HomeMy WebLinkAbout103434 Avalon by the Beach_CALCULATIONSWayne Automatic Fire Sprinkler Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 33442 954-917-3030 Job Name : Avalon Lot #7 Sheet Number : FP-3 Location : 132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Design Area : AREA #1 Contract : #103434 Data File : Area #1.WXF Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 1 Avalon Lot #7 Date 5/11/2021 HYDRAULIC CALCULATIONS for Project name:Avalon By The Beach Location:132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Drawing no:FP-3 Date:5/11/2021 Design Remote area number:AREA #1 Remote area location:Loft Occupancy classification:R-3 Density:.05 - Gpm/SqFt Area of application:2 Head Desig - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:Reliable (R3516) Semi-Recessed White Pendent No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams: - GPM Total water required (including hose streams):26.0 - GPM @ 54.9 - Psi Type of system:Wet (NFPA 13D) Volume of dry or preaction system:N/A - Gal Water supply information Date:4/30/2021 Location:Ocean Estates Drive & A1A Blvd Source:St. Lucie County Utlities Name of contractor:Wayne Automatic Fire Sprinklers, Inc. Address:1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442 Phone number:954-917-3030 Name of designer:Michael Crawford Authority having jurisdiction:St. Lucie County Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 2 Avalon Lot #7Date 5/11/2021 10203040E50R60U70S80S90E100R110P120130140150100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 63 C2 - Residual Pressure: 30 C2 - Residual Flow : 900 D1 - Elevation : 8.445 D2 - System Flow : 26.036 D2 - System Pressure : 54.936 Hose ( Demand ) : _______D3 - System Demand : 26.036 Safety Margin : 8.017 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 3 Avalon Lot #7Date 5/11/2021 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 E NFPA 13 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 00000111122345678101113 T NFPA 13 Tee Branch 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 U *CPVC 90' Elbow Tyco 0456791213000000000000 V *CPVC Tee Branch Tyco 03568101215000000000000 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 4 Avalon Lot #7 Date 5/11/2021 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 63.0 30 900.0 62.953 26.04 54.936 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes S1 22.0 4.9 7.0 12.96 S2 22.0 4.9 7.12 13.07 1 23.0 7.04 2 23.0 7.07 100 23.0 8.17 101 23.0 10.19 102 23.0 11.87 103 23.0 13.66 200 11.0 20.85 201 11.0 21.53 202 11.0 22.33 TR 11.0 23.78 BR -2.5 37.81 UG1 -2.5 39.06 BF1 3.0 36.76 BF2 -2.5 50.78 UG2 -2.5 50.87 M1 -2.5 56.98 TEE -2.5 57.09 TEST 2.5 54.94 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 5 Avalon Lot #7 Date 5/11/2021 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftngs Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqiv Len Total Pf Pn S1 12.96 0.874 U 4.0 1.000 7.000 K Factor = 4.90 to 150.0 0.0 4.000 -0.433 1 12.96 0.0940 0.0 5.000 0.470 Vel = 6.93 0.0 12.96 7.037 