOCATED IN AREAS WITH MINIMAL OBSTRUCTIONS SUCH AS VENT PIPES, CONDUIT, OR MECHANICAL EQUIPMENT. (NFPA 1 11.12.2.2.2.1) 3 FOR PV ARRAYS OCCUPYING UP TO 33 PERCENT OF THE PLAN VIEW ROOF AREA, A MINIMUM 18 IN. (457 MM) PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. FOR PV ARRAYS OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW ROOF AREA, A MINIMUM OF 36 IN. (914 MM) PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. (NFPA 1 11.12.2.2.2.2) 1.5 FT. WIDE FIRE ACCESS PATHWAY ROOF ACCESS POINT PV MODULES INSTALLED ON ROOF WITH EVEREST CROSSRAIL MOUNTING SYSTEM. THE MOUNTING SYSTEM IS UL 1703 CLASS A FIRE RATED ON A 6/12 SLOPED ROOF WHEN INSTALLED WITH TYPE 1, 2, OR 3 MODULES. THE APTOS SOLAR DNA-120 330 IS TYPE 1. 3.0 FT. WIDE SMOKE-VENTILATION SETBACK, PER NFPA 1 11.12.2.2.2.2 ROADWAY 1.5 FT. WIDE FIRE ACCESS PATHWAY 1.5 FT. WIDE FIRE ACCESS PATHWAY ROOF ACCESS POINT ROOF ACCESS POINT ROOF ACCESS POINT 1.5 FT. WIDE FIRE ACCESS PATHWAY PV MODULES INSTALLED ON ROOF WITH EVEREST CROSSRAIL MOUNTING SYSTEM. THE MOUNTING SYSTEM IS UL 1703 CLASS A FIRE RATED ON A 6/12 SLOPED ROOF WHEN INSTALLED WITH TYPE 1, 2, OR 3 MODULES. THE APTOS SOLAR DNA-120 330 IS TYPE 1. TOTAL PLAN VIEW ARRAY AREA IS 483.5 SQ.FT, WHICH REPRESENTS 19.7% OF TOTAL PLAN VIEW ROOF AREA (2459.4 SQ.FT) P-158037 GRID-TIED SOLAR POWER SYSTEM5231 OAKLAND LAKE CIRFORT PIERCE, FL 34951FIRE SAFETY PLAN DOC ID:158037-194829-1 DATE:4/23/21 CREATOR: REVIEWER: REVISIONS PV-7 DNA-120330W l 325W l 320WHigh-efficiency, Half-cut cell panelMaximize Energy ProductionResilient in extreme weather conditions 5400 Pa snow load175 mph wind load All-black design for pristine aesthetics25 year warantyExtended reliabilityAdvanced technology boosts power generationaptos solar technologyTMOur DNA Half-cut Cell Series impressively combines advanced technologies to maximize performance. Our patented DNA, Dual Nano Absorber, technology allows for panel operate at high efficiencies with excellent performance in high temperature environments. wwww.aptossolar.com l info@aptossolar.comALL-BLACK DESIGNULRLISTEDProduct CertificationsFactory Certifications9001140011800125 Year Linear Performance Warranty 1 year10 years25 years93.1%84.8%90.7%80.2%Aptos WarrantyStandard Warranty98%97%ELECTRICAL SPECIFICATIONS (+3%/-0%)STCrated output Pmpp(W)Open Circuit Voltage Vvoc(V)Short Circuit Current lsc(A)Rated Voltage Vmmp(V)Rated Current lmmp(A)32540.1010.4332.719.9333040.2710.5132.9110.02Standard Test Conditions for front-face of panel:1000 W/m , 25 C, measurement uncertainty <3%2TEMPERATURE COEFFICIENTSTEST OPERATING CONDITIONSMECHANICAL PROPERTIESTemperature Coefficients Pmpp-0.40%/ CTemperature Coefficients lsc+0.046%/ CTemperature Coefficients Voc-0.306%/ CNormal Operating Cell Temperature (NOCT)45 CCell TypeGlassFrameJunction BoxDimensionOutput CableWeightMonocrystallineLow Iron, TemperedAnodized Aluminum AlloyIP671684 x 1002 x 35mm4mm (EU)12AWG, 39.37in(1000mm)41.9lbs.