HomeMy WebLinkAboutProject InformationJob: 1282 Air Calcs, LLC Load Short Form Date: Jul 15, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7540 Hidden Hammock Ln, Vero Beach FL32966 Phone: 772.800.8413 Email:vcldlymne@aircals.com iL!roject intormation For: Thomas Residence, Air Conditioning Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34981 Design Information_ Htg Cig Infiltration Outside db (°F) 41 90 Method Simplified Inside db (°F) 70 75 Construction quality Average Design TD (°F) 29 15 Fireplaces 0 Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/Ib) 2 57 HEATING EQUIPMENT Make Trade . Model �AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 8.1 kW 27587 Btuh 18 OF 1367 cfm 0.050 cfm/Btuh 0.70 in H2O COOLING EQUIPMENT Make Goodman Mfg. Trade GOODMAN Cond GSX16S421A Coil ASPT49D14A AHRI ref 201785374 Efficiency 13.0 PER, Sensible cooling Latent cooling Total cooling Actual airflow Air flow factor Static pressure Load sensible heat ratio 16 SEER 28700 Btuh 12300 Btuh 41000 Btuh 1367 cfm 0.048 cfm/Btuh 0.70 in H2O 0.81 ROOM NAME Area (ft2) Htg load (Btuh) Cig load (Btuh) Htg AVF (cfm) CIgAVF (cfm) Bed 2 161 2281 1780 113 86 Bath 2 54 732 386 36 19 Lin 6 0 0 0 0 Hall 30 0 0 0 0 Bed 3 173 3095 2150 154 104 Family Room 185 4322 5511 215 266 Ktchen/Nook 215 1979 5092 98 246 Living Room 266 1967 4103 98 198 Laundry 77 539 888 27 43 Dining Room 108 2190 1884 109 91 Foyer 72 1155 607 57 29 Wtr Clst 28 1286 603 64 29 Linen 5 0 0 0 0 In— A7 771 1)F1 qp 1 MA lEO Calculations approved byACCAto meet all requirements of Manual J 8th Ed. 2020-Jul-16 08:13:40 -�- wrightsoft® fi-/B..bA4.WN.wryfamp Right RSU27054 Page 1 /jN�LryM ...oft HVA05313 S 25th St Thomas Res PSL Prop.rup Calc= MJ8 FrontDoorfaces: N iviaster twin Master Bedroom I/-y 217 I000 5505 0/-0 4222 00 274 It0 204 House d 1766 27488 28303 1367 1367 Other equip loads 1519 807 Equip. @ 0.95 RSM 27771 Latent cooling 7049 TP1TA1 0 470-L2 Donn7 qQA4a I AA7 1AF7 lJ I /1L0 I / V V -- Calculations -*- wrightsoft® rtaN/e.h,M1i.HVe��mp y RigM-Sute®Ur iversal 201919.020 RSU27054 / Iy/•\j•/1�1 ...oft WAC15313 S 25th St Thomas Res PSL Prop.rup Calc= MJ8 Frort Door faces: N 2020-Jul-16 08:13:40 Page 2 1282 Building Analysis Job: Jul Air Calcs, LLC 9 Y Date: Jul 15, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vicldlynm@aircalcs.com Project• • For: Thomas Residence, Air Conditioning Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34981 Design Conditions Location: Indoor: Heating Cooling St Lucie Cc Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2A 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Heating Component BtuhA2 Btuh % of load Walls 3.1 4597 15.8 Glazing 17.5 5887 20.3 Doors 3.7 148 0.5 Ceilings 0.9 1654 5.7 Floors 2.9 5103 17.6 Infiltration 2.0 3285 11.3 Ducts 6815 23.5 Piping 0 0 Humidification 0 0 Ventilation 1519 5.2 Adjustments 0 Total 290071 100.0 Cooling Component Btuh/ftz Btuh %ofload Walls 1.9 2752 9.5 Glazing 22.8 7641 26.3 Doors 3.7 150 0.5 Ceilings 0.8 1348 4.6 Floors 0 0 0 Infiltration 0.6 918 3.2 Ducts 7574 26.0 Ventilation 807 2.8 Internal gains 7920 27.2 Blower 0 0 Adjustments 0 Total 1 1 291101 100.0 Latent Cooling Load = 7049 Btuh Overall U-value = 0.112 Btuh/ftl °F Data entries checked. Intiltration Ducts nternal Gains wrightsoft® 2020-Jul-16 08:13:40 �._ •^� �� -«� - Right-Sute®Universal 201919.020 RSU27054 Page 1 ...oft HVAC15313 S 25th St Thomas Res PSL Prop rup Calc= MJ8 Frond Doorfaces: N Component Constructions Job: 1282 Air Cales, LLC Date: Jul 15, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: viddlynrie@alrcaics.com iwroject intormation For. Thomas Residence, Air Conditioning Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34981 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 28'N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U value Insul R Htg HTM Loss Clg HTM Gain ft' 8tuh&VF ft;°F/Btuh Btuh/ft' Btuh Btuhd2 Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8"Thk, 1/2" Gyp Bd Int Fnsh n 41 0.109 5.1 3.15 130 2.02 83 ne 300 0.109 5.1 3.15 944 2.02 604 se 208 0.109 5.1 3.15 654 2.02 419 sw 372 0.109 5.1 3.15 1172 2.02 750 nw 315 0.109 5.1 3.15 992 2.02 634 all 1235 0.109 5.1 3.15 3892 2.02 2490 Partitions Frm Wall, 1/2" Gyp.Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2'M", 16" 240 0.101 11.0 2.94 705 1.09 262 OC Stud Windows Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.21); n 39 0.650 0 18.8 726 11.9 459 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 14 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); ne 5 0.580 0 16.8 81 27.4 131 foreground = green grass (0.23); 1 ft overhang (1.2 ft Wndow ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); ne 16 0.580 0 16.8 262 22.3 347 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht sw 31 0.580 0 16.8 525 21.5 669 all 47 0.580 0 16.8 787 21.7 1017 Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); se 10 0.580 0 16.8 161 16.0 153 foreground = green grass (0.23); 6.6 ft overhang (1.6 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); se 41 0.580 0 16.8 686 21.7 886 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (6.8 ft window ht, 1 ft sep.); 9 ft head ht Impact, Clear Lowe, TEMP: Impact, Clear Lowe, TEMP; NFRC rated se 9 0.580 0 16.8 151 20.6 186 (SHGC=0.24); 50% blinds 45", medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3 ft window ht, 1 ft sep.); 6.8 ft head ht -rk wrightsoft® 2020Ju1-16 08:13*40 A ...�• ""�u.w� . w Right -Sate® Universal 2019 19.020 RSU27054 Page 1 oft HVAC15313 S 25th St Thomas Res PSL Prop.rup Cale= MJ8 Frond Doorfaces: N Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); sw 16 0.580 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 20 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.21); sw 40 0.650 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht Impact, TEMP, OBSC: Impact, TEMP, OBSC; NFRC rated (SHGC=0.24); sw 6 0.580 foreground = green grass (0.23); 1 ft overhang (3 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); nw 47 0.580 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); nw 16 0.580 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10 ft overhang (5.2 ft window ht, 3 ft sep.); 6.8 ft head ht nw 23 0.580 all 39 0.580 Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.21); nw 40 0.650 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 16 ft overhang (6.7 ft window ht, 3 ft sep.); 6.8 ft head ht Doors Door, and sctype: Fbrgls Door se 40 0.127 Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 1766 0.034 Floors On Grade Depth, Tile Ar Fnsh 178 0.989 0 16.8 262 13.4 209 0 18.8 747 22.0 871 0 16.8 101 25.1 151 0 16.8 787 22.3 1041 0 16.8 262 22.3 347 0 16.8 386 22.3 511 0 16.8 649 22.3 858 0 18.8 747 21.7 860 7.0 3.69 148 3.73 150 30.0 0.94 1654 0.76 1348 0 28.7 5103 0 0 t -114k wrightsoft® 2020-Jul-1608:13:40 �. ..,,•.•,o.�.•„m.��., , RightSute®Udversa1201919.020RSU27054 Paget ��...oft WAM313S25thStThomas Res PSLProp.rup C:alc=MJ8 FrontDoorfaces: N Pro ect Summa Job: Air Calcs, LLC J rY Jul 1 Date: Jul 5, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772:800.8413 Email: vicldlynne@aircalcs.com Project• • For: Thomas Residence, Air Conditioningg Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34951 Notes: Desi•n Information Weather: St Lucie Co Infl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 20674 Btuh Structure 20729 Btuh Ducts 6815 Btuh Ducts 7574 Btuh Central vent (48 cfm) 1519 Btuh Central vent (48 cfm) 807 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 29007 Btuh Use manufacturer's data n Rate/swingg multipplier Equipmentsensible load 0.95 27771 Btuh Infiltration Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2896 Btuh Ducts 2311 Btuh Central vent (48 cfm) 1842 Btuh Heating Cooling Outside air Area (ft2) 1766 1766 Equipment latent load 7049 Btuh Volume (T) 16274 16274 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 34819 Btuh Equiv. AVF (cfm) 103 54 Req. total capacity at 0.70 SHR 3.3 ton Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX16S421A AHRI ref Coil ASPT49D14A AHRI ref 201785374 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 8.1 kW Sensible cooling 28700 Btuh Heating output 27587 Btuh Latent cooling 12300 Btuh Temperature rise 18 OF Total cooling 41000 Btuh Actual airflow 1367 cfm Actual airflow 1367 cfm Airflowfactor 0.050 cfrnBtuh Airflowfactor 0.048 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. C -01-1- =10htac ft- 2020-Jul-16 08:13.40 r -�^• Right-Sate®Universal 2019 19.0.20 RSU27054 Page 1 iF .CsP� ...oft HVAQ5313 S 25th StThomas Res PSL Prop.rup Calc= MJ8 Front Door faces: N Air