HomeMy WebLinkAboutEvaluation Report; OSB & EPS Aluminium SkinOSB / EPS FOAM CORE COMPOSITE PANELS OSB / ALUMINUM SKIN EVALUATION REPORT MAXIMUM ALLOWABLE CLEAR SPAN TABLES: Total Load* Deflection Limit (U ) 4" Panels (Depth) 6" Panels De th 0.024" Alum Skin 1-LB EPS 0.030" Alum Skin 1-LB EPS 0.024" Alum Skin 1-LB EPS 0.030" Alum Skin 1-LB EPS 10 PSF 80 18'-W 20'-0" 22'-0" 24'-0" 120 17'5" 18'-11" 22'.0" 24'4' 180 15'-3" 16'-6" 19'-9" 21LT' 240 13'-10" 15'-0" 17'-11" 194' 15 PSF 80 17'5" 18'-11, 22,-0" 24'-0" 120 15'-3" 16'-6" 19'-9" " 21'-3 180 13'-3" 14'5" 17'-3" 18'-7" 240 12'-1" 13'-1" 15'-8" 18'-10" 20 PSF 80 15'-10" 17'-2" 20'-6" 22'-1" 120 13'-i0" 15'-0" 17'-11" IV-4" 1B0 12'-1" 13,_1" 15-8„ 16'_10" 240 10-12" 11'-11" 14'.3" 15-4" 25 PSF 80 14'-8" 15'-11" 191-0" 20'-6" 120 12'-10" 13'-11" 16'-7" 17'-11" 180 1 T-3" 12'-2" 14'-6" 15'-8" 240 10'-2" 11'-1" 13'-2" 14'-3" 30 PSF 80 13'-10" 15'-0" IT-11" 19'-4" 120 12'-1" 13'-1" 15'-8" 18'-10" 180 10'-7" 11'-5" 13'-B" 14'-9" 240 9W" 10'-5" 12'4' 13'-5" 35 PSF 80 13'-2" 14'-3" 17'-0" 18,4" 120 11'-6" 12-5" 14'-10" 16'-C" 180 10'-0" 10'-11" 12'-12" IT-12" 240 9'-1" 9'-11" 11'-10" 12'-9" 40 PSF 80 12L7" 13'-8" 16'.3" 17'-8" 120 10'-12" 11'-11" 14'.3" 15'4" 180 W-7" 101S" 12'4' 13'-5" 240 8'-8" 91S" 11-3" 12,-2" 45 PSF 80 12'-1" 13'-1" 15-8" 16'-10" 120 10'-7" 11'-5" 1 13-E 14'-9" 180 W-3" 10'-0" 1 11'-11" 12'-10" 240 8'4' 9'-1" 10'-1a, 1 11'-8" EPS ROOF PANEL SPAN DETAIL: 4' MAX WIDTH PER INTERLOCKING PANEL w i�" OS8 (2" PER FOOT MIN SLOPE) s 0°o r� 0. EPS CORE (1.0 PCF) 024" OR 0.030" ALUM SPAN (L) INSIDE TO INSIDE Deflection Total Limit Load* (U ) 4" Panels (Depth) 6" Panels (Depth) 0.024" Alum Skin 1-LB EPS 0.030" Alum Skin 1-LB EPS 0.024" Alum Skin 1-LB EPS 0.030" Alum Skin 1-1.6 EPS 50 PSF I 80 111-8" 12-8" 15'-1" 16'-3" 120 IV-2" 11'-1" 13'-2" 14'_3" 180 8'-11" 9.4. I V-6" 12'-5" 240 8'_1" 8'-9" 10'_6" 11,4" 55 PSF 80 11'-4" 12'-3" 14'-8" 15'4" 120 9'-10" 101-9" 12'-9" 13,_9" 180 1 8'-7" 9'-4" 1 V-2" 12'-0" 240 1 T-10" 8'-6" 1V-2" 10'11" 60 PSF BO IV-10" 11'-6" 14'-3" 15'-4" 120 V-7" IV-5" 12'-5" 13'-5" 180 814" 9'-1" 10'-101, 240 T-7" 8'-3" 9'-101, 10'.7" 65 PSF 80 101-0" 10'-7" 13-10" 14-11" 120 9'-4" 10'-2" 12'-1" 13'.0" 180 8,41 8'-10" 10'-7" 11'.5" 240 240 T5" IT 9-7" 10'4" 70 PSF 80 9'-4" 9'-10" 13'-5" 14'.0" 120 9'-1" 9'-10" 11'-10" IZ-9" 180 T-11" 8'-8" 10'.4" 11'-1" 240 7'-3" 7'40" 9-4" 10'-1" 75 PSF 80 8'-8" 9'-2" 12'-11" 13--1" 120 8'-8" 9'-2" 11'-6" IZ-5" 180 7'-9" 8'-5" 10'-1" 10'-10" 240 7-1" T-8" 9'-2" 9'-10" ! 