(19kg)I-V CURVEMaximum Series FuseMaximum System VoltageMaximum Load Capacity (Per UL1703)Fire Performance Class20A1,500 VDC (UL&IEC)5,400PA Snow Load175mph Wind RatingClass C/Type 11360mm32039.9210.3532.519.8421684mm1002mmCable Length1200mm860mm952mmaptos solar technologyTMDNA-120BLACK FRAME, BLACK BACKSHEETHIGH EFFICIENCY, HALF-CUT CELL PANELMODULE DIMENSIONS3140 De La Cruz Blvd., Ste. 200 Santa Clara, CA 95054www.aptossolar.com l info@aptossolar.comDNA-120-MF23-XXXWRESIDENTIAL l COMMERCIALDNA-120-MF23-320W DNA-120-MF23-325WDNA-120-MF23-330WNumber of Modules per Pallet30Pallet Dimensions (mm)1720X 1140 X 1140 Pallet weight (kg)PACKAGING CONFIGURATIONNumber of Pallets per 40ft HQ Container26620Container weight (kg)1612035mmAptos Solar Technology reserves the right to make specification changes without noticeULRLISTEDPRODUCT CERTIFICATIONSModule Efficiency18.96%19.25%19.54% The high-powered smart grid-ready Enphase IQ 7 Micro™ and Enphase IQ 7+ Micro™ dramatically simplify the installation process while achieving the highest system efficiency.Part of the Enphase IQ System, the IQ 7 and IQ 7+ Microinverters integrate with the Enphase IQ Envoy™, Enphase IQ Battery™, and the Enphase Enlighten™ monitoring and analysis software.IQ Series Microinverters extend the reliability standards set forth by previous generations and undergo over a million hours of power-on testing, enabling Enphase to provide an industry-leading warranty of up to 25 years. Enphase IQ 7 and IQ 7+MicroinvertersTo learn more about Enphase offerings, visit enphase.comData SheetEnphase MicroinvertersRegion: AMERICASEasy to Install• Lightweight and simple• Faster installation with improved, lighter two-wire cabling• Built-in rapid shutdown compliant (NEC 2014 & 2017)Productive and Reliable• Optimized for high powered 60-cell and 72-cell* modules• More than a million hours of testing• Class II double-insulated enclosure• UL listedSmart Grid Ready• Complies with advanced grid support, voltage and frequency ride-through requirements• Remotely updates to respond to changing grid requirements• Configurable for varying grid profiles• Meets CA Rule 21 (UL 1741-SA)* The IQ 7+ Micro is required to support 72-cell modules.1. No enforced DC/AC ratio. See the compatibility calculator at https://enphase.com/en-us/support/module-compatibility. 2. Nominal voltage range can be extended beyond nominal if required by the utility.3. Limits may vary. Refer to local requirements to define the number of microinverters per branch in your area.To learn more about Enphase offerings, visit enphase.com© 2018 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc. 2018-11-19INPUT DATA (DC) IQ7-60-2-US / IQ7-60-B-USIQ7PLUS-72-2-US / IQ7PLUS-72-B-USCommonly used module pairings¹235 W - 350 W +235 W - 440 W +Module compatibility60-cell PV modules only60-cell and 72-cell PV modulesMaximum input DC voltage48 V60 VPeak power tracking voltage27 V - 37 V27 V - 45 VOperating range16 V - 48 V16 V - 60 VMin/Max start voltage22 V / 48 V22 V / 60 VMax DC short circuit current (module Isc)15 A15 AOvervoltage class DC portIIIIDC port backfeed current0 A0 APV array configuration1 x 1 ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuitOUTPUT DATA (AC) IQ 7 MicroinverterIQ 7+ MicroinverterPeak output power250 VA295 VAMaximum continuous output power240 VA290 VANominal (L-L) voltage/range²240 V / 211-264 V208 V / 183-229 V240 V / 211-264 V208 V / 183-229 VMaximum continuous output current1.0 A (240 V)1.15 A (208 V)1.21 A (240 V)1.39 A (208 V)Nominal frequency60 Hz60 HzExtended frequency range47 - 68 Hz47 - 68 HzAC short circuit fault current over 3 cycles5.8 Arms5.8 ArmsMaximum units per 20 A (L-L) branch circuit³16 (240 VAC)13 (208 VAC)13 (240 VAC)11 (208 VAC)Overvoltage class AC portIIIIIIAC port backfeed current0 A0 APower factor setting1.01.0Power factor (adjustable)0.85 leading ... 0.85 lagging0.85 leading ... 