Calm, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Lr� Vero Beach, FL32966 Phone:772.800.8413 Email: viddlyrre@aircales.com 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area House 177.9 It 92 ft d 1765.8 ft' Bed 2 14.0 ft 8.1 ft heaV000l 1.0 x 161.3 ft 161.3 1112 Ty Construction number U-value (BtuhNN-°F) Or HTM (Btuh/ft') Area (fl or perimeter (ft) Load (Btuh) Area (T) or perimeter (ft) Load (Btuh) Heat T Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 yJ �G Blk Wall, Stucco Ext Impact, Clear Lowe Blk Wall, Stucco Ext Impact,Clear Lowe Impact,Clear Lowe Blk Wall, Stucco Ext Impact Clear Lowe Impact Clear Lowe Impact Clear Lowe, Door, v�dsctype Blk Wall, Stucco Ext Impact ClearLow-e Impact Clear Lowe ImpaaClearLowe Impact TEMP, OBSC Blk Wall, Stucco Ext Ie mpact,Clearl-ow Impai3,ClearLowe Impact, Clear Lowe Impact Clear Lowe Frm Wall, 1/2" Gyp.B 0.109 0.650 0.109 0.580 0.580 0.109 0.580 0.580 0.580 0.127 0.109 0.580 0.580 0.650 0.580 0.109 0.580 0.580 0.580 0.650 0.101 n n ne ne ne se se se se se sw sw sw sw sw nw nw nw nw nw - 3.15 18.85 3.15 16.82 16.82 3.15 16.82 16.82 16.82 3.69 3.15 16.82 16.82 18.85 16.82 3.15 16.82 16.82 16.82 18.85 2.94 2.02 11.92 2.02 27.37 2225 2.02 15.96 21.72 20.64 3.73 2.02 21.46 13.37 21.98 25.11 2.02 2225 2225 2225 21.70 1.09 80 39 320 5 16 307 10 41 9 40 464 31 16 40 6 440 47 -16 23 40 240 41 0 300 0 0 208 10 4 2 40 372 4 16 0 1 315 0 0 0 0 240 130 726 944 81 262 654 161 686 151 148 1172 525 262 747 101 992 787 262 386 747 705 83 459 604 131 347 419 153 886 186 150 750 669 209 871 151 634 1041 347 511 860 262 0 0 113 0 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 122 0 0 98 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 122 0 0 308 0 262 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 357 0 0 197 0 347 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 133 P C F Attic, Shngl Roof, R On Grade Depth, Tile 0.034 0.989 - - 0.94 28.68 0.76 0.00 1766 1766 1766 178 1654 5103 1348 0 161 161 161 14 151 402 123 0 6 c) AED excursion 819 -65 Envelope losstgain 17389 11891 1480 735 12 a) Infiltration 3285 918 231 65 b) Room ventilation 0 0 0 0 13 Internal gains. Occupants@ 230 4 920 0 0 Applianceslother 7000 500 Subtotal (lines 6 to 13) 20674 20729 1711 1300 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 5 4 14 Subtotal 20674 20729 1716 1303 15 Dud loads 33% 37% 6815 7574 33% 37% 566 476 Total roam load 27488 28303 2281 1780 Air required (cm) 1367 1367 113 86 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -!}�- wrigtitsoTte 2020-JU-16 08:13:40 RlghFSute@Universal2019 19.020 RSU27054 Page 1 ...oftHVAC15313S25thStThomasRes PSLProp.rup Calc=MJ8 FrontDoorfaces: N Air Calm, LLC Right-J® Worksheet Jab: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: \Acldlyrre@aireales.com 1 Room name Bath 2 Lin P B posed wall 6.0 It O ft 3 Room height 8.1 It heaUccol 8.1 It heaUeool 4 6 Room dimensions Room area 9.0 x 6.0 It 54.0 ft2 2.5 x 2.5 It 6.3 ft" Ty Construction number U-value (Btuh/11-7) Or HTM (Btuhfit2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool - Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 yJ G Blk Wall, Stu000 Ext Impact, Clear Lowe Blk Wall, Stu000 Ext 0.169 0.650 0.109 n n ne 3.15 18.85 3.15 2.02 11.92 2.02 0 0 49 0 0 44 0 0 138 0 0 88 0 0 0 0 0 0 0 0 0 0 0 0 \t7 11 Impact Clear Lowe Impact,. Clear Lowe Blk Wall, Stucco Ext Impact Clear Lowe Impact, Clear Lowe Impact, Clear Lowe, Door, vA sctype Blk Wall, Stucco E)d Impact, Clear Lowe Impact, Clear Lowe 0.580 0.580 0.169 0.580 0.580 0.580 0.127 0.109 0.580 0.580 ne ne se se se se se sw sw sw 16.82 16.82 3.15 16.82 16.82 16.82 3.69 3.15 16.82 16.82 27.37 22.25 2.02 15.96 21.72 20.64 3.73 2.02 21.46 13.37 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 81 0 0 0 0 0 0 0 0 0 131 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 G Impact Clear Lowe Impact TEMP, OBSC Blk Wall, Stucco Ext Impact,Clear Lowe Impact Clear Lowe 0.650 0.580 0.109 0.580 0.580 sw sw nw nw nw 18.85 16.82 3.15 16.82 16.82 21.98 25.11 2.02 2225 2225 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe Impact Clear Lowe Frm Wall,10 Gyp.B 0.580 0.650 0.101 nw nw 16.82 18.85 2.94 2225 21.70 1.09 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C Atfiq Shngl Roof, R 0.034 0.94 0.76 54 54 51 41 6 6 6 5 F On Grade Depth, Tile 0.989 28.68 0.00 54 6 