HomeMy WebLinkAboutTruss=LIFE SAFETY WARNING
This symbol identifies Life Safety Warnings that
should be read and given special attention to all
persons installing trusses.
SPACING NOTE
All trusses are to be set 2'-0" on
center except as noted.
MULTIPLE PLY TRUSSES MUST BE FASTENED
TOGETHER PER ENGINEERING BEFORE
SETTING. REFER TO ENGINEERING DRAWING
TO DETERMINE IF MULTIPLE PLY:
i
DON'T LIFT TRUSSES
WITH SPANS LONGER THAN
30' BY THE PEAK.
CONSULT BCSI
30' Sp nor less3
zt
To u Span
Spre er Bar
60 degrees
or less
:Tag line 40. 12 span .....
T\line *—•tgprox V3 to a---,
approx.
12 of Span.
REFER TO BCSI
REFER TO SCSI -
Truss must be set This way if crane Is used.
Truss must be set this way if crane is used.
Truss is an example, your truss may not match.
Truss is an example, your truss may not match.
Insist crane operator sets truss this way.
Insist crane operator sets truss this way.
Ali Load bearing Walls, headers,
beams, & lintels must be in place
at indicated height before trusses
i are installed. Ae
AIR HANDLER NOTE
Unless noted elsewhere on this layout, these trusses are not
designed for air handlers in the roof or for any other A/C
requirements. This may be in conflict with building code and A/C
Design requirements. Consult with Building Department and A/C
Contractor.
!WARNINGI
The size of these trusses makes it necessary that they a set by a profeesional builder
familiar with and experienced in the problems and dangers of setting large span trusses.
The builder and erector should consult with an engineer licensed in Florida specializing
in wood roof trusses about the safe erection of these trusses. The engineer should be at
the job site when trusses are erected to provide supervision and advice.
I' SEAT PLATES BY CHAMBERS TRUSS
i
Recommended STRONGBACK for Floor Trusses
Refer to information on truss engineering drawings.
(2) led nails C top & bottom of 2x4 vertical block.
NOTES:
*ALL BEAMS BY OTHERS.
*TRUSS TO LEDGER CONNECTIONS DESIGNED & SUPPLIED BY OTHERS.
*INTERNAL LOAD BEARING WALLS REQUIRED BY TRUSSES AS SHOWN ON THIS LAYOUT.
*BUILDER TO SHIFT FLOOR TRUSSES TO FIT A.C. DUCT AS NEEDED.
to bottom cord as
L, Do not stand on trusses n • {gyp p /+p j� f� hangers
HIP CARRIER LOCATED AS DIMENSIONED ON LAYOUT FABRICATION ION AGREEMENT
Until they 1 ey are braced per BCSI & properly nailed to straps and � 1 a n g e rS !! � TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED & RETURNED
Do of het floor trusses I I \ he undersigned acknowledges and agrees: -
u p $ d e d O W n . Refer to e n g I n e e rl n g d ra W I n g s - 1. Trusses will made in strict accordance with this truss placement diagram layout, which is the sole authority for
_ elermining successful
ul fabrication of the trusses.
2. All dimensions in this layout have been verified by the undersigned. ,
COANDER JACKS 3. Unless written notice Is provided by certified mail to Chambers Truss within ten (10) days of delivery the
ARE NOT BEVELED. SEE STANDARD ndersigned agrees that no backcharges will be allowed. In the event such written notice is furnished Chambers Truss
\ \ ci W
- \ ENGINEERING. j d� hall have three (3) business days in which to begin repairs required, or to substitute other trusses, at Chambers option.
N 0 o fter 10 days of delivery remedy will be according to Florida statute 558.
4. The undersigned acknowledges receipt of 'BCSI' summarysheet by TPI & WTCA.
5. Delivery is to job site. It is the buyer's responsibility to make the job site suitable for delivery. Chambers Truss has
he sole authority to determine the suitability of the job site or a portion of the job site for delivery. Chambers Truss will
n e responsible for dump delivery only. The buyer is responsible for additional delivery expenses if Chambers Truss has
o redeliver because job site is not prepared for delivery or buyer is not prepared for delivery of trusses. Buyer is
esponsible to Chambers Truss for towing costs due to site conditions.
` 5. Price as shown in paragraph 7 below is subject to change 0 any changes are made in this layout. A $50 per hour
ee for revisions may be charged by Chambers Truss.
7. This is a PURCHASE ORDER to Chambers Truss of the sum agreed to, or if no agreement a reasonable price.
nvoice will be made on delivery and paid within terms of net on delivery. Invoice may be made at scheduled date of
elivery if buyer cannot accept delivery of fabricated trusses. The undersigned agrees to pay Chambers Truss
24' D.C. THRU easonable attorney's fee for collections in event of payment not timely made. 1-1/2 % per month service charge will be
CORNER JACKS 24' 1. 1 111 dded for all sums not paid within terms.
ONLY B. Signature or Initials anywhere on this sheet Constitutes agreement to all terms herein.
c A 9. In consideration of Chambers Truss extending credit for this material the undersigned unconditionally guarantees
CORNER DETAIL ayment when due of any and all indebtedness owed to Chambers Truss by any entity receiving material and the
ndersigned agrees to pay such indebtedness including attorney's fees, if default in payment for material be made by the
OVERHANGS NOT SHOWN FOR CLARITY eclplenl.
10. In the event of any litigation concerning this agreement, the items furnished hereunder or payments referred to
erein, the parties agree that the sole venue for any such action will be Saint Lucie County, Florida.
11. Design responsibilities are per ""National Standard And Recommended Guidelines On Responsibilities For
- onstruclion Using Metal Plate Connected Wood Trusses ANSI/TPIIWTCA 4 - 2002""
12. Warranty is per Chambers Truss Warranty attached.
ATED --- - —
IGNED__
OR TITLE
4 spreader bar may be required per'BCSI" to prevent injury & damage.
0 0
0 0
0
6 0
SQUARE CUT END
4X2 TOP CHORD
LEDGER HEIGHT 1V- 9";,r
END DETAIL: TYPICAL FLOOR
5 t— .
1-01-07
4-01
1-10-08
PLUMB CUT END
2X4 TOP CHORD
LEDGER TOP 10'-3-11/1611
LEDGER BOTTOM 9'-2-1/4"
END DETAIL: EYEBROW JACK
Multiple ply trusses must be fastened together per engineering before they are
set, failure to do so can result in roof collapse.
Temporary and permanent bracing are required and can save life and property
and is the responsibility of the truss erector.
Study the contents of the information packet included on delivery before
setting trusses.
1906,
Trusses must be set and braced per design to prevent injury & damage.
Trusses must be set lumb and square
Do not set bunks or stack of plywood, roofing material or any other
concentrated loads on trusses, this can cause collapse.
DO NOT INSTALL TRUSSES USING THIS
USE PLAN DELIVERED WITH TRUSSES TO SET TRUSSES
■
31U5 Olean venue
Fort Pierce, Florida 34982.6423
800-551-5932
Fort Pierce 772.465.2012 Fax 772-465-8711
Vero Beach 772-569.2012 Stuart 772.286.3302
Web Site: CHAMBERSTRUSS.COM
Email: MAIL@CHAMBERSTRUSS.COM
LOADING/DESIGN CRITERIA REDUCIBLE
PER CODE SUCH As SBC 1604.6.1
DESIGN CRITERIA
County Saint Lucie County
Building Department Saint Lucie County
Wind Design Criteria ASCE 2010
Wind Design Method MWFRS(Directional)/C-C hybrid Wind ASCE 7-10
Roofing Material Shingle or Shake
Loading in PSF Roof R.D.L. Floor
Top Chord Live 20 40
Top Chord Dead 7 4.2 10
Bottom Chord Live `10-Non Conccurent 0
Bottom Chord Dead 10 3 5.
Total Load 47. 7.2 - 55
Duration Factor 1.25 1.00
Wind Speed 170mph
Top Chord C.B. - Sheathing by builder
Bottom Chord C.B. Sheathing by builder..
Highest Mean Height - 25'
Building Type Enclosed -
Building Category II: Non Restrictive -
Exposure Category D>Flat/unobstructed/exposed to wind over water...
Miles from Ocean 112
Conforms to Florida Building Code2017
R.D.L.=Restraining Dead Load C.B =Continuous Bracing.
Verify DESIGN CRITERIA shown above with the
building department and your engineer.`
Design Criteria is the responsibility of the
Building Designer and/or Engineer of Record
Chambers Truss Inc. Drawing Name: 75546
SCALE: 1 /4" = 1'-0"
183 total trusses, 34 unique designs
Wk
Designer: BLW Reviewed by: _
Date:10/02/18 '
FOR
Don Hinkle Construction
DESCRIPTION: CQ
HINKLE RESIDENCE
Page 1 of 2 CUSTOMER INITIALS EACH PAGE
75546
ME
SE
f
1
pLlessIn
t
, dSpre
L11ar,
Tag line 1/2 span +..�
Ta Tina �prox 2/3 to �.
g
epprox.
112 of Span.
REFER TO BCSI
REFER TO BCSI
Truss must be set this way a crane Is used.
Truss must be set this way if crane is used.
Truss Is an example, your truss may not match.
Truss is an example, your truss may not match.
Insist crane operator sets truss this way.
Insist crane operator sets truss this way.
30' S
All load bearing walls, headers,
beams, & lintels must be in place
at indicated height before trusses
V1\ are installed.
AIR HANDLER NOTE
Unless noted elsewhere on this layout, these trusses are not
designed for air handlers in the roof or for any other A/C
requirements. This may be in conflict with building code and A/C
Design requirements. Consult with Building Department and A/C
Contractor.
/!\ Do not stand on trusses until they are braced per BCSI &properly nailed to straps and hangers !! HIP CARRIER LOCATED AS DIMENSIONED ON LAYOUT FABRICATION AGREEMENT
TRUSSES CANNOT BE STARTED UNTIL THIS AGREEMENT IS SIGNED &RETURNED
he undersigned acknowledges and agrees:
1. Trusses will be made in strict accordance with this truss placement diagram layout, which is the sole authority for
�\ elermining successful fabrication of the trusses. - -
�� conrvoER JACKS 2. All dimensions in this layout have been verified by the undersigned.
ARE NOT BEVELED. 3.. Unless written notice is provided by certified mail to Chambers Truss within ten (10) days of delivery the
SEE STANDARD ndersigned agrees that no backcharges will be allowed. In the event such written notice is furnished Chambers Truss
�. ENGINEERING. d� hall have three (3) business days in which to begin repairs required, or to substitute other trusses, at Chambers option.
o her 10 days of delivery remedy will be according to Florida statute 558.
4, The undersigned acknowledges receipt .of'BCSI' summary sheet by TPI & WTCA
5. Delivery is to job site. It is the buyer's responsibility to make the job site suitable for delivery. Chambers Truss has "
he sole authority to determine the suitability of the job site or a. portion of the job site for delivery. Chambers Truss will
e responsible for dump delivery only. The buyer is responsible for additional delivery expenses if Chambers Truss has
o -redeliver because job. site is not prepared for delivery or buyer is not prepared for delivery of trusses. Buyer is
esponsible to Chambers Truss for towing costs due to site conditions.
6. Price as shown in paragraph 7 below is subject to change h any changes are made in this. layout. A $50 per hour
Be for revisions may be charged by Chambers Truss.
7. This is a PURCHASE ORDER to Chambers Truss of the sum agreed to, or if no agreement a reasonable price.
nvoice will be made on delivery and paid. within terms of net on delivery. Invoice may be made at scheduled date of
elivery if buyer cannot accept delivery of fabricated trusses. The undersigned agrees to pay Chambers Truss
24' D.C. THRU easonable attorney's fee for collections in event of payment not timely made. 1-1/2. %_per month service charge will be
CORNERJACKS
ONLY 24- Y 1-111 , dded for all sums not paid within terms.
8. Signature or initials anywhere on this sheet constitutes agreement to all terms herein.
9. In consideration of Chambers Truss extending credit for this material the undersigned unconditionally guarantees
CORNER DETAIL ayment when due of any and all indebtedness owed to Chambers Truss by any entity receiving material and the
undersigned agrees to pay such indebtedness including attorneys. fees, I default in payment for material be made by the
OVERHANGS NOT SHOWN FOR CLARITY eclplent.
10. In the. event of any litigation concerning this agreement, the items furnished hereunder or payments referred to
erein, the parties agree that the sole venue for any such action will be Saint Lucie County, Florida
11. Design responsibilities are per. ""National Standard And Recommended Guidelines On Responsibilities For
onslruclion Using Metal Plate Connected Wood Trusses ANSI/rPIANTCA 4 - 2002'"'
12. Warranty is per Chambers Truss Warranty attached.
MATCH POINT
! WARNING !
The size of these trusses makes it necessary that they a set by a profeesional builder
familiar with and experienced in the problems and dangers of setting large span trusses.
The builder and erector should consult with an engineer licensed in Florida specializing
in wood roof trusses about the safe erection of these trusses. The engineer should be at
the job site when trusses are erected to provide supervision and advice. y
SEAT PLATES BY CHAMBERS TRUSS
)ATED_
SIGNED
OR--- TITLE
A spreader bar may be required per "BCSI" to prevent injury &damage.
Multiple ply trusses must be fastened together per engineering before they are
set, failure to do so can result in roof collapse.
Temporary and permanent bracing are® fired and can save life and property
and is the responsibility of the truss erector. '
Study the contents of the information packet included on delivery before
setting trusses.
Trusses must be set and braced per design to prevent injury &damage.
�
Trusses must be set plumb and square
Do not set bunks or stack of plywood, roofing material or any other
concentrated Toads on trusses, this can cause collapse.
DO NOT INSTALL TRUSSES USING THIS
USE PLAN DELIVERED WITH TRUSSES TO SET TRUSSES
Oeaner
nue
Fort Pierce, Florida 34982.6423
800-551.5932
Fort Pierce 772.465.2012 Fax 772.465-E3711
Vero Beach 772-569-2012 Stuart 772-286-3302
Web Site: CHAMBERSTRUSS.COM
Email: MAEL@CHAMBERSTRUSS.COM
LOADING/DESIGN CRITERIA REDUCIBLE
PER CODE SUCH AS SBC 780,4.6.1
DESIGN CRITERIA.
County. Saint Lucie County.-
. Building Department Saint Lucie County
Wind. Design Criteria ASCE 2010
Wind Design .Method MWFRS(Directionaq/C-Chybrid Wind ASCE7-10
Roofing Material Shingle or Shake :
Loading in PSF Roof R.D.L. Floor
Top Chord Live ' 20 AO
Top Chord Dead 7 -4.2 YO
Bottom Chord Live - '10-Non Conccurent 0 -
Bottom Chord Dead 10 3 b
Total Load 47 7.2 55
Duration Factor 1.25 1.00
Wind Speed 170mph
Top Chord C.B. Sheathing by builder
Bottom Chord C.B. Sheathing by builder
Highest Mean Height hl 25'
Building Type
Enclosed
Building. Category. It: Non Restrictive
Exposure Category D>FlaUunobstructed/exposed to wind over ',vateri.:
.Miles from Ocean 1/2 -.;.
Conforms to Florida Building Code 2017
R.D.L=Restraining Dead Load C.B.=Continuous Bracing
Verify DESIGN CRITERIA shown above with the
building department and your engineer:
Design Criteria is the responsibility of the
Building Designer and/or Engineer of Record
Chambers Truss Inc: drawing Name: 75546
SCALE: 1/4" = 1'-0"
183 total trusses, 34 unique designs,
Designer: BLW Reviewed by: _
Date: 10/02/18
FOR J-;:JJ wile
Don Hinkle Construction
DESCRIPTION: P�
HINKLE RESIDENCE
Page 2 of 2 CUSTOMER. INITIALS EACH PAGE
75546------r---
Lumber design values are in accordance with"ANSI/TPI 1 section 6.3
These truss designs rely on lumber values established by others.
RE: 75546 - HINKLE RESIDENCE FLU Lu IJ
MiTek USA, Inc.
Site Information: Permitting Department 6904 Parke East Blvd.
FL
Customer Info: DON HINKLE CONSTRU TI(st. FQreNlaocn$P rflLR SIDENCT�mpa de133610-4115
tAa'
Lot/Block: lVlo
Address: 246 BIMINI DRIVE
City: FORT PIERCE State: FL
Name Address and License # of Structural Engineer of Record, If there is one, for the building.
Name: License #:
Address:
City: State:
General Truss Engineering Criteria & Design' Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2017/TP12014 Design Program: MiTek 20/20 8.1
Wind Code: ASCE 7-10 Wind Speed: 170 mph
Roof Load: 37.0 psf Floor Load: 55.0 psf
This package includes 38 individual, Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet
conforms to 61 G15-31.003, section 5 of the Florida Board of Professional Engineers Rules.
No.
I Seal#
Truss Name
Date
I No.
Seal#
Truss Name
I Date
1
IT15290545
JA
10/9/18,
118
IT15290562
I GRP
10/9/18
12
IT15290546IA1
110/9/18
119 'IT15290563IJ1
110/9/18 I
13
I T15290547
I ATA
110/9/18.
120 JT15290564
I J3 .
I-10/9/18 I
14
IT15290548
I ATB
110/9/18
121
I T15290565
I J5
110/9/18 I
15
IT15290549
I ATM
110/9/18
122
I T15290566
I J7
110/9/18 I
16
IT15290550
IF
110/9/18
123
I T15290567
I JC
110/9/18 I
17
IT15290551
I FLA
110/9/18
124
I T15290568
I JU
10/9/18 I
18
IT15290552
I FLB
110/9/18
125
I T15290569
I KJ5
110/9/18 I
19
IT15290553
I FLC
110/9/18
126
I T15290570
I KJ7
110/9/18 I
110
I T15290554
I G
110/9/18
127
I T15290571
I M
110/9/18 I
111
I T15290555
I G 1
110/9/18
128
I T15290572
I M 1
110/9/18
112
IT15290556
I G2
110/9/18
129
I T15290573
I M2
110/9/18
113
I T15290557
I G3
110/9/18
130
I T15290574
I M3
110/9/18
114
IT15290558
I GEM
110/9/18
131
I T15290575
I M4
110/9/18 I
115
IT15290559
I GRA
110/9/18
132
I T15290576
I M5
110/9/18 I
116
IT15290560
I GRF
110/9/18
133
I T15290577
I M6
110/9/18
117
IT15290561
I GRG
110/9/18
134
I T15290578
I M7
110/9/18
The truss drawing(s) referenced above have been prepared by
MiTek USA, Inc. under my direct supervision based on the parameters
provided by Chambers Truss.