80 PSF f 80 V-2" 8'-7" 12'-6" 12'4" 120 8'-2" 8'.7" 11'-3" 12,-2" 180 T-7" 8'-3" 9'-10" 10'-7" 240 6'-11" T-6" 8'-11" 9'4" *TOTAL LOAD = SUM OF ALL LOADS (WIND, LIVE, DEAD, ETC.) ACTING IN THE WORST CASE LOAD COMBINATION AS DETERMINED PER SEPARATE CERTIFICATION PANEL DEPTH MAXIMUM ALLOWABLE DESIGN PRESSURES: AS NOTED IN CLEAR SPAN TABLES DESIGN NOTES: oN 1. POSITIVE AND NEGATIVE DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL W M S i; S 4'54V'o' BE DETERMINED BY OTHERS ON A JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE STRUCTURAL REQUIREMENTS OF THE FLORIDA BUILDING' l.- rI o uui ��11 CODE SEVENTH EDITION (2020). N SITE -SPECIFIC PRESSURE REQUIREMENTS AS DETERMINED IN ACCORDANCE WITHg THE GOVERNING CODE SHALL BE LESS THAN OR EQUAL TO THE POSITIVE OR = ry2. W _ u NEGATIVE DESIGN PRESSURE CAPACITY VALUES LISTED HEREIN FOR ANY ASSEMBLY ii• ' w U x Z-� F> AS SHOW" ICH HAVE BEEN CALCULATED PER ALLOWABLE STRESS DESIGN � oa m 3. EPS CORE COMPOSITE PANELS SHALL BE CONSTRUCTED USING TYPE 3205-HI54 ;f z t yy ILN 13 v w � �; ALUMINUM & 1/2" ORIENTED STRAND BOARD (OSS)) FACINGS, 1.0 PCF EPS. THE EPS FOAM SHALL BE ADHERED TO THE FACINGS WITH ISOGRIP SP 2020 ADHESIVE E}_' oC" _1 "' w ; 0 H Z IL - "Iq (BY ASHLANO SPECIALTY), FABRICATION SHALL BE IN ACCORDANCE WITH APPROVED FABRICATION METHODS BY MANUFACTURER FOR ALL +� z D: w PANELS. 4. PANEL DEAD LOADS (EXCLUSIVE OF WEATHER -RESISTANT ROOFING MATERIALS) F O w HAVE BEEN FACTORED INTO CALCULATIONS FOR GRAVITY LOADS AS WELL AS O CALCULATIONS FOR PANEL PROPERTIES. FOR UPLIFT CALCULATIONS, USE ONLINE TOOL FOUND BY SCANNING THE QR CODE BELOW OR BY VISITING THE URL. S. NO 33-1/3% INCREASE IN ALLOWABLE STRESS HAS BEEN USED IN THE DESIGN OF THIS SYSTEM. GENERAL NOTES: 1. CONTRACTOR SHALL INVESTIGATE AND CONFORM TO ALL LOCAL BUILDING CODE w AMENDMENTS WHICH MAY APPLY. DESIGN CRITERIA BEYOND AS STATED HEREIN MAY REQUIRE y N ADDITIONAL SITE -SPECIFIC SEALED ENGINEERING. 