HomeMy WebLinkAboutNOA; Hurricane Master Model 824 or 811 Steel Sectional Garage DoorI MIAMI- ADE MIAMi-DADE COUNTY $ PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315 2599 NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy DAB. Door Company, Inc. 12195 NW 981 Avenue Hialeah Gardens, FL 33018 SCOPE: w, ti This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER-Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER ieserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code, including the High Velocity Hurricane Zone. DESCRIPTION: Hurricane Master® Model 8241811 Steel Sectional Garage Door 16' 2" Wide with Window Lite Option (DP +36.0, -44.0 PSF) APPROVAL DOCUMENT: Drawing No. 02-21 Rev L, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated 09/10/2002 and last revised on OCT 05, 2017, sheets 1 through 5 of 5, prepared by Al- Farooq Corporation, signed and sealed by Javad Ahmad, P.E., bearing the Miami -Dade County Product Control Revision stamp with the Notice of Acceptance number and expiration date by the Miami -Dade County Product Control Section. MISSILE IMPACT RATING: Large and Small Missile Impact Resistant LABELING: A permanent label with the manufacturer's name or logo, manufacturing address, model/series number, the positive and negative design pressure rating, indicate impact rated if applicable, installation instruction drawing reference number, approval number (NOA), the applicable test standards, and the statement reading `Miami -Dade County Product Control Approved' is to be located on the door's side track, Y" r bottom angle, or inner surface of a panel. rY;l !� RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change a in the applicable building code negatively affecting the performance ofthis product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal ofNOA. ADVERTISEMENT: The NOA number preceded by the words Miami Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be a th r by ac or . s ' " 'butors and shall be available for inspection at the job site at the re . B b O c This NOA revises NOA # 15-0304.01 and consi ' : of s e ' • ce es -1, E- and E-3, as well as approval document mentioned above. The submitted documentation was reviewed by ishaq I. Chanda, P.E. NOA No.17-1018.12 MIAMIOADE COUNTY Expiration Date: July 21, 2020 1 a • • �. , Approval Date: December 14, 2017 Page 1 �( % ' e r 1� �. DAB Door Company.. Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED I 1. Evidence submitted in previous files A. DRAWINGS 1. Drawing No. 02-21, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated 09/10/2002, with last revision K dated 03/09/2015, sheets 1 through 5 of 5, prepared by Al- Farooq Corporation, signed and sealed by Javad Ahmad, P.E. B. TESTS "Submitted under NOA # 11-0414.12" 1. Test Report on Uniform Static Air Pressure Test, Loading and Forced Entry Test per FBC, TAS 202-94, of "DAB 824 Sectional Residential Garage Door" prepared by Hurricane Engineering & Testing Inc., Report No. HETI-07-4200, dated 05/02/2007, signed