Truss Design Engineer's Name: Finn, Walter
My license renewal date for the state of Florida is February 28, 2019.
IMPORTANT NOTE' The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSI/TPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek. Any project specific information included is for MiTek's customers
file reference purpose only, and was not taken into account in the preparation of
these designs. MiTek has not independently verified the applicability of the design
parameters or the designs for any particular building. Before use, the building designer
should verify applicability of design parameters and properly incorporate these designs
into the overall building design perANSI/TPI 1, Chapter 2.
A6 2A19
. KASTNER, P.E.
SSIONAL ENGINEER
LICENSE # PE 39528
5320 FLORIDA PALWAVE.
COCOA, FL 32927
♦♦���,'C ' ERP A
�•`♦p' �G ENS ti� •�
.� V R ��
No 22839 �u
��^•.. STATE OF � ::�
A
- • ` alter Flnn PE�Vb:22839 •
MiTek USA, Inc. FIL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,201.8
Finn, Walter 1 of 2
®
Lumber design value§ are in- accordance with ANSI/TPI 1 section 6.3
These truss designs•rely.-.on lumber -values established by others.
`MiTek
RE: 75546 -HINKLE RESIDENCE
MiTek USA, Inc.
Site Information:
6904 Parke East Blvd.
Customer Info: DON HINKLE CONSTRUCTION Project Name: HINKLE RESIDEOBE' FLMo3�eq:4115
Lot/Block:
Subdivision:
Address: 246 BIMINI DRIVE
City: FORT PIERCE
State: FL '
Name Address and License # of Structural Engineer of Record, If there is one, for the building.
Name:
License #:
,Address:
City:
Stater
General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2017/TP12014
Design Program: MiTek 20/20 8.1
Wind Code: ASCE 7-10
Wind Speed: 170 mph
Roof Load: 37.0 psf
Floor Load: 55.0 psf
This package includes 38 individual, Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that Tam the Truss Design Engineer and this index sheet
conforms to 61G15-31.003, section 5 of the Florida Board of Professional Engineers Rules.
No.
Seal#
I Truss Name
Date
J No.
I Seal#
I Truss Name
I Date
1
T15290545
1 A
10/9/18
118
1 T15290562
1 GRP
10/9/18
12
I T15290546
I Al
110/9/18
119 .
I T15290563
I J1
110/9/18
13
I T1 5290547
1 ATA
110/9/18 I120
I T15290564
I J3
110/9/18
14
I T15290548
I ATB
110/9/18 '
I21
I T15290565
I J5
110/9/18
15
I T15290549
I ATM
110/9/18 J
22
I T15290566
I J7
110/9/18
16
I T15290550
I F
10/9/18 i123
I T15290567
I JC
110/9/18
17 .
I T15290551
I FLA
110/9/18 �124
I T15290568
I JU
110/9/18
18
I T15290552
I FLB
110/9/18 1125
I T15290569
I KJ5
110/9/18
19
1 T15290553
1 FLC
110/9/18 1126
I T15290570
I KJ7
110/9/18
110
I T15290554
I G
110/9/18
127
I T15290571
I M
110/9/18
11
T15290555
I G1
110/9/18 '128
I T15290572
I M1
110/9/18 I
12 I
T15290556
I G2
110/9/18 '129
I T15290573
1 M2 110/9/18
J
113 . I
T15290557
I G3
110/9/18 ,130
I T15290574.
1 M3
110/9/18 I
114 1
T15290558
I GEM
110/9/18 .131
I T15290575
1 M4 110/9/18
I
115 1
T15290559
I GRA
110/9/18 '132
I T15290576
1 M5 110/9/18
116 1
T15290560 I
GRF
110/9/18
133
I T15290577
1 M6
110/9/18
117 1
T15290561 I
GRG
110/9/18 !134
I T15290578
1 M7
110/9/18
The truss drawing(s) referenced above have; been prepared by
MiTek USA, Inc. under my direct supervision based on the parameters
provided by Chambers Truss.
Truss Design Engineer's Name:, Finn, Walter
My license renewal date for the state of Florida is February 28, 2019.
IMPORTANT NOTE: The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSI/TPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek. Any project specific information included is for MiTek's customers
file reference purpose only, .and was not taken into account in the preparation of
these designs. MiTek has not independently verified the applicability of the design
parameters or the designs for any particular building. Before use, the building designer
should verify applicability of design parameters and p joperly incorporate these designs
into the overall building design per ANSI/TPI 1, Chapter 2.
'CER P R ♦,
No 22839
:A=
r �
• �. STATE OF
�♦ ems:. < O R Q• 'C?;�
i •.
Walter'P. Flnn PE No.22639
MiTek; USA, Inc. FL Cert 6634
6904: Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
Finn, Walter 1 of 2
I
RE: 75546 -HINKLE RESIDENCE
Site Information:
Customer Info: DON HINKLE CONSTRUCTION Project Name: HINKLE RESIDENCE Model:
Lot/Block: Subdivision:
Address: 246 BIMINI DRIVE
'City: FORT PIERCE State: FL
No.
Seal#
Truss Name
Date
35
1 T15290579
M8
1 10/9/18 1
136
1 T15290580
1 M9
1 10/9/18
137
J T15290581
1 P
1 10/9/18 1
138
I T15290582
I P1
1 10/9/18
2of2
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290545
75546
A
COMMON
11
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MITek Industries, Inc. I ue Uct 9 12:bb:14 2U1 B rage 1
1 ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-NoffGbNt9LOiRWvMandxFehzGPRpf_RV45SeCzyV8Jx
2-3-13 7-2-15 12-2-0 17-1-2 22-0-3 24-4-0
2-3-13 4-11-2 4-11-2 4-11-2 4-11-2 2-3-13
Scale = 1:40.0
4x5 =
I7T
a
116x8 = 3x6 = - B 3x4 =
3x4 = 3x8 = 6x8 =
2-0-0 2- 3 12-2-0
22-0-3 2$-4; 0 24-4-0
1 02 0 00 - 3 9-10-3
9-10-3 0-`3-i3 2-0-0
Plate Offsets (X Y)-- fS:0-3-8 0-3-01 I11:0-3-8 0-3-0)
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.26
TC 0.32
Vert(LL) -0.12
9-11 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.46
Vert(CT) -0.24
9-11 >985 240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.59
Horz(CT) 0.02
8 . n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Wind(LL) 0.05
9 >999 240
Weight: 118lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 8-0-1 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 8=900/0-7-10, 11=900/0-7-10
Max Horz 11=276(LC 11)
Max Uplift 8= 794(LC 12), 11=-944(LC 12)
FORCES. (lb) -Max Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 428/0, 3-4=-872/972, 4-5=-872/978, 6-7=-427/0
BOT CHORD 1-11=0/392, 9-11=-833/956, 8-9= 826/824, 7-8=0/390
WEBS 4-9=-306/406, 5-9� 267/422, 5-8=.921/1408, 6-8=-241/635, 3-9=-266/427,
+ 3-11=-921/1414,2-11=-242/632
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2).Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 12-2-0, Exterior(2) 12-2-0 to
18-2-0 zone; cantilever left and right exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) . This truss has been designed for a live load of 20.Opsf on,the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
8=794, 11=944.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 8634
6904 Parke East Blvd. Tampa FL 33810
Date:
October 9,2018
® WARNING - Verfly design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII-7473 rev. 10/0=015 BEFORE USE.
Design valid for Use only connectors. This design Is based only upon parameters shown, and Is for on Individual building component, not
a truss system. Before use, the building designer mor�st verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent trickling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
ftJlOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabricatiort storage, delivery, erection and bracing of trusses and truss systems, seeAAISW11 CualByCtBetla, DSB-89 and SCSI BugdZRg Component
6904 Parke East Blvd.
Safety intouna8bnovailable from Truss Plate institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290546
75546
Al
HIP
2
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. Tue Oct 9 12:55:15 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-r?C1 TxOVwf8Y3fUY8PgAosE8XpodOSgeliCBkPyVBJw
2-3-13 6-10-3 11-0-0 13-4-0 17-5-13 22-0-3 24-4-0
2 4-6-6 4-1-13 2-4-0 4-1-13 4-6-6 2-3-13
a
3x4 =
2-0-0
4x5 =
3x4 =
4x5 =
3x4 =
8-8-3
Scale = 1:40.7
Io
6x8 =
LOADING (psf)
SPACING-
2-0-0
CS1.
DEFL. in
(loc) Well Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.28
Vert(LL) -0.10
9-10 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.36
Vert(CT) -0.21
9-10 >999 240
BCLL 0.0 '
Rep Stress Incr
YES
WB 0.52
Horz(CT) 0.02
9 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Wind(LL) -0.10
11-13 >999 240
Weight:121 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 7-7-7 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 13=900/0-7-10, 9=900/0-7-10
Max Horz 13=-250(LC 10)
Max Uplift 13=-944(LC 12), 9=-794(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-464/7, 3-4=-886/1074, 4-5= 843/1056, 5-6=-886/1074, 7-8=-464/7
BOT CHORD 1-13=0/427, 11-13=-908/935, 10-11=-589/757, 9-10=-869/811, 8-9=0/427
WEBS 2-13=-222/610, 3-13=-936/1407, 3-11=-217/384, 6-10= 218/385, 6-9= 936/1407,
7-9=-222/610
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 11-0-0, Extedor(2) 11-0-0 to
13-4-0, Interior(1) 22-0-3 to 24-4-0 zone; cantilever left and right exposed ;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed fora 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
13=944, 9=794.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
WARNING - Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE.
Design volid for use only with MITek8 connectors. This design Is bored only upon parametersshown, and is for a7 67divldual building component not
a truss system. Before use, the building designer must verify the applicablllty of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual, truss web and/or chord members only. Additional temporary and permanent bracing
MiTek
prevent
Is always required for stability and to prevent collapse with possible personal
Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss
systems, seeANSUIPII AualByCiBedo, DSB-89 and SCSI Bulldog Component
6904 Parke East Blvd.
Safety lntoimatlonavallable from Truss Plate Institute, 218 N. Lee Street
Suite 312, Alexandda, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290547
75546
ATA
ATTIC
2
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:16 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-JBmPhHP7hyGPhp3ki6LPK3nF7D 1 W 7sAoXPxlGryV8Jv
2-3-13 9-0-7 i 15-4-4 19-6-0 23-7-12 29-11-9 36-8-3 i 39-0-0 i
2-3-13 6-8-10 6-3-13 4-1-12 4-1-12 6-3-13 6-8-10 2-3-13
5x6 =
6.00 12
Scale = 1:64.8
19 18 " 16 15 13 12
3x5 = 3x6 11 6x8 = 5x8 MT18HS = 3x4 = 6x8 = 3x6 11 3x5 =
3x4 = 5x8 MT18HS =
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017ITP12014
CSI.
TC 0.55
BC 0.83
WB 0.77
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Attic
in (loc) I/deft L/d
1.04 16-18 >398 240
-1.11 16-18 >370 180
0.06 12 rda n/a
-0.56 15-16 176 360
PLATES GRIP
MT20 244/190
MT18HS 244/190
Weight: 207lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly
applied or 4-3-13 oc puffins.
BOT CHORD 2x4 SP M 30'Except' BOT CHORD Rigid ceiling directly applied or 5-7-9 oc bracing.
14-17: 2x4 SP M 31 WEBS
1 Row at midpt 10-13, 2-18
WEBS 2x4 SP No.3 JOINTS
1 Brace at Jt(s): 20
REACTIONS. (lb/size) 12=152610-7-10, 19=1526/0-7-10
Max Harz 19= 442(LC 10)
Max Uplift 12=-1231(LC 12), 19=-1374(LC 12)
Max Grav 12=1650(LC 19), 19=1650(LC 18)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-2584/1972, 3-5=-2389/1930, 5-6=-503/527, 6-7=-503/527, 7-9=-2389/1930,
9-10= 2584/1972
BOT CHORD 18-19— 296/551, 16-18= 1610/2624, 15-16= 1264/2267, 13-15=-1610/2292
WEBS 5-20=1761/1497, 7-20= 1761/1497, 7-15=-155/539, 9-15=-578/425, 9-13=-328/328,
10-1 3=-1 770/2125, 10-12=-1562/1760, 5-16=-155/539, 3-16= 578/426, 3-18=-327/328,
2-18= 177012135, 2-19= 1565/1760
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft Cat.
II; Exp D; Encl., GCpt=0.18; MW FRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-6-0, Exterior(2) 19-6-0 to
25-6-0 zone; cantilever left and right exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) All plates are MT20 plates unless otherwise indicated.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Ceiling dead load (5.0 psf) on member(s). 5-20, 7-20
7) Bottom chord live load (40.0 psf) and additional bottom chord dead load (5.0 psf) applied only to room. 15-16
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=ib)
12=1231,19=1374.
9) ATTIC SPACE SHOWN IS DESIGNED AS UNINHABITABLE.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Vedly design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE 111II-7473 rev. 1010312015 BEFORE USE
Design valld for use only with Mllekv connectors. This design Is based only upon parameters shown, and Is for an Individuoi building component, not
�
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual ,truss web and/or chord members only. Additional temporary and permanent bracing
MiTek"
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss, systems, seeAMWMII 6ualCyCrBeda, DSB-89 and BCSI BuIlding Component
6904 Parke East Blvd.
Safety Infotmaflonavailable from Truss Plate Institute, 218 N. Lee Street. Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type '
Qty
Ply
HINKLE RESIDENCE
T15290548
75546
ATB
ATTIC
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:18 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-GZuA6zQN DaW 7w7D7pXOtPUsa71 j_bj N5?jQsLkyV8Jt
2-3-13 9-0-7 15-4-4 19-0-0 0-0- 23-7-12 29-11-9 36-8-3 39-0-0
2-3-13 6-B-10 6-3-13 3-7-12 1-0- 3-7.12 6-3-13 6-6-10 2-3-13
10
0
5.00 F12
5x6 =
5x6 =
6 7
Scale = 1:67.1
3x5 = 3x6 II 6x8 = 6x8 MT18HS= 5x8 MT1BHS= 6x8 = 3x6 11 3x5 =
39-0-0
2- -13 9-0-7 15-4-4 19-0-0 20-0-0 2W-'I2 i 29-11-9
36-8-3 37�-q-0 i
�2-0-0
2-0.0 0- - 3 6-8-10 6-3-13 3.7.12 1.0-0 3.7.12 6-3-13
6.8-10 0- 3
Plate Offsets (X,Y)-- f4:0-3-0,Edgel, f6:0-3-0,0-2-41, f7:0-3-0,0-2-41, f9:0-3-0,Edgej, f14:0-3-8,0-3-01, (19:0-3-8,0-3-01
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/dell Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.58
Vert(LL) 0.99 17-19 >415 240
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.83
Vert(CT) -1.07 17-19 >385 180
MT18HS 244/190
BCLL 0.0
Rep Stress Incr YES
WB 0.91
Horz(CT) 0.06 13 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Attic -0.54 16-17 184 360
Weight: 211 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly
applied or 4-3-1 oc purlins.
BOT CHORD 2x4 SP M 30'Except' BOT CHORD Rigid ceiling directly applied or 5-2-10 oc bracing.
15-18: 2x4 SP M 31 WEBS 1 Row at micipt 2-19,
11-14
WEBS 2x4 SP No.3 JOINTS 1 Brace at Jt(s): 21
OTHERS 2x4 SP No.3
REACTIONS. (lb/size) 20=152610-7-10, 13=152610-7-10
Max Harz 20=-432(LC 10)
Max Uplift 20=-1374(LC 12), 13=-1231(LC 12)
Max Grav 20=1653(LC 18), 13=1653(LC 19)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-2589/2126, 3-5=-2388/2034, 5-6— 516/556, 6-7= 455/548, 7-8=-516/556,
8-10=-2388/2034, 10-11= 2589/2126
BOT CHORD 19-20=-287/541, 17-19=-1798/2621, 16-17=1 366/2264, 14-16=1763/2297
WEBS 2-20— 1565/1789, 2-19=-1953/2140, 3-19= 323/356, 3-17= 576/505, 5-17=-164/545,
5-21= 1737/1580, 21-22= 1727/1563, 8-22= 1737/1580, 8-16= 164/545, 10-16=-576/505,
10-14=-323/356, 11-14= 195212130, 11-13= 1562/1789, 6-21=-259/368, 7-22=-259/367
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; VuIt=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-0-0, Extedor(2) 19-0-0 to
20-0-0, Interior(1) 28-5-13 to 39-0-0 zone; cantilever left and ;right exposed ;C-C for members and forces & MW FRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) All plates are 3x4 MT20 unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
8) Ceiling dead load (5.0 psf) on member(s). 5-21, 21-22, 8-22
9) Bottom chord live load (40.0 psf) and additional bottom chord dead load (5.0 psf) applied only to room. 16-17
10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
20=1374, 13=1231.
Walter P. Finn PE No.22839
11) ATTIC SPACE SHOWN IS DESIGNED AS UNINHABITABLE.
MiTek USA, Inc. FL Cart6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED M?EKREFERANCE PAGE M11-7673 rev. 10/03/2015 BEFORE USE.
Design vaild for use only with MllekV connectors. lhts design Is based only upon parameters shown, and is for an 67dlvidual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek"
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss, systems, seeANSUIPIr Quality CrIlle , DSB•89 and SCSI BUOd/ng Component
6904 Parke East Blvd.
Safety ln/onnaflon3val able from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
city
Ply
HINKLE RESIDENCE
T15290549
75546
ATM
ROOF SPECIAL
11
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:19 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-kmSYJJRO_te_YHoJNEv7yiPgJQ6XKFJEDNAPtAyVBJs
19-2-0
i 2.1-13 i 6-10-8 11-2-0 i12-4-1113-4-1$ 18-5-6 18-1_tr9
2 4-6-11 4.3-8 1-2.11 1-0-2 5-0.11 d-5-8,
0-3-0 Scale = 1:45.9
7 8
0
0
12 3x8 =
13
3x4 = 5x6 = 7x8 = 7x10 MT18HS =
2-0-0 2-3-13 11-2-0
7-3-8
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-6-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC2017/TP12014
CSI.