2. THIS DOCUMENTLS ONLY a VALID WITH ORIGINAL SIGNATURE AND SEAL OFA P.E. OFTHIS FIRM AND, IF PRINTED, WITH A RED'ELIT2 STAMP ACROSS THE DOCUMENT FACE. = ay 3. THE ARCHITECT/ENGINEER OF RECORD FOR THE PROJECT SUPERSTRUCTURE WITH a o z a O�� WHICH THIS DESIGN IS USED SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED BY THE ence F1 Z 6 O be a �u DI > z PERMITTING CONTRACTOR. 4, SEPARATE'SITE-SPECIFIC' SEALED ENGINEERING SHALL BE REQUIRED IN ORDER O o LU G o � o. TO DEVIATE FROM LOADS, DEFLECTIONS, OR SPANS CONTAINED HEREIN. LINEAR INTERPOLATION OF THE ALLOWABLE SPAN TABLES LISTED HEREIN SHALL NOT BE J o = � 0.24 x PERMITTED. CONTACT THIS ENGINEER FOR ALTERNATE SPAN CALCULATIONS AS MAY Be REQUIRED. Q v U O !s O S. THE CONTRACTOR SHALL CAREFULLY CONSIDER POSSIBLE IMPOSING LOADS ON ROOF, INCLUDING BUT NOT LIMITED TO LLJ V z Z F" �i w , of m u ANY CONCENTRATED LOADS WHICH MAY JUSTIFY GREATER DESIGN CRITERIA. THIS ADDITIONAL ROOF LOAD O O O CRITERIA SHALL BE PROPERLY ANALYZED BY A LICENSED ENGINEER OR REGISTERED ARCHITECT. u O o 6. THE CONTRACTOR IS RESPONSIBLE TO INSULATE OR PROTECT ALL MEMBERS FROM ,� toO WU. DISSIMILAR MAT_P.TALS TO PREVENT ELECTROLYSIS. In 7. THE SYSTEM DETAILED HEREIN IS GENERIC AND DOES NOT PROVIDE INFORMATION FOR A SPECIFIC SITE. FOR SITE CONDITIONS DIFFERENT FROM THE CONDITIONS CL W DETAILED HEREIN, A LICENSED ENGINEER OR REGISTERED ARCHITECT SHALL PREPARE SITE SPECIFIC DOCUMENTS FOR USE IN CONJUNCTION WITH THIS DOCUMENT. 8. ENGINEER SEAL AFFIXED HERE TO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR et. at. INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM o MATERIAL FABRICATION, SYSTEM ERECTION & CONSTRUCTION PRACTICES BEYOND THAT WHICH IS CALLED FOR BY LOCAL, S'I�ATE, & _ m m8 FEDERAL CODES & FROM DEVIATIONS OF THIS PLAN, 9. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED. 10. ALTERATIONS, ADDITIONS, OR OTHER MARKINGS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE THIS CERTIFICATION. ADD (2)�/�"CONTINUOUS �, ADHESIVE LINES DIRECTLY ON EPS, 1" FROM OSB EDGE, SEAL )DINT CLEAR SPAN TABLES DIRECTIVE: s (1) (1) %s" FROM OSB EDGE CONTINUOUS CAULKING 1. FIND ALLOWABLE COMPOSITE PANEL CLEAR SPAN IN TABLE FOR APPROPRIATE PANEL DEPTH, FACING THICKNESS, AND EPS CORE a" R ■ I i " oss " ose DENSITY SELECTED. , id INN! o 0 0 0 0 0 0 0 0 0 0 2. ANCHOR COMPOSITE