HomeMy WebLinkAboutBuilding PlansSCOPE OF WORK NEW FIRELITE (ES-50X) FIRE ALARM SYSTEM WITH INITIATING DEVICES 8: NOTIFICATION APPLIANCES. NEW FIRE ALARM ANNUNCIATOR (ANN-80-A8). BUILDING IS NOT SPRINKLERED. THE NEW SYSTEM WILL INCLUDE: • SMOKE DETECTORS ABOVE FACP B THROUGH OUT THE FACILITY. • MANUAL PULL STATIONS WITHIN S OF EGRESS DOORS. • CEILING MOUNT STROBES IN RESTROOMS. • CEILING MOUNT HORN/STROBES THROUGH OUT THE FACILITY. THE NEW FIRE ALARM SYSTEM SHALL MONITOR & CONTROL ALL INITIATING DEVICES Ft NOTIFICATION APPLIANCES. THE NEW FIRE ALARM SYSTEM SHALL COMMUNICATE TO THE MONITORING STATION VIA LTE DIGITAL CELLULAR FIRE ALARM COMMUNICATOR. BUILDING INFORMATION USE & OCCUPANCY CLASSIFICATION BUILDING CONSTRUCTION TYPES • ASSEMBLY (A) O A-1 A-2 o A-3 O A-4 O A-5 TYPE 1 0 TYPE I -A 0 TYPE I-B 0 O BUSINESS (B) TYPE II 0 TYPE II -A O TYPE II-B 0 O EDUCATIONAL (E) TYPE III 0 TYPE III -A 0 TYPE III-B 0 0 FACTORY Et (F) INDUSTRIAL0 O F-1 O F-2 TYPE IV 0 TYPE IV-B 0 HIGH HAZARD (H) 0 H-1 0 H-2 0 H-3 0 H-4 0 H-5 TYPE V 01 TYPE V-A 0 TYPE V-B 0 0 INSTITUTIONAL (1) 01-1 0 1-2 0 1-3 0 1-4 0 1-5 AUTOMATIC SPRINKLER PROTECTION • MERCANTILE (M) NO 0 PARTIAL 0 FULL 1 0 RESIDENTIAL (R) 0 R-1 0 R-2 0 R-3 0 R-4 BUILDING AREA: 3,860 SQ.FT. 0 STORAGE (S) 0 S-1 O S-2 NUMBER OF FLOORS: 1 0 UTILITY 8: MISC. (U) OCCUPANT LOAD: FIRE ALARM CABLE LEGEND ID AWG COND SHIELD CLASS* ID AWG COND SHIELD CLASS* M 18 2 N FPLP B 18 2 Y FPLP C 18 4 N FPLP D 16 2 N FPLP E 16 2 Y FPLP F 16 4 N FPLP V 14 2 N FPLP H 14 4 N FPLP J 12 2 N FPLP K 12 4 N FPLP FIRE ALARM CABLE TOTAL LENGTH A 250 FEET (SLC CABLE) G 200 FEET (NAC CABLE) C 100 FEET (ANNUNCIATOR CABLE) DRAWING ACCEPTANCE THIS DRAWING IS TO BE USED ONLY FOR THE PURPOSE OF PLACING AND LOCATING JOHNSON CONTROLS EQUIPMENT AND IS NOT TO BE USED FOR ANY OTHER PURPOSES. IT IS THE RESPONSIBILITY OF THE LOCAL JOHNSON CONTROLS SALES Ft SERVICE OFFICE (SSO) TO REVIEW THE CONTENT OF THESE DRAWINGS FOR ACCURACY AND COMPLIANCE WITH LOCAL AND STATE CODES PRIOR TO RELEASING THEM TO THE FIELD. RECORD DRAWINGS ALL WORK PERFORMED IN THE FIELD SHALL BE ACCURATELY RECORDED ON THESE DRAWINGS AND RETURNED TO THE JOHNSON CONTROLS OFFICE AT THE ADDRESS LISTED ABOVE. MONITORING LOCATIONS JOHNSON CONTROLS ALARM SERVICE CO:360682-221 14200 EXPOSITION AVE. SERVICE CENTER NUMBER:768 AURORA, CO. 80012 UL LISTING: S949-183 1-800-428-7124 CODE ANALYSIS 2015- International Building Code 2015- International Fire Code 2014- National Electrical Code 2015- International Mechanical Code 2015- NFPA 101 Life Safety Code GENERAL NOTES 1 ALL APPLICABLE PERMITS SHALL BE OBTAINED PRIOR TO STARTING WORK. 2 WORK SHALL COMPLY WITH ALL APPLICABLE CODES. POWER (120VAC) TO ALL FIRE ALARM AND SECURITY PANELS SHALL BE SUPPLIED FROM DEDICATED, UNSWITCHED AND CLEARLY IDENTIFIABLE 3 SOURCES. 4 ALL DOORS WHICH ARE CONTROLLED BY ELECTRONIC LOCKING DEVICES SHALL BE CONFIGURED TO MEET ALL CODES. 5 ALL DEVICES EITHER INSTALLED WITHIN THE SCOPE OF THIS PROJECT OR AFFECTED BY THIS PROJECT SHALL BE TESTED. 6 ALL CABLE SHALL BE RATED FOR THE ENVIRONMENT IN WHICH IT 15 INSTALLED. 7 ALL WORK SHALL BE PERFORMED IN A PROFESSIONAL MANNER. 8 AREAS AFFECTED BY THE SCOPE OF THIS PROJECT SHALL BE KEPT CLEAN AND TRASH REMOVED DAILY. 