and sealed by Candido F. Font, P.E. 2. Test Report on Large Missile Impact Test per FBC, TAS 201-94 and Cyclic Wind Pressure Test per FBC, TAS 203-94, df `CAB 824 Sectional Residential Garage Door", prepared by Hurricane Engineering & Testing Inc., Report No. HETI-11-3204, dated 01/2012011, signed and sealed by Candido F. Font, P.E. 3. Test Report on Tensile Test per ASTM E8-08 of "Sectional Residential Door (skin)", prepared by Hurricane Engineering & Testing Inc, Report No. HETI-11-T100, dated 01/21/2011, signed and sealed by Candido F. Font, P.E. "Submitted under NOA # 05-0228.02" 4._ Test Report on Large Missile impact Test and. Cyclic Wind Pressure Test, of "Sectional Residential Door with Windows", prepared by Hurricane Engineering & Testing Inc., Report No. B ETI 03-1328, dated 07/15/2003, signed and sealed by Rafael E. Droz-Seda, P.E. 5. Test Report on Uniform Static Air Pressure Test, of "Sectional Residential Door" prepared by Hurricane Engineering & Testing Inc., Report No. HETI 03-1329, dated 07/15/2003, signed and sealed by Rafael E. Droz-Seda, P.E. 6. Test Report on Tensile Test per ASTM E-8 of "Sectional Residential Door (skin)", prepared by Hurricane Engineering & Testing Inc, Report No. HETI 03-T078, dated 10/31/2003, signed and sealed by Rafael E. Droz-Seda, P.E. "Submitted under NOA # 03-0210.04" 7. Test report on Salt Spray (Corrosion) Test per ASTM B 117 of a painted G-40 steel panels, prepared by Celotex Corporation, Test Report No. 258592, dated 08/17/1998, signed by W. A. Jackson, P.E. C. CALCULATIONS "Submitted underNOA # 14-0814.10" 1. Anchor verification calculations prepared by Al-Farooq Corporation, dated 09/22/2014 and 07/24/2014, signed and sealed by Javad Ahmad, P.E. Jshaq LL Chanda, P.E. Product Control Examiner NOA No.17-1018.12 Expiration Date: July 21, 2020 Approval Date: December 14, 2017 E-1 DAB Door Company, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED C. CALCULATIONS (Cont.) "Submitted under NOA # 11-0414.12" 2. Anchor verification calculations prepared by Al-Farooq Corporation, complying with F.B.0 2007, dated 04/07/2011, signed and sealed by Javad Ahmad, P.E. 3. Anchor verification calculations prepared by Al-Farooq Corporation, complying with F.B.0 2007, dated 12/1912008, signed and sealed by Humayoun Farooq, P.E. "Submitted under NOA # 09-0128.02" D. QUALITY ASSURANCE 1. Miami Dade Department of Regulatory and Economic Resources (RER) E. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No.13-0717.01, issued to SABIC Innovative PIastics, for their Lexan Sheet Products, approved on 11/28/2013 and expiring on 07/17/2018. 2. Notice of Acceptance No.14-0311.08, issued to Insulfoam, LLC, for their Insulfoam Expanded Polystyrene Insulation, approved on 08/14/2014 and expiring on 11/29/2017. 3. Notice of Acceptance No.11-0926.07, issued to Dyplast Products, LLC, for their Expanded Polystyrene Block Type Insulation, approved on 11/10/2011 and expiring on 01/11/2017. 