TC 0.94
BC 0.61
WB 0.61
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (Ioc) I/defl Ud
-0.37 10-11 >524 360
-0.72 10-11 >271 240
-0.01 9 n/a n/a
0.71 10-11 >275 240
PLATES
MT20
MT18HS
Weight: 122lb
GRIP
244/190
244/190
FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD 2-0-0 oc puffins (5-3-13 max.), except end verticals
BOT CHORD 2x4 SP M 30 *Except*
(Switched from sheeted: Spacing > 2-0-0).
9-10: 2x6 SP 240OF 2.0E
BOT CHORD Rigid ceiling directly applied or 4-8-8 oc bracing.
WEBS 2x4 SP No.3 *Except*
JOINTS
1 Brace at Jt(s): 7, 1, 12
7-9: 2x8 SP 240OF 2.OE, 5-10,6-12: 2x4 SP M 30, 9-13: 2x6 SP No.2
OTHERS 2x4 SP No.3
REACTIONS. (lb/size) 9=921/Mechanical, 11 =1 026/0-7-10
Max Harz 11=814(LC 12)
Max Uplift 9= 843(LC 12), 11= 824(LC 12)
Max Grav 9=1511(LC 18), 11=1107(LC 18)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-498/0, 2-3=-315/90, 3-5=-1028/188, 5-6=-723/191, 6-7= 1577/1646,'
9-12=-851/978, 7-12= 816/999
BOT CHORD 1-11=0/491, 10-11 =-1 576/1489, 9-10= 984/1037
WEBS 3-10=-540/716, 5-10= 45/530, 6-12=-2371/1502, 2-11 =-1 571625, 3-11 =-1 125/542
NOTES-
1) Wind: ASIDE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=601t; L=60ft eave=7ft Cal.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C 6derior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-2-0 zone; cantilever left
exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) All plates are MT20 plates unless otherwise indicated.
3) The Fabrication Tolerance at joint 9 =16%
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Ceiling dead load (5.0 pst) on member(s). 5-6, 6-12
7) Bottom chord live load (40.0 psf) and additional bottom chord dead load (5.0 psf) applied only to room. 9-10
8) Refer to girders) for truss to truss connections.
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 to uplift at joint(s) except Qt=lb)
9=843, 11=824.
10) Graphical purlin representation does not depict the size or the orientation of the purlin along the top and/or bottom chord.
11) ATTIC SPACE SHOWN IS DESIGNED AS UNINHABITABLE.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cent 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING . Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII.7473 rev. 10/03/2015 BEFORE USE.
Design valid fot use only with MlTekO connectors. This design Is based only Upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to buckling Individual truss web and/or chord members only. Addilional temporary and permanent bracing
MiTek'
prevent of
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
6904 Parke East Blvd.
fabrication, storage, delivery, erection and bracing of trusses and truss systems. seeANSW11 GuaBlyCrlleda, DSB-09 and BC51 Bulfdlgg Component
Tampa, FL 33610
Safety lnfamlalronavallable from Truss Plate Institute. 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290550
75546
F
HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL o. 130 s viar i i MG w , i an n wuau,oa, n ice. , uc — o w. �yam ,
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-CyOwXfSelBmr9RNWxyQMVvxg1 gRC3d5OS1 vyQcyV8Jr
i 23 i 8-10-8 16-10-1 24-7-15 32-7-8 39-0-8 39-6ro
2-3-13 6-6-11 7-11.9 7-9-13 7-11-90-5-6
Scale = 1:68.9
6x10 MT18HS = 6x10 MT18HS =
5.00 12 5x6 = 6x10 MT18HS = 4x12 =
3 21 4 22 5 623 24 7 25
BHS II
14 rr
4x5 — 7x14 = 5x8 _ 4x4 = 3x4 11 5x8 — Wit =
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc) I/dell Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 1.00
Vert(LL)
0.74 12-13 >602 240
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.65
Vert(CT)
-0.39 12-13 >999 240
MT18HS
244/190
BCLL 0.0
Rep Stress Incr YES
WB 0.90
Horz(CT)
-0.16 9 n/a n/a
BCDL 10.0
Code FBC2017ITP12014
Matrix -MS
Weight: 250lb
FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30 `Except'
TOP CHORD Structural wood sheathing directly applied, except end verticals.
3-5,5-7: 2x6 SP 240OF 2.0E
BOT CHORD Rigid ceiling directly applied or 2-2-0 oc bracing.
BOT CHORD 2x6 SP No.2
WEBS
1 Row at midpt 4-15,
6-13, 6-10
WEBS 2x4 SP No.3 `Except'
2 Rows at 1/3 pis 2-15,
8-10
2-16,8-9: 2x6 SP No.2, 4-15,6-13,6-10: 2x4 SP M 30
REACTIONS. (lb/size) 16=1544/0-7-10, 9=1362/0-7-10
Max Harz 16=177(LC 11)
Max Uplift 16=-2580(LC 12), 9= 2277(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-211/594, 2-3= 2277/5435, 3-4=-2082/5285, 4-6=-3426/8427, 6-7=-2147/5521,
• 7-8=-2343/5684, 8-9= 1279/3081
BOT CHORD 1-16= 619/250, 15-16= 737/250, 13-15= 8109/3426, 12-13= 8217/3434,
10-12= 8217/3434, 9-10=-882/335
WEBS 2-16=-1394/3242, 3-15=-1522/561, 4-15=1553/3516, 4-13= 751/319, 6-12=-673/307,
• 6-1 0=-1 504/3322, 7-1 0=-1 516/567, 2-15= 4201/1798, 8-10=-4221/1776
NOTES-
1) Unbalanced root live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 8-10-8, Exterior(2) 8-10-8 to
39-3-4 zone; cantilever left exposed ; porch left and right exposed;C-C for members and forces & MW FRS for reactions shown;
Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
16=2580, 9=2277.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
0 WARNING- Vedly design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE Mll-7473 rev. 10103MIS BEFORE USE.
'
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
M!Tek•
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and Trusslsystems, seeANMPI► CUaMyCdfeda, DSB-89 and BCS►BuQd/ng Component
6904 Parke East Blvd.
Safety/nfonnaBonovallable from Truss Plate Institute, 218 N. Lee Streetl Suite 312, Alexandria, VA 22314,
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290551
75546
FLA
Floor
12
1
Job Reference (optional)
cnamoerS i russ, inc., r-on: vierce, r-L
0-3-8
H, 260
5x6 11 3x4 =
1 2
2x3 I
3
o. 1— mat 1i a10 1-ien aiuuauioa,n ouo
ID:OGfzZgnsSSbOPbDkj8M4r0yXnLm-8L7gxKTuHoOZPkWu2NSgaK1FEe4ZXaNgvL03UVyV8Jp
1I I 2I ��I 1r 54 3
Sc21e = 1:32.7
3x4 = 2x3 I I 3x4 = 2x3 11 3x4 = 2x3 11 3x4 = 5x6 I I
4 5 6 7 8 9 10 11
18 17 16 15 14 13 12
2x3 I 4x8 = 3x5 = 2x3 11 3x4 = 4x8 = 2x3 II
12-1-0
Plate Offsets (X Y)-- f1:0-3-0 Edgel f6:0-1-8 Edgel f7:0-1-8 0-0-01
f11:0-3-0 Edge], f12:0-1-8,Edgel,f14:0-1-8,Edgel,[15:0-1-8,Edgel
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/defl Ud
PLATES GRIP
TCLL 40.0
Plate Grip DOL 1.00
TC 0.64
Vert(LL) -0.22 15-16 >995 480
MT20 244/190
TCDL 10.0
Lumber DOL 1.00
BC 0.78
Vert(CT) -0.29 15-16 >769 360
BCLL 0.0
Rep Stress Incr YES
WB 0.72
Horz(CT) -0.04 11 n/a n/a
BCDL 5.0
Code FBC2017[TP12014
Matrix-S
Weight: 108lb FT=20%F, 11%E
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30(flat)
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30(flat)
except end verticals.
WEBS 2x4 SP No.3(flat)
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (lb/size) 1=1009/0-3-0, 11=1009/0-3-0
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-3=-1248/013-4=-1244/0, 4-5= 2454/0, 5-6= 2454/0, 6-7=-2387/0, 7-8=-2387/0, 8-9=-1238/0, 9-11=-1242/0
BOT CHORD 16-17=0/2024, 15-16=0/2387, 14-15=0/2387, 13-14=0/2023 ,
WEBS 7-14=-400/0, 1-17=0/1512, 3-17= 254/0, 4-17=-966/0, 4-16=0/533, 5-16=-331/0, 6-16=-307/331, 11-13=0/1504,
9-13� 268/0, 8-13=-973/0, 8-14=0/736
NOTES-
1) Unbalanced floor live loads have been considered for this design.
2) Recommend 2x6 strongbacks, on edge, spaced at 10-0-0 oc and fastened to each truss with 3-1 Od (0.131" X 3") nails.
Strongbacks to be attached to walls at their outer ends or restrained by other means.
3) Cap between inside of top chord bearing and first diagonal or vertical web shall not exceed 0.500in.
WalterP. Finn PE No.22839
MiTek USA, Inc. FL Cart 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING- Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE M11.7473 rev. 101032015 BEFORE USE.
'
Design valid for use only with MITekV connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify The applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek°
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
storage, delivery, erection and bracing of trusses and Truss systems, seeANSW11 GualtlyCrBedd, DSB-89 and BCSI Bu➢ding Component
6904 Parke East Blvd.fabrication,
Safety /nrormahbmvallabie from Truss Plate Institute, 218 N. Lee Street, Suite 312. Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290562
75546
FLB
Floor
3
1
Job Reference (optional)
Chambers I cuss, Inc., Fort Pierce, FL
0-3-8
H i 2-6-0 1-2-8 ' 2-8-8
3x6 I
1 2 3 4
5
8.1:SU s mar 11 zui tf NIr I eK Inaustrles, inc. I ue uct v 1Z:b0:23 Zul v rage i
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-cXh39gU W268QOu55c4_36YZV?2W OG3hg8?BcOxyV8Jo
2-0-0 ,i 1-5-4
2x3 II
6 7 8
2x3 I 4x6 I
9 10 11
sale = 1:32.7
0
0 6
m N
2x3 11 3x6 = 2x3 11 3x8 = 2x3 11
12-1-0
-3- 4-4-6 9-11-8 10-11-8 11-11-8 18-9-4 1 0- 2
-3- 4-1-0 5-7-0 1-0-0 1-0-0 0-1-8 6-8-0 3-
Plate Offsets (X,Y)-- [3:0-1-8,Edge], [5:0-1 -8, Edge], [6:0-1-8,Edge], [7:0-1-8,0-0-0], [11:0-3-0,Edge], [12:0-1-8,Edge], [14:0-1-8,Edge], [15:0-1-8,Edge], [16:0-1 -8, Edge],
I18:0-1-8.Edael
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc)
I/defl
Ud
TOLL 40.0
Plate Grip DOL
1.00
TO 0.32
Vert(LL)
-0.11 13-14
>999
480
TCDL 10.0
Lumber DOL
1.00
BC 0.43
Vert(CT)
-0.16 13-14
>999
360
BOLL 0.0
Rep Stress Incr
YES
WB 0.52
Horz(CT)
-0.01 11
n/a
n/a
BCDL 5.0
Code FBC2017/TP12014
Matrix-S
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30(flat) TOP CHORD
BOT CHORD 2x4 SP M 30(flat)
WEBS 2x4 SP No.3(flat) BOT CHORD
REACTIONS. (lb/size) 1=132/0-3-0, 11=762/0-3-0, 17=1126/0-5-8
Max Uplift 1=-31(LC 7)
Max Grav 1=352(LC 8), 11=762(LC 1), 17=1209(LC 7)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-3=-322/216, 3-4=-295/510,'4-5=-295/512, 5-6=-836/0, 6-7=-1372/0, 7-8=-1372/0,
8-9= 904/0, 9-11= 908/0
BOT CHORD 17-18=-216/317, 16-17=0/836, 15-16=0/1372, 14-15=0/1372, 13-14=0/1329
WEBS 1 -1 8=-263/386, 3-17— 488/0, 6-16=-660/0, 5-16=0/386, 5-17=-1188/0, 11-13=0/1098,
9-13=-261/0, 8-13=-527/0
PLATES GRIP
MT20 244/190
Weight: 113 lb FT = 20%F, 11 %E
Structural wood sheathing directly applied or 6-0-0 oc puffins,
except end verticals.
Rigid ceiling directly applied or 10-0-0 oc bracing, Except:
6-0-0 oc bracing: 17-18.
NOhTES-
1) Unbalanced floor live loads have been considered for this design.
2) All plates are 3x4 MT20 unless otherwise indicated.
3) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1.
4) Recommend 2x6 strongbacks, on edge, spaced at 10-0-0 oc and fastened to each truss with 3-10d (0.131" X 3") nails.
Strongbacks to be attached to walls at their outer ends or restrained by other means.
5) Gap between inside of top chord bearing and first diagonal or vertical web shall not exceed 0.500in.
6) CAUTION, Do not erect truss backwards.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6034
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING -Verity design parameters and READ NOTES ON THIS AND INCLUDED.MR•EK REFERANCE PAGE M0-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MITek9 connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of individual (truss web and/or chord members only. Additional temporary and permanent bracing
M!Tek'
Is always required for stabillfy and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSUWPII AuallfyCrCeda, DSB-89 and BCSI Mdfng Component
6904 Parke East Blvd.
Safety Infolmallonavallable from Truss Plate Institute, 218 N. Lee Street; Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290553
75546
FLC
Floor
6
1
Job Reference o tional
Cnambers I russ, Inc., ion I-lerce, rL
0-1-8
H ' 2-6-0
2x3 I I
2x3 =
1
6
3x4 =
2
0.iou s Mar 11 eu 10 Ivi el( 11aasrntls, It IG. I ue vu a IG:DO:GR LV Io rays I
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-4jFRMOV8pQGHe2gHAoVlfl6fwRrt? W YzNftAZOyV8Jn
03i�v, 2-0-0 1-5-4 3-
1 1:25.2
6x8 = 2x3 I 3x4 = 2x3 11 3x4 = 4x6 11
'3 4 5 6 7 8 9
3x6 = 2x3 I 3x4 = 3x8 = 2x3 1
6x8 =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) I/deft Ud
PLATES GRIP
TCLL 40.0
Plate Grip DOL
1.00
TC 0.37
Vert(LL)
-0.11 11-12 >999 460
MT20 244/190
TCDL 10.0
Lumber DOL
1.00
BC 0.47
Vert(CT)
-0.1511-12 >999 360
BCLL 0.0
Rep Stress Incr
YES
WB 0.55
Horz(CT)
-0.02 9 n/a n/a
BCDL 5.0
Code FB02017ITP12014
Matrix-S
Weight: 88lb FT=20%F, 11%E
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30(flat)
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc puffins,
BOT CHORD 2x4 SP M 30(flat)
except end verticals.
WEBS 2x4 SP No.3(flat)
BOT CHORD
Rigid ceiling, directly applied or 10-0-0 oc bracing.
REACTIONS. (lb/size) 15=788/0-5-8, 9=794/0-3-0
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1439/0, 3-4=1439/0, 4-5=-1509/0, 5-6=-1509/0, 6-7=-947/0, 7-9=-951/0
BOT CHORD 14-15=0/937, 13-14=0/1509, 12-13=0/1509, 11-12=0/1420
WEBS 2-15=-1147/0, 2-14=0/622, 3-14=-234/273, 4-14= 704/185, 9-11=0/1151, 7-11= 262/0, 6-11=-585/0, 6-12=-31/339
NOTES-
1) Onbalanced floor live loads have been considered for this design.
2) Recommend 2x6 strongbacks, on edge, spaced at 10-0-0 oc and fastened to each truss with 3-10d (0.131" X 3") nails.
Strongbacks to be attached to walls at their outer ends or restrained by other means.
3) Gap between inside of top chord bearing and first diagonal or vertical web shall not exceed 0.5001n.
4) CAUTION, Do not erect truss backwards.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING- Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE M11-7473 rev. 10/03l2015 BEFORE USE.
Design vaild for use only with MlTekD connectors. This design Is based only upon patameeers shown, and Is for an Individual building component not
�'
a truss system. Before use, the building designer must verily the applicability of design parameters and properly Incorporate this design Into the overall
design. Bracing Indicated is to buckling individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTeW
building prevent of
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
6904 Parke East Blvd.
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSM11 QualByCrferfa, DSB-89 and BCSI BulldL7gComponent
Tampa, FL 33610
Safety Informatlonavailable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Job
Truss
Truss Type
Qry
Ply
HINKLE RESIDENCE
T15290554
75546
G
Hip
1
1
Job Reference o tional
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:25 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-ZwppaMWmajPBGCFTIVOXCzenerCfkuz7cJdj5gyVBJm
2-3-13 6-10-3 11-0-0 16-8-9 22-3-7 28-0-0 32.1.13 36.8.3 39-0.0
2-3-13 4-6-6 4-1-13 5-8-9 5-6-13 5-8-9 4-1-13 4-6� 2-3-13
5.00 FIT
3x4 =
5x8 = 3x4 11 4x6 = 5x8 =
4 27 5 28 6 7 29 B
Scale=1:65.9
6x8 = 3x4 = 3x6 = 3x8 = 3x4 = 3x6 = 3x4 = 6x8 = 3x5 =
3x5 =
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.26
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017lTP12014
CSI.
TC 0.53
BC 0.44
WB 0.86
Matrix -MS
DEFL. in (too) I/defl Ud
Vert(LL) -0.13 15-16 >999 360
Vert(CT) -0.26 15-16 >999 240
Horz(CT) -0.08 12 n/a n/a
Wind(LL) 0.26 15-16 >999 240
PLATES GRIP
MT20 244/190
Weight: 207lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied or4-7-11 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD
Rigid ceiling directly applied or 4-9-1 oc bracing.