9 FIRE ALARM CABLING SHALL NOT BE PAINTED. EXPOSED CONDUCTORS SHALL BE RUN ALONG CEILING JOISTS AND GIRDERS. ALL. WIRING TO BE CONCEALED FROM PUBLIC VIEW. EXPOSED WIRING 10 SHALL NOT BE RUN IN A"SPAN" FASHION BETWEEN BAR JOISTS OR GIRDERS. IF NECESSARY SUCH WIRING SHALL BE SECURED TO THE STRUCTURAL CEILING BETWEEN JOISTS OR GIRDERS. it EXPOSED WIRING TO BE SUPPORTED BY BUILDING STRUCTURE AT NO MORE THAN FIVE (5) FOOT INTERVALS. 12 ALL WIRING IN FINISHED AREAS SHALL BE CONCEALED. 13 ALL JUNCTION BOXES AND CABLE SPLICES SHALL BE IN ACCESSIBLE LOCATIONS. 14 ALL CABLE RUNS SHALL BE NEATLY BUNDLED, WRAPPED TIGHT AND PROPERLY SECURED. 15 CONTRACTOR RUNNING WIRE MUST MARK BOTH ENDS OF WIRE AND PROVIDE A WIRE LEGEND FOR ALL LOCATIONS. 16 ALL CABLING SHALL BE TAGGED AT ALL JUNCTION POINTS AND SHALL TEST FREE FROM GROUNDS OR CROSSES BETWEEN CONDUCTORS. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDE A MULTI -SYNC MODE SLAVE CONNECTION BETWEEN ALL 17 SYNC MODULES. PROVIDE INDEPENDENT CONTROL OF THE VISUAL AND AUDIBLE SIGNALS. 18 IF REQUIRED BY THE AHJ, PROVIDE SILENCING OF AUDIBLE DEVICES WHILE THE VISUAL DEVICES CONTINUE TO OPERATE. ALL SURFACE -MOUNTED NOTIFICATION APPLIANCES SHALL BE INSTALLED WITH DECORATIVE BACKBOX OR DECORATIVE SKIRT COVERING THE RACO 19 OR OTHER INDUSTRY -STANDARD BACKBOX. ALL CEILING -MOUNTED NOTIFICATION APPLIANCES TO BE INSTALLED ON THE BOTTOMS OF BEAMS OR JOISTS. STROBES SHALL BE VISIBLY 20 UNOBSTRUCTED. CEILING MOUNTED NOTIFICATION APPLIANCE LOCATIONS SHALL BE COORDINATED WITH THE MECHANICAL DUCTWORK TO AVOID VISUAL OBSTRUCTION. NOTIFICATION APPLIANCES THAT ARE VISIBLY OBSTRUCTED BY MECHANICAL DUCTWORK SHALL BE INSTALLED ON A THREADED 21 SUPPORT SUSPENDED BELOW THE BUILDING STRUCTURE AND SHALL BE AT AN ELEVATION TO PROVIDE UNOBSTRUCTED VISUAL NOTIFICATION BELOW THE MECHANICAL DUCT. 22 COORDINATE EXACT PLACEMENT OF ALL DEVICES WITH THE ARCHITECTURAL PLANS, OWNER, AND GENERAL CONTRACTOR PRIOR TO INSTALLATION. SMOKE DETECTORS SHALL BE MOUNTED ON CEILINGS AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE SMOKE DETECTORS A MINIMUM OF 23 THREE (3) FEET FROM MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. 24 SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL, PROVIDE CONNECTIONS TO WATER FLOW SWITCHES, SUPERVISORY VALVE TAMPER SWITCHES (SWITCHES PROVIDED BY OTHERS). PROVIDE CABLING 25 AND WIRING CONNECTIONS TO ALL SWITCHES. PROVIDE COORDINATION WITH THE SPRINKLER CONTRACTOR. PROVIDE DEDICATED 120VAC POWER TO FACP AND AUXILIARY POWER SUPPLIES. POWER SHALL BE PROVIDED BY AND COORDINATED WITH THE 26 ELECTRICAL CONTRACTOR. CONDUCTORS MUST BE INSTALLED IN EMT CONDUIT. LABEL THE DEDICATED CIRCUIT BREAKER(S) "FIRE ALARM CIRCUIT." ALL REMOTE BOOSTER POWER SUPPLIES CONNECTED TO A DEDICATED CIRCUIT BREAKER(S) SHALL BE LABELED AND TESTED IN THE OFF POSITION AS 27 PART OF THE 24-HOUR BATTERY TEST PERFORMED. 28 PROVIDE LOCKOUT TAG(S) FOR ALL CIRCUIT BREAKERS FOR THE FIRE ALARM SYSTEM(S). MOUNT THE FIRE ALARM CONTROL PANEL AND AUXILIARY POWER SUPPLIES. COORDINATE EXACT LOCATION WITH THE OWNER PRIOR TO 29 INSTALLATION. THE DIGITAL ALARM COMMUNICATION TRANSMITTERS (DACT) SHALL CLEARLY IDENTIFY THE TRANSMITTED SIGNAL AS "WATER FLOW', "GENERAL 30 ALARM', AND "SUPERVISORY" OR'TROUBLE" AS A MINIMUM. HOLES IN WALLS OR FLOOR CUTS MADE DURING THE PERFORMANCE OF THIS WORK SHALL BE PATCHED SO AS TO COMPLETELY CONCEAL THE HOLES 31 AND CUTS WHERE THEY WOULD OTHERWISE BE EXPOSED TO VIEW. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING 32 OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 33 COORDINATE THE MONITORING OBLIGATION OF THE FIRE ALARM SYSTEM WITH THE LANDLORD AND APPLICABLE CODES. IN NO CASE SHALL THE CONDUCTORS WITHIN METALLIC RACEWAY EXCEED 40% FILL. IN SUCH SITUATIONS LARGER SERIES WIRE MOLD OR OTHER 34 CONDUIT SHALL BE USED. 35 ALL WORK WILL FOLLOW CURRENT NEC STANDARDS FOR CONDUIT, GROUNDING, INSTALLATION OF WIRING AND WIRE TYPES. 7—ELEVEN, INC. UNITED STATES SHEET INDEX SHEET DESCRIPTION FA001 GENERAL SHEET FA101 DEVICE PLACEMENT PLAN FA201 RISER DIAGRAMS & SEQUENCE OF OPERATIONS FA301 PRODUCTTYPICALS FA401 POWER CALCULATIONS i MULTILEADERS TYPE DESCRIPTION ry �rY/x�J CABLE MULTILEADER v\-' REVISION MULTILEADER CA MULTILEADER: XX HEET NUMBER DETAIL/SHEET XXX XXX DEVICE MULTILEADER: XXXX XX XXX X SYSTEM-FLOOR/LEVEL-DEVICE NUMBERS DOOR/DETAIL NUMBERS TAGS TYPE DESCRIPTION Q CABLE ID TAG CABLE TAG CABLE TAG XXX-XX-XXX -XXX-X DEVICE TAG: SYSTEM TYPE/FLOOR-LEVEL/DEVICE NUMBER SHEET NUMBER/DETAIL # SHEET NOTE TAG IDENTIFIERS TYPE DESCRIPTION IDENTIFIER eELEVATION XX DETAIL/SHEET NUMBER SECTION IDENTIFIER: � DETAIL/SHEET NUMBER INITIATING DEVICE ADDRESSING LEGEND DEVICE ADDRESS J L1 :D_oo1 ADDRESSABLE DETECTOR NUMBERING DEVICE DESIGNATOR (D=DETECTOR, M-MODULE) ADDRESSABLE LOOP_F ADDRESSABLE MODULE NUMBERING L1:P-001 ADDRESSABLE POINT NUMBERING NOTIFICATION DEVICE ADDRESSING LEGEND CIRCUIT DESIGNATOR FIRE ALARM PANEL NAC 5r DEVICE DESIGNATOR FACPA-1 �/ STROBE. HORN ONLY. STROBE ONLY DEVICESTROBE. HORN ONLY. STROBE ONLY DEVICE NUMBERING r CIRCUIT DESIGNATOR NAC BOOSTER POWER SUPPLY �r DEVICE DESIGNATOR #=BmsterPanel Number NAC #:1-1 HORN / STROBE. HORN ONLY. STROBE ONLY DEVICE NUMBERING ABBREVIATIONS SYMB DESCRIPTION AC ALTERNATING CURRENT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AMP AMPERE AUX AUXILIARY AWG AMERICAN WIRE GAUGE BEG BELOW FINISH GRADE BLDG BUILDING C CM CEILING MOUNTED CIRC CIRCUIT CL CENTER LINE C CHIME COND CONDUIT CO COMPANY DC DIRECT CURRENT DIA DIAMETER DN DOWN DWG DRAWING DEG DEGREE ELEC ELECTRICAL EA EACH EXT EXTERIOR EX EXISTING DEVICE EQUIP EQUIPMENT EC ELECTRICAL CONTRACTOR XP EXPLOSION PROOF FA FIRE ALARM FL FLOOR FT FEET GC GENERAL CONTRACTOR GND GROUND HW HARDWIRED H HIGH AUDIBLE SETTING ID IDENIFICATION IN INCHES KW KILOWATT LVL LEVEL L LOW AUDIBLE SETTING MAX MAXIMUM MIN MINIMUM MFR MANUFACTURER MNS MASS NOTIFICATION SYSTEM MTD MOUNTED N4 NEMA 4 - NON CORROSION -PROOF ENCLOSURE N4X NEMA 4-CORROSION-PROOF ENCLOSURE N12 NEMA 12 - SEALED ENCLOSURE ND NEW DEVICE NAC NOTIFICATION APPLIANCE CIRCUIT # NUMBER PNL PANEL PH 0 PHASE PS POWER SUPPLY QTY QUANITITY REQD REQUIRED SEC SECONDARY SLC SIGNAL LINE CIRCUIT TEMP TEMPERATURE TYP TYPICAL UPS UNINTERRUPTED POWER SUPPLY V VOLTAGE VAC VOLTAGE ALTERNATING CURRENT VDC VOLTAGE DIRECT CURRENT W WM WALL MOUNTED W WATTS WP WEATHERPROOF WG WIRE GUARD WD WIRELESS DEVICE W/ WITH FIRE ALARM SYMBOLS QTY SYMB DESCRIPTION MANUFACTURER BACK BOX MODEL/ PART NUMBER CSFML/UL 01 FACP FIRE ALARM CONTROL PANEL FIRELITE FACORY