4. Notice of Acceptance No.11-0926.06, issued to Dyplast Products, LLC, for their Dyplast ISO-C1 Polyisocyanurate Insulation, approved on 11/10/2011 and expiring on 01/1 i/2017. 5. Notice of Acceptance No.10-1129.04, issued to Cellofoam North America Inc, for their Expanded Polystyrene Block Insulation, approved on 02/24/2011 and expiring on 02/24/20I6. "Submitted under NOA # 05-0228.02" 6. Test Report on Accelerated Weathering Using Xenon Arc Light Apparatus Test per ASTM G155 of "PVC Extrusion Material", prepared by Hurricane Engineering & Testing, Inc., Report No. BETI 04-A002, dated 09/27/2004, signed and sealed by Rafael E. Droz-Sella, P.E. 7. Test Reports on Tensile Test per ASTM D638 of "PVC Extrusion Material", prepared by Hurricane Engineering & Testing Inc., Report No. HETI 04-T251, dated 11/29/2004 signed and sealed by I. Ghia, P.E. S. Test Report on Self -Ignition Temperature Test, Rate of Burn Test and Smoke Density Test of "REHAU non -foam PVC extrusion material", prepared by ETC Laboratories, Report No. 04-761-15019.0, dated 05/06/2004, signed and sealed by J. L. Doldan, P.E. F. STATEMENTS "Submitted under NOA # 14-0814.10" 1. Statement letter of code conformance to the 51 edition (2014) FBC and no financial interest issued by Al-Farooq Corporation, dated 05/13/2014, signed and sealed by Javad Ahmad, P.E. Ishaq 1. Chanda, P.E. Product Control Examiner NOA No.17-1018.12 Expiration Date: July 21, 2020 Approval Date: December 14, 2017 E -2 DAB Door Comaanv, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUB. 2. New Evidence submitted. A. DRAWINGS 1. Drawing No. 02-21 Rev L, titled "24 GA. Roll Formed Steel Sectional Garage Door", dated 09/10/2002 and last revised on OCT 05, 2017, sheets 1 through 5 of 5, prepared by Al-Farooq Corporation, signed and sealed by Javad Ahmad, P.E. Note: This revision consist of editorial changes to comply with FBC 2017. B. CALCULATIONS 1. None C. QUALITY ASSURANCE 1. Miami Dade Department of Regulatory and Economic Resources (RER). D. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No.17-0221.06, issued to Insulfoam, LLC, for their Insulfoam Expanded Polystyrene Insulation, expiring on 11/29/2022. 2. Notice of Acceptance No.16-1108.04, issued to Dyplast Products, LLC, for their Dyplast ISO-Cl Polyisocyanurate Insulation, expiring on 01/11/2022. 3. Notice of Acceptance No.15-1203.04, issued to Cellofoam North America Inc, for their Expanded Polystyrene Block Insulation, expiring on 02/24/2021. 4. Notice of Acceptance No.15-0915.08, issued to SABIC Innovative Plastics, for their Lexan Sheet Products, expiring on 07/17/2018. E. STATEMENTS 1. Statement letter of conformance to FBC 2014 (51h Edition) and FBC 2017 (6th Edition), prepared by Al Farooq Corporation, dated 10/05117, signed and sealed by Javad Ahmad, P.E. F. OTHER 1. This NOA revises NOA #15=0304.01, expiring 07/21/20. 1�,kt!