K Factor = 4.89 S2 13.07 0.874 V 3.0 1.000 7.117 K Factor = 4.90 to 150.0 0.0 3.000 -0.433 2 13.07 0.0955 0.0 4.000 0.382 Vel = 6.99 0.0 13.07 7.066 K Factor = 4.92 1 11.08 0.874 3U 12.0 53.750 7.037 to 150.0 V 3.0 15.000 0.0 102 11.08 0.0703 0.0 68.750 4.830 Vel = 5.93 0.0 11.08 11.867 K Factor = 3.22 1 1.88 0.874 0.0 11.000 7.037 to 150.0 0.0 0.0 0.0 2 1.88 0.0026 0.0 11.000 0.029 Vel = 1.01 2 13.07 0.874 V 3.0 6.000 7.066 to 150.0 0.0 3.000 0.0 100 14.95 0.1223 0.0 9.000 1.101 Vel = 7.99 100 0.0 0.874 U 4.0 12.500 8.167 to 150.0 0.0 4.000 0.0 101 14.95 0.1223 0.0 16.500 2.018 Vel = 7.99 101 0.0 0.874 V 3.0 10.750 10.185 to 150.0 0.0 3.000 0.0 102 14.95 0.1223 0.0 13.750 1.682 Vel = 7.99 102 11.09 0.874 U 4.0 1.250 11.867 to 150.0 0.0 4.000 0.0 103 26.04 0.3413 0.0 5.250 1.792 Vel = 13.93 103 0.0 1.101 U 5.0 13.000 13.659 to 150.0 0.0 5.000 5.197 200 26.04 0.1108 0.0 18.000 1.995 Vel = 8.78 200 0.0 1.101 V 5.0 1.083 20.851 to 150.0 0.0 5.000 0.0 201 26.04 0.1108 0.0 6.083 0.674 Vel = 8.78 201 0.0 1.101 V 5.0 2.250 21.525 to 150.0 0.0 5.000 0.0 202 26.04 0.1109 0.0 7.250 0.804 Vel = 8.78 202 0.0 1.101 U 5.0 8.083 22.329 to 150.0 0.0 5.000 0.0 TR 26.04 0.1108 0.0 13.083 1.450 Vel = 8.78 TR 0.0 1.101 Zik 0.0 10.000 23.779 to 150.0 2U 10.0 10.000 11.818 * * Fixed Loss = 5.971 BR 26.04 0.1108 0.0 20.000 2.217 Vel = 8.78 BR 0.0 1.598 3U 21.0 40.000 37.814 to 150.0 V 8.0 29.000 0.0 UG1 26.04 0.0181 0.0 69.000 1.246 Vel = 4.17 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 6 Avalon Lot #7 Date 5/11/2021 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftngs Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqiv Len Total Pf Pn UG1 0.0 2.067 E 5.0 6.000 39.060 to 120.0 0.0 5.000 -2.382 BF1 26.04 0.0078 0.0 11.000 0.086 Vel = 2.49 BF1 0.0 2.067 E 5.0 6.000 36.764 to 120.0 Zig 0.0 5.000 13.930 * * Fixed Loss = 11.548 BF2 26.04 0.0078 0.0 11.000 0.086 Vel = 2.49 BF2 0.0 2.067 E 5.0 6.000 50.780 to 120.0 0.0 5.000 0.0 UG2 26.04 0.0077 0.0 11.000 0.085 Vel = 2.49 UG2 0.0 2.047 G 1.441 5.000 50.865 to 150.0 T 14.412 15.853 6.000 * * Fixed Loss = 6 M1 26.04 0.0054 0.0 20.853 0.113 Vel = 2.54 M1 0.0 2.047 G 1.441 10.000 56.978 to 150.0 V 10.0 11.441 0.0 TEE 26.04 0.0054 0.0 21.441 0.116 Vel = 2.54 TEE 0.0 6.34 2E 46.217 200.000 57.094 to 140.0 T 49.518 100.687 -2.166 TEST 26.04 0.0 G 4.952 300.687 0.008 Vel = 0.26 0.0 26.04 54.936 K Factor = 3.51 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 33442 954-917-3030 Job Name : Avalon Lot #7 Sheet Number : FP-3 Location : 132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Design Area : AREA #2 Contract : #103434 Data File : Area #2.WXF Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 1 Avalon Lot #7 Date 5/11/2021 HYDRAULIC CALCULATIONS for Project name:Avalon By The Beach Location:132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Drawing no:FP-3 Date:5/11/2021 Design Remote area number:AREA #2 Remote area location:Bedroom #2 Occupancy classification:R-3 Density:.05 - Gpm/SqFt Area of application:1 Head Desig - SqFt Coverage