172 0 6 0 0 0 6 c) AED excursion -14 0 Emelopeloss+gain 441 247 6 5 12 a) Infiltration 99 28 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 540 275 6 5 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 10 8 -6 -5 14 Subtotal 550 282 0 0 15 Ducloads 33% 37% 181 103 33% 37%1 0 0 Total room load 732 386 0 0 Airrequired (dm) 36 19 0 0 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- 2020-JLA-1 6 08:13:40 Right-Sute®Universal 201919.020 RSU27054 Page 2 oft HVAC\5313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Door faces: N Air Calcs, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicldlyrm@aircalcs.com 1 Room name Hall Bed 3 2 3 Exposed wall Room height 0 ft 8.1 ft heaV000l 27.5 ft 8.1 It heat/cool 4 5 Room dimensions Room area 3.5 x 8.5 It 29.8 ft2 1.0 x 172.5 ft 172.5 ft Ty Construction number U-value (Btuh/lf.- F) Or HTM (Btu Area (ft-) or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool 6 11 yJ �G Blk Wall, Sttic oo Ext Impac,Clear Low-e Blk Wall, Stucco EA Impad, Clear Lowe Impa4ClearLowe 0.109 0.650 0.109 0.580 0.580 n n ne ne ne 3.15 18.85 3.15 16.82 16.82 2.02 11.92 2.02 27.37 22.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 122 0 0 0 0 122 0 0 0 0 383 0 0 0 0 245 0 0 Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe 0.109 0.580 0.580 se se se 3A5 16.82 16.82 2.02 15.96 21.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe, Door, Msotype Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe 0.580 0.127 0.109 0,580 0.580 se se sw sw sw 16.82 3.69 3.15 16.82 16.82 20.64 3.73 2.02 21.46 13.37 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact Clear Lowe Impact TEMP, OBSC 0.650 0.580 sw sw 18.85 16.82 21.98 25.11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe 0.109 0.580 0.580 nw nw nw 3.15 16.82 16.82 2.02 9995 2225 0 0 0 0 0 0 0 0 0 0 0 0 101 16 0 86 0 0 270 262 0 173 347 0 Impact, Clear Lowe impact, Clear Lowe Frm Wall, 1/2" Gyp.B 0.580 0.650 0.101 nw nw 16.82 18.85 2.94 2225 21.70 1.09 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C Atfic, Shngl Roof, R 0.034 0.94 0.76 30 30 28 23 173 173 162 132 F On Grade Depth, Tile 0.989 28.68 0.00 30 0 0 0 173 28 789 0 6 c) AED excursion -1 45 Envelopeloss/gain 28 221 1865 941 12 a) Infiltration 0 0 454 127 b) Room ventilation 0 0 0 0 13 Internal gains: Oo ipants @ 230 0 0 0 0 Appliancesrother 0 500 Subtotal (lines 6 to 13) 28 22 2320 1568 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution -28 -22 8 7 14 Subtotal 0 0 2328 1574 15 Dudloads 33% 37% 0 0 33% 37%1 767 575 Total room load 0 0 3095 2150 Air required (cm) 0 0 154 104 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rw 2020-Jul-16 08:13:40 RightSute®Universal 2019 19.020 RSU27054 Page 3 oft HVAC15313S25thStThomas Res PSLProp.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynne@aircalcs.com 1 Room name Family Room Kitchen/Nook 2 Exposed wall 25.0 It 10.5 ft 3 Room height 10.1 It heal/coal 10.1 ft heat/cool 4 5 Room dimensions Room area 1.0 x 185.0 It 185.0 ft2 1.0 x 214.5 ft 214.5 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (BtuhAt2-°F) (Btu hAt2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool 6 yJ �(' Blk Wall, Stucco Bd Impact Clear Lowe Blk Wall, Stucco Ext 0.109 0.650 0.109 n n ne 3.15 18.85 3.15 Z02 11.92 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact Clear Lowe impact 0.580 0.580 ne ne 16.82 16.82 27.37 22.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impact, Clear Lowe Impact Clear Lowe 0.109 0.580 0.580 se se se 3.15 16.82 16.82 2.02 15.96 21.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact Clear Lowe, Door, v�d so type 0.580 0.127 se se 16.82 3.69 20.64 3.73 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impact Clear Lowe Impact Clear Lowe 0.109 0.580 0.580 sw sw sw 3.15 16.82 16.82 2.02 21.46 13.37 101 0 0 61 0 0 193 0 0 124 0 0 61 0 16 45 0 16 142 0 262 91 0 209 Impact Clear Lowe Impact TEMP, OBSC 0.650 0.580 sw sw 18.85 16.82 21.98 25.11 40 0 0 0 747 0 871 0 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impact Clear Lowe Impact Clear Lowe 0.109 0.580 0.580 nw nw nw 3.15 16.82 16.82 2.02 2225 2225 152 31 0 120 0 0 379 525 0 242 694 0 45 0 16 30 0 0 94 0 262 60 0 347 Impact Clear Lowe 0.580 nw 16.82 2225 0 0 0 0 0 0 0 0 lmpactClearl-owe Frm Wall,12' Gyp.B 0.650 0.101 nw 18.85 2.94 21.70 1.09 