HomeMy WebLinkAboutAPPROVED, HVAC Layout & Energy CalcsEnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 44/6/2021 3:14 PM
Project Name:
Owner:
Builder Name:
Permit Office:
Jurisdiction:
WATERSTONE LOT-33
Street:
City, State, Zip:FT. PIERCE , FL , 34951
5117 Armina Pl
Permit Number:
Design Location:FL, Fort Pierce County:St. Lucie (Florida Climate Zone 2 )
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area above grade (ft²)
New (From Plans)
Detached
1
No
2321
7. Windows
a. U-Factor:
S H G C :
b. U-Factor:
S H G C :
c. U-Factor:
S H G C :
Dbl, U=0.32 78.67 ft²
SHGC=0.30
Dbl, U=0.32 63.11 ft²
SHGC=0.27
Dbl, U=0.55 41.00 ft²
SHGC=0.34
9. Floor Types
a. Slab-On-Grade Edge Insulation
b. Floor over Garage
c. N/A
R=0.0 968.00 ft²
R=19.0 386.00 ft²
R=f t ²
10. Wall Types
a. Frame - Wood, Exterior R=13.0 1178.70 ft²
b. Concrete Block - Ext Insul, Exterior R=4.1 936.00 ft²
c. Frame - Wood, Exterior R=11.0 340.89 ft²
11. Ceiling Types
a. Under Attic (Vented)R=30.0 1353.00 ft²
f t ² R=b. N/A
c. N/A R = f t ²
12. Ducts
a. Sup: Attic, Ret: Attic, AH: Main
13. Cooling systems
14. Heating systems
15. Hot water systems
a. Electric Cap: 40 gallons
b. Conservation features
None
d. N/A R=f t ²
Area Weighted Average Overhang Depth:1.069 ft.
Area Weighted Average SHGC:0.296
Description Area
Insulation Area
Insulation Area
Insulation Area
16. Credits Pstat
5
(197.8 sqft.)
(2455.6 sqft.)
(1353.0 sqft.)
(1354.0 sqft.)
Conditioned floor area below grade (ft²)0
a. Central Unit
a. Electric Strip Heat
k B t u / h r
47.0 SEER:16.00
Efficiency
k B t u / h r Efficiency
26.0 COP:1.00
f t ² R
6 616
EF: 0.940
8. Skylights
c. U-Factor:(AVG)
S H G C ( A V G ) :
N/A
N/A
f t ²
Area
Glass/Floor Area:0.085 Total Proposed Modified Loads:
Total Baseline Loads:
64.40
69.56 PASS
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code.
PREPARED BY:
DATE:
I hereby certify that this building, as designed, is in compliance
with the Florida Energy Code.
OWNER/AGENT:
DATE:
BUILDING OFFICIAL:
DATE:
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
FORM R405-2020
04/06/2021
4/20/2021
PROJECT
Title:
Owner Name:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
1
WATERSTONE LOT-33
Family Type:
New/Existing:
Bedrooms:
Conditioned Area:
Total Stories:
Worst Case:
Rotate Angle:0
No
1
2321
5
New (From Plans)
Detached
Address Type:
Lot #
Block/Subdivision:
PlatBook:
Street:
County:
City, State, Zip:
FL , 34951
FT. PIERCE ,
St. Lucie
5117 Armina Pl
Street Address
Comment:
Building Type:User
Cross Ventilation:No
Whole House Fan:No
TMY Site
Design Temp Int Design Temp Heating Design Daily Temp
Design Location 2.5 %97.5 %Degree Days Moisture RangeWinterSummer
CLIMATE
90 70 75 299 62 Low39FL_VERO_BEACH_MUNIFL, Fort Pierce______
Number Name Area Volume
BLOCKS
1 Block1 2321 19032.2
Number Name Area Volume
SPACES
Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished
1 Main 2321 19032.2 Yes 6 5 Yes Yes1Yes
#Floor Type Area Tile Wood Carpet
FLOORS
Perimeter R-Value Joist R-ValueSpacePerimeter
1 386 ft² 0 0 1______19Floor over Garage 19 - - - - - - - -Main
2 968 ft² 0 0 1______Slab-On-Grade Edge Insulatio - - - -0134.3 ft Main
#Type Materials Color Absor.
Roof Solar Deck
Insul.
Pitch
ROOF
Tested
Roof
Area
Gable
Area
Emitt
Tested
EmittSA
(deg)
Rad
Barr
1 Gable or Shed Composition shingles 1466 ft² Medium 0.4 0 22.62______N282 ft² 0.9 NoN
ATTIC
#Type Ventilation Area RBS IRCCVent Ratio (1 in)
______1 Full attic Vented 1353 ft² N N150
#Ceiling Type R-Value Area Framing Frac Truss Type
CEILING
Space Ins Type
1 Under Attic (Vented)30 1353 ft² 0.1 Wood______Main Blown
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
#Wall Type R-Value Area
Adjacent Framing Solar
Ornt Fraction Absor.