0.85 laggingEFFICIENCY@240 V@208 V@240 V@208 VPeak efficiency97.6 %97.6 %97.5 %97.3 %CEC weighted efficiency97.0 %97.0 %97.0 %97.0 %MECHANICAL DATAAmbient temperature range-40ºC to +65ºCRelative humidity range4% to 100% (condensing)Connector type (IQ7-60-2-US & IQ7PLUS-72-2-US)MC4 (or Amphenol H4 UTX with additional Q-DCC-5 adapter)Connector type (IQ7-60-B-US & IQ7PLUS-72-B-US)Friends PV2 (MC4 intermateable). Adaptors for modules with MC4 or UTX connectors:- PV2 to MC4: order ECA-S20-S22- PV2 to UTX: order ECA-S20-S25Dimensions (WxHxD)212 mm x 175 mm x 30.2 mm (without bracket)Weight1.08 kg (2.38 lbs)CoolingNatural convection - No fansApproved for wet locationsYesPollution degreePD3EnclosureClass II double-insulated, corrosion resistant polymeric enclosureEnvironmental category / UV exposure ratingNEMA Type 6 / outdoorFEATURESCommunicationPower Line Communication (PLC)MonitoringEnlighten Manager and MyEnlighten monitoring options.Both options require installation of an Enphase IQ Envoy.Disconnecting meansThe AC and DC connectors have been evaluated and approved by UL for use as the load-break disconnect required by NEC 690.ComplianceCA Rule 21 (UL 1741-SA)UL 62109-1, UL1741/IEEE1547, FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO. 107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according manufacturer’s instructions.Enphase IQ 7 and IQ 7+ Microinverters THigh quality, German-engineered system for residential and commercial installations T4 rail sizes available to suit all structural conditions TUniversal components for all rail types TUse 2 innovative components to turn this system into Shared Rail or Tilt Up TMK3 technology provides highest rail engagement TRoof attachments for all roof types T100% code compliant, structural validation for all solar states TFast installation with minimal component count result in low total installed cost TSimple to design using our code compliant online design tool, BaseProduct warranty · · in system alliance25yearswww.everest-solarsystems.comCrossRail SystemComponents CrossRail 48-XPart NumberDescription4000662CrossRail 48-X 166'', Mill4000663CrossRail 48-X 166'', Dark4000675CrossRail 48-X 180'', Mill4000665CrossRail 48-X 180", DarkCrossRail 48-XLPart NumberDescription4000695CrossRail 48-XL 166'', Mill4000705CrossRail 48-XL 166'', DarkCrossRail 80Part NumberDescription4000508CrossRail 80 168" Rail MillCrossRail End ClampPart NumberDescription4000429CR EC Silver, 30-50mm, Shared RL 30-45mm4000430CR EC Dark, 30-50mm, Shared RL 30-45mm4000003Shared Rail EC Silver, SS 46-50mm4000004Shared Rail EC Dark, SS 46-50mmCrossRail Mid Clamp StandoffPart NumberDescription4000601-HCR MC Silver, 30-50mm, 13 mm Hex4000602-HCR MC Dark, 30-50mm, 13 mm HexYeti ClampPart NumberDescription4000050-HYeti Hidden EC for CR, Mill, 13 mm HexCrossRail Structural Rail ConnectorPart NumberDescription4000051Rail Connector CR 44-X, Set, Mill4000052Rail Connector CR 44-X, Set, Dark4000385RailConn CR 48-X,48-XL Struct Set, Mill4000386RailConn CR 48-X,48-XL Struct Set, DarkL-Foot Slotted SetPart NumberDescription4000630L-Foot Slotted Set, Mill4000631L-Foot Slotted Set, DarkAluminum End ClampPart NumberDescription4005344CrossRail EC Silver, AL 32-33mm4005169CrossRail EC Silver, AL 34-36mm4005290CrossRail EC Silver, AL 37-38mm4005170CrossRail EC Silver, AL 39-41mm4005291CrossRail EC Silver, AL 42-44mm4005171CrossRail EC Silver, AL 45-47mm4005292CrossRail EC Silver, AL 