� \ . U. •,yt—\ o. Ishaq I. Chanda, P.E. Product Control- Examiner NOA No.17-1018.12 Expiration Date: July 21, 2020 Approval Date: December 14, 2017 E -3 7-1/2' X 2-1/4• X 18 GA YU GALV. STEEL CENTER HINGE �\ W/ (4) #14 X 5/8' SMS i '\ m I WITHOUT DELRON SLEEVE (STD.) p 7-1/2" X 3' X .071' GALV. STEEL i 0 0 END ROLLER HINGE p p W/ (6) #14 X 5/8' SMS WITHOUT DELRON SLEEVE (STD.) WITH DELRON SLEEVE (OPTIONAL) p i m 7-1/z• X 2-1/4" X .071' LOCK `\�---- GALV. STEEL CENTER HINGE 2 DOOR ` m w/ (4) 014 X 5/B' SMS _ _ _ _/_ ` WITH DELRON SLEEVE l � of V. 1 1 1" W X .15 THK. LATCH \\ CENTER HINGSTANDARD LOCK �\ E \ SPRING LOADED SLIDE BOLT (BOTH SIDES FASTENED W/ (4) #14 X 1/2' SJM.S. MIN. LOCK ENGAGEMENT CONFORMS TO SECTION 1008 REGARDING GARAGE DOORS r- .158 DIA. GALV. AIRCRAFT TYPE 5WNW NCO -PRESS EFACTOR 4 m 1I 1 A O 14 I2-3/4-W X 5-5/8-H X .090' THK. STEEL PLATE, 1-3/8' DEEP WITH (3) 914 X 3/4' SELF DRIWNG SCREWS BRACKET STD. LIFT DOOR TOTAL � OF DOOR 'U' 8AR5 AT HEIGHT CONSISTS OF EACH DOOR 6'-6' 2 SECTIONS 18. 2 SECTIONS 21' B'-B' 1 SECTION 18" 3 SECTIONS 21' 7' 4 SECTIONS 21" - 7'-3• - - V-6' 5 SECTIONS 1B" - 7'-9' 4 SECTIONS 18" 1 SECTION 21' e' 3 SECTIONS 18" 2 SECTIONS 21' 2 SECTIONS 18" 3 SECTIONS 21" 1 SECTION 18" 4 SECTIONS 21' 8'-9' 5 SECTIONS 21' - 9' 6 SECTIONS 18' - 9'-3" 5 SECTIONS 18" 1 SECTION 21" ' 4 SECTIONS 1B' 2 SECTIONS 21" 9'-9' 3 SECTIONS 18' 3-SECIIONS 21' 10. 2 SECTIONS 18" 4 SECTIONS 21' 1 0'-3' 1 SECTION 18' S SECf10N5 21- S2 s 10'-6' a SECTIONS 21' - 10'-B' 6 SECTIONS 18' 1 SECTION 21' 11' 5 SECTIONS 18" 2 SECTIONS 21' 11'-3' 4 SECTIONS 18' 3 SECTIONS 21' 11'-B' 3 SECTIONS 18' 4 SECTIONS 21' 11'-9' 2 SECTIONS 18" S SECTIONS 21' •� 12' 1 SECTIONS 18' B SECTIONS 21' 12'-3' 7 SECTIONS 21' - 12'-6' a SECTIONS 18" 2 SECTIONS 21' 12'-0" 5 SECTIONS is- 3 SECTIONS 21' 13, ONS 1B' 4 SECTIONS 21' 13'-3' ONS121- S SEC110NS 21' 13'-6' ON 6 SECTIONS 21' 13'-9. ON7 SECTIONS 21• 14' ON - 14'-3'ON RSECnONS 3 SECTIONS 21; 14'-6' ON 4 SECTIONS 21'14'-9' ON 5 SECTIONS 21' 15' ON 6 SECTIONS 21' 15'-S' ONS 16" 7 SECTIONS 21' 15'-6" 1 SECTION 18" 8 SECTIONS 21' 15'-9' 9 SECTIONS 21' - 18' 6 SECTIONS 15. 4 SECTIONS 21' NUT TOP FIXTURE 5-1/2" X 2-3/4' X 0.1' STEEL PLATE WITH ONE 5/16-18 MS W/ NUT FASTENED TO END STILE WITH (6) 014 X 3/4" SELF DRILLING SCREWS SEE SHEET 3 FOR TOP BRACKET OPTIONS OPTIONAL DOOR VIEWER TO BE INSTALLED En AT ANY CENTER STILE CENTER STILES SEE SCH. 'A' 1:3 LJ13 9[:3 Eji M 7-7/8' X 3-1/8" X .DID- L OPTIONAL VENTS STEEL PLATE (3) 5' WIDE AT 7" O.C. MAX. WITH (4) 014 X 3/4' SDS OPNG. AREA NOT TO EXCEED 120 SQ. IN. OPTIONAL FLUSH FACE I WOOD GRAIN DESIGN L — A CENTER STILE THIS PRODUCT IS RATED FOR LARGE MISSILE IMPACT INSIDE ELEVATION ourslDE RAISED PANEL EMBOSSED DOOR HANDLE END STILE LOCK BAR GUIDES INSTALLED ON END STILE (4) 004 X 5/8' SKIS e Q jWff-H X .6W LOCK BAR GES IN TRACK ON EACH SIDE OF DOOR CENTER STILES OUTSIDE KEYED LOCOPTION LOCK BAR LOCKING SHOWN ALTERNATE TO SPRING LOADED SLIDE BOLT LOCKS SHOWN ABOVE I 8'-0' TO 9'-10" _I DOOR WIDTHS DOOR TESTED IN ACCORDANCE TAS-20 THE TASF UIR MENTSFOR IOF AND FLORIDA II 1. THIS PRODUCT HAS BEEN DESIGNED AND TESTED TO COMPLY WITH THE REQUIREMENTS OF THE 2014 (STH EDTIIDN)/2017 (67H EDITION) FLORIDA BUILDING CODE INCLUDING HIGH VELOCITY HURRICANE ZONE (HVHZ). 