WEBS 2x4 SP No.3 WEBS
1 Row at midpt 3-19, 9-12
REACTIONS. (lb/size) 19=1443/0-7-10, 12=1443/0-7-10
Max Horz 19=-250(LC 10)
Max Uplift 19=-1423(LC 12), 12= 1280(LC 12)
FORCES. Qb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-335/0, 3-4=-1966/2377, 4-5= 2294/2885, 5-7=-2294/2885, 7-8=-2294/2888,
8-9=-1966/2376, 10-11=-334/0
BOT CHORD 1-19=0/307, 18-19=-1907/1748, 16-18=-1817/1777, 15-16=-2420/2294, 13-15=-1778/1775,
12-13= 1868/1648, 11-12=0/306
WEBS 2-19=-262/627, 3-19=-1881/2482, 3-18=-l44/269, 4-16=-876/735, 5-16= 322/590,
7-15=-363/580, 8-15=-880/736, 9-13=-144/269, 9-12=-1881/2482, 10-12= 261/627
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=soft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 11-0-0, Extedor(2) 11-0-0 to
36-8-3, Interior(1) 36-8-3 to 3M-0 zone; cantilever left and right exposed ;C-C for members and forces & MW FRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
19=1423, 12=1280.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date: '
October 9,2018
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE 11111-7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with MITek0 connectors. This design Is based only upon parameters shown, and is for an IndlViduai building component, not
�^
a Truss system. Before use, the building designer must verify the appllcdbllity of design parameters and properly Incorporate this design Into the overall
Bracing Indicated Is to buckling Individual truss web and/or chord members only. Additional Temporary and permanent bracing
MiTek'
building design. prevent of
Is always required for stability and To prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSUM11 Qualify CrBedu, DSB-89 and BCSI Building Component
6904 Parke East Blvd.
Safety/ntormaBorpvailable from Truss Plate Institute, 218 N. Lee StreeTJ. Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss We
Qty
Ply
HINKLE RESIDENCE
T15290555
75546
G1
HIP
1
1
Job Reference o tional
Chambers Truss, Inc., Fort tierce, FL 8. I "u IsIVlar 1 1 eu I6 IVII I eK muubrrreb, nic. rue UUL a ic.ao;cr cu r o rage i
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-VIxZ?2X15LfrV W Psrw2?HOk6efv9CgOP3d6g9iyVBJk
i 2-3.13 7-7-13 13-0-0 19-6-0 26.0-0 i 31-4-3 _ i 36-8-3 i 39-0-0
2-3-13 5-4-0 5-4-3 6-6-0 6-6-0 5-0-3 5-4-0 2-3-13
Scale = 1:65.9
r
5x8 = 3x4 11 5x8 =
4 27 28 5 29 30 6
3x6 11 Sx6 — 3x6 = 3x8 = 3x4 = 5x6 —_ 3x6 11 3x5 =
3x5 =
3x4 =
3x6 =
2-0-0 2.3-d 3 7.7-13 13-0 0 19-60 26-0-0 i 31-0.3 _ 36-8-3 37 q-039.0.0 i
2-0-0 0- - 3 5-4-0 Sd.4 6-6-0 6-6-0 5-0.3 5-4-0 0.- 3 2."
Plate Offsets (X Y)-- f4:0-5-12 0-2-81 (6:0-5-12,0-2-81
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL. in
(loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.60
Vert(LL) -0.11
14 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.31
Vert(CT) -0.21
14-16 >999 240
BCLL 0.0
Rep Stress Incr
YES
WB 0.76
Horz(CT) 0.06
10 n/a n/a
BCDL 10.0
Code FBC20171TP12014
Matrix -MS
Wind(LL) 0.22
14 >999 240
Weight: 210lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-11-0 oc pudins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 5-2-0 or bracing.
WEBS 2x4 SP No.3
WEBS
1 Row at midpt 2-17, 8-11
REACTIONS. (lb/size) 18=1443/0-7-10, 10=1443/0-7-10
Max Horz 18=-296(LC 10)
Max Uplift 18=-1423(LC 12), 10=-1280(LC 12)
FORCES. (lb) -Max. Comp./Max- Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1961/2349, 3-4=-1904/2373, 4-5— 2016/2640, 5-6=-2016/2640, 6-7=-1904/2373,
7-8=-1 961/2349
BOT CHORD 17-18=-252/409, 16-17=-2015/1890, 14-16=-1768/1720, 12-14=-1732/1707,
11-12=-1979/1758
WEBS 2-18= 131511859, 2-17=-2186/1766, 3-17= 239/469, 3-16= 226/290, 4-16=-127/263,
4-14=-577/511, 5-14=-401/702, 6-14=-577/511, 6-12=-127/263, 7-12=-225/290,
7-11= 239/469, 8-11=-2185/1766, 8-10=-1315)1860
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25111; B=60ft; L=60ft; eave=7ft; Cat.
11; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 13-0-0, Extedor(2) 13-0-0 to
34-5-13, Interior(1) 34-5-13 to 39-0.0 zone; cantilever left and right exposed ;C-C for members and forces & MW FRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
18=1423,10=1280.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
A WARNING. Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE Mll-7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with ARITekb cohneciors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicablllty of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek•
Is always required for stability and to prevent collapse with possible peksonal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and trussllsystems, seeANS&WII GualByCdleda, DSB-89 and SCSI Buld/ng Component
Safety Intotlnallonavallable from Truss Plate Institute, 218 N. Lee Streeti Suite 312. Alexandria, VA 22314.
6904 Parke East Blvd.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290556
75546
G2
Hip
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:28 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-zVVxCOYfseni7f 2PdZEpbGHD3CndhZlHrNi9yVBJj
i 2-3-13 8-9-3 15-0-0 19-6-0 24-0-0 30-2-13 _, _ 36-8-3 39-0.0 t
2-3-13 6-5-6 6-2-14 4-6-0 4-6-0 6-2-14 6-5-6 2-3-13
5.00 F,2 5x6 =
5 28
3x4 =
6
5x6 =
729
Scale=1:67.1
3x5 = 3x6 11 5x6 = 4x6 = 3x8 = 5x6 = 3x6 11 3x5 =
3x8 =
4x6 =
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0 '
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017lTP12014
CSI.
TC 0.61
BC 0.47
WB 0.67
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) I/defl Ud
-0.19 15-16 >999 360
-0.36 15-16 >999 240
0.05 12 n/a n/a
0.19 . 16 >999 240
PLATES GRIP
MT20 244/190
Weight:211 lb Ff=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied or 5-0-1 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD
Rigid ceiling directly applied or 5-0-15 oc bracing.
WEBS 2x4 SP No.3 WEBS
1 Row at midpt 2-18, 10-13
REACTIONS. (lb/size) 19=1443/0-7-10, 12r1443/0-7-10 ,
Max Harz 19= 341(LC 10)
Max Uplift 19=-1423(LC 12), 12= 1280(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-2033/2430, 4-5=-1817/2297, 5-6= 1695/2256, 6-7=-1695/2256, 7-8=-1817/2297,
8-10=-2034/2430
BOT CHORD 18-19=-290/508, 16-18=-2080/2039, 15-16=1751/1729, 13-15=-2044/1812
WEBS 2-19= 1305/1896, 2-18=-2204/1748, 4-18= 163/399, 4-16= 352/506, 5-16=-433/444,
6-16= 279/377, 6-15=-279/377, 7-15= 433/444, 8-15=-352/506, 8-13= 163/399,
10-13=-2203/1748, 10-12=-1305/1896
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 15-0-0, Exterior(2) 15-0-0 to
32-5-13, Intedor(1) 32-5-13 to 39-0-0 zone; cantilever left and right exposed ;C-C for members and forces & MW FRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.0psf.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
19=1423,12=1280,
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING- Verity design parameters and READ NOTES ON THIS AND INCLUDED M?EK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE
Design valid for use only with MITeil5 connectors. This design Is based ohly upon parameters shown, and is for art Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual iruss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSIMII Qualify Cdtede, DSB-09 and BCSI Building Component
6904 Parke East Blvd.
Sorely IntonnoNonzivallable from Truss Plate Institute, 218 N. Lee Street', Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290557
75546
G3
Hip
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MITek Industries, Inc. I ue Oct 9 12:bb:29 2018 Nage 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-Rh3KPkZHdyvZlpZEyL4TMppQySXmgl?i WxbxEbyV8Ji
2-3-13 9-10-9 17-0-0 i 22-0-0 29-1-7 36-8-3 39-0-0
2-3-13 7-6-12 7-1-7 5-0-0 7-1-7 7-6-12 2-3-13
Scale=1:67.1
5x8 =
5.00 12 5x8 =
3x6 11 5x6 = 4x6 = 3x4 = 3x4 = 4x6 = 5x6 = 3x6 11 3x5 =
3x5 =
Plate Offsets (X Y)-- (3:0-0-0 0-1-121 (3:0-1-12 0-3-01i5:0-4-0,0-1-131,[6:0-4-0,0-1-13],18:0-0-0,0-1-121
18:0-1-12.0-3-01
LOADING, (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc) I/dell Lid
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.74
Vert(LL)
0.56 15-17 >738 240
MT20
2441190
TCDL 7.0
Lumber DOL 1.25
BC 0.56
Vert(CT) -0.67
15-17 >614 180
MT18HS
244/190
BCLL 0.0 '
Rep Stress Incr YES
WB 0.66
Horz(CT)
0.05 11 n/a n/a
BCDL 10.0
Code FBC20171TP12014
Matrix -MS
Weight: 200 lb
FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied or 4-9-12
oc puriins.
BOT CHORD 2x4 SP M 30 BOT CHORD
Rigid ceiling directly applied or 4-11-1 oc bracing.
WEBS 2x4 SP No.3 WEBS
1 Row at midpt 2-17,
4-15, 7-14, 9-12
REACTIONS. (lb/size) 18=1443/0-7-10, 11=1443/0-7-10
Max Horz 18=386(LC 11)
Max Uplift 18=-1423(LC 12), 11=-1280(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (Ib) or less except when shown.
TOP CHORD 2-4=-2130/2394, 4-5=-1712/2117, 5-6=-1620/2062, 6-7=-1712/2117, 7-9= 2130/2394
BOT CHORD 17-18� 287/560, 15-17=-2033/2152, 14-15=-1386/1600, 12-14=-1997/1862
WEBS 2-18=1349/1892, 2-17= 2119/1702, 4-17=-115/343, 4-15=-643l750, 5-15=-304/375,
6-14= 304/375, 7-14= 643/750, 7-12= 115/343, 9-12= 2118/1702, 9-11— 1346/1892
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=6011t; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(i) 6-0-0 to 17-0-0, Exterior(2) 17-0-0 to
22-0-0, Interior(1) 30-5-13 to 39-0-0 zone; cantilever left and right exposed ;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
18=1423,11=1280.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33810
Date:
October 9,2018
a�
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MITek8 connectors. This design Is based only upon parameters shown, and Is form Individual building component not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiT®k"
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the 6904 Parke East BNd-
fabricatlom storage, delivery, erection and bracing of trusses and Truss systems, seeANSWI1 GuaMy CrBeffa, DSB-69 and BCSI Bugding Component
Sa/efylnlonnaMOrpvaliable from Truss Plate Institute, 218 N. Lee Streeter Suite 312, Alexandria, VA 22314. Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290558
75546
GEM
MONOPITCH SUPPORTED
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
1
8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:30 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-vtcid4avOG 1 QMz7R W2civOMkLsxcPJ HslbKUm 1 yV8Jh
3x4 111
5
9 8 7 6
2x3 II 2x3 11 2x3 11 3x4 11
Scale=1:20.8
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017/TPI2014
CSI.
TC 0.18
BC 0.26
WB 0.21
Matrix-S
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
in (loc) Well Ud
n/a n/a 999
n/a n/a 999
0.00 6 n/a n/a
PLATES GRIP
MT20 244/190
Weight:31 lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 5-0-0.
(lb) - Max Harz 9=232(LC 12)
Max Uplift All uplift 100 lb or less at joints) 6 except 7=-185(LC 12), 8=-141(LC 18), 9= 351(LC
12)
Max Grav All reactions 250 lb or less at joint(s) 6, 7, 8 except 9=390(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -A([ forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-615/149, 2-3=-396/99, 3-4=-299/75
BOT CHORD 1-9=-154/630
WEBS 4-7= 169/565,2-9= 211/714
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft B=60fh L=60ft; eave=2ft Cat.
N; Exp D; Encl., GCpi=0.18; MW FRS (directional) and C-C Comer(3) 0-0-0 to 6-0-0, Exterior(2) 6-0-0 to 6-10-4 zone; cantilever left
exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Truss designed for wind loads in the plane of the truss only. Forstuds exposed to wind (normal to the face), see Standard Industry
Gable End Details as applicable, or consult qualified building designer as per ANSI/TPI 1.
3) Gable studs spaced at 2-0-0 oc.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 6 except (jt=lb)
7=185, 8=141, 9=351.
7) Non Standard bearing condition. Review required.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
A WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED M/TEK REFERANCE PAGE MII-7473 rev. 10/03/2015 BEFORE USE.
°
Design valld for use only with MiTekV connectors. This design Is based only upon parameters shown, and Is for on Individual building component, hot
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek"
prevent
Is always required for stability and to prevent collapse with possible personal Injury and properly damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss'systems, seeANS►/IPII GualllyCrBe11a, DSB-89 and BCS1 Bu➢dhig Component
6904 Parke East Blvd.
Safety tnfonnallonovallable from Truss Plate Institute, 218 N. Lee Street Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Uly
Ply
HINKLE RESIDENCE
T15290559
75546
GRIN
HIP GIRDER -
2
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:31 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-N4A4gPaX9Z9H_7id4m7XREurAGD W BdP?_F421 UyV8Jg
2-3-13 5-8-12 9-0-0 12-2-0 15-4-0 18-7-4 22-0-3 24 _5
2-3-13 3-4-15 3-3-4 3-2-0 3-2-0 3-3 4 3-4-15 2-3-13
4x5 =
3x4 =
21 5 22
4x5 =
Scale=1:40.7
3x4 =
6x8 = 3x8 = 4x0 3x8 = 6x8 = ""�
2-0-0 0-3-13 3-4-15 3-3-4
3-2-
LOADING (psf)
SPACING- 2-0-0
CSI.
TCLL 20.0
Plate Grip DOL 1.25
TC 0.43
TCDL 7.0
Lumber DOL 1.25
BC 0.51
BCLL 0.0
Rep Stress incr NO
WB 0.80
BCDL 10.0
Code FBC2017/TP12014
Matfix-MS
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 *Except*
2-14,8-10: 2x6 SP No.2
REACTIONS. (lb/size) 14=1428/0-7-10, 10=1427/0-7-10
Max Harz 14-205(LC 6)
Max Uplift 14= 1968(LC 8), 10=-1818(LC 8)
Max Grav 14=1642(LC 32), 10=1641(LC 31)
15-4-0 18-7.4
DEFL. in (loc) I/defl Ud PLATES GRIP
Vert(LL) 0.2011-1.3 >999 240 MT20 244/190
Vert(CT) -0.17 11-13 >999 240
Horz(CT) -0.07 10 n/a n/a
Weight: 126 lb FT = 20%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 4-7-8 oc puriins.
BOT CHORD Rigid ceiling directly applied or 4-5-10 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-305/124, 3-4=-2475/2820, 4-5=-2293/2675, 5-6= 2291/2688, 6-7=-2473/2835
BOT CHORD 1-14= 103/315, 13-14=-1999/2032, 11-13= 2654/2533, 10-11=-2026/1878
WEBS 2-14=-254/372, 3-13= 734/653, 4-13= 519/562, 6-11= 525/561, 7-11= 735/689,
8-10=-253/345, 3-14= 2266/2677, 7-10= 2264/2569, 5-13= 380/484, 5-11= 383/484
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; 8=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi--O.18; MWFRS (directional); cantilever left and right exposed ; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) * This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at=lb)
14=1968,10=1818.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 405 lb down and 536 lb up at
9-0-0, 221 lb down and 265 lb up at 11-0-12, 221 lb down and 265 lb up at 12-2-0, and 221 lb down and 265 lb up at 13-3-4, and
405 lb down and 536 lb up at 15-4-0 on top chord, and 409 lb down and 458 lb up at 9-0-0, 72 lb down and 24 lb up at 11-0-12, 72
lb down and 24 lb up at 12-2-0, and 72 lb down and 24 lb up at 13-3-4, and 409 lb down and 458 lb up at 15-3-4 on bottom chord.
The design/selection of such connection device(s) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (pit)
Vert: 1-4=-54, 4-6=-54, 6-9— 54, 15-18= 20
Concentrated Loads (lb)
Vert: 4= 151(F) 6=-151(F) 12� 42(F) 13= 165(F) 11=-165(F) 5= 99(F) 21=-99(F) 22= 99(F) 23= 42(F) 24=-42(F)
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cori 6634
8904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verrly design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE MII.7473 rev. 101032015 BEFORE USE.
Design vaild for use only with MITekV connectors. This design is based only Upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicablilty of design parameters and properly Incorporate this design Into the overall
,
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek*
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and Truss systems, seeANS&J?P11 Oaa►ByCdleft DSB-89 and SCSI BUDdrng Component
6904 Parke East Blvd.
Safety Informationavailable from Truss Plate Institute. 218 N. Lee Street. Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
city
Ply
HINKLE RESIDENCE
T15290560
75546
GRF
HIP GIRDER
1
2
Job Reference (optional)
L:namDers I russ, Inc., i--on tierce, r-L 6.13u 5 Mar 11 ZV7 D IVII I eK Inausrrres, mu. i ue vcr a IZ:DD:oo zV I D ra9e i
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-k1_zt7eg_6na4ubatJi68HcbOHxmpu6k7Xno_hyV8Jb
2-3-13 7-0-0 12-7.1 18-0-6 23-5-10 28-10-15 34-6-0 39-6-0
2-3-13 4-B-3 5-7-1 5-5-5 5-5-5 5-5-5 5-7-1
5x8 MT18HS =
5.00 12 3x4 =
3 24 25 4 26 27 28
3x4 =
3x4 11 5x8 MTi8HS WB =
29 5 30 6 31 7 3233 34
5x8 MT18HS =
3x4 =
835 36 37 9
Scale=1:66.9
3x6 II 38 39 ._ 40 41 17 42 -- 43 44 45 -- 46 14 4/ — 49 bV M11
3x5 = 4x5 = 3x4 = 3x6 = 3x8 = 3x4 = 3x6 = 3x4 = 4x5 =
2-0-02- -13 7-0-0 12-7-1 18-0-6 23-5-10 28-10-15 34-6-0 39-6.0
2-0-00- - 3 4-8-3 5-7-1 5-55 5.5-5 5-5-5 5-7-1 5-0-0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc)
I/deft
Ud
TCLL 20.0
Plate Grip DOL
1.25
TC 0.85
Vert(LL)
1.07 15-16
>414
240
TCDL 7.0
Lumber DOL
1.25
BC 0.47
Vert(CT)
0.99 15-16
>449
180
BCLL 0.0 *
Rep Stress Incr
NO
WB 0.83
Horz(CT)
-0.17 11
n/a
n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 *Except* BOT CHORD
2-20,10-11: 2x6 SP No.2
OTHERS 2x4 SP No.3
REACTIONS. (lb/size) 20=1953/0-7-10, 11=1769/0-7-10
Max Horz 20=135(LC 7)
Max Uplift 20=-4054(LC 8), 11=-3746(LC 8)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-112/269,2-3=-2800/6034, 3-4=-4670/10101, 4-5=-5700/12268, 5-7=-5700/12268,
° 7-8= 5722/12311, 8-9= 4724/10197, 9-10= 2898/6204, 10-11 =-1 715/3616
BOT CHORD 19-20= 342/163, 18-19= 5437/2512, 16-18=-9941/4670, 15-16=-1215015722,
13-15=-10036/4724, 12-13=-5604/2606, 11-12= 327/167
WEBS 2-20= 1834/3774, 2-19=-5458/2568, 3-19=-430/606, 3-18=-5098/2458, 4-18=-1004/1905,
4-16=-2493/1176, 5-16=-438/682, 7-15=A50/686, 8-15=-2440/1147, 8-13=-989/1872,
9-13=-5016/2422,9-12=383/520,10-12=-5404/2505
PLATES GRIP
MT20 244/190
MT18HS 244/190
Weight: 410 lb Fr = 20%
Structural wood sheathing directly applied or 6-0-0 oc purlins,
except end verticals.