BACKBOX ES-50X UL624 01 FAA FIRE ALARM ANNUNCIATOR FIRELITE 2 GANG ANN-80-A8 S2424 01 DOC FIRE ALARM DOCUMENT BOX FIRELITE FACTORY BACKBOX 06-SS000672 ' 01 FAC FIRE ALARM COMMUNICATOR TELULAR FACTORY BACKBOX TG-7FS 5789 01 SS SURGE SUPPRESSOR D ITEK DK-D5-D50120240 02 ❑F FIRE ALARM PULLSTATION FIRELITE 2 GANG BG-12LX S711 06 OS SMOKE DETECTOR - PHOTOELECTRIC FIRELITE 2 GANG SD365 51059 01 AIM ADDRESSABLE INPUT MODULE FIRELITE 2 GANG MMF-300 52424 02. S ADDRESSABLE RELAY MODULE FIRELITE CRF-3D0 52424 02 p® ADDRESSABLE INPUT MODULE FIRELITE 2 GANG MMF-300 52424 02 ® RTS REMOTE TEST SWITCH SYSTEM SENSOR 1 GANG RTS151 KEY 52424 04 STROBE - CEILING MOUNTED SYSTEM SENSOR 2 GANG SCRL 55512 / 54011 04 # HORN/STROBE - CEILING MOUNTED SYSTEM SENSOR 2 GANG PC2RL S5512 /S4011 01 # Wp HORN/STROBE- WEATHERPROOF WALL MOUNTED SYSTEM SENSOR SELF BOX P2RK S5512 / 54011 01 ©F WATERFLOW SWITCH 02 VS TAMPER SWITCH Johnson Controls JOHNSON CONTROLS GLOBAL CENTER OF EXCELLENCE 1800 INTERNATIONAL PARK DRIVE STE 500 BIRMINGHAM AL 35243 STEVEN.JAREDI.DEVINE-EXT@JCI. COM (205) 940-7354 AESBL LICENSE # 1667 KEYPLAN: 14 GEBBENS DRAKE SCOTT, INC 9201 E 63rd STREET, SUITE 100 RAYTOWN,MISSOURI "133 (816)358-1/90 ENGINEERING FLORIDA COA #4630 LOG: DATE �Oaorri'1S FA DESIGN 0 a � o z o o V n N > ^e F Z JZ O (aj Z J Z 2 65 a. tt > r p Q Q w O uj Na=4 0 rn w rn W 0 � u' � S m Q N m V w 7-ELEVEN INC. a a a UNITED STATES I CTRL UNIT ANNUNCIATION I NOTIFICATION ETYI 9 6• B #" 3 +`Y :fitt i,".,�siay�r.�sfs'"c�+`"a§i#`�. II� ®®IIII1®®®®®IIiIIIII'®®III,IIII1IIII1 .. .r ��c� cp ST vl.��D 1.5A ACED g ck T E 'EN SIVI BY 0of. 73101NDRIO RD FORT PIERCE, FL 34951 DESIGNED BY: JARED DEVINE NICET-3- 139483 DRAWN BY: MEGHA CHECKED BY: JARED DEVINE NICET-3- 139483 JOB / CASE # SHOP DRAWINGS L T�®rj SHEET: 5 5�Tr�T 'V1 GENERAL SHEET FA001 I • I - I • I - I- I ,1-1-1 30" X 42" - ARCH Et SIZE LAST PRINTED: 4/7/2021 11:57:19 AM LAST SAVED BY: LUCASF FILE PATH: K:)2Un79//l2ULIDy/ /.UVYU\/`Lleven sav44-rA v2u1n-w24U2/ /.Owg N J c M1 a= S J I75EE �-M ml 9 u- IF I: U bO ? o z -:............................— .-- i C�1. \ \ � F C ; C - I �S41 _ =d 4.. \ FAA H hil; ❑s� E �. ., _-..-.-. m m ..__._ :.,.......mmma<o.�= -_ ` �+-L;..-5� '.__— :.....}'-- - -_—_ �-_ _ _ <�. G I 1 VS VS' _.: 103 €v : .. - c_ -.-.- .._ ____ r i— �. - �— {—_ .... . - -..-__ .....-.. ... `fi_- _ .—_ _ —._'� _-_— ......_.—__ __ __ ____ _— - - Al �- 0-31 — TO VAULT—� b _ 1 v Ati I --- I'm E on SHEET NOTES e A NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE q}q� ALARM". FIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. MONITOR MODULE TO BE INSTALLED FOR CELL COMMUNICATOR SUPERVISION. w� DEVICE PLACEMENT PLAN ] 0 "= A NED w SCALE: 1 /4' -l'-O" g SCALE: 1/4"=1'-0" (IN FEET) oE 0 2: 4' 8' as I••I•e•I•e•I••1 30' X 42"- ARCH E1 SIZE LAST PRINTED: 4/7/2021 11:57:22 AM LAST SAVED BY: LLICASF FILE PATH:K:\20215977\20215977.DWG\7-Eleven 38944-FA 020121-07240277.dwg GENERAL NOTES 1 ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2 WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS 3 UNLESS OTHERWISE NOTED; CEILING MOUNTED DEVICES ARE SPACED FOR CEILINGS FLAT SMOOTH 10' OR LESS 4 DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED. 5 ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 6 WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4'. 