2. ANCHORS SHALL BE CORROSION RESISTANT, SPACED AS SHOWN ON DETAILS AND INSTALLED PER MANUF'S INSTRUCTIONS. SPECIFIED EMBEDMENT TO BASE MATERIAL SHALL BE BEYOND WALL DRESSING OR STUCCO. 3. A LOAD DURATION INCREASE IS USED IN DESIGN -OF ANCHORS INTO WOOD ONLY. 4. MATERIALS INCLUDING BUT NOT LIMITED TO STEEL/MErAL SCREWS, THAT COME INTO CONTACT WITH OTHER DISSIMILAR MATERIALS SHALL MEET THE REQUIREMENTS OF THE 2014/2017 FLORIDA ITLDG. CODE do ADOPTED STANDARD! 5. 719S PRODUCT APPROVAL IS GENERIC AND DOES NOT PROVIDE INFORMATION FOR A SITE SPECIFIC PROJECT. 1- LIFE SAFETY OF THIS PRODUCT, ADEQUACY OF STRUCTURE RECEVING THIS PRODUCT AND S.ALWG AROUND OPENING FOR WATER INFILTRATION RESISTANCE ETC. CONDITIONS NOT SHOWN IN THIS DRAWING ARE TO BE ANALYZED SEPARATELY. AND 70 BE RENEWED BY BUILDING OFRMAL 6. MANUFACTURER'S LABEL SHALL BE LOCATO ON A READILY VISIBLE LOCATION IN ACCORDANCE WITH SECTION 1709.9.3 OF FLORIDA BUILDING CODE LABELING TO COMPLY WITH SECTION 170'a?- �•'�- rmDUCE P"S� ®� ® ® FIIY4 X 3/4' SELF DRIWNG SCREWS 4Pb'L *Ab Ibc Fbdb BEUSEDW".x Quo 1a LIEU OF 814 X 5/8' SMS AcasPlucr Na ti l0( Iz I 10'-0" TO 11'-10' _I I 14'-0' TO 15'-10' _I E+PLr�Bec OBI! wV 2 ZOP DOOR WIDTHS DOOR WIDTHS �CA Q1 Nan n—nn i 12'-0" TO 13'-10' _I I IV-11" TO 16'-2, DOOR WIDTHS DOOR WIDTHS DAB DOORS INC. Hurricane Master® Model 824/811 Max. Size 16'-2" X 16'-0" High With Window Lite Option DESIGN PRESSURE RATING = + 36.0 PSF !worn — 44.0 PSF CEDER SOLES CONFIGURATION DOOR WIDTHS i OF CENTER STILES 8'-0' TO 9'-10' 2 10'-0' TO 11'-10' 2 12'-D' TO 13'-10' 3 14'-0' TO 15'-10' 4 15--11- TO 16'-2' S `- h r �IL2 56 O 0 W o IL �m V Gurd 0 C% 2 ppano i o'atio; 0 jISmQ� as-10 o � m N M P C O Taint cQ- o � aL H° e E o I ::j O Z 0 N d O N C3 e = 1 �WGEN@F'• `�� 7 STA. OF •Q(/` 1 02 dfawing no. �RiORIOP. saeJ� � 28Y WOOD MIN. �8 1/4- DIA LAG SCREWS AT D5LAG S 6CENDS 6' AND15"D.MXI2w6owe111 �NO.C.� OPTION 'A\'_� OPTION 'e' \V� WOOD BUCK CONNECTION TO WOOD SUBSTRATE (WOOD SPECIFIC GRAVITY SG=0S5 MIN.) THE INSTALLATION METHODS SHOWN ABOVE SHOWS 2X6 SYP WOOD BUCK ATTACHMENT TO WOOD STRUCTURES. IF THESE METHODS ARE FOLLOWED NO ADDITIONAL CALCULATIONS/DESIGN WILL BE REQUIRED FOR DESIGN OF GARAGE DOOR ANCHORAGE FOR DOOR REPLACEMENT APPLICATIONS WITH NO ENGINEER OF RECORD, INSTALLATION MAY BE VERIFIED AND APPROVED BY THE BUILDING OFFICIAL UPON INSPECTION. 5/16' X 1-5/8' LAG SCREWS AT 12" O.C. WOOD BUCK CONNECTION TO MASONRY \• PRESSURE TREATED 2X6 SYP WOOD JAMBS WHICH SHALL BE ANCHORED TO GROUTED REINFORCED MASONRY BLOCK WALL OR CONIC. COLUMN WITH 1/4' ULTRACON BY 'ELCO' WITH SPACING OF 12" D.C. INTO GROUT FILLED BLOCK WALL, WITH 2-1/4" MIN. EMBED 13" O.C. NTO 3000 PSI CONCRETE, WITH 1-3/4" MIN. EMBED 2-1/2" MIN. EDGE DISTANCE I/4" TAPPER-BY'POWERS' WITH -SPACING OF 11° O.C. INTO GROUT FILLED BLOCK WALL, WITH 1-1/2" MIN. EMBED 13 O.C. INTO 3000 PSI CONCRETE, WITH 1-3/4 MI . EMBED 1/16" X 2-1/2' 3" MIN. EDGE DISTANCE FILLET WELDS 3/8" CONFLEX BY 'ELCO' OR AT 12' O.C. MAX 