Rigid ceiling directly applied or 4-3-1 oc bracing.
NOTES-
1) 2-ply truss to be connected together with 1 Od (0.131 "x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row at 0-9-0 oc, 2x6 - 2 rows staggered at 0-9-0 oc.
Bottom chords connected as follows: 2x4 - 1 row at 0-9-0 oc.
Webs connected as follows: 2x6 - 2 rows staggered at 0-9-0 oc, 2x4 - 1 row at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
3) Unbalanced roof live loads have been considered for this design.
4) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpl=0.18; MW FRS (directional); cantilever, left exposed ; porch left and right exposed; Lumber DOL=1.60 plate
grip DOL=1.60
5) Provide adequate drainage to prevent water ponding.
6) All plates are MT20 plates unless otherwise indicated.
7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
8) * This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
20=4054,11=3746.
Walter P. Finn PE No.12839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
A WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MI1-7473 rev. 10/03/2015 BEFORE USE.
Design.vaild for use ordy with MITek) connectors. this design is based only upon parameters shown, and is for an kldiViduai building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing indicated Is to prevent buckling of Individualtruss web and/or chord members only. Additional temporary and permanent bracing
MOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSVW11 CUa1ByCrItaft DSB-89 and 8CS1 HUHMIg Component
6904 Parke East Blvd.
Safety lnformallonovallable from Truss Plate Insfltute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
'Qty
Ply
HINKLE RESIDENCE
T15290560
75546
GRF
HIP GIRDER
t
2
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL tm. ju s mar 11 zui8 Ivrl i eK industries, inc. rue uci u i2;56;36 GV 1 o rays c
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-kl_zt7eg_6na4ubatJi6BHcbOHxmpu6k7Xno_hyVBJb
NOTES-
10) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 229 lb down and 375 Ib up at 7-0-0, 164 lb down and 194 Ito up at
9-0-12, 164 lb down and 194 lb up at 11-0-12, 164 lb down and 194 lb up at 13-0-12, 164 lb down and 194 lb up at 15-0-12, 164 lb down and 194 lb up at 17-0-12, 164
lb down and 194 lb up at 19-0-12, 164 lb down and 194 lb up at 20-9-0, 164lb down and 194 lb up at 22-5-4, 164 lb down and 194 lb up at 24-5-4, 164 lb down and 194
lb up at 26-5-4, 164 lb down and 194 lb up at 28-5-4, 164 lb down and 194 lb up at 30-5-4, and 164 lb down and 194 lb up at 32-5-4, and 229 lb down and 375 lb up at
34-6-0 on top chord, and 235 lb down and 219 lb up at 7-0-0, 31 lb down and 74 lb up at 9-0-12, 31 lb down and 74 lb up at 11-0-12, 31 lb down and 74 lb up at 13-0-12
, 31 lb down and 74 lb up at 15-0-12, 31 Ito down and 74 lb up at 17-0-12, 31 lb down and 74 lb up at 19-0-12, 31 lb down and 74 lb up at 20-9-0, 31 lb down and 74 lb
up at 22-5-4, 31 lb down and 74 lb up at 24-5-4, 31 lb down and 74 lb up at 26-5-4, 31 lb down and 74 lb up at 28-5-4, 31 lb down and 74 lb up at 30-5-4, and 31 lb
down and 74 lb up at 32-5-4, and 235 lb down and 219 lb up at 34-5-4 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=-54, 3-9=-54, 9-10=-54, 11-21=-20
- Concentrated Loads (lb)
Vert: 3= 66(F) 6=-41(F) 9=-66(F) 19=12(F) 12=12(F) 24=-41(F) 25=-41(F) 26=41(F) 28=-41(F) 29=-41(F) 30=-41(F) 31=-41(F) 32=-41(F) 34=-41(F) 35=-41(F)
36=-41(F) 37=-41(F) 38=-13(F) 39= 13(F) 40=-13(F) 41= 13(F) 42=-13(F) 43=-13(F) 44=-13(F) 45=-13(F) 46= 13(F) 47=-13(F) 48=-13(F) 49= 13(F) 50=-13(F)
®WARMING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE MI1-7473 rev. 10/032015 BEFORE USE.
Design valid for use only with Wlllel<�V connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use. the building designer must vedfy The applicability of design parameters and properly Incorporate this design Into the overall
truss only. Additional temporary and permanent bracing
Wek°
building design. Bracing indicated is to prevent buckling of individual web and/or chord members
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
6904 Parke East Blvd.
fabrication, storage, delivery, erection and bracing of trusses and Truss systems, seeANSUIP/l Qua►By Ci feft DSO-69 and SCSi Buddfng Component
Tampa, FL 33610
SatefyfntomlaMonovallable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290561
75546
GRG
HIP GIRDER
1
1
Job Reference (optional)
cnam0ers I russ, Inc., r0rr Fierce, I-L MIsU s Mar 11 zU10 rwr r eK muusmes, Inc. r ue vcr a rz:Da:aa zo I o Faye i
ID:QGf7ZgnsSSbOPbDkjBM4rQyXnLm-8cf6W8hZH 198xMK9YRGpmwEBJUvYOEW BgUOTaOyV8JY
i 2-3-13 5-7-7 9-0.0 14-3-14 19-6-0 24-&2 i 30-0-0 33-4-9 i 36-B-3 i 39-0-0�
2-3-13 3-3-10 5-3-14 5-2-2 5-2-2 5-3-14 3-4-9 3-3-10 2-3-13
J
10x14 MT18HS 11
5.00 F,2
4
3x10 I
5x6 = 5x8 MT18HS = 5x6 =
26 27 5 28 29 30 6 7 31 32 33 834 35
7x10 MT18HS =
36 9
Scale = 1:65.3
6x10
3
6x10
10
3x4 I I
3x4 11
2
tt
7x8 = 21 20 19 37 18 38 39
4x5 = 4x4 = 6x8 = 4x6 =
9m-0
17 40 41 42 43 16 44 15 45 , 14 13
_ 7x8 =
4x8 dx6 = 6x8 = 4x4 =
v
2 I4
6
4x5 =
LOADING (psf)
SPACING-
2-0-0
CSL
DEFL.
in
(loc)
I/defl
L/d
PLATES
GRIP
TCLL 20.0
Plate Grip DOIL
1.25
TC 0.68
Vert(LL)
0.63
17
>651
240
MT20
244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.72
Vert(CT)
-0.45
17
>921
240
MT18HS
244/190
BCLL 0.0 '
Rep Stress incr
NO
WB 0.85
Horz(CT)
-0.16
13
n/a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Weight: 253lb
FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 -Except- TOP CHORD
4-7,7-9: 2x6 SP 240OF 2.0E BOT CHORD
BOT CHORD 2x6 SP No.2 `Except` WEBS
15-19: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3 *Except*
2-21,11-13: 2x6 SP No.2, 3-21,10-13: 2x4 SP M 30
REACTIONS. (lb/size) 21=2463/0-7-10, 13=2463/0-7-10
Max Harz 21=201(LC 7)
Max Uplift 21=-3111(LC 8), 13=-2969(LC 8)
Max Grav 21=2813(LC 29), 13=2814(LC 30)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=423/199, 2-3� 361/257, 3-4= 4824/5113, 4-5=-6485/6864, 5-6=-7107/7490,
6-8=-7107/7490, 8-9= 6490/6881, 9-10= 4826/5143, 10-1 1=-360/257,11-12=-359/198
BOT CHORD 1-21=-203/437, 20-21= 3658/3753, 18-20= 4477/4534, 17-18=-6562/6560,
16-17= 6579/6492, 14-16— 4505/4400, 13-14=-3713/3604, 12-13=-203/363
WEBS 2-21=-304/408, 3-20=-1091/1081, 4-18=-2539/2561, 5-18=-1201/1427, 5-17=-773/837,
6-17=-651/898, 8-17= 767/833, 8-16— 1201/1427, 9-16=-2536/2565, 10-14=-1091/1082,
11-13=-304/389, 3-21=-4129/4539, 10-13=-4132/4439
Structural wood sheathing directly applied or 3-3-5 oc purlins.
Rigid ceiling directly applied or 3-5-3 oc bracing.
1 Row at midpt 4-18, 9-16
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional); cantilever left and right exposed; Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) The Fabrication Tolerance at joint 4 = 16%, joint 9 = 12%
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ot=lb)
21=3111,13=2969.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED mrrEKREFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE
'
Design valid for use only with MITeW connectors. This design Is based only upon parameters shown, and Is for an Individual binding component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek°
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss'.'systems, seeANSVW11 GualdyCriterla, DSB-89 and SCSI SuMbIlg Component
6904 Parke East Blvd.
Satetyinlormotionzivailable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290561
75546
GRG
HIP GIRDER
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MfI eK Industries, Inc. I us Oct 9 12:55:39 20173 t'age 2
I D:OGfzZgnsSSbOPbDkjBM4rOyXnLm-8cf6W 8hZH 198xMK9YRGpmwE8J UvYOE W Bq UOTaOyVBJY
NOTES-
9) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 405 lb down and 536 lb up at 9-0-0, 221 lb down and 265 lb up at
11-0-12, 221 lb down and 265 lb up at 13-0-12, 221 lb down and 265 lb up at 15-0-12, 221 lb down and 265 lb up at 17-0-12, 221 lb down and 265 lb up at 19-0-12, 221
lb down and 265 lb up at 19-11-4, 221 lb down and 265 lb up at 21-11-4, 221 lb down and 265 lb up at 23-11-4, 221 lb down and 265 lb up at 25-11-4, and 221 lb down
and 265 lb up at 27-11-4, and 405 lb down and 536 lb up at 30-0-0 on top chord, and 409 lb down and 458 lb up at 9-0-0, 72 lb down and 24 lb up at 11-0-12, 72 lb down
and 24 lb up at 13-0-12, 72 lb down and 24 lb up at 15-0-12, 72 lb down and 24 lb up at 17-0-12, 72 lb down and 24 lb up at 19-0-12, 72 lb down and 24 lb up at 19-11-4
, 72 lb down and 24 lb up at 21-11-4, 72 lb down and 24 lb up at 23-11-4, 72 lb down and 24 lb up at 25-11-4, and 72 lb down and 24 lb up at 27-11-4, and 409 lb down
and 458 lb up at 29-11-4 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
10) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front.(F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-4=-54, 4-9=-54, 9-12= 54, 1-12=-20
. Concentrated Loads (lb)
Vert: 4=-151(13) 7=-99(B) 9= 151(B) 19= 42(B) 20=-165(B) 14= 165(B) 26=-99(B) 27=-99(B) 29=-99(B) 30= 99(B) 31=-99(B) 32=-99(B) 33=-99(B) 35= 99(B)
36=-99(B) 37=-42(B) 38=-42(B) 39= 42(B) 40=-42(B) 41=-42(13) 42=-42(B) 43= 42(B) 44= 42(B) 45= 42(B)
® WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MIrEK REFERANCE PAGE M0.7473 rev. 1010312015 BEFORE USE
"
Design valid for use only with MITe',V connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only, Additional temporary and permanent bracing
MiTek°
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSVWII CualtlyCi feria, DSB-89 and BCSI BuIlding Component
6904 Parke East Blvd.
Safety tnfonnationovailable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290562
75546
GRP
HALF HIP GIRDER
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. Tue Oct 9 12:55.40 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-coD Uj UhB2KH?ZVuM69n2J7m lauKelgpK28107SyV8JX
2-3-13 7-0-0 11-5-11 15-9-10 20-1-9 24-7-4 25-8-0 ,
2-3-13 4-8-3 4-5-11 4-3-15 4-3-15 4-5-11 1-0-12
6x8 MT18HS =
5.00 12
3x4 =
20 214 22
2x3 11 5x8 MT18HS = 3x5 =
23 0 24 6 25 r 26 27
Scale=1:42.0
Sx6 =
6 28 9
3x6 II 4x5 = JXb 3x8 = 3x6 = 4x6 11
3x4 = 3x4 =
2-0-0 2- - 3 7-0-0
11-5-11
15-9-10
2%1-9
24-7-4
2-0-0 0- - 3 4-8-3
4-5-11
4-3-15
4-3-15
4-5-11
Plate Offsets (X,Y)--
(3:0-5-120-2-8j, f6:0-4-0,Edgej
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc)
I/dell
Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.71
Vert(LL)
0.35 12-14
>751
240
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.34
Vert(CT)
0.33 12-14
>813
180
MT18HS
244/190
BCLL 0.0 '
Rep Stress Incr NO
WB 0.91
Horz(CT)
-0.07 10
n/a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Weight: 134 lb
FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 `Except` BOT CHORD
8-10: 2x6 SP No.2 WEBS
REACTIONS. (lb/size) 10=1155/0-6-14, 16=1208/0-7-10
Max Horz 16=235(LC 8)
Max Uplift 10=-2442(LC 5), 16=-2455(LC 8)
Max Grav 10=1155(LC 1), 16=1209(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. All forces 250 (lb) or less except when shown.
TOP CHORD 2-3= 1504/3257, 3-4=-2012/4409, 4-5= 1985/4285, 5-7= 1985/4285, 7-8=-1318/2805,
• 8-1t1103/2292
BOT CHORD 15-16=-299/97, 14-15=-3046/1327, 12-14=-4409/2012, 11-12=-2805/1318
WEBS 2-16=-1101/2189, 2-15=-2901/1379, 3-14=-1679/839, 4-14=-357/532, 5-12=352/550,
7-12=-1794/812, 7-11 =-775/1 529, 8-11=-3335/1554
Structural wood sheathing directly applied or 5-0-3 oc purlins,
except end verticals.
Rigid ceiling directly applied or 3-4-11 oc bracing.
1 Row at midpt 2-15, 8-11
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDLr3.Opsf; h=25ft; B=60f; L=60ft eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional); cantilever' left exposed ; porch left and right exposed; Lumber DOL=1.60 plate
grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Will fit between the bottom chord and, any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
10=2442, 16=2455.
8) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 229 lb down and 375 lb up at
7-0-0, 164 lb down and 194 lb up at 9-0-12, 164 lb down and 194 lb up at 11-0-12, 164 lb down and 194 lb up at 13-0-12, 164 lb
down and 194 lb up at 14-6-8, 164 lb down and 194 lb up at 16-6-8, 164 lb down and 194 lb up at 18-6-8, and 164 lb down and 194
lb up at 20-6-8, and 164 lb down and 194 lb up at 22-6-8 on top chord, and 235 lb down and 219 lb up at 7-0-0, 31 lb down and 74
lb up at 9-0-12, 31 lb down and 74 lb up at 11-0-12, 31 lb down and 74 lb up at 13-0-12, 31 lb down and 74 lb up at 14-6-8, 31 lb
down and 74 lb up at 16-6-8, 31 lb down and 74 lb up at 18-6-8, and 31 lb down and 74 lb up at 20-6-8, and 31 lb down and 74 lb
up at 22-6-8 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
9) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
Walter P. Finn PE No.22939
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Vedly design parameters and READ NOTES ON THIS AND INCLUDED M/7EK REFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon pararnetets shown, and Is for an individual building component, not
��
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individualtruss web and/or chord members only. Additional temporary and permanent bracing
MOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guldance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSUIPI1 Qua►By, CrBeda, DSO-69 and BCSI BuRdrng Component
6904 Parke East Blvd.
Safety Informationovallable from Truss Plate Institute, 218 N. Lee Street, Suite 312 FJexandrla, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290562
75546
GRP
HALF HIP GIRDER
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
8.130 s Mar 11 2018 MI I eK Industries, Inc. I ue Uct 9 12:b5:41 2g18 Page 2
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-5?nsxgipoeQsBfTYfsl HrLJTKIgtU63THoVZfuyV8J W
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
,Uniform Loads (plf)
Vert: 1-3=-54, 3-8=-54, 8-9=-54, 10-17= 20
Concentrated Loads (lb)
Vert:3=-66(B) 15=12(B)20— 41(B) 21=-41(B) 22=-41(B) 23=-41(13) 24= 41(B) 25=-41(13)26=-41(13) 27=-41(B)29= 13(B) 30=-13(B) 31= 13(B) 32=-13(B) 33=-13(B)
34=-13(B) 35=-13(B) 36=-13(B)
® WARNING - Verilydesign parameters and READ NOTES ON THIS AND INCLUDED M/rEK REFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE.