per sprinkler:400 - SqFt Type of sprinklers calculated:Reliable (R3516) Semi-Recessed White Pendent No. of sprinklers calculated:1 In-rack demand:N/A - GPM Hose streams: - GPM Total water required (including hose streams):20.0 - GPM @ 56.9 - Psi Type of system:Wet (NFPA 13D) Volume of dry or preaction system:N/A - Gal Water supply information Date:4/30/2021 Location:Ocean Estates Drive & A1A Blvd Source:St. Lucie County Utlities Name of contractor:Wayne Automatic Fire Sprinklers, Inc. Address:1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442 Phone number:954-917-3030 Name of designer:Michael Crawford Authority having jurisdiction:St. Lucie County Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 2 Avalon Lot #7Date 5/11/2021 10203040E50R60U70S80S90E100R110P120130140150100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 63 C2 - Residual Pressure: 30 C2 - Residual Flow : 900 D1 - Elevation : 8.445 D2 - System Flow : 20.024 D2 - System Pressure : 56.860 Hose ( Demand ) : _______D3 - System Demand : 20.024 Safety Margin : 6.111 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 3 Avalon Lot #7Date 5/11/2021 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 E NFPA 13 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 00000111122345678101113 T NFPA 13 Tee Branch 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 U *CPVC 90' Elbow Tyco 0456791213000000000000 V *CPVC Tee Branch Tyco 03568101215000000000000 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 4 Avalon Lot #7 Date 5/11/2021 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 63.0 30 900.0 62.971 20.02 56.86 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes S3 22.0 4.9 16.7 20.02 3 23.0 17.32 1 23.0 18.04 2 23.0 18.17 100 23.0 18.28 101 23.0 18.49 102 23.0 18.66 103 23.0 19.76 200 11.0 26.18 201 11.0 26.6 202 11.0 27.09 TR 11.0 27.98 BR -2.5 41.0 UG1 -2.5 41.76 BF1 3.0 39.43 BF2 -2.5 52.83 UG2 -2.5 52.88 M1 -2.5 58.95 TEE -2.5 59.02 TEST 2.5 56.86 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 5 Avalon Lot #7 Date 5/11/2021 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftngs Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqiv Len Total Pf Pn S3 20.02 0.874 U 4.0 1.000 16.700 K Factor = 4.90 to 150.0 0.0 4.000 -0.433 3 20.02 0.2100 0.0 5.000 1.050 Vel = 10.71 0.0 20.02 17.317 K Factor = 4.81 3 4.32 0.874 3U 12.0 46.750 17.317 to 150.0 0.0 12.000 0.0 1 4.32 0.0123 0.0 58.750 0.721 Vel = 2.31 1 0.0 0.874 0.0 11.000 18.038 to 150.0 0.0 0.0 0.0 2 4.32 0.0124 0.0 11.000 0.136 Vel = 2.31 2 0.0 0.874 V 3.0 6.000 18.174 to 150.0 0.0 3.000 0.0 100 4.32 0.0122 0.0 9.000 0.110 Vel = 2.31 100 0.0 0.874 U 4.0 12.500 18.284 to 150.0 0.0 4.000 0.0 101 4.32 0.0123 0.0 16.500 0.203 Vel = 2.31 101 0.0 0.874 V 3.0 10.750 18.487 to 150.0 0.0 3.000 0.0 102 4.32 0.0123 0.0 13.750 0.169 Vel = 2.31 0.0 4.32 18.656 K Factor = 1.00 3 15.71 0.874 V 3.0 7.000 17.317 to 150.0 0.0 3.000 0.0 102 15.71 0.1339 0.0 10.000 1.339 Vel = 8.40 102 4.31 0.874 U 4.0 1.250 18.656 to 150.0 0.0 4.000 0.0 103 20.02 0.2099 