3/8' LOT BY 'ITV( YATH SPACING OF 23' O.C. INTO 3000 PSI CONCRETE. WITH 2-1/2" MIN. EMBED 3' MIN. EDGE DISTANCE CONTINUOUS ANGLE TRACK 3/8" HLC SLEEVE BY 'HILTI' WITH SPACING OF 10' O.IN TO NTO GROUT FILLED BLOCK WALL, WITH 1-1/4' MIN. EMBED, 4' MIN. EDGE DIST. 15' O.C. NTO 3000 PSI CONCRETE, WITH 1-1/4' MIN. EMBED AND 2-1/2' MIN. EDGE DISTANCE PREPARATION OF JAMBS BY OTHERS FOR NEW CONSTRUCTION ENGINEER OF RECORD OR ARCHITECT TO VERIFY ADEQUACY OF SUPPORTING STRUCTURE TO SUPPORT LOADS IMPOSED BY DOOR SYSTEM. FOR DOOR REPLACEMENT IN RETROFIT BUILDINGS WITH NO ENGINEER OF RECORD, DOOR INSTALLATION MAY BE REVIEWED AND APPROVED BY BUILDING OFFICIAL UPON INSPECTION. MAXIMUM EXTERIOR(+) LOAD PER JAMB (16.16' X 62 PSF)/2 = 291 Lbs per Ft. MAXIMUM INTERIOR(-) LOAD PER JAMB s (16.16' X 44 PSF)/2 = 355.5 Lba per Ft. REINFORCEMENT r' m 1/2' X 1-3/4' X .058' � A 18 X 1' FORMED STEEL to SELF DRILLING SCREWS B X 1' OR T. w W tV 3/16' 'RIVE' STEEL RIVETS SELF DRILLING SCREWS OR MULTIGRIP W/ DOME AT 48' OTC. 3/16' 'RIVE%' STEEL RIVETS 0 pZ h h ,cgW� MULTIGRIP W/ DOME HEAD AT 48" O.C. Q N p ORCEMENT Qi p 1 /2" X 1-33/F4"" X 0 8 FORMED STEEL O O O �V.. {gY �►O[ n 8pp W'STRIP ADAPTER ALUMINUM ADAPTER V Oa o SEEELIP O a I): Q RUBBER W'STRIPPING RUBBER W STRIPPING G o7 r Z U, 050 .040 .534 .700 LL 3 891 IL�L�L4„ 222111 166�222JJJI .3d8 I�T F^1.750�� 1.790--I � BOTTOM SEAL OPTIONS PR(11)UCF REVSW W N m AS W-plyly sIlb lbe Fled" burBnR Cafe � t Arceplaace Na / "• O / ) Z �NM E:%Wri A 772- .(y1 Ip ti 4 LL ANCHOR SPACING ANCHORS STRUCTURE EMBED SPACING EDGE DIST. t/+ 8 136 E rp c e -3/6- HLC SLEEVE BY HILTI CONC. 1-1 4 8' 2' 3 8' CONFLEX BY ELCO' FlLLEO BLOCK 3-3 4 ��, 0j am w e, 3 3 B' DYNABOLT BY 'fIY/' CONIC. 1-1.2 8' STEEL STRUCTURE BY OTHERS 3 8 POWER -BOLT BY POWERS CONIC. 8' 2" MUST SUPPORT THE LOADS IMPOSED c p pp Z 0 s. BY DOOR SYSTEM 3 8 SLEEVE -ALL BY MPSONS CONIC. 1-12 8' 3' Lo p o CONCRETE Pc - 3000 PSI MIN. d v N o C-90 GROUT FILLED BLOCK Pm 20011 PSI LAN, 5/16' DIA. BOLTS v r WITH WASHER & NUT 0 f AT 12' O.C. MAX. E DIST EDG1-1//4 X 2-1/Y X 14 GA ANGLE11-1/2"12 c Y�1CONT...STEEL GA GALV. STEELFLAT BRACKETS t3' LONG 2-1 /9' x 1°x14 GA. iW/ AT 12O.C. IN DOOR OPNG.GgLV. STEELTRACKAT 18' O.C. ABOVE DOOR OPNG. FASTENED TO TRACK PLATESCONNECTED TO CONT: ANGLE W/(2T 1/4-20X5/8' TRUSS HO. SPOT WELDS IS (3) AT EACH SIDE SLOTTED f1 S. & LOCK NUT REVERSE TRACK ONTIN U0 AN TRA K y WRI •L TO STEEL TO CONCRETE AND FILLED BLOCK m 592 sT of drawing no. ',,��Aza.Da�.cy1��, 02-21 1m 0_ W IS PANEL GA. (.024) STEEL MIN. * -PLASTIC COMPLIES WITH CHAPTER 26 OF FBC SEE EVIDENCE PAGE DIA. WASHER ®8 X 3/4' SMS 21 3/4' -0 3/8" FROM ENDS MAX. AND 7" O.C. MAX. WDW. WIDTH 12 (4) #8 X 3/4" SMS _ ti 18 1/B" -O 1-3/8" FROM ENDS \ m .4 d D.L.O. AND 6-1/2" O.C. MAX. a 3 ° I 175 X .062 DEEP A O C GROOVE I 1/4" POLYCARSONATE LEXAN BY 'SABIC INNOVATIVE PLASTICS' NOA 015-0915.08 175 X .062 DEEP GROOVE (4) 18 X 3/4" SMS _,—® 1-3/8" FROM ENDS AND 6-1/2" O.C. MAX. a8 X 3/4" SMS .