Design valld for use only with MITek:0 connectors. This design Is based only upon parameters shown, and Is for on individual building component, hot
�^
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MOW
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
6904 Parke East Blvd.
fabrication, storage, delivery, erection and bracing of trusses and truss
Safety tntonnatbn ivaiiable from Truss Plate Institute, 218 N. Lee Stree
systems, seeANSYWI1 AUaBPyCrCeda, DSB-89 and SCSI Building Component
r Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290663
75546
J1
JACK -OPEN
18
1
Job Reference (optional)
cnamners I russ, Inc., t-on coerce, I -I_
3-0-0
O. IOU b IVRII I I ZU r O IVII I UK JIMUbLueb, If 1U. I Ue VIA W IZ:DD.Y 14U IO rilae 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-5?nsxgipoeQsBfTYfsl HrLJTCIggUHfTHoVZfuyV8J W
3x6 11 5
3-0-0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/defl
Ud
TCLL 20.0
Plate Grip DOL
1.25
TC 0.72
Vert(LL)
-0.00
5
>999
240
TCDL 7.0
Lumber DOL
1.25
BC 0.36
Vert(CT)
0.00
5
>999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.23
Horz(CT)
0.04
3
n1a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MP
LUMBER -
TOP CHORD 2x4 SP No.3
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 3=-117/Mechanical, 4=-181/Mechanical, 5=515/0-7-10
Max Horz 5=98(LC 12)
Max Uplift 3= 117(LC 1), 4=-181(LC 1), 5=-741(LC 12)
Max Grav 3=155(LC 12), 4=258(LC 12), 5=515(LC 1)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
WEBS 2-5=-236/787
Scale = 1:10.8
PLATES GRIP
MT20 244/190
Weight: 11 lb FT = 20%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 3-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) zone; cantilever left exposed; porch left and right
exposed;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) a This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
3=1 17, 4=1 81, 5=741.
Walter P. Finn PE No.22836
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MI EK REFERANCE PAGE 111I1-7473 rev. 1010312015 BEFORE USE.
Design valid for use only wllh NilTe10 connectors. This design Is based only upon parameters shown, and Is for an Individual building component not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
building design. Bracing Indicated Is to buckling Individual truss web and/or chord members only. Additional temporary and permanent bracing
MOW
prevent of
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
rg Component
storage, delivery, erection and bracing of trusses and truss systems, seeANSUIPir GuallyCriteria, DSB-89 and BCSI Bundling
Parke East
East Blvd.fabrication,
Tampa, Parke
Safety/nionnaflorravallable from Truss Plate Insfitute, 218 N. Lee Street; Suite 312, Alexandria, VA 22314.33610
Job
Truss
Truss Type
Ply
Ply
HINKLE RESIDENCE
T15290564
75546
J3
JACK -OPEN
18
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:43 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-1 NvcLW k3KFgaQzdxnHKlwmOpp6FHyBnmk6_gknyV8JU
5-0-0
5-0-0
Scale=1:14.9
24 11
2-0-0 2-3-13
r 2-0-0 0-3-13
5-0-0
2-8-3
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.71
Vert(LL)
0.01 4-5 >999 240
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.80
Vert(CT)
0.01 4-5 >999 180
BCLL 0.0
Rep Stress Incr YES
WB 0.19
Horz(CT)
0.04 3 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MP
Weight: 17lb FT=20%
LUMBER-
BRACING -
TOP CHORD 20 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 5-0-0 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 3=30/Mechanical, 4= 9/Mechanical, 5=344/0-7-10
Max Horz 5=165(LC 12)
Max Uplift 3— 72(LC 9), 4=-67(LC 13), 5=-508(LC 12)
Max Grav 3=63(LC 17), 4=21(LC 3), 5=344(LC 1)
FORCES. (Ib) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 316/112
BOTCHORD 1-5=-119/329
WEBS 2-5=-248/652
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60fh eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional) and C-C Exterior(2) zone; cantilever left exposed ; porch left and right
exposed;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 3, 4 except Qt=lb)
5=508.
Walter P. Finn PE No.22939
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verity design parameters and READ NOTES ON THIS AND INCLUDED MDEK REFERANCE PAGE MI1-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MlTek0 connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek`
Is always required for stabllih' and to prevent collapse with possible personal Injury and property damage. For general guidance regarding'the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSUWII QUOMY Ci feda, DSB-89 and BCSI BaBdlgq Component
6904 Par
Parke East Blvd.
Safety rnformationavailable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
'
T15290565
75546
J5
JACK -OPEN
36
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
2x3 II
LOADING (psf) SPACING- 2-0-0 CSI.
TCLL 20.0 Plate Grip DOL 1.25 TC 0.37
TCDL 7.0 Lumber DOL 1.25 BC 0.92
BCLL 0.0 Rep Stress Incr YES WB 0.21
BCDL 10.0 Code FB02017/TPI2014 Matrix -MP
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP No.3
WEBS 2x4 SP No.3
REACTIONS. (Ib/size) 3=95/Mechanical, 4=33/Mechanical, 5=385/0-7-10
Max Horz 5=232(LC 12)
Max Uplift 3_ f 77(LC 12), 4=-122(LC 9), 5= 570(LC 12)
Max Grav 3=128(LC 17), 4=71(LC 3), 5=385(LC 1)
8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:43 2018 Page 1
ID:QGfzZgnsSSbOPbDkjBM4rQyXnLm-1 NvcLWk3KFgaQzdxnHKlwmOvB6DLyBTmk6_gknyVBJU
7-0-0
7-0-0
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-430/170
BOT CHORD 1-5=-157/436
WEBS 2-5=-350/722
Scale=1:19.8
4-8-3
DEFL. in (loc) I/dell Ud PLATES GRIP
Vert(LL) 0A0 4-5 >536 240 MT20 244/190
Vert(CT) 0.10 4-5 >554 180
Horz(CT) -0.06 3 n/a n/a
Weight: 23 Ito FT = 20%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 6-11-4 zone; cantilever left
exposed; porch left and right exposed;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 elide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at=lb)
3=177, 4=122, 5=570.
Walter P. Finn PE No.12639
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd, Tampa FL 33610
Date:
October 9,2018
A WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE
I
Design valid for use only with MiTek© connectots. This design Is based only upon parameters shown, and Is for an individual binding component not
�"
a truss system. Before use, the building designer must verify The applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual, truss web and/or chord members only. Additional temporary and permanent bracing
MiTek"
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, dellvery, erection and bracing of trusses and truss systems, seeANSVIPI► Quallly Cdteda, DSB-89 and BCSI BuRding Component
6904 Parke East Blvd.
Safety/ntormatlonovallable from Truss Plate Institute, 218 N. Lee Street, Suite 312. Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Y3ty
Ply
HINKLE RESIDENCE
T15290566
75546
J7
JACK -OPEN
22
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. Tue Oct 9 12:55:44 2018 Page 1
• ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-VaT?Zskh5ZoR27C7L_s_TzxzEVaLhcvwzmjEGDyV8JT
4-8-2 9-0-0
4-8-2 4-3-14
3x6 11
LOADING (psf) SPACING- 2-0-0 CSI.
TCLL 20.0 Plate Grip DOL 1.25 TC 0.79
TCDL 7.0 Lumber DOL 1.25 BC 0.87
BCLL 0.0 Rep Stress Incr YES WB 0.33
BCDL 10.0 Code FBC2017/TP12014 Matrix -MS
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP No.3
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 3=153/Mechanical, 4=62/Mechanical, 5=446/0-7-10
Max Horz 5=299(LC 12)
Max Uplift 3=-249(LC 12), 4=-6(LC 9), 5=-469(LC 12)
Max Grav 3=205(LC 17), 4=112(LC 3), 5=446(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 628/211
BOT CHORD 1-5=-188/512
WEBS 2-5=-415/1110
Scale: 1/2"=1'
9-0-0
DEFL. in (loc) I/defl Ud PLATES GRIP
Vert(LL) 0.12 4-5 >686 240 MT20 244/190
Vert(CT) -0.16 4-5 >510 240
Horz(CT) -0.12 3 n/a n/a
Weight: 29 lb FT = 20%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 3-10-4 oc purlins.
BOT CHORD Rigid ceiling directly applied or 8-1-8 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25f; B=60ft; L=60ft; eave=7ft; Cat.
11; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extehor(2) 0-0-0 to 6-0-0, Intefior(1) 6-0-0 to 8-11-4 zone; cantilever left
exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 4 except Qt=lb)
3=249, 5=469.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING- Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE Mll-7473 rev. 10/03/2015 BEFORE USE.
m
Design valid for use orgy with lvirfekb connectors. This design Is bored only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
Individual truss members only. Additional temporary and permanent bracing
MiTek*
building design. Bracing Indicated Is to prevent buckling of web and/or chord
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSMIr GualgyCdleda, DSB-89 and BCSI BuOdlnq Component
6904 Parke East Blvd.
Safety lnronnaRonavailabie from Truss Plate Institute, 218 N. Lee Sheet, Suite 312, Alexandria. VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290567
76646
JC
Jack -Closed
8
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:45 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-zmONmClJstwlfHnJui NDOBTIzv1 mQ7a3CQTnogyV8JS
1-10-8
1-10-8
3x4 =
PROVIDE BEARING CONNECTION(S) TO RESIST
HORIZONTAL REACTION(S) SHOWN.
ADEQUATE SUPPORT REQUIRED.
1.10.8
1-10-8
2x3 11
Scale = 1:8.4
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/deft L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.16
Vert(LL) -0.00
6 n1r 120
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0:4.1
Vert(CT) -0.00
6 n/r 120
BCLL 0.0 '
Rep Stress Incr YES
WB 0.11
Horz(CT) 0.00
n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MP
Weight: 7lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 1-10-8 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 3=136/Mechanical, 2= 0/Mechanical
Max Horz 3=256(LC 12), 2=-193(LC 12)
Max Uplift 3= 224(LC 12)
Max Gram 3=136(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown
TOP CHORD 1-2=-634/179
BOT CHORD 1-3=-161/656
WEBS 2-3=-105/372
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25tt; B=60ft; L=60ft; eave=7ft Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional) and C-C Extedor(2) zone; cantilever left and right exposed ;C-C for members and
forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed fora 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except.(jt=lb)
3=224.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
A WARNING- Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII-7473 rev, 1010312015 BEFORE USE.
'
Design valid for use only with MlTekb connectots. This design is based only upon potarnelers showfil, and Is for an individual building component, net
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into The overall
building design. Bracing Indicated is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
prevent
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of Trusses and Truss systems, seeANSI/IP(I Cual9yCIfeda, DSO-69 and BCSI BuRdfng Component
6904 Parke East Blvd.
Sa►etyintonnaf onavallable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
'Qty
Ply
HINKLE RESIDENCE
T15290568
75546
JU
JACK -OPEN
18
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL
8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55.45 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-zmON mClJstwlfHnJ ui NDOBTJQv24Q813COTnogyVBJS
1-0-0
3x4 =
PROVIDE BEARING CONNECTION(S) TO RESIST
HORIZONTAL REACTION(S) SHOWN.
ADEQUATE SUPPORT REQUIRED.
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc)
I/defl
Ud
TCLL 20.0
Plate Grip DOL
1.25
TC 0.13
Vert(LL)
-0.00 6
n/r
120
TCDL 7.0
Lumber DOL
1.25
BC 0.33
Vert(CT)
-0.00 6
n/r
120
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
0.00
n/a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MP
LUMBER -
TOP CHORD 2x4 SP No.3
BOT CHORD 2x4 SP No.3
REACTIONS. (lb/size) 2=0/Mechanical, 3=73/Mechanical
Max Horz 2= 118(LC 12), 3=151(LC 12)
Max Uplift 3= 122(LC 12)
Max Grav 3=73(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-262/74
BOT CHORD 1-3=-84/348
Scale =1:6.5
PLATES GRIP
MT20 244/190
Weight: 3 lb FT = 20%
BRACING -
TOP CHORD Structural wood sheathing directly applied or 1-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) zone; cantilever left exposed ;C-C for members and forces &
MW FRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) **This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
3=122.
Waller P. Finn PE No.22639
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII.7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MITeWV connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Addillonal temporary and permanent bracing
MiTek
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSVWII CuaNyCi fella, DSO-69 and BCS1 BuRdigg Component
6904 Parke East Blvd.
Sdtefy/nfolmaf/onovallabie from Truss Plate Institute, 218 N. Lee Street;Suite 312. Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Ply
HINKLE RESIDENCE
T15290569
75546
KJ5
DIAGONAL HIP GIRDER
�Qty
3
1
Job Reference o tional
Chambers Truss, Inc., Fort Pierce, FL o. rote s mar r i �v! o IVII ! — jiUat
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-Ryal_YmydA29HQMVSPuSY000FJ N09ZDCR4CKK6yV8J R
5-2-9 1 6-0-9 9-10-1
5-2-9 0-10-0 3-9-8
Scale=1:19.6
3x4 =
2-9-9 0-5-6 2-9-9
3-9-8
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) Well Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.38
Vert(LL) 0.11
6-7 >725 240
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.41
Vert(CT) 0.09
6-7 >851 240
BCLL 0.0 '
Rep Stress Incr NO
WB 0.15
Horz(CT) -0.00
4 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Weight: 42 Ib Fr = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 4=93/Mechanical, 5=3/Mechanical, 7=347/0-10-13
Max Horz 7=231(LC 8)
Max Uplift 4= 131(LC 8), 5= 195(LC 8), 7=-949(LC 8)
Max Grav 4=101(LC 17), 5=114(LC 26), 7=956(LC 31)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-702/624, 2-3=-700/659
BOT CHORD 1-7=-573/707, 6-7-158/367
WEBS 3-7= 545/502, 3-6=-411/177
NOTES-
1) Wind: ASCE 7-10; VuIt=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional); cantilever left exposed; porch left and right exposed; Lumber DOL=1.60 plate
Grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
4=131, 5=195, 7=949.
6) "NAILED" indicates 3-1Od (0.148"x3") or 2-12d (0.148"x3.25") toe -nails per NDS guidlines.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-4=-54, 5-8=-20
Concentrated Loads (IN
Vert: 11=148(F=74, B=74) 13= 90(F=-45, B— 45) 14=222(F=111, B=111)
Walter P. Finn PE No.22639
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MIrEK P.EFERANCE PAGE MII-7473 rev. 10/032015 BEFORE USE.
Design valid for use only with Ml ie',M connectors. This design Is based only upon parameters shown, and is for an Individual building component, not �
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual iruss web and/or chord members only. Additional temporary and permanent bracing MOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and Truss systems, seeAMSVWII QualRyCrBerfa, DSB-89 and SCSI Building Companenf 6904 Parke East Blvd.
Safety lnformallo► 3vallable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290570
75546
KJ7
DIAGONAL HIP GIRDER
6
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:47 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXn Lm-v987BunaOUAOvaxiO7Ph5cZaojjpuywMfkyutYyV8JO
3-2-15 6-7-8 7-8-1 12-8-0
3-2-15 3-4-9 1-0-9 4-11-15
=1:24.6
axy — wr�i�r=u 8 —.1— 44 =
NAILED 3x5 II NAILED NAILED NAILED 3x4 =
NAILED
2-9-9
2-9-9
,3.2-1§
0-5-6r
7-8-1
4-5-2
11-8-u
4-11.15
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
Well
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC
0.39
Vert(LL)
0.13
6-7
>882
240
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC
0.37
Vert(CT)
-0.06
6-7
>999
240
BCLL 0.0 '
Rep Stress Incr
NO
WB
0.44
Horz(CT)
0.01
4
n/a
n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 56lb FT=20%
LUMBER -
TOP CHORD 2x4 SP M 30
SOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3
REACTIONS. (lb/size) 4=128/Mechanical, 5=151/Mechanical, 8=421/0-10-13
Max Horz 8=298(LC 8)
Max Uplift 4= 219(LC 8), 5=-430(LC 8), 8=-1129(LC 8)
Max Grav 4=131(LC 28), 5=345(LC 22), 8=1152(LC 31)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-750/599, 2-3= 945/692
BOT CHORD 1-8=-558/763, 7-8=-558/465, 6-7= 756/679
WEBS 2-8= 729/817, 3-6=-755/842, 2-7=-1125f748
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MW FRS (directional); cantilever left exposed; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) . This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 Ib uplift at joint(s) except Qt=lb)
4=219, 5=430, 8=1129.
6) "NAILED" indicates 3-1Od (0.148"x3") or 2-12d (0.148"x3.25") toe -nails per NDS guidlines.
7) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (pit)
Vert: 1-4=-54, 5-9=-20
Concentrated Loads (lb)
Vert: 12=148(F=74, B=74) 14=-37(F=-19, 6=-19)15=-90(F=-45, B=-45) 16=222(F=111, B=111) 18=-10(F=-5, B— 5)
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED miTEK REFERANCE PAGE MI1-7473 rev. 10/032015 BEFORE USE.
Design valld for use only with MITekV connectors. ihis design Is based only upon parameters shown, and Is for an individual building component, hot
�
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
Individual truss members only. Additional temporary and permanent bracing
MiTek`
building design. Bracing Indicated Is to prevent buckling of
Is always required for stability and to prevent collapse with possible p4sonal
web and/or chord
Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss
ding Component
systems, seeANSIRPII AualifyCrffefla, DSO-89 and BCSI Building
East
rkEast Blvd.
Pae
a Parke
Tam P33610
Safetyfn/omlaflonavallable from Truss Plate Institute, 218 N. Lee Street,
Suite 312. Alexandria, VA 22314.
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290571
75546
M
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek industries, Inc. Tue Oct 9 12:55.48 2018 Page 1
I D:QGfzZgnsSSbOPbDkjeM4rQyXnLm-NLiVPDnC9oltW kW uagwwdp5nb73RdPXVuOh RP?yV8JP
2-3-13 6-8-4 10-10-8 14-9-0 18-11-0 19 2 0
2-3-13 4-4-7 4-2-4 3-10-8 4-2-0 0-3-0
4x4 =
16
3x4 =
5
Scale=1:31.5
3x4 11
6 7
3x4 = 11 6x8 = 3x6 = 3x8 = 6x8 =
2-0-0 013- 3
8-6-11
8-0-8
Plate Offsets (X Y)--
f 11.0-3-8 0-3-01
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/dell
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.26
Vert(LL)
-0.07
9-11
>999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC 0.35
Vert(CT)
-0.15
9-11
>999
240
BCLL 0.0 '
Rep Stress Incr
YES
WB 0.42
Horz(CT)
-0.02
8
n/a
n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Wind(LL)
0.03
9
>999
240
Weight: 104lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
SOT CHORD 2x4 SP M 30
WEBS 2x4 SP No BOT CHORD
REACTIONS. (lb/size) 8=6181Mechanical, 11=792/0-7-.10
Max Harz 11=365(LC 12)
Max Uplift 8=-619(LC 12), 11= 797(LC 12)
Structural wood sheathing directly applied or 6-0-0 oc purlins,
except end verticals.