7 ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND 8 PERPENDICULAR TO THE BUILDING STRUCTURE: CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. INSTALLER MAY REROUTE IF. 9 NECESSARY, BUT NOTIFICATION DISTANCE SHALL NOT EXCEED LENGTHS PROVIDED IN VOLTAGE DROP CALCULATIONS. SLC SHALL NOT EXCEED PANELS MAX CAPABILITY. FIRE ALARM CABLE LEGEND ID AWG COND SHIELD CLASS* A IS N FPLP B 18 2 Y FPLP C 18 4 N FPLP D 16 2 N FPLP E 16 2 Y FPLP _ F 16 4 N FPLP G 14 2 N FPLP H 14 4 N FPLP J 12 2 N FPLP K 12 4 N FPLP FIRE ALARM CABLES TOTAL LENGTH A 250 FEET (SLC CABLE) G 200 FEET (NAC CABLE) C 100 FEET (ANNUNCIATOR CABLE) JOHNSON CONTROLS GLOBAL CENTER OF EXCELLENCE 1800 INTERNATIONAL PARK DRIVE STE 500 BIRMINGHAM AL 35243 STEVEN. JARE D 1. DEVI N E-EXT@J CI. COM (205) 940-7354 AESBL LICENSE # -1667 CENTER OF EXCELLENCE NETWORK INSTALLING CONTRACTOR: KEYPLAN: G 3BENS DRAKE SCOTT. INC 9201 E. 63rd STREET, SMITE 100 RAYTORTI, MISSOURI 64133 (816)358-1.790 ENGINEERING FLORIDA COA#4630 7-ELEVEN, INC. UNITED STATES 73101NDRIO RD FORT PIERCE, FL 34951 DESIGNED BY: JARED DEVINE NICET-3- 1394831 DRAWN BY: MEGHA CHECKED BY: JARED DEVINE NICET-3- 139 JOB / CASE # SHEET: DEVICE PLACEMENT PLAN a' �v `r E 6'( EmEL 85 =E LN FV o �a I • • •7 • • • I • t • 1 • t • 1 30" X 42" -ARCH E1 SIZE LAST PRINTED: 4/7/2021 11:57:23 AM LAST SAVED BY: LUCASF FILE PATH: 75 '� 15 15 15 75 C C C C V1-8 V1-7 V1-6 V1-5 V1-4 V1-3 V1-2 V1-1 RISER DIAGR SCALE: 1/8'=V-0" 1,s ( y Y`. h k s 15977\20215977.DW13\7-Eleven 38944-FA 02012107240277.dwg WP 185 V2-1 V Dedicated 120 VAC 20 Amp Cimuit(Locked) VJ I A ,enwc FAA Fire Lite I 4 ,N0 FFLP ES-50X FACP M1-1 M1-2 M1-3 M1-4 Llm I1 CELL uA. trees a.ad teWe UNIT Line-E t? mow. too-a�-na SS000672 Dedicated E20 VAC c.,•m 20 Amp Ci raai KLocked) M1-1-/5 M1-6 M1-7 M1-8 M1-9 M1-10 M1�-11 RISER DIAGRAM NOTE DEVICE WIRING SHOWN IS CONCEPTUAL. POINT TO POINT CONNECTIONS MAY VARY. REFER TO FLOOR PLANS FOR REQUIRED EQUIPMENT LOCATIONS. THE ELECTRICAL CONTRACTOR SHALL REFERENCE EQUIPMENT INSTALLATION DOCUMENTS, DRAWING TERMINATION DETAILS, AND RISEIR DIAGRAM FOR COMPLETE EQUIPMENT INSTALLATION. SHOULD ANY CONFLICT ARISE BETWEEN DESIGNED PLANS, BATTERY CALCULATIONS, VOLTAGE DROPS, AND ACTUAL INSTALLATION SHALL BE BROUGHT TO THE ATTENTION OF JCI IN WRITING UPON DISCOVERY AND PRIOR TO ELECTRICAL ROUGH. SHEET NOTES 1 NEW FIRE ALARM PANEL SHALL BE CONNECTED TO DEDICATED 120 VAC POWER. LABEL CKT BREAKER "FIRE ALARM'. 2 FIRE ALARM PANEL SHALL COMMUNICATE TO MONITORING STATION VIA SOLE PATH CELLULAR COMMUNICATION. 3 MONITOR MODULE TO BE INSTALLED FOR CELL COMMUNICATOR SUPERVISION. Z GENERAL NOTES 1 ALL ADDRESSABLE DEVICES REQUIRE SLC LOOP FROM THE FACP TO OPERATE. REFER TO RISER/ONE-LINE DIAGRAM FOR REFERENCE. 2 WIRE RUNS ARE DIAGRAMMATIC. ACTUAL INSTALLATION MAY VARY. CIRCUIT LENGTH SHALL NOT EXCEED DISTANCES PROVIDED IN VOLTAGE DROP CALCULATIONS. 3 UNLESS OTHERWISE NOTED; CEILING MOUNTED DEVICES ARE SPACED FOR CEILINGS FLAT SMOOTH 10' OR LESS 4 DEVICE LOCATIONS ARE APPROXIMATE, EXACT LOCATIONS SHALL BE FIELD VERIFIED. 5 ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED PER NEC ARTICLE 760 (NATIONAL ELECTRIC CODE). 