48mm4005172CrossRail EC Silver, AL 49-50mmEverFlash eCompPart NumberDescription4000015EverFlash eComp + SRS Slide Kit, Mill4000366EverFlash eComp Kit, Black4000679EverFlash eComp Kit, Mill LF, Dark Flash4000367EverFlash eComp Kit, Silver4000027EverFlash eComp+SR Slide Kit, Dark4000029EverFlash eComp+SR Slide, LF Mill, DarkEverest Ground LugPart NumberDescription4000006-HEverest Ground Lug Set, 13 mm HexPart NumberDescription4000054EverFlash XP Slider Kit, Mill4000055EverFlash XP Slider Kit, Dark4000057EverFlash XP Kit, Mill LF, Dark Flash4000060EverFlash XP Comp Kit, Dark4000061EverFlash XP Comp Kit, MillEverFlash XP CompFlat Tile HookPart NumberDescription4000034Flat Tile Hook, Set, W/ lagsTC Wire Management ClipPart NumberDescription4000069Wire Management Clip, TCCrossRail 44-XPart NumberDescription4000019CrossRail 44-X 166'', Mill4000020CrossRail 44-X 166'', Dark4000021CrossRail 44-X 180", Mill4000022CrossRail 44-X 180", Darkwww.everest-solarsystems.comCrossRail System Product Sheet US11 | 0620 · Subject to change · Product illustrations are exemplary and may differ from the original. The Enphase IQ Combiner 3™ with Enphase IQ Envoy™ consolidates interconnection equipment into a single enclosure and streamlines PV and storage installations by providing a consistent, pre-wired solution for residential applications. It offers up to four 2-pole input circuits and Eaton BR series busbar assembly. Enphase IQ Combiner 3 (X-IQ-AM1-240-3) To learn more about Enphase offerings, visit enphase.com Data Sheet Enphase Networking Smart • Includes IQ Envoy for communication and control • Flexible networking supports Wi-Fi, Ethernet, or cellular • Optional AC receptacle available for PLC bridge • Provides production metering and optional consumption monitoring Simple • Reduced size from previous combiner • Centered mounting brackets support single stud mounting • Supports back and side conduit entry • Up to four 2-pole branch circuits for 240 VAC plug-in breakers (not included) • 80 A total PV or storage branch circuits Reliable • Durable NRTL-certified NEMA type 3R enclosure • Five-year limited warranty • UL listed To learn more about Enphase offerings, visit enphase.com © 2018 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ Combiner 3, and other trademarks or service names are the trademarks of Enphase Energy, Inc. 2019-11-04 MODEL NUMBER IQ Combiner 3 X-IQ-AM1-240-3 IQ Combiner 3 with Enphase IQ Envoy™ printed circuit board for integrated revenue grade PV production metering (ANSI C12.20 +/- 0.5%) and optional* consumption monitoring (+/- 2.5%). ACCESSORIES and REPLACEMENT PARTS (not included, order separately) Enphase Mobile Connect™ CELLMODEM-03 (4G/12-year data plan) CELLMODEM-01 (3G/5-year data plan) CELLMODEM-M1 (4G based LTE-M/5-year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 microinverters. (Available in the US, Canada, Mexico, Puerto Rico, and the US Virgin Islands, where there is adequate cellular service in the installation area.) Consumption Monitoring* CTCT-200-SPLIT Split core current transformers enable whole home consumption metering (+/- 2.5%). * Consumption monitoring is required for Enphase Storage Systems Wireless USB adapterCOMMS-KIT-01 Installed at the IQ Envoy. For communications with Enphase Encharge™ storage and Enphase Enpower™ smart switch. Includes USB cable for connection to IQ Envoy or Enphase IQ Combiner™ and allows redundant wireless