Rigid ceiling directly applied or 6-0-0 oc bracing.
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-497/39, 2-3= 270/53, 3-4=-670/737, 4-5— 597/765
BOT CHORD 1-11=-7/465, 9-11= 1109/760, 8-9=-582/399
WEBS 2-11=-224/576, 3-11=-778/1176, 3-9= 194/403, 5-9=-290/313, 5-8=-587/869
,NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 10-10-8, Exterior(2)10-10-8
t6 19-2-0 zone; cantilever left exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) Provide adequate drainage to prevent water ponding.
.3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) " This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
8=619, 11=797.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL'33610
Date:
October 9,2018
® WARNING - Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE M11-7473 rev. 1010312015 BEFORE USE.
Design valld for use only with MITekV connectors. This design Is based only upon parameters shown, and Is for an Individual building component, riot
�
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSI/IPII QualityCrBalb, DS9•89 and BCSI Buud61g Component
Safety Infomratlonavailable from Truss Plate Institute, 218 N. Lee Slreet,ISuite 312. Alexandria, VA 22314.
6904 Parke East Blvd.
Tampa, FL 33610
Job
Truss
Truss Type
holy
Ply
HINKLE RESIDENCE
T15290572
75546
M1
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:49 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-sXGucZogw5Qk8u447YR9A1 eugW LsMnRf72R?xRyVBJO
2-3-13 7-8-5 12-10-8 18-11-0 1-2-0
2-3-13 5-4-8 5-2-3 6-0-8 0-3-0
4x8 = 3x4 11 Scale=1:36.7
5 6
3x4 = 3x6 11 , 3x6 = 3x4 = 6x8 =
2x3 11
7-8-5
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0 '
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017fTP12014
CSI.
TC 0.56
BC 0.59
WB 0.76
Matrix -MS
DEFL. in
Vert(LL) -0.11
Vert(CT) -0.21
Horz(CT) -0.02
Wind(LL) 0.21
(loc) I/dell L/d
8-10 >999 360
8-10 >947 240
7 n/a n/a
B-10 >919 240
PLATES GRIP
MT20 244/190
Weight: 99 Ib FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 6-0-8 oc bracing.
REACTIONS. (lb/size) 7=618/Mechanical, 11=79210-7-10
Max Horz 11=432(LC 12)
Max Uplift 7=-639(LC 12), 11=-777(LC 12)
Max Grav 7=627(LC 17), 11=792(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (Ib) or less except when shown.
TOP CHORD 1-2=-639/432, 2-3=-804/750, 3-4= 543/601, 5-7= 173/329
BOT CHORD 1-11= 465/635, 10-11= 1033/741, 8-10— 1033/741, 7-8=-685/495
WEBS 2-11=-494/877, 3-8- 298/415, 4-8=-232/340, 4-7= 654/900
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60fh L=60ft; eave=7ft; Cat.
11' Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 12-10-8, Exterior(2) 12-10-8
to 19-2-0 zone; cantilever left exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) Provide adequate drainage to prevent water ponding.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
7=639, 11=777.
Walter P. Finn PE No.22838
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33616
Date:
October 9,2018
A WARNING- Verdy design parameters and READ NOTES ON THIS AND INCLUDED M/TEK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE.
Design vaild for use only with MiTek' connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must vedfy the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek*
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, dellvery, erection and bracing of trusses and truss systems. seeANS►/IPII Quality ClUede, DS8-89 and BCSI Bugding Component
6904 Parke East Blvd.
Safety lnfannaBanovailable from Truss Plate Institute, 218 N. Lee Street.ISuite 312. Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290573
75546
M2
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:50 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-KjgGpvpShPYbm2fHhFzOiEB2TwgB5FgoLiAYTtyV8JN
2-3-13 7-8-5 14-10-8 18-11-0 1 D-2-0
2-3-13 5-4-8 7-2-3 4-0-8 0-3-0
4x10 = 3x4 11
Scale=1:39.3
s_nn - 4 5 6
3x4 = 2x3 11 2x3 11 " — 3x4 = 6x8 =
5-4-8
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0 '
BCDL 10,0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress [nor YES
Code FBC2017/TPI2014
CSI.
TC 0.62
BC 0.65
WB 0.69
Matrix -MS
DEFL. in
Vert(LL) -0.14
Vert(CT) -0.29
Horz(CT) -0.02
Wind(LL) 0.27
(loc) I/dell Ud
8-10 >999 360
8-10 >687 240
7 n/a n/a
8-10 >740 240
PLATES GRIP
MT20 244/190
Weight: 104lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 5-6-9 oc bracing.
REACTIONS. (lb/size) 7=618/Mechanical, 11=79210-7-10
Max Horz 11=499(LC 12)
Max Uplift 7=-663(LC 12), 11=-753(LC 12)
Max Grav 7=658(LC 17), 11=792(LC 21)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-705/455, 2-3=-857/708, 3-4=-420/355
BOT CHORD 1-11= 461/693, 10-11=-1099/816, 8-10=-1089/816, 7-8=-500/368
WEBS 2-11= 463/792, 3-8=-496/647, 4-8=-273/390, 4-7=-695/941
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 14-10-8, Extedor(2) 14-10-8
to 19-2-0 zone; cantilever left exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Refer to girder(s) for truss to truss connections.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
7=663,11=753.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cod 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verity design parameters and READ NOTES ON THIS AND INCLUDED MrrEK REFERANCE PAGE Mll-7473 rev. 1010312015 BEFORE USE.
Design vaild for use only with tv1100 connectors. This design Is based Only upon parameters shown, and is for an Individual building component not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of individual'truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSV7PII ®ua►tlyCifede, DSO-89 and SCSI Building Component
6904 Parke East Blvd.
Sa/efyinrorma@onavallable from Truss Plate Institute, 218 N. Lee Sheet, Suite 312. Alexandrla, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLERESIDENCE
T15290574
75546
M3
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 Mtl ek Industries, Inc. I ue Oct 9 iz:55:51 zula Page 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-ow0e1 Fg4SjgSNCETFzUdFSjF9K2_ghuyaMw50JyVBJM
2-3-13 7-8-6 11-6-11 16-10-8 18-11-0 19-2-0
2-3-13 5-4-9 3-IVI 5-3-13 2-0-8 0-3-0
4x8 = 3x4 II Scale = 1:43.4
5.00 F12 6 7 8
3x4 = 13x6 11
3x4 =
3x6 =
3x4 = =
6x89
2-0-0 2 - 3
7-8-6
16-10-8
18-ti-0
2-0-0 0- - 3
5-4-9
9-2-3
2-0-8
Plate Offsets (X Y)--
(6.0-5-8 0-2-01
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (roc)
Well
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC
0.49
Vert(LL)
-0.18 10-12
>999
360
MT20 244/190
TCDL 7.0
Lumber DOL
1.25
BC
0.55
Vert(CT)
-0.41 10-12
>485
240
BCLL 0.0
Rep Stress Incr
YES
WB
0.76
Horz(CT)
-0.02 9
n/a
n/a
BCDL 10.0
Code FBC2017[TP12014
Matrix -MS
Wind(LL)
0.20 10-12
>985
240
Weight: 114lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 BOT CHORD
REACTIONS. (lb/size) 9=618/Mechanical, 13=792/0-7-10
Max Harz 13=566(LC 12)
Max Uplift 9— 690(LC 12), 13— 726(LC 12)
Max Grav 9=694(LC 17), 13=792(LC 21)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 638/211, 2-3=-827/499, 3-5=-790/624
BOT CHORD 1 -13=-247/647,12-13=-9541786, 10-12=-844/604
WEBS 2-13= 557/870, 3-12=-157/332, 6-10= 520/594, 6-9=-771/920, 5-12=-2531310,
5-10= 556/822
Structural wood sheathing directly applied or 6-0-0 oc purlins,
except end verticals.
Rigid ceiling directly applied or 6-8-8 oc bracing.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft 8=60ft; L=60ft; eave=7ft; Cat.
Il; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 16-10-8, Extedor(2) 16-10-8
to 19-2-0 zone; cantilever left exposed ;C-C for members and forces & MW FRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) * This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Refer to girder(s) for truss to truss connections.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
9=690, 13=726.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE MI1-7473 rev. 1010312015 BEFORE USE.
Deslgn valid tot use only with MITeka connectors. This design is based only upon parameters shown. and Is for an Individual building component, hot
a truss system. Before use, the building designer must verify the applicability
building design. Bracing Indicated Is to prevent buckling of Indivlduail'truss
Is always required for stability and to prevent collapse wah possible personal
of design parameters and properly Incorporate this design Into the overall
web and/or chord members only. Additional temporary and permanent bracing
Injury and property damage. For general guidance regarding the
MiTek*
fabrlcatlon, storage, delivery, erection and bracing of trusses and truss
systems, seeANSUID11 QuaBtyCrCeda, DSB-89 and BCS1 BuBdhig Component
6904 Parke East Blvd.
Tampa, FL 33610
Safety Infomration3vailable from Truss Plate Institute, 218 N.'Lee Street,
Suite 312, Alexandria, VA 22314.
Job
Truss
Truss Type
Ply
HINKLERESIDENCE
T75290575
75546
M4
HALF HIP
�Qty
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:52 2018 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-G6xOEbri DOol?Lpfpg?sofGODkQsZFg5pOffymyVBJ L
19-2-0
2-3-13 6-9-12 12-3-2 18-10-8 _ 18-1u0
2-3-123 4-5-15 5-5.6 6-7.6 0-�-8
0-3-0 Scale = 1:46.1
5.00 ri2 6 7
m
I6
6
3x6 I 3x6 — ax4 US =
3x4 =
2-0-0 0- - 3 7-5-9
19-1-10
Plate Offsets (X Y)-- [1.0-2-0 Edge], [4.0-3-0 Edge]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) Well Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.60
Vert(LL) -0.18
8-9 >999 360
MT20 2441190
TCDL 7.0
Lumber DOL 1.25
BC 0.45
Vert(CT) -0.40
8-9 >497 240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.28
Horz(CT) -0.02
8 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Wind(LL) 0.18
8-9 >999 240
Weight: 97lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc puffins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 7-1-0 oc bracing.
WEBS
1 Row at midpt 6-8, 5-8
REACTIONS. (lb/size) 8=600/Mechanical, 11=79210-7-10
Max Horz 11=635(LC 12)
Max Uplift 8= 690(LC 12), 11=-695(LC 12)
Max Grav 8=752(LC 17), 11=792(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-668/178, 2-3=-882/447, 3-5=-7461337, 6-8=-174/352
BOT CHORD 1-11=-201/694, 9-11= 884/845, B-9=-701/622
WEBS 2-11= 622/897, 3-9=4521307, 5-9= 98/337, 5-8=-769/868
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.0psf; h=25ft; B=601t; L=60ft eave=7ft; Cat.
Ik Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-0-4 zone; cantilever left
exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load noncoricurrent with any other live loads.
3) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = IO.Opsf.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
8=690, 11=695.
Walter P. Finn PE No.22839
61iTek USA, Inc. FL Cart 0634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE.
Design valid for use only with MlTekV connectors. This design Is based only upon parameters shown, and is for on individual building component not
�'
Im
a truss system. Before use, The building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
Indicated Is to buckling Individual truss web and/or chord members only. Additional temporary and permanent bracing
6V1iTek*
building design. Bracing prevent of
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSUM11 Cuallly CAeda, DSO-69 and BCSI Buedfng Component
6904 Parke East Blvd.
Safety/ntotmaRorravallable from Truss Plate institute, 218 N. Lee Street, Suite 312, Alexandria. VA22314.
Tampa, FL 33610
Job
Truss
Truss Type
Uty
Ply
HINKLE RESIDENCE
T15290576
75546
M5
MONOPITCH
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MiTek Industries, Inc. I ue Oct 9 12:55:54 2018 rage 1
ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-CV3nfHszle2OEfz2w51 Kt4LjgX5L19BOGK81ceyVBJJ
6-9-12 12-3-2 12r7 10 18-11-0 19 2-0
6-9-12 5-5-6 0-4- 6-3-6 0j3t0
5.00 F12 g 7 Scale = 1:46.3
11 8
3x6 II 3x6 = 3x4 = 6x8 =
3x4 =
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0 '
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017/TP12014
CSI.
TC 0.61
BC 0.45
WB 0.28
Matrix -MS
DEFL. in
Vert(LL) -0.18
Vert(CT) -0.40
Horz(CT) -0.02
Wind(LL) 0.18
(loc) I/defl Ud
8-9 >999 360
8-9 >497 240
8 n/a n/a
8-9 >999 240
PLATES GRIP
MT20 244/190
Weight: 98lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 7-1-0 oc bracing.
OTHERS 2x4 SP No.3
WEBS
1 Row at midpt 6-8, 5-8
REACTIONS. (lb/size) 8=618/Mechanical, 11=792/0-7-10
Max Harz 11=648(LC 12)
Max Uplift 8=-728(LC 12), 11=-688(LC 12)
Max Grav 8=780(LC 17), 11=792(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-665/169, 2-3=-878/427, 3-5=-741/315, 6-8= 197/400
B01'CHORD 1-11= 191/690, 9-11= 890/846, 8-9=-696/621
WEBS 2-11= 620/887, 3-9— 153/313, 5-9— 104/337, 578= 768/863
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-2-0 zone; cantilever left
exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
8=728,11=688.
Walter P. Finn PE No.22839
MiTek USA, Inc, FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING- Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE MI1-7473 rev. 1010312015 BEFORE USE.
m
[�_-slgn valid for use only with MlTe',0 connectors. This design Is based of ly upon parameters shown, and Is for ai Individual building component, not
a truss system. Before use, the building designer must verify the applicabllity of design parameters and properly Incorporate this design Into the overall
buckling Individual only. Additional temporary and bracing
MOW
building design. Bracing Indicated Is to prevent of Muss web and/or chord members permanent
Is always required for stability and to prevent collapse with possible perrsonal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSfRPII GualOyCrlfeda, DSO-69 and SCSI Bu0dIngComponent
6904 Parke East Blvd.
Safety Infannallo►rovailabte from Truss Plate Insfitute, 218 N. Lee Street, Sulte 312, Alexancirla, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type +
City
Ply
HINKLE RESIDENCE
T15290577
75546
M6
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:55:56 2018 Page 1
ID:QGfzZgnsSSbOPbDkj8M4rOyXnLm-StBX4yuDGFI kUz7Q2W 3oyVR38LnoV3ghkedshXyV8JH
6-9-12 12-3-2 12-9-15 18-11-0 19; P,-0
6-9-12 5-5-6 0-6-1 6-1-1 0-3-0
5.00 FIT 6 7 Scale=1:46.2
1
0
0
11
8
3x6 11 3z6 =
3x4 =
6x8 =
3x4 =
2-0.0 2 - 3 9-9-6
18-11-0
2-0-0 0- - 3 7-5-9
9-1-10
Plate Offsets (X Y)-- (1:0-2-0 Edgef i4:0-3-0 EdgeI
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.61
Vert(LL) -0.18
8-9 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.45
Vert(CT) -0.40
8-9 >497 240
BCLL 0.0 '
Rep Stress Incr YES
WB 028
Horz(CT) -0.02
8 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Wind(LL) 0.18
8-9 >999 240
Weight: 97lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 7-1-0 oc bracing.
WEBS
1 Row at midpt 6-8, 5-8
REACTIONS. (lb/size) 8=614/Mechanical, 11=79210-7-10.
Max Horz 11=644(LC 12)
Max Uplift 8=-716(LC 12), 11=-690(LC 12)
Max Grav 8=776(LC 17), 11=792(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2— 665/172, 2-3=-879/433, 3-5= 741/321, 6-8= 192/390
BOT CHORD 1-11= 194/690, 9-11=-889/846, 8-9=-699/622
WEBS 2-11= 621/890, 3-9=-153/311, 5-9=-102/337, 5-8=-768/867
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
�I; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 19-1-0 zone; cantilever left
exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
3) * This truss has been designed for alive load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members, with BCDL = I O.Opsf.
4) Refer to girder(s) for truss to truss connections.
5) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Ot=lb)
8=716, 11=690. i
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE M11-7473 rev. 10/03=15 BEFORE USE.
Design valid for use only with MITeka connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into The overall
building design. Bracing indicated is to buckling of individual web and/or chord members only. Additional temporary and permanent bracing
M!Tek7
prevent (truss
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of Trusses and truss systems, seeANSUIPI f puaiHy CrBeda, DSB-69 and SCSI BuIldhig Component
6904 Parke East Blvd.
Satetyintormafonovailable from Truss Plate Institute, 218 N. Lee Street Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
tIty
Ply
HINKLE RESIDENCE
T15290578
75546
M7
HALF HIP
1
1
Job Reference o tional
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 11 2018 MI I eK industries, Inc. I ue vcl 9 12:55:bf 21118 Page 1
I D:QGfzZgnsSSbOPbDkj8M4rQyXn Lm-d4lvHlurl YRb57idbDb 1 VjzGZ150EOBgyl NQDzyV8JG
2-3-13 7-8-5 11-9-1 , 17-0-0 18-11-01�-2-0
2-3-13 5-4-8 4-0-12 5-2-15 1-11-0 0-3-0
4x8 = 3x4 11 Scale=1:43.7
5.00 F,2 6 7 8
12
"
9
3x4 = 3x6
5x6 =..
3x4 = 6x8 =
2.0-0 2- - 3 7-8-5
17.0-0
18-11-0
2-0-0 0- - 3 5-4-8
9-3-11
1-11-0
Plate Offsets (XY)--
f6.0-5-80-2-01 f11'0-2-40-3-01
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc)
Well
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC
0.50
Vert(LL)
-0.17 10-11
>999
360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC
0.55
Vert(CT)
-0.38 10-11
>521
240
BCLL 0.0 '
Rep Stress Incr YES
WB
0.77
Horz(CT)
-0.02 9
n/a
n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Wind(LL)
0.20 10-11
>992
240
Weight: 115lb FT=20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 BOT CHORD
REACTIONS. (lb/size) 9=618/Mechanical, 12=792/0-7-10
Max Horz 12=570(LC 12)
Max Uplift 9= 692(LC 12), 12=-724(LC 12)
Max Grav 9=697(LC 17), 12=792(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-638/211, 2-3=-828/503, 3-5— 778/603
BOT CHORD 1-12=-250/648, 11-12= 962r/88, 10-11= 824/592
WEBS 2-12= 559/879, 3-11= 162/330, 6-10= 533/603, 6-9— 776/923, 5-11=-250/316,
5-10= 564/827
Structural wood sheathing directly applied or 6-0-0 oc puffins,
except and verticals.