6 WHERE CONDUIT IS REQUIRED, MINIMUM SIZE SHALL BE 3/4'. 7 ALL CABLES SHALL BE RUN UNEXPOSED THROUGHOUT THE ENTIRE CABLE PATH. OPEN RUN CABLES CONCEALED ABOVE CEILING OR UNDER FLOORS SHALL BE ROUTED UNIFORMLY AND 8 PERPENDICULAR TO THE BUILDING STRUCTURE. CABLES TURNS SHALL BE ROUTED AT 90 DEG. ANGLES TO THE BUILDING. NO DIAGONAL RUNS ARE PERMITTED. THE CIRCUIT PATHWAYS ARE DIAGRAMMATIC FOR EASE OF ILLUSTRATION. INSTALLER MAY REROUTE IF 9 NECESSARY, BUT NOTIFICATION DISTANCE SHALL NOT EXCEED LENGTHS PROVIDED IN VOLTAGE DROP CALCULATIONS. SLC SHALL NOT EXCEED PANELS MAX CAPABILITY. Johnson �t L: Controls JOHNSON CONTROLS GLOBAL CENTER OF EXCELLENCE 1800 INTERNATIONAL PARK DRIVE STE 500 BIRMINGHAM AL 35243 STEVEN.JAREDi. DEVINE-E)Cr@JCL COM (205) 940-7354 AESBL LICENSE # 1667 In CENTER OF EXCELLENCE NETWORK INSTALLING CONTRACTOR KEYPLAN: GIBBENS DRAKE SCOTT, INC 92DI E. 63td STREET, SWTE 100 RAYTOWN, A4SSOURI 64133 (816)358-1790 ENGINEERING FLORIDA COA 04630 ISSUE FA DESIGN 7-ELEVEN, INC. UNITED STATES 73101NDRIO RD FORT PIERCE, FL 34951 DESIGNED BY: JARED DEVINE NICET-3- 139483 DRAWN BY: MEGHA CHECKED BY: JARED DEVINE NICET-3- 139483 JOB / CASE # SHEET: RISER DIAGRAMS E SEQUENCE OF OPERATIONS x � CONDUIT PENETRATION U.L. C-AJ-1045 i 6 Ou 1 OR 2 HOUR RATED CONCRETE 3M FIRE BARRIER BLOCK WALL ASSEMBLY }T CP 25WB+ CAULK OR EQUAL PACKING MATERIAL J • ,. �. CONDUIT NOTES: 1 CONDUIT SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 2 THE ANNULAR SPACE BETWEEN CONDUIT AND PERIPHERY OF OPENING SHALL BE 0 TO 1-3/8" 3 MAXIMUM OF (1) CONDUIT PER FIRE TOP SYSTEM. PACKING MATERIAL - MINIMUM 4" THICKNESS OF MINIMUM 8 PCF MINERAL WOOL BATT INSULATION SHALL BE FIRMLY 4 PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL SHALL BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK MATERIAL. 5 CAULK MATERIAL - MINIMUM 1 /2" THICKNESS OF FILL MATERIAL SHALL BE APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL. FIRE ALARM - FIRE RATED CONCRETE BLOCKWALL SCALE: NTS BATTERY WIRING SHOULD BE AT LEAST 1 /4" APART FROM AC WIRES O 1 I &LI ■0 O BATTERY gT. �q 9 5 CONDUIT PENETRATION U.L. W-L-1001 CABLE PENETRATION U.L. W-L-3149 1 OR 2 HOUR RATED GYP. 3M FIRE BARRIER WALLBOARD ASSEMBLY CP 25WB+ CAULK OR EQUAL NOTES: i CONDUIT SHALL BE INSTALLED AT CENTER OF STUD CAVITY WIDTH AND SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. CAULK FILL MATERIAL SHALL COMPLETELY FILL ANNULAR SPACE BETWEEN CONDUIT AND WALL; AND WITH A WIDTH 2 OF 114 " DIAMETER BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT ITS EGRESS OF THE WALL. FOR CONDUIT 1" DIAMETER AND SMALLER, ANNULAR SPACE SHALL BE 0 TO 3/16". FOR CONDUIT 4" DIAMETER AND SMALLER, ANNULAR SPACE SHALL BE 0 TO 1-1 /2". 3 MAXIMUM OF (1) CONDUIT PER FIRE TOP SYSTEM. 4 CONSULT CURRENT U.L. FIRE RESISTANCE DIRECTORY FOR DETAILS. FIRE ALARM - FIRE RATED GPY. WALLBOARD SCALE: NTS NOTE: WHEN USING THIS SCHEME, THE USE OFTHE PRIMARY OR SECONDARY DIALER TO CONNECT TO TELCO IS WHAT DETERMINES WHETHER THE TG-7 IS MEANT TO WORK AS A BACK-UP OR PRIMARY COMMUNICATOR. FIRE ALARM - TELCO CONN THROUGH THE ALARM PANEL (BACK OR PRIMARY FIRE ALARM PANEL CONDUIT FIRE ALARM DISCONNECT FIRE ALARM - POWER DISCONNECT SCALE: NTS SCALE: NTS FLOW SWITCH CONDUIT DER SWITCH FROM LAST DEVICE FIRE ALARM - DEVICE WIRING SCALE: NTS BREAK WIRE DO NOT LOOP STROBE PRECEDING STROBE OR POWER SUPPLY 1 OR 2 HOUR RATED GYP WALLBOARD ASSEMBLY 3M FIRE BARRIER CP 25WB+ CAULK OR EQUAL CABLE OR CABLE BUNDLE NOTES: 1 CONDUIT SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 2 THE ANNULAR SPACE BETWEEN CABLE/CABLE BUNDLE AND PERIPHERY OF OPENING SHALL BE 0 TO 1". 