0.0 5.250 1.102 Vel = 10.71 103 0.0 1.101 U 5.0 13.000 19.758 to 150.0 0.0 5.000 5.197 200 20.02 0.0682 0.0 18.000 1.228 Vel = 6.75 200 0.0 1.101 V 5.0 1.083 26.183 to 150.0 0.0 5.000 0.0 201 20.02 0.0682 0.0 6.083 0.415 Vel = 6.75 201 0.0 1.101 V 5.0 2.250 26.598 to 150.0 0.0 5.000 0.0 202 20.02 0.0681 0.0 7.250 0.494 Vel = 6.75 202 0.0 1.101 U 5.0 8.083 27.092 to 150.0 0.0 5.000 0.0 TR 20.02 0.0682 0.0 13.083 0.892 Vel = 6.75 TR 0.0 1.101 Zik 0.0 10.000 27.984 to 150.0 2U 10.0 10.000 11.647 * * Fixed Loss = 5.8 BR 20.02 0.0682 0.0 20.000 1.364 Vel = 6.75 BR 0.0 1.598 3U 21.0 40.000 40.995 to 150.0 V 8.0 29.000 0.0 UG1 20.02 0.0111 0.0 69.000 0.767 Vel = 3.20 UG1 0.0 2.067 E 5.0 6.000 41.762 to 120.0 0.0 5.000 -2.382 BF1 20.02 0.0047 0.0 11.000 0.052 Vel = 1.91 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 6 Avalon Lot #7 Date 5/11/2021 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftngs Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqiv Len Total Pf Pn BF1 0.0 2.067 E 5.0 6.000 39.432 to 120.0 Zig 0.0 5.000 13.342 * * Fixed Loss = 10.96 BF2 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 BF2 0.0 2.067 E 5.0 6.000 52.827 to 120.0 0.0 5.000 0.0 UG2 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 UG2 0.0 2.047 G 1.441 5.000 52.880 to 150.0 T 14.412 15.853 6.000 * * Fixed Loss = 6 M1 20.02 0.0033 0.0 20.853 0.069 Vel = 1.95 M1 0.0 2.047 G 1.441 10.000 58.949 to 150.0 V 10.0 11.441 0.0 TEE 20.02 0.0034 0.0 21.441 0.072 Vel = 1.95 TEE 0.0 6.34 2E 46.217 200.000 59.021 to 140.0 T 49.518 100.687 -2.166 TEST 20.02 0.0 G 4.952 300.687 0.005 Vel = 0.20 0.0 20.02 56.860 K Factor = 2.65 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 33442 954-917-3030 Job Name : Avalon Lot #7 Sheet Number : FP-3 Location : 132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Design Area : AREA #3 Contract : #103434 Data File : Area #3.WXF Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 1 Avalon Lot #7 Date 5/11/2021 HYDRAULIC CALCULATIONS for Project name:Avalon By The Beach Location:132 Ocean Estates Drive_Lot #7 Fort Pierce, Florida 34 Drawing no:FP-3 Date:5/11/2021 Design Remote area number:AREA #3 Remote area location:Outdoor Living Occupancy classification:R-3 Density:.05 - Gpm/SqFt Area of application:1 Head Desig - SqFt Coverage per sprinkler:400 - SqFt Type of sprinklers calculated:Reliable (R3516) Semi-Recessed White Pendent No. of sprinklers calculated:1 In-rack demand:N/A - GPM Hose streams: - GPM Total water required (including hose streams):20.0 - GPM @ 57.6 - Psi Type of system:Wet (NFPA 13D) Volume of dry or preaction system:N/A - Gal Water supply information Date:4/30/2021 Location:Ocean Estates Drive & A1A Blvd Source:St. Lucie County Utlities Name of contractor:Wayne Automatic Fire Sprinklers, Inc. Address:1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442 Phone number:954-917-3030 Name of designer:Michael Crawford Authority having jurisdiction:St. Lucie County Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 2 Avalon Lot #7Date 5/11/2021 