PANELS TO EXISTING HOST STRUCTURE AND OPTIONAL w = o°o°D°o° EXISTING SUPPORTING MEMBERS PER SEPARATE CERTIFICATION. °e o° 0°0°0°0°0°0 GUTTER Z 0 0000 000a °000°00000°Q°° 0000000000000 20-29649 0 0 0 o OR GRIP o O 00000oa00oa °°00000000 SCM E: CAP 0.024"-0.030° ALUMINUM VISIT ECALC.10/29649 PAGE DESCRIPTION: OVERHANG 36" MAX O/H AT FRONT & 259'o TMPCROSS SECTION AT K 701-1 FOR SITE SPECIFIC DEVIATIONS 8 MORE INFORMATION ABOUT THIS DOCUMENT O OF LAST PANEL WIDTH AT SIDES OR SCANTHIS OR CODE (UP TO 12" MAX O/H AT SIDES) VISIT ENGINEERINGEIPRESS.COWEASTERN �l FOR ADDITIONAL PLANS, REPORTS & RESOURCES a, ELITE ROOF/OPEN WALL MASTER PLAN SHEET DETAILS NOT SHOWN TO SCALE FOR CLARITY. A CONNECTION TO STRUCTURE: WOOD OR CONCRETE I X3' LAG BOLT @ 10- O.C. & ENDS TO 2' SOUND FASCIA. ENSURE FASCIA IS SECURELY FASTENED TO 024' EACH RAFTER WITH (1)i±' X 3" LAG MIN. CENTER FLASHING LAGS TO RAFTERS. ENSURE 1K' MIN. PENETRATION CONCRETE EALED TO PRE -DRILL HOLE TO AVOID SPLITTING' OR FILLED fi WALL(TYP) D ROOF PANEL CONNECTION FRONT ELEVATION ROOF SPAN IT MIN ROOF PITCH Isy PER 12", MAX IS 2' IN 12' SEAL30INT 7777, CONTINUOUS CAULKING 9. O.C. I IS• O.C. 6063-T6 T.-GU -T # P005 S' TARNO SKI ROOF/COLUMN IF L LAYOUT VALID FOR 11) JOBLN ONLY IF EYtsT3ry - ELnE E SECTION AT BEARING 16815 ._. 4'-OMEII4 0ME EXISTING r %' OR7R(3SSRBEAM PER "x13:"EMBED.: i EP-2 COLUMN I3$C 28 6•D.0 8.O.C. STRUCR)RE C -CARRY ° • TAPCON @ 2 '• • 0 14 : [ (BY OTHERS) • o ° • 150 C �F �BaANEL 4EL TABLES ON . • & AL FROM .. . C, g 3 0 C 53 LE ENDS BTU. ® 18 P METµERS USED ] i[_DETAI & IA SPACINGOR 2' NOMINAL STRUCTURAL ELifEX' O.C• L ROOFSO SNTMSO USut. SUS S PA��TACBLE PoR RFATER 170 C PSF }00 ER 'r77•�OpE0. LNG FACIA MINIMUM EP-23\ �A�EL S VANEL \ i14XY4' SMS ® 7' O.0 (8) PER 4' PANEL TOP &/ 'NOTE: USE Y'xlY,' EMBED BOTTOM. ADD (2) SMS 2• & 4- FROM EACH TAPCONS, 2K' & 4%- FROM ENDS, ENCLOSURE END TOP & BOTTOM. HEAVY 14" MAX O.C. TO HOLLOW BLOCK ADHESIVE CAULK TOP & BOTTOM CONTINUOUS B ENCLOSURE TO CONCRETE DECK ANCHORING DETAIL PSEE GENERAL NOTE *PEERI� COLUMN PER TABLES OR 2'X3'x3'x�- ANGLE WITH (2) Y4"XlY4' EMBED. SEALED SITE SPECIFIC TAPCONS W/ %" MIN. WASHER DIAMETER TO DRAWINGS/CALCULATIONS SLAB, 2W APART & 3- FROM SLAB EDGE & (6) #14 SMS TO COLUMN, )4' FROM ANGLE EDGES, IN