3 MAXIMUM OF A 1" DIAMETER CABLE BUNDLE PER FIRESTOP SYSTEM. 4 CAULK MATERIAL - MINIMUM 5/8 "THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL. MINIMUM 1 /2" DIAMETER BEAD OF CAULK APPLIED AT THE CABLE/WALLBOARD INTERFACE AT POINT CONTACT LOCATION ON BOTH SIDES OF WALL. 5 CONSULT CURRENT U.L. FIRE RESISTANCE DIRECTORY FOR DETAILS. FIRE ALARM - FIRE RATED GPY. WALLBOARD NOTES: 1 CONDUIT SHALL BE USED FOR ALL EXPOSED FIRE ALARM CABLING INSTALLED BELOW JOISTS AND BEAMS. 2 CONDUIT SHALL BE A MINIMUM OF 3/4". FIRE ALARM -CEILING TO WALL TRANSITION AND OPEN WIRING SCALE: NTS \v� SCALE: NTS ��- WEATHERPROOF J-BOX / .WITH ELECTRICALLY SUPERVISED / COVER TAMPER e \ 1/2" WEATHERPROOF BOX SUPPORT (FS50-1C ARLINGTON OR EQUIVALENT) I� 1/2" X 36" RIGID CONDUIT FIRE ALARM PANEL CONDUIT TO DEDICATED LOCKED BRANCH CIRCUIT 120 VAC/20AMP SOURCE EOL RESISTOR AT LAST DEVICE STROBE/HORN FIRE RATED CABLE OR CONDUIT EOL RESISTOR y AT LAST DEVICE FIRE ALARM -STROBE -HORN/STROBE DEVICE WIRING SCALE: NTS BREAK WIRE DO NOT 100P PRECEDING HORN + OR POWER SUPPLY - BREAK WIRE DO NOT LOOP PRECEDING STROBE _ OR POWER SUPPLY NEXT HORN OR EOL NEXT STROBE OR EOL DISTRIBUTION PANEL DEDICATED LOCKED CIRCUIT BREAKER 4S JUNCTION BOX NOTES: 1 ALL CONDUIT SIZE WILL BE DETERMINED BY WIRE FILL. 2 ALL ELECTRICAL BOXES WILL BE DETERMINED BY CONDUIT SIZE AND WIRE FILL. FIRE ALARM - WATERFLOW Et BUTTERFLY TAMPER SWITCHES SCALE: NTS VISUAL APPLIANCE MOUNTING HEIGHT CONSIDERATIONS IN SLEEPING ROOMS: MIN DISTANCE IN SLEEPING ROOMS IS 24" (610mm) FROM CEILING TO TOP OF LENS FOR 1IOCD STROBES WITHIN 16' OF THE PILLOW. 177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING. THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER. CEILING STRUCTURE u¢erur000nnr DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA 72) FOR CEILING HEIGHTS LESS THAN 86", THE VISUAL LENS MOUNTING HEIGHTS SHALL BE WITHIN 6" OF THE CEILING _ 96" AFF MAX (RDA @ NFPA) 1 2 60" 96" AFF MAX (IBC) AFF MIN (IBC) Y 80" AFF MIN (ADA &NFPA) -� AUDIBLE/VISUAL Et VISUAL ONLY APPLIANCES SYNCHRONIZE MORE THAN TWO APPLIANCES THAN IN ANY FIELD OF VIEW --- A/C SUPPLY OR RETURN DIFFUSER 36 ///// vxx 48" AFF MAX (ADA & NFPA) ti 42" AFF MIN (ADA 5: NFPA) 4 TO EXIT DOOR 60" MAX C�- !ITCH J OCTAGON JUI V n FIRE ALARM - DROP CEILING Et J BOX SCALE: NTS AUDIBLE ONLY: NFPA 72 AUDIBLE APPLIANCE 6" MIN BELOW FINISHED CEILING 3 AUDIBLE ONLY: 90" MIN AFF i► 60" AFF TO CENTER _OF LCD DISPLAY WALL 12" a 5 Za .00 FINISHED FLOOR ` - •• d •,• . •4d.