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 P C Attic, Shngl Roof, R 0.034 0.94 0.76 185 185 173 141 215 215 201 164 F On Grade Depth, Tile 0.989 28.68 0.00 185 25 717 0 215 11 301 0 6 c) AED excursion 1891 131 Envelope loss/gain 2735 2262 1263 1001 12 a) infiltration 515 144 216 60 b) Room ventilation 0 0 0 0 13 internal gains: Occupants@ 230 1 230 2 460 Appliancesrother 1400 2200 Subtotal (lines 6 to 13) 3249 4036 1479 3722 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 1 1 10 8 14 Subtotal 3251 4037 1489 3729 15 Ducloads 33% 37% 1072 1475 33% 37% 491 1362 al room load TTX.rt 4322 5511 1979 5092 required (dm) 215 266 98 246 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - - wr�gF�tsoTt� 2020-hd-16 08:13:40 Right-Sute®Universal2019 19.020 RSU27054 Page 4 ...oft HVAC15313 S 25th St Thomas Res PSL Prop rup Catc = MJ8 Front Doorfaces: N Air Calm, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email:,Acklynm@alrcalcs.com 1 Room name Living Room Laundry 2 3 Exposed wall Room height 7.5 It 10.1 ft heaU000l 0 ft 8.1 ft heatl000l 4 5 Room dimensions Room area 1.0 x 265.5 ft 265.5 ft' 7.0 x 11.0 ft 77.0 ft' Ty Construction number U-value (BtuhAt'--°F) Or HTM (Btuh/t') Area (ft') or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat C001 Gross NA'/S Heat Cool Gross NA'/S Heat Cool 6 V�! L- G Blk Wall; Stucco Ext impact; Clear Lowe Blk Wall, Stucco 6d mpact,ClearLowe pact mpact Clear Lowe im Blk Wall, Stucco Ext Impact, Clear Lowe Impact, Clear Lowe Impact Clear Lowe, Door, vdsctype Blk Wall, Stucco Ext impacLClear Lowe mpacttClear Lowe Impact Clear Lowe Impact, TEMP, OBSC Blk Wall, Stucco Ext Impact, Clear Lowe Impact Clear Lowe Impact Clear Lowe Impact, Clear Lowe Fmt Wall,1/2" Gyp.B 0.109 0.650 0.109 0.580 0.580 0.109 0.580 0.580 0.580 0.127 0.109 0.580 0.580 0.650 0.580 0.109 0.580 0.580 0.580 0.650 0.101 n n ne ne ne se se se se se sw sw sw sw sw nw nw nw nw nw 3.15 18.85 3.15 16.82 16.82 3.15 16.82 16.82 16.82 3.69 3.15 16.82 16.82 18.85 16.82 3.15 16.82 16.82 16.82 18.85 2.94 2.02 11.92 2.02 27.37 22.25 2.02 15.96 21.72 20.64 3.73 2.02 21.46 13.37 21.98 25.11 2.02 2225 2225 2225 21.70 1.09 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 76 0 0 0 40 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 36 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 114 0 0 0 747 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 73 0 0 0 860 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 113 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 113 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 333 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 124 P C F Attic, Shngl Roof, R On Grade Depth, Tile d.034 0.989 0.94 28.68 0.76 0.00 266 266 266 8 249 215 203 0 77 77 77 0 72 0 59 0 6 c) AED excursion 196 -33 Envelope loss/gain 1325 1332 405 150 12 a) Infiltration 154 43 0 0 b) Room ventilation 0 0 1 0 0 13 Internal gains. Occupants @ 230 1 230 0 0 Appliances/other 1400 500 Subtotal (lines 6 to 13) 1479 3005 405 650 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1479 3005 405 650 15 Ductloads 33% 37%1 488 1098 33% 37% 134 238 7 Total room load 1967 4103 539 888 Air required 98 196 27 43 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rr - 2020-Jd-16 08:13:40 RightSute®Universal 2019 19.020 RSU27054 Page 5 oft HVAC15313S25thStThomas Res PSLProp.rup Calc=MJ8 FrontDoorfaces: N Air Calcs, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicl4"@aircalcs.com 1 Room name Dining Room Foyer • 2 3 Exposed wall Room height 12.0 It 10.1 ft heaticool 8.0 It 10.1 ft heat/cool 4 5 Room dimensions Room area 12.0 x 9.0 ft 108.0 ft2 8.0 x 9.0 ft 72.0 ft2 Ty Construction number U-value (Btuh/t2-°F) Or HTM (Btuhflt2) Area (ft2) or perimeter (ft) Load (Btuh) Area 00) or perimeter ' (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VjJ �G Blk Wall, Stucco E)d Impact, Clear Lowe Blk Wall, Stucco Ext 0.109 0.650 0.100 n n ne 3.15 18.85 3.15 2.02 11.92 2.02 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 Impact, Clear Lowe Impact, Clear Lowe 0.580 0.580 ne ne 16.82 16.82 27.37 22.