HeightWidth
Ft In Ft InTo
Cavity Sheathing
R-ValueSpace Grade%
Below
1 13 0Main008388SFrame - Wood 0.30.25Exterior309.3 ft² ____
2 4.1 0Main080188NConcrete Block - Ext Insul 0.30Exterior156.0 ft² ____
3 13 0Main000358EFrame - Wood 0.30.25Exterior280.0 ft² ____
4 4.1 0Main080358EConcrete Block - Ext Insul 0.30Exterior303.3 ft² ____
5 13 0Main008388SFrame - Wood 0.30.25Exterior309.3 ft² ____
6 4.1 0Main088388SConcrete Block - Ext Insul 0.30Exterior335.1 ft² ____
7 13 0Main000358WFrame - Wood 0.30.25Exterior280.0 ft² ____
8 4.1 0Main084168WConcrete Block - Ext Insul 0.30Exterior141.6 ft² ____
9 11 0Main088338-Frame - Wood 0.30.25Exterior291.8 ft² ____
10 11 0Main08858-Frame - Wood 0.30.25Exterior49.1 ft² ____
#Door Type U-Value AreaStorms
DOORS
Ornt Space Width
Ft In Ft In
Height
1 Insulated .16 20 ft² None______W Main 863
2 Wood .28 17.8 ft² None______-Main 8682
#Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening
WINDOWS
Overhang
Orientation shown is the entered, Proposed orientation.
Wall
ID Imp
1 S Double (Clear)0.62 0.26 15.0 ft² 1 ft 0 in 0 ft 6 in NoneMetal None______Yes1 N
2 E Double (Clear)0.32 0.3 30.0 ft² 1 ft 0 in 0 ft 6 in NoneMetal None______Yes3 N
3 E Double (Clear)0.32 0.3 12.0 ft² 1 ft 0 in 10 ft 6 in NoneMetal None______Yes4 N
4 E Double (Clear)0.32 0.3 21.7 ft² 1 ft 0 in 10 ft 6 in NoneMetal None______Yes4 N
5 E Double (Clear)0.55 0.34 41.0 ft² 1 ft 4 in 11 ft 0 in NoneMetal None______Yes4 N
6 S Double (Clear)0.32 0.3 15.0 ft² 1 ft 0 in 0 ft 6 in NoneMetal None______Yes5 N
7 W Double (Clear)0.32 0.27 30.8 ft² 1 ft 0 in 0 ft 6 in NoneMetal None______Yes7 N
8 W Double (Clear)0.32 0.27 15.8 ft² 1 ft 0 in 0 ft 6 in NoneMetal None______Yes7 N
9 W Double (Clear)0.32 0.27 16.4 ft² 1 ft 0 in 10 ft 6 in NoneMetal None______Yes8 N
#Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
GARAGE
1 386 ft² 386 ft² 64 ft 9.3 ft 1______
Method CFM 50 ACH 50ELASLAScope
INFILTRATION
ACHEqLA#
2220.4 7121.82.000364Wholehouse .1276228.7Proposed ACH(50)1
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
HEATING SYSTEM
#System Type Efficiency Capacity DuctsSubtypeBlockSpeed
1 Electric Strip Heat/COP:1 25.98 kBtu/hr ______sys#1None1
#System Type Efficiency Capacity Air Flow SHR
COOLING SYSTEM
DuctsSubtypeBlockSubtype
1 Central Unit/SEER: 16 47 kBtu/hr c f m 0.7______sys#1Split1 Singl
#System Type EF Cap Use SetPnt Conservation
HOT WATER SYSTEM
SubType Location
1 Electric 0.94 40 gal 62.3 gal 120 deg None______None Garage
FSEC
Company Name System Model #Collector Model #
Collector
SOLAR HOT WATER SYSTEM
Storage
FEFCert #Area Volume
None None f t ² ______
#Location R-Value Area Location Area
---- Supply -------- Return ----
Leakage Type Handler
CFM 25Air
QN RLF
DUCTS
Heat Cool
HVAC #
TOT OUT
CFM25
1 Attic 6 616 ft² Attic 306 ft² Default Leakage Main ( D e f a u l t ) ______1 1 ( D e f a u l t )
TEMPERATURES
Programable Thermostat: Y Ceiling Fans:
Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec
[ ] Dec
[X] Dec[X] Nov
[X] Nov
[ ] Oct
[X] Oct
[ ] Sep
[ ] Sep
[ ] Aug
[ ] Aug
[ ] Jul
[ ] Jul[ ] Jun
[ ] Jun
[X] Jun
[ ] May
[ ] May
[ ] Apr
[X] Apr
[X] Mar
[X] Mar
[X] Feb
[ ] Feb
[X] Jan
[ ] Jan
Heating
Venting
Thermostat Schedule:HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling (WD)AM
PM
78
80
78
80
78
78
78
78
78
78
78
78
78
78
78
78
80
78
80
78
80
78
80
78
Cooling (WEH)AM
PM
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WD)AM
PM
66
68
66
68
66
68
66
68
66
68
68
68
68
68
68
68
68
68
68
68
68
66
68
66
Heating (WEH)AM
PM
66
68
66
68
66
68
66
68
66
68
68
68
68
68
68
68
68
68
68
68
68
66
68
66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default(8 lbs/sq.ft.0 ft² 0 ft 0.3 Main
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 4
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
5117 Armina Pl , FT. PIERCE, FL, 34951
4/6/2021 3:14 PM4/6/2021 3:14 PM
EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 93
The lower the EnergyPerformance Index, the more efficient the home.