Rigid ceiling directly applied or 6-8-2 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Eiderior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 17-0-0, Exterior(2) 17-0-0 to
19-2-0 zone; cantilever left exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) Provide adequate drainage to prevent water ponding.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ` This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
9=692, 12=724.
Walter P. Finn PE No.22836
MiTek USA, Inc. FL Cert 6634
6004 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MIrEKREFERANCE PAGE 11111.7473 rev. 10/03/2015 BEFORE USE.
Design valid for use only with MlTe10 connectors. This design Is based only upon patameters shown, and is for an Individual beading component not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabricatlon, storage, delivery, erection and bracing of trusses and Truss systems, seeAMWMII QualifyCifedd, DSB-69 and BCSI Building Component 6904 Parke East Blvd.
Safety Informallonovallable from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314. Tampa, FL 33610
Job
Truss
Truss Type
City
Ply
HINKLE RESIDENCE
T15290579
75546
MS
HALF HIP
1
1
Job Reference o tional
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc.- Tue Oct 9 12:55:58 2018 Page 1
w ID:QGfzZgnsSSbOPbDkj8M4rQyXnLm-5GJ HVevTosZSjGGp9x6G1 wW PW 9P7ztx_By7zi PyVBJF
2-3-13 7-8-6 15-0-0 18-11-0 1-2-0
2-3-13 5-4-9 7-3-11 3-11-0 0-3-0
4x10 = 3x5 11 Scale = 1:40.1
4 5 c
3x4 = 2x3 II 2x3 I I ��" 3x4 = 6x8 =
2 0 0 0-r3-13 5-4-9 '
7-3-11
3-11-0
Plate Offsets (X Y)-- 13.0-3-0 0-3-41 (4.0-6-8 0-2-01
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) Well Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.61
Vert(LL) -0.14
8-10 >999 360
MT20 244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.65
Verl(CT) -0.29
8-10 >681 240
BCLL 0.0 '
Rep Stress Incr YES
WB 0.68
Horz(CT) -0.10
6 n/a n/a
BCDL 10.0
Code FBC2017/TP12014
Matrix -MS
Wind(LL) 0.26
8-10 >755 240
Weight: 104lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 5-8-0 oc bracing.
REACTIONS. (Ib/size) 6=-207/Mechanical, 7=826/Mechanical, 11=788/0-7-10
Max Harz 11=503(LC 12)
Max Uplift 6=-207(LC 1), 7=-807(LC 12), 11=-749(LC 12)
Max Grav 6=161(LC 12), 7=835(LC 17), 11=788(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-698/427, 2-3=-850/677, 3-4=-402/315, 5-7=-308/443
BOT CHORD 1 -1 1=-433/686, 10-11=-1075/810, 8-10=-10741810, 7-8=-462/351
WE13S 2-11= 463/793, 3-8=-509/674, 4-8— 286/397, 4-7= 689/904
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; 8=60ft; L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 15-0-0, Exterior(2) 15-0-0 to
19-1-4 zone; cantilever left exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Refer to girder(s) for truss to truss connections.
7) Refer to girder(s) for truss to truss connections.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except (jt=lb)
6=207, 7=807, 11=749.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING. Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEKREFERANCE PAGE 11411-7473 rev. 1010312015 BEFORE USE.
Design veld for use only with Mllek9 connectors. This design Is based only upon parameters shown, and Is for an Individualbuilding component, not
a Truss system. Before use, The building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
is to buckling Individual'itruss chord members only. Additional temporary and permanent bracing
{MiTek"
building design. Bracing Indicated prevent of web and/or
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSVM11 Dual lyCrBedo, DSB-89 and SCSI Building Component
6904 Parke East Blvd.
safety lntotmailotlavailabie from Truss Plate Institute, 218 N. Lee Street, Suite 312, Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type '
Qty
Ply
HINKLE RESIDENCE
T15290580
75546
M9
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.13o s mar 11 2u1 a MI I eK mousrnes, Inc. i ue Oci 9 i2:56:U0 2 i8 Pay e r
M ID:QGfzZgnsSSbOPbDkjeM4rQyXnLm-lfQ2wKxkKTpAzaQCHM8k6Lbmyy5ORIJGfFc4glyV8JD
2-3-13 7-8-5 13-0-0 18-11-0 16-7r0
2-3-13 5-4-8 5-3-11 5-11-0 0-3-0
4x8 = 3x4 II Scale = 1:35.2
5 6
3x4 = 3x6 11 2x3 11 -- 3x4 =^� —
2-0-0 0- - 3
5-4-8
5-3-11
5-11-0
Plate Offsets (X Y)--
l4.0-5-4 0-2-41
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/dell
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1,25
TC 0.55
Vert(LL)
-0.11
8-10
>999
360
MT20 2441190
TCDL 7.0
Lumber DOL
1.25
BC 0.60
Vert(CT)
-0.21
8-10
>931
240
BCLL 0.0 '
Rep Stress Incr
YES
WB 0.75
Horz(CT)
-0.02
7
n/a
n/a
BCDL 10.0
Code FBC20177TP12014
Matrix -MS
Wind(LL)
0.22
8-10
>907
240
Weight; 99 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3 BOT CHORD
REACTIONS. (lb/size) 7=618/Mechanical, 11=79210-7-10 .
Max Harz 11=436(LC 12)
Max Uplift 7= 641(LC 12), 11=-776(LC 12)
Max Grav 7=628(LC 17), 11=792(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 643/434, 2-3=-807/747, 3-4=-536/586, 5-7=-169/321
BOT CHORD 1-11= 465/638, 10-11=-10371745, 8-10=-1037/745, 7-8=-674/487
WEBS 2-11= 493/873, 3-8=310/430, 4-8= 236/342, 4-7— 654/900
Structural wood sheathing directly applied or 6-0-0 oc purlins,
except end verticals.
Rigid ceiling directly applied or 6-0-5 oc bracing.
NOTES-
1) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60ft eave=7ft Cat.
M; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 13-0-0, Exterior(2) 13-0-0 to
19-2-0 zone; cantilever left exposed ;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
2) Provide adequate drainage to prevent water ponding.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections. ,
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
7=641,11=776.
Walter P. Finn PE No.22639
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
October 9,2018
® WARNING - Vertly design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE.
Design voild for use only with tATek® connectors. This design I; based only upon parameters shown, and Is for an Individual building component, not
�
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
Is always required for stability and to prevent collapse wtih possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANSIRPII QualdfyCrBeda, DSO-69 and BCSI Bu®dtng Component
6904 Parke East Blvd.
Safety lnfomtaftotrovailable from Truss Plate Institute, 216 N. Lee Street, Suite 312. Alexandria, VA 22314.
Tampa, FL 33610
Job
Truss
Truss Type
Qty
Ply
HINKLE RESIDENCE
T15290581
75546
P
HALF HIP
1
1
Job Reference (optional)
Chambers Truss, Inc., Fort Pierce, FL 8.130 s Mar 112018 MiTek Industries, Inc. Tue Oct 9 12:56:01 2018 Page 1
L. I D:QGfzZgnsSSbOPbDkj8M4rQyXnLm-Vr_Q7gyM5nx1 ak?Og3fzfZ8tkMSUAA2QtvLdMkyV8JC
2-3-13 5-8-12 9-0-0 16-9-10 24-7-4 25-8-0 ,
2-3-13 3-4-15 3-3-4 7-9-10 7-9-10 1-0-12
5x12 MT1 BHS —
Scale=1:42.0
I
3x6 I,I
5x8, MT18HS = 6x8 =
5 1 c io 7 io a
3x4 = nxa — Oxv
2.0-0 2- 3 9-0-0 16.9-10 24-7-4
2-0-0 0- - 3 6-8-3 7-9-10 7-9-10
Plate Offsets (XY)-- f4:0-8-8 0-2-0) f6:0-4-0 Edgel f7:0-3-8,0-3-01, f9:Edge,0-3-81, f13:0-3-8,0-3-01
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) 1/,defl Ud
PLATES
GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.81
Vert(LL) 0.35
9-10 >761 240
MT20
244/190
TCDL 7.0
Lumber DOL 1.25
BC 0.54
Vert(CT) -0.16
9-10 >999 240
MT18HS
244/190
BCLL 0.0 '
Rep Stress Incr YES
WB 0.85
Horz(CT) -0.04
9 n/a n/a
BCDL 10.0
Code FBC2017/TPI2014
Matrix -MS
Weight: 129 lb
FT = 20%
LUMBER-
BRACING -
I
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural Wood sheathing directly applied or 6-0-0 oc purlins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3 *Except*
BOT CHORD
Rigid ceiljrig directly applied or 3-9-0 oc bracing.
7-9,4-10,7-10: 2x4 SP M 30
WEBS
1 Row at midpt 7-10
REACTIONS. (lb/size) 9=877/0-6-14, 13=998/0-7-10
Max Horz 13=302(LC 12)
Max Uplift 9=-1522(LC 12), 13=-1641(LC 12)
Max Grav 9=877(LC 1), 13=999(LC 21)
FORCES. (Ib) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 3-4=-1130/3151, 4-5=-1175/3303, 5-7=-1175/3303, 7-9=-807/2028
BOT CHORD 12-13=-2685/888, 10-12=-3003/1022
WEBS 3-12= 455/230, 4-12=-602/194, 4-1 0-337/249, 5-10= 471/806, 7-10= 3562/1257,
2-13=-240/452, 3-13=-114812845
NO'TES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft', L=60ft; eave=7ft; Cat.
II; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2) 0-0-0 to 6-0-0, Intedor(1) 6-0-0 to 9-0-0, Exterior(2) 9-0-0 to
17-5-13 zone; cantilever left exposed; porch left and right exposed;C-C for members and forces & MWFRS for reactions shown;
Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) All plates are MT20 plates unless otherwise indicated.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by;2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
9=1522, 13=1641.
Walter P. Finn PE No.22839
h7Tek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33810
Date:
October 9,2018
®WARNING - Vedly design parameters and READ NOTES ON THIS AND INCLUDED M/TEK REFERANCE PAGE 11,1II-7473 rev. 10/03)2015 BEFORE USE.
Design valid rot use only with MITe.0 connectors. This design Is based ordy upon parameters shown, and Is for on Individual building component not
�
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design Into the overall
building design. Bracing Indicated Is to buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek°
prevent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, seeANS&711 GualCyCi leda, DSB-89 and BCSI Bullding Component
Safety lnfolmallonavatlable from Truss Plate Institute, 218 N. Lee Street.! Suite 312. Alexandria, VA 22314.
6904 Parke East Blvd.
Tampa, FL 33610
Job
Truss
Truss Type •
Qty
Ply
HINKLE RESIDENCE
T15290582
75546
P1
HALF HIP
1
1
Job Reference (optional)
unamoers i russ, inc., I-orr melee, I-L
2-3-13 5-8-4
2-3-13 3-4-7
A
b.1dU s Mar l 1 zui b IVII I eK mausures, Inc. I ue uci u lz:bb:ud zui tl
5-3-12 6-9.10 6.9-10 ' 1-0-12
48 2x3 11
4 5 17
Scale=1:42.0
6x8 =
6 18 7
3x4 =
6x8 = 3x4 = '1Xb 3x10 = 4x6 11
2-0-0
11-0-0
LOADING (psf)
TCLL 20.0
TCDL 7.0
BCLL 0.0 '
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2017/TP12014
CSI. -
TC 0.60
BC 0.65
WB 1.00
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
in (loc) I/dell Ud
0.44 11-12 >598 240
-0.21 11-12 >999 240
-0.04 8 n/a n/a
PLATES GRIP
MT20 244/190
Weight: 134lb FT=20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc pudins,
BOT CHORD 2x4 SP M 30
except end verticals.
WEBS 2x4 SP No.3 *Except'
BOT CHORD Rigid ceiling directly applied or 3-3-5 oc bracing.
6-8: 2x4 SP M 30
WEBS
1 Row at midpt 6-9
REACTIONS. (lb/size) 8=877/0-6-14, 12=998/0-7-10
Max Harz 12=369(LC 12)
Max Uplift 8=-1535(LC 12), 12=-1628(LC 12)
Max Grav 8=877(LC 1), 12=999(LC 21)
FORCES. (lb) -Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 1-2= 126/328, 2-3= 112/365, 3-4=-1083/2952, 4-5=-878/2477, 5-6=-878/2477,
• 6-8=-815/2109
BOT CHORD 1-12=-273/99, 11-12=-2834/910, 9-11= 2870/951
WEBS 4-11=-875/272, 4-9=-109/483, 5-9=-412/714, 6-9= 2937/1036, 3-12=-1150/2632
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-10; Vult=170mph (3-second gust) Vasd=132mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=60ft; L=60fh eave=7fh Cat.
11; Exp D; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2) 0-0-0 to 6-0-0, Interior(1) 6-0-0 to 11-0-0, Exterior(2) 11-0-0 to
19-5-13 zone; cantilever left exposed ; porch left and right exposed;C-C for members and forces & MW FRS for reactions shown;
Lumber DOL=1.60 plate grip DOL=1.60
3) Provide adequate drainage to prevent water ponding.
4) This truss has been designed for a 10,0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by2-0-0 wide
Will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except at=lb)
8=1535, 12=1628.
Walter P. Finn PE No.22839
MiTek USA, Inc. FL Cart 8834
6904 Parke East Blvd. Tampa FL 33810
Date:
October 9,2018
0 WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED A11TEK REFERANCE PAGE MII-7473 rev. 1010312015 BEFORE USE.
'
Design valid for use only with MITel b connectors. This design Is based only upon parameters shown, and Is for an IndlVidudi buAdirg component, not
a Truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additlonal temporary and permanent bracing
MOW
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrlcailom storage, delivery, erection and bracing of trusses and Truss systems, seeANSVIP11 QualityCrItedo, DS"9 and BCSI Bugdlgq Component
6904 Parke East Blvd.
Safety lnformallanovailable from Truss Plate Institute, 218 N. Lee Street, Suite 312. Alexandrla, VA 22314.
Tampa, FL 33610
Symbols
PLATE LOCATION AND ORIENTATION
3�4 Center plate on joint unless x, y
offsets are indicated.
Dimensions are in ft-in-sixteenths.
Apply plates to both sides of truss
and fully embed teeth.
For 4 x 2 orientation, locate
plates 0-1116" from outside
edge of truss.
This symbol indicates the
required direction of slots in
connector plates.
'Plate location details available in MiTeir20120
software or upon request.
PLATE SIZE
The first dimension is the plate
4 x 4 width measured perpendicular
to slots. Second dimension is
the length parallel to slots.
LATERAL BRACING LOCATION
Indicated by symbol shown and/or
by text in the bracing section of the
output. Use T or I bracing
if indicated.
BEARING
Indicates location where bearings
(supports) occur. Icons vary but
reaction section indicates joint
number where bearings occur.
Min size shown is for crushing only.
Industry Standards:
ANSI/TPI1; National Design Specification for Metal
Plate Connected Wood Truss Construction.
DSB-89: Design Standard for Bracing.
BCSI:. Building Component Safety Information,
Guide to Good Practice for Handling,
Igstalling & Bracing of Metal Plate
Connected Wood Trusses.
Numbering System
6-4-8 1 dimensions shown in ft-in-sixteenths
(Drawings not to scale)
2 3
TOP CHORDS
8 7 6 5
JOINTSARE GENERALLYNUMBEREDAETTERED CLOCKWISE
AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO
THE LEFT.
CHORDS AND WEBS ARE IDENTIFIED BY END JOINT
NUMBERS/LETTERS
PRODUCT CODE APPROVALS
ICC-ES Reports:
ESR-1311, ESR-1352, ESR1988
ER-3907, ESR-2362, ESR-1397, ESR-3282
Trusses are designed for wind loads in the plane of the
truss unless otherwise shown.
Lumber design values are in accordance with ANSI/TPI 1
section 6.3 These truss designs rely on lumber values
established by others.
© 2012 MiTek® All Rights Reserved
,p
MiTek� .
MiTek Engineering Reference Sheet: MII-7473 rev. 10/03/2015
® General Safety Notes
Failure to Follow Could Cause Property
Damage or Personal Injury
1. Additional stability bracing for truss system, e.g.
diagonal or X-bracing, is always required. See BCSI.
2. Truss bracing must be designed by an engineer. For
wide truss spacing, individual lateral braces themselves
may require bracing, or alternative Tor I
bracing should be considered.
3. Never exceed the design loading shown and never
stack materials on inadequately braced trusses.
4. Provide copies of this truss design to the building
designer, erection supervisor, property owner and
all other Interested parties.
5. Cut members to bear tightly against each other.
6. Place plates on each face of truss at each
joint and embed fully. Knots and wane atjolnt
locations are regulated by ANSI/TPI 1.
7. Design assumes trusses will be suitably protected from
the environment in accord with ANSI/TPI 1.
8. Unless otherwise noted, moisture content of lumber
shall not exceed 19% at time of fabrication.
9. Unless expressly noted, this design is not applicable for
use with fire retardant preservative treated, or green lumber.
10, Camber is a non-structural consideration and is the
responsibility of truss fabricator. General practice is to
camber for dead load deflection.
11. Plate type, size, orientation and location dimensions
indicated are minimum plating requirements.
12. Lumber used shall be of the species and size, and
in all respects, equal to or better than that
specified.
13. Top chords must be sheathed or purlins provided at
spacing indicated on design.
14. Bottom chords require lateral bracing at 10 ft. spacing,
or less, if no ceiling Is installed, unless otherwise noted.
15, Connections not shown are the responsibility of others.
16. Do not cut or alter truss member or plate without prior
approval of an engineer.
17. Install and load vertically unless indicated otherwise.
18. Use of green or treated lumber may pose unacceptable
environmental, health or performance risks. Consult with
project engineer before use.
19. Review all portions of this design (front back words
and pictures) before use. Reviewing pictures alone
is not sufficient.
20. Design assumes manufacture in accordance with
ANSI/TPI 1 Quality Criteria.