10203040E50R60U70S80S90E100R110P120130140150100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 63 C2 - Residual Pressure: 30 C2 - Residual Flow : 900 D1 - Elevation : 3.248 D2 - System Flow : 20.024 D2 - System Pressure : 57.568 Hose ( Demand ) : _______D3 - System Demand : 20.024 Safety Margin : 5.403 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire SprinklerPage 3 Avalon Lot #7Date 5/11/2021 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 E NFPA 13 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 00000111122345678101113 T NFPA 13 Tee Branch 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 U *CPVC 90' Elbow Tyco 0456791213000000000000 V *CPVC Tee Branch Tyco 03568101215000000000000 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 4 Avalon Lot #7 Date 5/11/2021 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 63.0 30 900.0 62.971 20.02 57.568 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes S4 10.0 4.9 16.7 20.02 4 11.0 17.32 203 11.0 23.26 201 11.0 27.31 202 11.0 27.8 TR 11.0 28.69 BR -2.5 41.7 UG1 -2.5 42.47 BF1 3.0 40.14 BF2 -2.5 53.54 UG2 -2.5 53.59 M1 -2.5 59.66 TEE -2.5 59.73 TEST 2.5 57.57 Flow Summary - NFPA 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1 Wayne Automatic Fire Sprinkler Page 5 Avalon Lot #7 Date 5/11/2021 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftngs Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqiv Len Total Pf Pn S4 20.02 0.874 U 4.0 1.000 16.700 K Factor = 4.90 to 150.0 0.0 4.000 -0.433 4 20.02 0.2100 0.0 5.000 1.050 Vel = 10.71 0.0 20.02 17.317 K Factor = 4.81 4 20.02 0.874 U 4.0 21.333 17.317 to 150.0 V 3.0 7.000 0.0 203 20.02 0.2099 0.0 28.333 5.948 Vel = 10.71 203 0.0 0.874 0.0 19.250 23.265 to 150.0 0.0 0.0 0.0 201 20.02 0.2099 0.0 19.250 4.041 Vel = 10.71 201 0.0 1.101 V 5.0 2.250 27.306 to 150.0 0.0 5.000 0.0 202 20.02 0.0681 0.0 7.250 0.494 Vel = 6.75 202 0.0 1.101 U 5.0 8.083 27.800 to 150.0 0.0 5.000 0.0 TR 20.02 0.0682 0.0 13.083 0.892 Vel = 6.75 TR 0.0 1.101 Zik 0.0 10.000 28.692 to 150.0 2U 10.0 10.000 11.647 * * Fixed Loss = 5.8 BR 20.02 0.0682 0.0 20.000 1.364 Vel = 6.75 BR 0.0 1.598 3U 21.0 40.000 41.703 to 150.0 V 8.0 29.000 0.0 UG1 20.02 0.0111 0.0 69.000 0.767 Vel = 3.20 UG1 0.0 2.067 E 5.0 6.000 42.470 to 120.0 0.0 5.000 -2.382 BF1 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 BF1 0.0 2.067 E 5.0 6.000 40.141 to 120.0 Zig 0.0 5.000 13.342 * * Fixed Loss = 10.96 BF2 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 BF2 0.0 2.067 E 5.0 6.000 53.536 to 120.0 0.0 5.000 0.0 UG2 20.02 0.0047 0.0 11.000 0.052 Vel = 1.91 UG2 0.0 2.047 G 1.441 5.000 53.588 to 150.0 T 14.412 15.853 6.000 * * Fixed Loss = 6 M1 20.02 0.0034 0.0 20.853 0.070 Vel = 1.95 M1 0.0 2.047 G 1.441 10.000 59.658 to 150.0 V 10.0 11.441 0.0 TEE 20.02 0.0033 0.0 21.441 0.071 Vel = 1.95 TEE 0.0 6.34 2E 46.217 200.000 59.729 to 140.0 T 49.518 100.687 -2.166 TEST 20.02 0.0 G 4.952 300.687 0.005 Vel = 0.20 0.0 20.02 57.568 K Factor = 2.64 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Revision: 50.52.1