-0 3/8' FROM ENDS AND 7. O.C. MAX. 6" DIA. WASHER DOOR PANEL 24 GA (.024) STEEL MIN. .500 r-- r.250 al I I �� o 02 N I 0 h n h 1.r65 1.725 Q g S N CD 1.144 d 5 cV 0 G yi city„ .176 h--.8D0 O aQ ° * EXTERIOR FRAM * INTERIOR FRAME RIGID PVC ONE PIECE INJECTION RIGID PVC ONE PIECE INJECTION Q Q i�7i 0I�0 P,4,t t,-� 20 WoW � L¢J A N J M N M � le. as zoP O o N � i • N � IV III''nII'II IFS 0 3/8' FROM ^ENDS O AND 4-1/2" O.C. MAX., DOOR PANEL 24 GA (.024) STEEL MIN. MIN. INSIDE ELEVATION RAISED PANEL EMBOSSED DOOR WITH OPTIONAL WINDOWS MTODUCEREV19 'WINDOW LITES CAN BE IN ANY LOCATION IN DOOR SECTION �i Coft stnl AaeW-1 N, _.175 X .062 DEEP E�plrall�e 41c EXTERIOR till 9gi . drawing �'�.` 02-21 `�� sheet 5 of 5 RIVETS 5/16" X 1-5/8" LAG SCREWS INTO WOOD OR 2-3/4' X 5-1/2' X 3" % .1 Be' 5/16' SLEEVE ANCHORS 1-1/4° EMBED INTO MASONRY N GAL/. STEELWITH "TOP ROLLER BRACKET ON EACH SIDE 3 PER BRACKET FASTENED W/ (6) 9 14 X 5/8" S.M.S. - 14 GA GALV. STEEL ADJUSTABLE 2-1/2" X 4-1/4" X 13 GA. STEEL PLATES `SUOE FASTENED TO BRACKET - WELDED TO 1-1/2" X 1-1/2' X 14 GA. ANGLE 1'L/ 5/16-18 X 3/4" HEX HEAD FASTENED TO TRACK / M. SCREWS & NUTS. WITH (4) 1/4-20 SS. BOLT & NUTS TOP BRACI(ET (STANDARD) TOP BRACKET (OPTIONAL) LOW HEADR M DOOR HORIZONTAL REINFORCEMENT 1/2" X 1-3/4" X .058" FORMED STEEL �GLLED TO PANEL AND FASTENED TO VERTICAL STILES WITH 2" X 5-1/2' % .104' (2) 3/16" POP RIVETS GALV. STEEL pp FASTENED W.0 4 ROLL64 BRACKET OR LOW HEADROOM DOOR OPTION �— HORIZONTAL REINFORCEMENT 1/2' X 1-3/4" X .058" FORMED STEEL GLUED TO PANEL AND FASTENED TO VERTICAL STILES WITH (2) 3/16' POP RIVETS 5/16" MEETING RIB PLASTIC/STEEL ROLLERS 1.82" DIA. X .50" W/ .44 DIA X 4-1/4" STEM OPTIONAL INSULATIONS: 150-25 POLY-ISOCYANURATE DENSITY - 2.0 PCF N.OA #16-1108.04 OR DENSITY - 1.03 PCF N.OA 815-1203.04 9Y 'INSl4tOAM LLG'Llc' DENSITY - 0.92 PCF H•OA ®17-0221.06 14 GA. GALV. STEEL ROLLERHI 14ES FASTENED MIN. .024" ROLL FORMED STEEL PANEL 12 GA. GALV. STEEL BOTTOM OOTTO B RACK14 X SFASTEN SD sf ylo —A SEE SHEET 2 FOR LOCATION OF REINFORCING TRUSSES HORIZ. TRACK SUPPORT, CENTER SUPPORT REOD. ON DOORS EXSEE01NG 8 FT. IN HEIGHT II RACK LENGTH - OPENING HEIGHT PLUS 12" GA GALY. STEEL TRACK HO PT ANGLE X 1/8'HEIGHTS 1-1/2' X 1/2" DOOR FOR DOOR HEIGHTS WI 8 FF, WITHOUT INSULATION OR WINDOWS, 11! 2' % 2" X 1/8' HOfl(L ANGLE X �Y FOR DOOR HEIGHTS ABOVE B FT. OR DOORS WITH INSULATION OR WINDOWS Z m SPOT WELDED TO HORIZ. TRACK WITH TWO WELDS AT 1-1/2-APART y m Iy h 'ES FIRST AT 3' O.C., T AT 9' O.C. CONNECTED TO FLAG BRACKET ANGLE W/ 3/8-18 X 3/4' BOLT & NUT I- a' a IL �0 AND TO SPRING SHAFT GUIDE WITH (2) 1/4-20 X 5/8" BOLT & NUT G j N 11W'L V�ya 0 a e, VERTICAL TRACK 2. 