• .a .. TAG DESCRIPTION AUDIOVISUAL DEVICE 1 80" AFF MIN (ADA 8 NFPA) MEASUREMENTS SHOWN TO THE BOTTOM OF LEN 96" AFF MAX (ADA E NFPA) MEASUREMENTS SHOWN TO THE TOP OF LEN 80" AFF MIN (IBC) MEASUREMENTS SHOWN TO THE BOTTOM OF DEVICE 96" AFF MAX (IBC) MEASUREMENTS SHOWN TO THE BOTTOM OF DEVICE VISUAL DEVICE 2 80" AFF MIN (ADA Et NFPA) MEASUREMENTS SHOWN TO THE BOTTOM OF LEN 96" AFF MAX (ADA & NFPA) MEASUREMENTS SHOWN TO THE TOP OF LEN 80" AFF MIN (IBC) MEASUREMENTS SHOWN TO THE BOTTOM OF DEVICE 96" AFF MAX (IBC) MEASUREMENTS SHOWN TO THE BOTTOM OF DEVICE AUDIBLE DEVICE AUDIBLE ONLY: 90" MIN AFF (OTHER MOUNTING HEIGHTS SHALL BE PERMITTED BY THE AHJ PROVIDING IT MEETS THE SOUND LEVEL OUTPUT REQUIRED 3 AUDIBLE ONLY: NFPA 72 AUDIBLE APPLIANCE 6" MIN BELOW FINISHED CEILING WALL MOUNT APPLIANCE SHALL HAVE THEIR TOP ABOVE FINISHED FLOOR HEIGHT OF NOT LESS THAN 90" AFF TAG DESCRIPTION FIRE ALARM PULLSTATION 4 42" AFF MIN (ADA B NFPA) MEASUREMENTS SHOWN ARE TOP OF PULL HANDLE 48" AFF MAX (ADA B: NFPA) MEASUREMENTS SHOWN ARE TOP OF PULL HANDLE FIRE ALARM CONTROL PANEL 5 FIRE ALARM PANEL: INSTALL FIRE ALARM CONTROL PANEL 60" MIN AFF 8 72" MAX TO CENTER OF LCD DISPLAY THE OPERABLE PART OF FIRE ALARM CONTROL PANEL SHALL NOT BE LESS THAN 60" MIN Et 72" MAX TAG DESCRIPTION SMOKE DETECTOR 6A 12" MEASUREMENT SHOWN TO THE CLOSEST EDGE OF THE DETECTOR HEAT DETECTOR 68 1 12" MEASUREMENT SHOWN TO THE CLOSEST EDGE OF THE DETECTOR SMOKE DETECTOR 7A 36" MIN MEASUREMENTS SHOWN TO THE CLOSEST EDGE OF THE SMOKE DETECTOR A/C SUPPLY OR RETURN DIFFUSER HEAT DETECTOR 7B 36" MIN MEASUREMENTS SHOWN TO THE CLOSEST EDGE OF THE SMOKE DETECTOR A/C SUPPLY OR RETURN DIFFUSER NOTES: FOR CEILINGS WITH BEAM DEPTHS OF LESS THAN 10% OF THE CEILING HEIGHT(0.1 H), SMOOTH CEILING SPACING SHALL BE PERMITTED. FOR CEILINGS WITH BEAM DEPTHS EQUAL TO OR GREATER THAN 10% OF THE CEILING HEIGHT (0.1 H) AND BEAM SPACING EQUAL TO OR GREATER THAN 40 % OF THE CEILING HEIGHT (0.4 H), SPOT -TYPE DETECTORS SHALL BE LOCATED ON THE CEILING IN EACH BEAM POCKET. 12" Controls JOHNSON CONTROLS GLOBAL CENTER OF EXCELLENCE 1800 INTERNATIONAL PARK DRIVE STE 500 BIRMINGHAM AL 35243 STEVEN.JARED 1.DEVINE-EXT@JCI.COM (205) 940-7354 AESBL LICENSE # 1667 CENTER OF EXCELLENCE NETWORK INSTALLING CONTRACTOR: KEYPLAN: 14 GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MISSOURI 64133 (816)358-1790 ENGINEERING FLORIDA COAp#4630 q n.�l/rmb ISSUEISSUE L0 MARK DATE TNT I DESCRIPTION 00 102/11/211 MB I FA DESIGN n FIRE ALARM - OSEtY TAMPER SWITCH GATE VALVE v I �� SCALE: NTS on I•�•I•�•I.1•I•�•I 30" X 42"- ARCH E1 SIZE LAST PRINTED: 4/7/2021 11:57:25 AM LAST SAVED BY: LUCASF FIRE ALARM - AUDIBLE DEVICE WIRING SCALE: NTS FILE PATH:K:\20215977\20215977.DWG\7-Eleven 38944-FA 020121-07240277.dwg FIRE ALARM - DEVICE MOUNTING HEIGHTS SCALE: NTS FA301 2 c E N If J Johnson a I' Controls JOHNSON CONTROLS GLOBAL CENTER OF EXCELLENCE 1800 INTERNATIONAL PARK DRIVE STE 500.. BIRMINGHAM AL 35243 STEVEN. JAREDI. DEVI NE-EXT@JCI.COM (205) 940-7354 AESBL LICENSE # 1667 CENTER OF EXCELLENCE NETWORK INSTALLING CONTRACTOR KEYPLAN: GIBBENS DRAKE SCOTT, INC 9201 E. 63rd STREET, SUITE 100 RAYTOWN, MiSSOURI 64133 (816) 358-1790 ENGINEERING FLOREDA COA #4630 ISSUE LOG: 7-ELEVEN, INC. UNITED STATES 7310 INDRIO RD FORT PIERCE, FL 34951 DESIGNED BY: JARED DEVINE NICET-3. 139483 DRAWN BY: MEGHA CHECKED BY: JARED DEVINE NICET-3- 139483 JOB / CASE # SHEET: POWER CALCULATIONS A _ m s= POWER CALCULATIONS ° A u € SCALE: FF O S 92 WWO 1 • 1 . 1 ... l . , . I ... 1 30" X 42" - ARCH E1 SIZE LAST PRINTED: 4/7/2021 11:57:26 AM LAST SAVED BY: LUCASF FILE PATH:'K:\20215 77120215977.DWG\7-Eteven 38944-FA 020121-07240277.dwg