HVHZ ONLY ' ONE EACH SIDE OF COLUMN USE 2"X3'X3'Xl/4- ANGLES W/ (8)- A14 SMS TO COLUMN ALT. CONNECTION TO WOOD DECK: USE (4) }° X EA. ANGLE (16 TOTAL) ° 4' LAG BOLTS TO CONNECT TO SOLID 2X WOOD �i • STRUCTURE (i2 SYP OR BETTER) BELOW. LAGS I.MUST PENETRATE THRU DECKING INTO STRUCTURAL WOOD SUBSTRATE BELOW NOTE: DESIGN AND INTEGRITY OF WOOD DECK NEW/EXISTING CONBELOW IS BY OTHERS AND OUTSIDE THE SCOPE FOOTING. SEE SITE SPECIFIC OF THIS CERTIFICATION AND MUST BE DETAIL OR ADDITIONAL FOOTING DESIGNED TO CARRY ALL IMPOSING LOADS BY ENGINEERING SHEET THIS DESIGN. C EAVE BEAM CONNECTION @ WALL 11 EPS POLY (USED AS REQURIED WHEN • t •..'•" • : ROOF .: •.: Q '. CONNECTING TO WALL) Ll WTHRUBOLT THROUGH rk--4 2'x3'.%' ANGLETO ROOF, 3'x3'x%' ANGLE FASTENED TO INSIDE & BOTTOM OF CARRY BEAM W/ (2) Y4'?HRUBOLTS CARRY BEAM PERSIDE, (5) #14 SMS BOTTOM, TABLES OR SEALED FASTENED TO CBS WALL W/ (2) SITE SPECIFIC V.'%)V4' EMBED TAPCONS OR TO RAWINGS/CALCULATIONS WOOD (MIN 2X, INTEGRITY BY OTHERS),WITH (3)i14xl%' EMBED WOOD SCREWS EA ANGLE EXTRUSIONS: VERIFY FIELD EXTRUSION DIMENSIONS WITH DESIGN DIMENSIONS PRIOR TO USE. ALTERNATE ENGINEERING WILL BE REQUIRED FOR DIMENSIONS LESS THAN THOSE AS SPECIFIED HEREIN. ALL EXTRUSIONS TO BE 606346ALUMINUM. .093" OR .12s" .125' 3X3 a SQUARE DEPTH AS TUBE REQUIRED "M.: 4 X 4 X .125• (2'MIN.) NOT SHOWN 2- OR 3'--f t--3'SQUARE_...t ANGLES TOP (TYP BOTTOM) SEE TABLE TO LEFT 16' 1180 D GUTTER I o 0 o e o o e e° o o RL = (OPT.) o °° a ooe oeo°o 0 OPTION I:USE ia' LAG BOLTS W/ 1" MIN. WASHER DIAMETER,, 1' MIN. LONGER THAN PANEL THICKNESS SPACED PER LAG SPACING TABLE THIS DETAIL. BOTH OPTIONS: (2) %1 THRUBOLTS, CARRY BEAM - TO COLUMN OPTION 2: Y." THRUSOLTS TO• ROOF, 4- FROM ENDS & 17• O.C. TO 2'x2.46- ANGLES (EITHER SIDE IF REQUIRED BY BUILDING DEPT). BOTH OPTIONS: 2'x3'x)¢' ANGLE, (6) #14 SMS EA LEG, EA SIDE OF COLUMN COLUMN PER TABLES OR SEALED SITE SPECIFIC DRAWING/CALCULATIONS -CARRY BEAM PER TABLES OR SEALED SITE SPECIFIC DRAWINGS/CALCULATIONS NOTCH COLUMN IN CENTER TO FIT CARRY BEAM SNUG OPTION: NOTCH COLUMN ON FRONT FACE TO MOUNT CARRY F BEAM SPLICE OVER COLUMN (1)y' LAG BOLT INTO EACH CARRY (5) #14 SMS EA. BEAM END, 1" MIN SIDE OF PLATE LONGER THAN a•wx cxoM un aoorswc '� PANEL THICKNESS o e° v o °°• v i °• e