communication with Encharge and Enpower. Circuit Breakers BRK-10A-2-240 BRK-15A-2-240 BRK-20A-2P-240 Supports Eaton BR210, BR215, BR220, BR230, BR240, BR250, and BR260 circuit breakers. Circuit breaker, 2 pole, 10A, Eaton BR210 Circuit breaker, 2 pole, 15A, Eaton BR215 Circuit breaker, 2 pole, 20A, Eaton BR220 EPLC-01 Power line carrier (communication bridge pair), quantity - one pair XA-PLUG-120-3 Accessory receptacle for Power Line Carrier in IQ Combiner 3 (required for EPLC-01) XA-ENV-PCBA-3 Replacement IQ Envoy printed circuit board (PCB) for Combiner 3 ELECTRICAL SPECIFICATIONS Rating Continuous duty System voltage 120/240 VAC, 60 Hz Eaton BR series busbar rating 125 A Max. continuous current rating (output to grid)65 A Max. fuse/circuit rating (output)90 A Branch circuits (solar and/or storage)Up to four 2-pole Eaton BR series Distributed Generation (DG) breakers only (not included) Max. continuous current rating (input from PV)64 A Max. total branch circuit breaker rating (input)80A of distributed generation / 90A with IQ Envoy breaker included Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy MECHANICAL DATA Dimensions (WxHxD)49.5 x 37.5 x 16.8 cm (19.5” x 14.75” x 6.63”). Height is 21.06" (53.5 cm with mounting brackets). Weight 7.5 kg (16.5 lbs) Ambient temperature range -40º C to +46º C (-40º to 115º F) Cooling Natural convection, plus heat shield Enclosure environmental rating Outdoor, NRTL-certified, NEMA type 3R, polycarbonate construction Wire sizes • 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors• 60 A breaker branch input: 4 to 1/0 AWG copper conductors• Main lug combined output: 10 to 2/0 AWG copper conductors• Neutral and ground: 14 to 1/0 copper conductors Always follow local code requirements for conductor sizing. Altitude To 2000 meters (6,560 feet) INTERNET CONNECTION OPTIONS Integrated Wi-Fi 802.11b/g/n Ethernet Optional, 802.3, Cat5E (or Cat 6) UTP Ethernet cable (not included) Cellular Optional, CELLMODEM-01 (3G) or CELLMODEM-03 (4G) or CELLMODEM-M1 (4G based LTE-M) (not included) COMPLIANCE Compliance, Combiner UL 1741, CAN/CSA C22.2 No. 107.1, 47 CFR, Part 15, Class B, ICES 003 Production metering: ANSI C12.20 accuracy class 0.5 (PV production) Compliance, IQ Envoy UL 60601-1/CANCSA 22.2 No. 61010-1 Enphase IQ Combiner 3 TEverest’s very own comp shingle flashing and mount! TBest in class - 3 stages of waterproofing TAll CrossRail hardware included and preassembled TUL 441 Section 27 Rain test TTAS 100-95 Wind driven rain testButyl gasket seals L-Foot - Flashing con-nectionEPDM sealing washer on lag boltDome provides fully encapsulated raised sealPart NumberDescription4000057EverFlash XP Kit, Mill LF, Dark Flash4000060EverFlash XP Comp Kit, Dark4000061EverFlash XP Comp Kit, Millwww.everest-solarsystems.comEverFlash XP CompEverFlash XP Comp Product Sheet US03 | 0120 · Subject to change · Product illustrations are exemplary and may differ from the original. EverFlash XP Comp FlashingPart NumberDescription4000037EverFlash XP Flashing 24ga Galv, Dark4000056EverFlash XP Flashing 24ga Galv, MillComponents EverFlash XP L-Foot and Butyl GasketPart NumberDescription4000036EverFlash XP L-Foot Mill4000038EverFlash XP L-Foot Dark4000063XP Butyl Gasket, LfootLag Bolt and Washer TMaterial: stainless steel TEPDM backed washer TPreassmbled TMaterial: aluminum TFinish: mill or dark TT-Bolt for CrossRail included TMaterial: galvalume TFinish: mill or dark