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impact, Clear Lowe ImpaaClear Lowe 0.1b9 0.580 0.580 se se se 3.15 16.82 16.82 2.02 15.96 21.72 121 0 41 80 0 4 253 0 686 162 0 886 81 10 0 31 10 0 98 161 0 62 153 0 Impad,Clear Lowe, Door, wdsotype 0.580 0.127 se se 16.82 3.69 20.64 3.73 0 0 0 0 0 0 0 0 0 40 0 40 0 148 0 150 Blk Wall, Stucco F-A Impact, Clear Lowe Impact, Clear Lowe 0.109 0.580 0.580 sw sw sw 3.15 16.82 16.82 2.02 21.46 13.37 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe Impact, TEMP, OBSC 0.650 0.580 sw sw 18.85 16.82 21.98 25.11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 VN Blk Wall, Stucco Ext Impact Clear Lowe Impac,Clear Lowe 0.109 0.580 0.580 nw nw nw 3.15 16.82 16.82 2.02 2225 2225 0 0 0 0 0 0 0 0 0 b 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe Impact, Clear Lowe Fmt Wall, 1t2" Gyp.B 0.580 0.650 0.101 nw nw - 16.82 18.85 2.94 2225 21.70 1.09 0 0 5 0 0 5 0 0 15 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 P C Attic, Shngl Roof, R 0,034 - 0.94 0.76 108 108 101 82 72 72 67 55 F On Grade Depth, Tile 0.989 - 28.68 0.00 108 12 344 0 72 8 229 0 6 c) AED excursion 175 -22 Envelope loss/gain 1400 1311 704 398 12 a) Infiltration 247 69 165 46 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 1647 1380 869 444 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1647 1380 869 444 15 Dud loads 33% 37% 543 504 33% 37% 286 162 Total room load 2190 1884 1155 607 Air required (cm) 109 91 57 29 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -ria- wrigtitsoTt® 2020-Jt9-l6 08:13:40 RightSute® Universal 201919.020 RSU27054 Page 6 ...oft WAM313 S 25th St Thomas Res PSL Propxup Calc= MJ8 Front Doorfaws: N Air Calm, LLC RighW@ Worksheet House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vialdlyme@alrcalcs.com Job: 1282 Date: Jul 15, 2020 By. Vicki Lynne Nisa 1 '2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Wtr Clst 11.5 ft 8.1 ft heaV000l 3.5 x 8.0 It 28.0 fN Linen 1.5 It 8.1 It heaUocol 3.5 x 1.5 It 5.3 ft' Ty Construction number U-value (BtuhA2_-F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (8tuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 y/ L Blk Wall, Stucco Ext Impact Clear Lowe Blk Wall, Stucco Ext Impac,ClearLowe Impact Clear Low-e Blk Wall, Stu000 Ext Impac,Clear Lowe Impad,Clear Lowe Impact, ClearLow-e, Door, wd sctype Elk Wall, Stuom Ext impac,Clear Lowe Impac,Clear Lowe Impact Clear Lowe Impac,TEMP,OBSC Elk Wall, Stucco bd ImpaaClear Lowe Impact Clear Love Impact Clear Lowe Impact, Clear Lowe Frm Wall,1i2" Gyp.B Attic, Shngl Roof, R On Grade Depth, Tile 0.109 0.650 0.109 0.580 0.580 0.109 0.580 0.580 0.580 0.127 0.109 0.580 0.580 0.650 0.580 0.109 0.580 0.580 0.580 0.650 0.101 0.034 0.989 n n ne ne ne se se se se se sw sw sw sw sw nw nw nw nw nw 3.15 18.85 3.15 16.82 16.82 3.15 16.82 16.82 16.82 3.69 3.15 16.82 16.82 18.85 16.82 3.15 16.82 16.82 16.82 18.85 2.94 0.94 28.68 2.02 11.92 2.02 27.37 22.25 2.02 15.96 21.72 20.64 3.73 2.02 21.46 13.37 21.98 25.11 2.02 2225 2225 2225 21.70 1.09 0.76 0.00 0 0 0 0 0 28 0 0 0 0 65 0 0 0 6 0 0 0 0 0 0 28 28 0 0 0 0 0 28 0 0 0 0 59 0 0 0 1 0 0 0 0 0 0 28 12 0 0 0 0 0 89 0 0 0 0 185 0 0 0 101 0 0 0 0 0 0 26 330 0 0 0 0 0 57 0 0 0 0 119 0 0 0 151 b 0 0 0 0 0 21 0 0 0 0 0 0 0 0 0 0 0 12 0 0 0 0 0 0 0 0 0 0 5 5 0 0 0 0 0 0 0 0 0 0 12 0 0 0 0 0 0 0 0 0 0 5 2 0 0 0 0 0 0 0 0 0 0 38 0 0 0 0 0 0 0 0 0 0 5 43 0 0 0 0 0 0 0 0 0 0 24 0 0 0 0 0 0 0 0 0 0 4 0 -G vN P C F 6 c) AED excursion 27 -2 Envelope loss/gain 732 375 86 27 12 a) Infiltration b) Room ventilation 190 0 53 0 25 0 7 0 13 Internal gains: Occupants @ 230 Appiianceslother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 921 428 111 34 14 j5 Less wdemal load Less transfer Redistribution Subtotal Ducloads 33% 37% 0 0 46 967 319 0 0 14 442 161 33% 37% 0 0 -111 0 0 0 0 -34 0 0 Total room load Air required (cm) 1286 64 603 29 0 01 0 0 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed. -P}i- w !R!Mtsoft- 2020-Jul-16 08:13:40 ^�^•" RightSuiteOUniversal201919.020RSU27054 Page7 oft HVAC15313S25thStThomasRes PSLProprup Calc=MJ8 From Door faces: N Air Calm, LLC Right-J® Worksheet House Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicldlynne@aircales.com Job: 1282 Date: Jul 15, 2020 By. Vicki Lynne Nisa 1 2 3 4 5 Room name E-,posed wall Room height Room dimensions Room area WIC 7.0 It 8.1 ft heat/mol 1.0 x 41.5 It 41.5 f' Master Bath 14.0 ft 8.1 ft heaU000l 1.0 x 128.8 ft 128.8 ft' Ty Construction number U-value (Btuh&t -F) Or HTM (Btuhllt2) Area (ft) or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross NAIS Heat Cool 6 11 VI/ �G Blk Wall, Stucco Ext Impact Clear Lowe Blk Wall, Stucco 6d Impact Clear Lowe Impact, Clear Lowe Blk Wall, Stucco E)d Impact, Clear Lowe Impact Clear Lowe Impact, Clear Lowe, Door, vd sctype Blk Wall, Stuoro Ext Impact Clear Lowe Impact, Clear Lowe Impact Clear Lowe Impact TEMP, OBSC Blk Wall, Stump Ext Impact,Clearl-owe mpac,Clear Lowe Impact, Clear Lowe Impact Clear Lowe Frm Wall,10 Gyp.B Attic, Shngl Roof, R On Grade Depth, Tile 0.109 0.650 0.109 0.580 0.580 0.109 0.580 0.580 0.580 0.127 0.109 0.580 0.580 0.650 0.580 0.109 0.580 0.580 0.580 0.650 0.101 0.034 0.989 n n ne ne ne se se se se se sw sw sw sw sw nw nw nw nw nw 3.15 18.85 3.15 16.82 16.82 3.15 16.82 16.82 16.82 3.69 3.15 16.82 16.82 18.85 16.82 3.15 16.82 16.82 16.82 18.85 2.94 0.94 28.68 2.02 11.92 2.02 27.37 22.25 202 15.96 21.72 20.64 3.73 2.02 21.46 13.37 21.98 25.11 2.02 2225 2225 2225 21.70 1.09 0.76 0.00 0 0 0 0 0 0 0 0 0 0 57 0 0 0 0 0 0 0 0 0 0 42 42 0 0 0 0 0 0 0 0 0 0 57 0 0 0 0 0 0 0 0 0 0 42 7 0 0 0 0 0 0 0 0 0 0 179 0 0 0 0 0 0 0 0 0 0 39 201 0 0 0 0 0 0 0 0 0 0 114 0 0 0 0 0 0 0 0 0 0 32 0 0 0 36 0 0 77 0 0 9 0 0 0 0 0 0 0 0 0 0 0 0 129 129 0 0 36 0 0 68 0 0 2 0 0 0 0 0 0 0 0 0 0 0 0 129 14 0 0 115 0 0 214 0 0 151 0 0 0 0 0 0 0 0 0 0 0 0 121 402 0 0 73 0 0 137 0 0 186 0 0 0 0 0 0 0 0 0 0 0 0 98 0 P C F 6 c) AED excursion -8 41 Envelope losssbain 418 137 1002 536 12 a) Infiltration b) Room ventilation 116 0 32 0 231 0 65 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 534 170 1234 600 Less external load 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 46 580 0 14 184 0 20 1253 0 6 606 15 Ducloads 33% 37% 191 67 33% 37%1 413 222 Total room load Air required (dm) 1 771 38 251 12 1 1666 1 83 828 40 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rld- wrigtitsoftm 2020-Jd-16 08:1340 • " Right-Sute®Universal 201919.020RSU27054 Page oft HVAC15313 S 25th St Thomas Res PSL Prop.rup Calc= MJ8 From Door faces: N Air Calcs, LLC Right-J® Worksheet Job: 1282 House Date: Jul 15, 2020 By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: v cldlynne@aircalcs.00m 1 Room name Master Bedroom -2 Exposed wall 33.4 It 3 Room height 9.4 It heaU000l 4 5 Room dimensions Room area 1.0 x 216.5 It 216.5 ft2 Ty Construclion number U-value (Btuh/ft2-"F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area or perimeter Load Heat 7 Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 �C Blk Wall, Stucco Ext Impac , Clear Low-e 0.109 0.650 n n 3.15 18.85 2.02 11.92 80 39 41 0 1w 726 83 459 Wall, Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 T-IBlk mpact,ClearLowe Impact, Clear Lowe 0.580 0.580 ne ne 16.82 16.82 27.37 22.25 0 0 0 0 0 0 0 0 Blk Wall, Stucoo.Ext ImpaaClear Lowe Impa4Clear Lowe 0.109 0.580 0.580 se se se 3.15 16.82 16.82 2.02 15.96 21.72 0 0 0 0 0 0 0 0 0 0 0 0 Impact, Clear Lowe, Door, wd so type 0.580 0.127 se se 16.82 3.69 20.64 3.73 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext Impac,Clear LmAe Impact, Clear Lowe 0.109 0.580 0.580 sw sw sw 3.15 16.82 16.82 2.02 21.46 13.37 169 31 0 138 4 0 435 525 0 278 669 0 Impact, Clear Lowe Impact, TEMP, OBSC 0.650 0.580 sw sw 18.85 16.82 21.98 25.11 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext ImpaaClearLow Impact Cleare Lowe 0.109 0.580 0.580 nw nw nw 3.15 16.82 16.82 2.02 2225 2225 66 0 0 43 0 0 135 0 0 86 0 0 Impact, Clear Lowe Impact, Clear Lowe Frm Wall, IQ" Gyp.B 0.580 0.650 0.101 nw nw 16.82 18.85 2.94 2225 21.70 1.09 23 0 0 0 0 0 386 0 0 511 0 0 P C Attiq Shngl Roof, R 0.034 0.94 0.76 217 217 203 165 F On Grade Depth, Tile 0.989 28.68 0.00 217 33 958 0 6 c) AED excursion 160 Envelope loss/gain 3498 2413 12 a) Infiltration 642 179 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13) 4140 3092 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 4140 3092 15 Duct loads 33% 37% 1365 1130 -T- Total room load 5505 4222 Air required (dm) 2741 204 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed. -- wrightsoR• 2020Jr9-16 08:13:40 Right-Sute@Uriversal 20l9 19.020 RSU27054 Page 9 oft HVAC45313 S 25th St Thomas Res PSL Prop.rup Calc = MJ8 Front Doorfaces: N Air Calcs, LLC Duct System Summary House Air Calm, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicdlynne@alrcalcs.com e-roject intormation For: Thomas Residence, Air Conditioning Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34981 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowestfriction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.509 / 0.191 in H2O 0.149 in/100ft 1367 cfm 469 Supply Branch Detail Table Job: 1282 Date: Jul 15, 2020. By. Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.509 / 0.191 in H2O 0.149 1n/100ft 1367 cfm Name Design (Btuh) Htg (cfm) Clg (cfM) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath 2 h 732 44 22 0.232 4.0 Ox 0 VI Fx 19.3 200.0 st1 Bed.2 h 2281 136 103 0.227 7.0 Ox 0 VI Fx 24.3 200.0 st1 Bed 3 h 3095 185 125 0.149 8.0 Ox 0 VI Fx 41.2 300.0 st4 Dining Room h 2190 131 109 0.243 7.0 Ox 0 VI Fx 9.4 200.0 st3 Family Room c 2756 129 160 0.155 8.0 Ox 0 VI Fx 29.4 300.0 st4 Family Room -A c 2756 129 160 0.153 8.0 Ox0 VIFx 33.8 300.0 st4 Foyer h 1155 69 35 0.213 5.0 OXO VIFx 38.9 200.0 st2 KitchendNook c 1697 39 98 0.237 6.0 Ox0 VIFx 14.4 200.0 st1 KitchanNook-A c 1697 39 98 0.153 6.0 OXO VIFx 32.3 300.0 st4 KitcheNNook-B c 1697 39 98 0.150 6.0 Ox 0 VI Fx 40.1 300.0 st4 Laundry c 888 32 51 0.244 4.0 Ox 0 VI Fx 8.9 200.0 SO Living Room c 2052 59 119 0.212 7.0 Ox 0 VI Fx 39.6 200.0 st2 Living Room -A c 2052 59 119 0 0 Ox 0 VI Fx 0 0 Master Bath h 1666 99 48 0.212 6.0 Ox0 VIFx 39.8 200.0 st2 Master Bedroom h 2752 164 122 0.205 7.0 Ox 0 VI Fx 48.6 200.0 st2 Master BedroorrrA h 2752 164 122 0.213 7.0 OX 0 VI Fx 39.0 200.0 st2 wic h 771 46 15 0.215 4.0 OXO VIFx 36.8 200.0 st2 wtr Gist h 1286 77 35 1 0.210 5.0 Ox 0 VI Fx 42.5 200.0 st2 • � ft wrightso® 2020-Jul-16 08:13:41 R�1 +R•NM1,���.�,�w�, Right -Sate® Universal 201919.020RSU27054 Pagel +�...oftWAC15313S25thStThomasRes PSLProp.rup Calc=MJ8 FrontDoorfaces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st4 PeakAVF 521 641 0.149 599 14.0 0 x 0 VinIFIX st1 st1 PeakAVF 740 864 0.149 809 14.0 0 x 0 VinIFIX st2 PeakAVF 678 496 0.205 863 12.0 0 x 0 VInIFIx st3 PeakAVF 163 161 0.243 609 7.0 0 x 0 VInIFIx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (Cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Mat Trunk rb4 Ox0 374 259 127.9 0.149 477 12.0 Ox 0 MFx rt1 rb3 Ox 0 185 125 85.4 0.224 529 8.0 Ox 0 MFx rt1 rb2 Ox 0 136 103 76.9 0.248 509 7.0 Ox 0 MFx rt1 rb1 Ox 0 886 1034 83.2 0.229 585 18.0 Ox 0 VIFx rt1 Return Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 1581 1521 0.149 725 20.0 0 x 0 VnIFIX Boldritalic values have been manually overridden -!}i- wrighftoft- �� AMn.ria.A.nuewm...r—,, RightStite®Uriversal 2019 19.0.20 RSU27054 / A...oft HVAC15313S25thStThomas Res PSLPropaup Calc=MJ8 Fron<Doorfaces: N 2020-JLA-16 08:13:41 Page 2 Manual S Compliance Report Job: 1282 Air Calks, LLC p p Date: Jul 15, 2020 House By. Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: %Addlyme@aircalm.com Project Information For. Thomas Residence, Air Conditioning Unlimited, LLC 5313 S 25th St, Fort Pierce, FL 34981 Design Conditions Outdoor design DB: 90.4°F Sensible gain: 29110 Btuh Entering coil DB: 76.5°F Outdoor design WB: 77.4°F Latent gain: 7049 Btuh Entering coil WB: 63.7°F Indoor design DB: 75.0°F Total gain: 36158 Btuh Indoor RH: 50% Estimated airflow: 1367 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer Goodman Mfg. Actual airflow: 1367 cfm Sensible capacity: 28700 Btuh Latent capacity: 12300 Btuh Total capacity: 41000 Btuh Model: GSX16S421A+ASPT49D14A 99% of load 175% of load 113% of load SHR: 70% Heating Equipment Design Conditions design DB: 41.07 Heat loss: 29007 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Manufacturer: Actual airflow: Output capacity: Elec strip Model: 1367 cfm 8.1 kW 95% of load -Meets all requirements ofACCA Manual S. Entering coil DB: 68.5°F Temp. rise: 50 OF wrightsoft- 2020-19-16 08:13:41 �/�ry AN,1eN/w,4htr�.bh.,M fomVe^Y Right-Sdte®Urrversal 2019 19.020 RSU27054 Page 1 ...oft HVAQ.5313S25thStThomasRes PSLProp.rup CaIc=MJB Front Door faces: N N 4 moo.�dn u ; Al D• 6� mdn ln:vmn-.. D'n1V Rmm r •�': LU w �a� �• .� C - -- 7 - .A ._ C FLOOR PLAN Job M 1282 Air Caics, LLC Scale: 1 : 243 Performed by Vicki Lynne Nisa for: Page 1 Thomas Residence 7550 Hidden Hammock Ln Right -Suite® Universal 2019 5313 S 25th St Vero Beach, FL 32966 19.0.20 RSU27054 Fort Pierce, FL 34981 Phone: 772.800.8413 2020-Jul-16 08:14:01 vickilynne@aircalcs.com ... 25th St Thomas Res PSL Prop.rup