e °pO ° 0 0 6' WIDE X L/e• THICK-� T- COLUMN PER TABLES OR ALUM PRATE ON EACH SEALED SITE SPECIFIC SIDE OF CARRY BEAM DRAWINGS/CALCULATIONS c SIDE 0.093" LAP BEAM WALL •+ (SEE 2" X 51 X THICKNESSES a LEFT) TO LOSS •TMP° 0.093' TUBE SI BEAM TOP DE - � �' 2 X VARIES 2X4 .136 .045' a 2 X 3 2 X 3 i 2X5 .134° .050'14 SMS o SNAP o BOX 2X6 .134' .050' iD ENDS & '^ BEAM ri BEAM STM: 2' % 2' X 2X7 .134' .OSB" O.C. 2X8 .210' .072'AX. TOP 3°OX 0.093' X 2X9 .210•.072 vBOTTOM (NOT SHOWN) 2X10 .390• .092 _I "2.' 2.0' T'--2.0''�i CONCRETE OR WOOD D III B BELOW. SEE DETAIL'S' FOR IWI' LUMN PER TABLE ATTACHMENT. DESIGN AND OR SITE -SPECIFIC INTEGRITY OF DECK UNDER ENGINEERING SEPARATE CERTIFICATION OR BY OTHERS ROOF PANEL ACCESSORIES: NOTE: CERTIFICATION OF SKYLIGHT BY SEPARATE CERTIFICATION. DETAIL ILLUSTRATES TYPICAL CONNECTION METHODS ONLY. REFER TO SKYLIGHT DETAILS FOR FURTHER INFORMATION WHICH GOVERNS. *10-201" TEK SCREWS, (1) E06 CORNER & (1) 0 u• usmE� KYLIGHT MID -LENGTH, U.N.O. ON SKYLIGHT PROD. APPROVAL SKYLTG hp;i;S,ENSr[TVESURE SWINDOW WELD D TAPE 24' X 48' MAX SKYLIGIF OPEN5.aoo�c�v (DETAIL SEPARATE) ANBEAM RECEMN CHANNEL • ' CONDUIT FAN SUPPORT 2' X 3' X .070" ADHERE ALL 4 SIDES WIRING & DRC ARE FAN INTEGRITY BY OTHERS GENERAL NOTES: l) THIS STRUCTURE HAS BEEN DESIGNED & COMPLIES WITH THE REQUIREMENTS OF THE 2010 FLORIDA BUILDING COD£. STRUCTURE SHALL IE FABRICATED IN ACCORDANCE WITH ALL GOVERNING CODES. CONTRACTOR SHALL INVESTIGATE AND CONFORM TO ALL LOCAL BUILDING :ODE AMENDMENTS WHICH MAY APPLY. DESIGN CRITERIA OR SPANS BEYOND STATED HEREIN MAY REQUIRE ADDITIONAL SITE SPECIFIC iEALED ENGINEERING. ALL LOADS BASED ON SCREENS WITH 1SX14 MESH, CATEGORY 1, Kd=0.85, PARTIALLY ENCLOSED (Gtpl-+/-0.55), MRH PER FBC TABLE 2002.4(1), CATEGORY I PER AAMA/NPEAINSA 2100-02, AND ASCE 7-10 AS APPLICABLE. THIS DOCUMENT SHALL NOT BE USED OR REPRODUCED WITHOUT THE ORIGINAL SIGNATURE & RAISED SEAL OF C.T.'GUS' TARNOWSKI, '.E. & MUST HAVE'EL1TE' IN RED ACROSS THE FACE OF THIS DRAWING. ALTERATIONS, ADDITIONS, HIGHLIGHTING, OR OTHER MARKINGS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR CERTIFICATION. !) THE EXISTING STRUCTURE MUST BE CAPABLE OF SUPPORTING THE LOADED COMPOSITE ROOF -SCREEN WALL STRUCTURE AS DETERMINED IY OTHERS OR BY SPECIAL ENGINEERING BY UNDERSIGNED ENGINEER ATTACHED HERETO. NO WARRANTY IS CONTAINED HEREIN. 