2.13 C SECTION A —A 1I� y qq cl Q w fn 0 IL Zy� O .1 17 CKET PLACEMENTS mE� DOOR HEIGHT • SECTION HEIGHTS 1ST 2ND 3RD 4TH 5TH BRA 81 62 B3 84 85 86 B7 88 6'-0" 18" 18" 18' 18" N/A 1" TO 2" 11-3/4" 23" 34" 45" 56" 67" - 6'-6" 21' 18" 18" 21" N/A 1' TO 2" 11-3 4" 23' 34° 45° 56° 7'-0" 21' 21' 21' 21" N/A 1' TO 2" 11-3/4 23' 34' 45° 56' " - 7'-6" 18" 18" 18" 1B" 18" 1' TO 2" 11-3/4" 23' 34" 45' 56' 167" ° 78-1/4"B'-0' 34' 45' 56" " 78-1/4" "-SGUIIUNS ARC NU-0-- o —l— - — —11— FOR DOORS MORE THAN 8 FT. HIGH, USE ADDITIONAL TRACK BRACKETS AT 10" O.C. ►RODDC f REVISED 1.9' X 2.19" X 3.3" X .090" o caoplylag wilb 1Le Fhm". STEEL TRACK BRACKETS IsuwaR Cole m 2-3/16' HIGH AcceLNaacc No /O Z CONNECTED TO TRACK WITH 11PIr!stdea Date 1/4' BOLTS & NUTS. m 81fdr' atY Ba�Oad m m m M m N m m TACK CON�GURATIQNCONFlGURATIQN VERTICAL LIB G L STANDARD STANDARD L11I( LOW HADROOM DOUBLE TRACK AVAILABLE TRACK OPTION ,1LLILLJi, 1: 7 2 u a TA OF ' •�'`� draw ng$ no. �..... .... � 02-21 A II .055' X 2-1/4' X 3/4" X 2' GALV. STEEL U.BAR REINFORCING TRUSS 0 BOTTOM OF PANEL TRUSS FASTENED TO VERTICAL INTERMEDIATE STILES W/ TWO 014 X 5/8" S.M.S. AND TO END STILE W/ FOUR #14 X 3/4" SELF DRILLING S. Z� �u z z 00 _ in INTERMEDIATE SECTION TOP SECTION OPTIONAL STOP MOULDING BY DOOR INSTALLER STEEL TRACK BRACKET FASTENED TO WOOD JAMB WITH 14 X 5/8" SMS 5/16- X 1-5/8- LAG SCREW 6 PER HINGE (FULLY THREADED) HEX WASHER HEAD TYPE A 1/2- X 1-3/4" X .058" FORMED STEEL ONE PER BRACKET GLUED TO PANEL AND SECURED TO END STILE WITH (4) 3/16' POP RIVETS SOUTHERN PINE ,%4•,' 1-7/8' X 2-5/8- X .049" STEEL -0.. S. •;f CENTER STILE. GLUED AND RIVETED TO PANEL W/ (4) 3/16' RIMS 3/16• 1- MIN. ( �"4/1HINGE/8• Ste' POP RIVETS DIST. I 1 1.9' X 2.19" X 3.3' X .090" STEEL TRACK BRACKETS SEE SHEET 3 FOR SPACING STEEL TRACK 14 GA X 2-1/8- X 1' (STANDARD) 12 GA X 3-SF 1M6" NED TO TRACK PLATES) W/ 1/4-2D X 5/8" TRUSS NO. SLOTTED M.S. h LOCK NUT 24 GA STEEL PANEL Z m FLAPS BENT OVER PANEL 1 a q 0 1 S io 000.�.� 1/2' PUNCHED HOLES 04'0:0. ul O 0 I 0 CL a 0 o U) m� e' I ice, IKtOB(1Ct(i&yTgBp {L ZN_ o $ I Plrin rwF7urM. E '(o a uo f S Wmt�. Dal17-fa(g.12 �- e A. 3/16- POP RIVETS J �� D�"nCoand M AT 4" O.C. (6) FOR 21" STILES c (5) FOR 18" STILES .024" STL PANEL END STILE h M LL OUTSIDE OF 000 . a.a li r 8 o-co oo E�D OJ (-1 cy) .p N J o Z a N r C ,n r o mom$ SOLID BRASS DOOR VIEWER ' !� NBY o 3/4' X z" X 2-1/2" X .049" STEEL 'SCHL16'AGE IA HOLERITY HARDWARE' � END SOLE, CONNECT TO PANELS WITH INSTALLED IN 9/ IO DIA HOLES IN CENTER STILE FLAPS AND (5) OR (6) 3/16- ALUM RIVETS POSITIONED AT EYE LEVEL SEE DETAIL ABOVE ANCHORS AT TRACK BRACKET EDGE •}/R' me POWER-ROLT BY 'POWERS' o 6 "'STANCE 1 A) 2' MIN. EMBED INTO CONCRETE (3000-BSI MIN.) 2' MIN. EDGE DISTANCE w o 11-3/16 4/8' 4" DIA H - tY FFVE BY 'HILT' m .� °� ' •"°� ' B) 1-1 / MIN. EMBED INTO CONCRETE OR FILLED BLOCK b 2-1/4" MIN. EDGE DISTANCE INTO CONCRETE 4" MIN. EDGE DISTANCE INTO FILLED BLOCK CONCRETE Vc - 3000 PSI MIN. c d a r a C-90 GROUT FILLED BLOCK I'm= 2000 PSI MIN. 'H 50$ 3 a ANCHOR TYPE A OR B c V �1 PER BRACr^a aa°c¢er meciur. 1111I11111/T7j a-zo ss BOLT 7-1/2". X .050� INTERIORSIDE7-t/z" x .o7t' NUT GALV. STEEL END ROLLER HINGE CENTER HINGE 1.82- Obl X .50" STEEL ROLLERS (STD. TROLLER 1.82" DIA X .50" NYLON ROLLERS (OPTIONAL SHAFT 2.75" DIA. X .50" STEEL ROLLERS (OPTIONAL SECTION B-B 2.75" DIAL X .50" NYLON ROLLERS (OPTIONAL) WITH 5" STEM 1 N 0. 0592 OF drowing4 no.