1) COMPOSITE ROOF AND WALL MEMBERS SHALL BE CONSTRUCTED USING MINIMUM TYPE 3005-H25 ALUMINUM FACINGS, (1) OR (2) PCF %STM C-578-83 CARPENTER BRAND EPS ADHERE TO ALUMINUM FACINGS WITH ASHLAND CHEMICAL 2020D ISO GRIP. FABRICATION TO BE B) :LTTE PANEL PRODUCTS ONLY IN ACCORDANCE WITH APPROVED FABRICATION METHODS. 1) ALL EXTRUSIONS SHALL BE ALUMINUM ALLOY TYPE 6063-TS ONLY. i) ALL FASTENERS TO BE 2024-T4 OR 7075-T73 ALLOY, NON-MAGNETIC STAINLESS STEEL, SAE GRADE 5 STEEL MIN, OR CADMIUM PLATED )R OTHER CORROSION RESISTANT MATERIAL AND SMALL COMPLY WITH SECTION S, 2005 ALUMINUM DESIGN MANUAL, THE ALUMINUM LSSOCUITION, INC., & APPLICABLE FEDERAL, STATE, AND LOCAL CODES. i) FASTENERS SHALL HAVE A HEAD AND/OR BE PROVIDED WITH K' DIAMETER WASHER MINIMIUM UNLESS NOTED OTHERWISE. i) ALL CONNECTIONS SHALL BE BOLTED OR FASTENED WITH SHEET METAL SCREWS AS SHOWN AND IN ACCORDANCE WITH PROPER `ASTENING METHODS AND CODES. ANY FASTENER STRIPPED OR NOT ADEQUATELY HOLDING SHALL BE REPLACED. 1) THE CONTRACTOR IS RESPONSIBLE TO INSULATE ALUMINUM MEMBERS FROM DISSIMILAR METALS TO PREVENT ELECTROLYSIS. i) ALL TAPCONS MUST BE ITN CARBON STEEL TAPCONS OR EQUIVALENT W/ 1%' EMBED, 3• MIN. EDGE DISTANCE, FASTENED TO MINIMUM rga 3 LL W � cQi o W W ZZ a Z W CC Q G }} {F. LPL O X9 O W c w L ILL~�"ml y =r2� Q wW a O LO U Lu0.o�... rgl�jZ E O U —1,�A Z WUvU a O Li mW s0. K w 5 � IL w mWa 00- MAXIMUM COLUMN SPACING - 8FT, MAX COLUMN HEIGHT - 10FT, MAX LIVE LOAD = SSPSF, MAX WIND VELOCITY 8L EXPOSURE - PAGE DESC !MPH, 'D', CONNECTIONS VALID UP TO THE MAX 6IN. THICK ROOF SPAN PER ELITE ROOF FLORIDA STATEWIDE APPROVED SPAN TABLE E SPECIFIC ENGINEERING REQUIRED FOR ANY DETAIL WHICH DEVIATES FROM THIS PLAN OR BEYOND THESE LIMITATIONS. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et INDEMNIFIES AND SAVES HARMLESS THIS ENGINEER FOR ALL COSTS AND DAMAGES INCLUDING LEGAL FEES AND APPELLATE FEES IULTING FROM MATERIAL FABRICATION, SYSTEM ERECTION, AND CONSTRUCTION PRACTICES BEYOND THAT WHICH IS CALLED FOR BY 7LL, STATE, AND FEDERAL CODES AND FROM DEVIATIONS OF THIS PLAN. EXCEPT AS EXPRESSLY PROVIDED IN THIS SPECIFICATION, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE IMENDED. C. Tuy