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area (ft²)
New (From Plans)
Detached
1
5
No
2321
7. Windows**
a. U-Factor:
S H G C :
b. U-Factor:
S H G C :
c. U-Factor:
S H G C :
d. U-Factor:
S H G C :
Dbl, U=0.32 78.67 ft²
SHGC=0.30
Dbl, U=0.32 63.11 ft²
SHGC=0.27
Dbl, U=0.55 41.00 ft²
SHGC=0.34
other (see details)15.00 ft²
other (see details)
9. Floor Types
a. Slab-On-Grade Edge Insulation
b. Floor over Garage
c. N/A
R=0.0 968.00 ft²
R=19.0 386.00 ft²
R=f t ²
10. Wall Type and Insulation
a. Frame - Wood, Exterior R=13.0 1178.70 ft²
b. Concrete Block - Ext Insul, Exterior R=4.1 936.00 ft²
c. Frame - Wood, Exterior R=11.0 340.89 ft²
11. Ceiling Type and insulation level
a. Under Attic (Vented)R=30.0 1353.00 ft²
f t ² R=b. N/A
c. N/A R = f t ²
12. Ducts, location & insulation level
13. Cooling systems
14. Heating systems k B t u / h r
15. Hot water systems
a. Electric Cap: 40 gallons
EF: 0.94
b. Conservation features
None
d. N/A R=f t ²
Description Area
Insulation Area
Insulation Area
Insulation Area
Credits (Performance method)Pstat
Area Weighted Average Overhang Depth:
Area Weighted Average SHGC:
1.069 ft.
0.296
a. Electric Strip Heat 26.0 COP:1.00
a. Central Unit 47.0 SEER:16.00
k B t u / h r
Efficiency
Efficiency
a. Sup: Attic, Ret: Attic, AH: Main 6 616
R f t ²
8. Skylights
a. U-Factor(AVG):
S H G C ( A V G ) :
Description Area
N/A
N/A
f t ²
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature:Date:
Address of New Home:City/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
Page 1 of 1
FORM R405-2020
4/6/2021 3:14 PM
5117 Armina Place
4/20/2021
Ft Pierce
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
Florida Building Code, Energy Conservation, 7th Edition (2020)
ADDRESS:5117 Armina Pl
FT. PIERCE , FL , 34951
Permit Number:
The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
MANDATORY REQUIREMENTS - See individual code sections for full details.
R402.4 Air leakage (Mandatory).
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
R401.3 Energy Performance Level (EPL) display card (Mandatory).
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5
R402.4.3 Fenestration air leakage.
R402.4.1.1 Installation.
Exception: Site-built windows, skylights and doors.
R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors, and outdoor combustion air. Where
using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight-fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
Exception:
R402.4.1.2 Testing.
R402.4.1 Building thermal envelope.
The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer’s instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
The building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
SECTION R401 GENERAL
SECTION R402 BUILDING THERMAL ENVELOPE
MANDATORY REQUIREMENTS - (Continued)
Building framing cavities shall not be used as ducts or plenums.
Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation.
If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5
R403.3.5 Building cavities (Mandatory).
R403.4 Mechanical system piping insulation (Mandatory).
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory).
SECTION R403 SYSTEMS
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be “substantially leak free” in
accordance with Section R403.3.3.
Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer’s air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Rough-in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer’s air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2.
1.
Exceptions:
A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
2.
1.
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer’s designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
1.
2.
R403.5.1.1 Circulation systems.
R403.5.1.2 Heat trace systems.
Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
MANDATORY REQUIREMENTS - (Continued)
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 ½ inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water-heating systems to be turned off.
R403.5.6.2 Water-heating equipment. Water-heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water-heating systems should meet the following criteria:
Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
Be installed at an orientation within 45 degrees of true south.
1.
2.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
When installed to function as a whole-house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
R403.6.1 Whole-house mechanical ventilation system fan efficacy.
E x c e p t i o n :
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole-house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
1.
2.
3.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
For SI: 1 cfm = 28.3 L/min.a.When tested in accordance with HVI Standard 916
HRV or ERV
In-line fan
Bathroom, utility room
Bathroom, utility room
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY AIRFLOW RATE MAXIMUM
(CFM)(CFM/WATT)
a
Any
Any
10
90
1.2 cfm/watt
2.8 cfm/watt
1.4 cfm/watt
2.8 cfm/watt
Any
Any
<90
Any
(CFM)
Range hoods Any 2.8 cfm/watt Any
MANDATORY REQUIREMENTS - (Continued)
R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
Where public health standards require 24-hour pump operation.
R403.10.2 Time switches.
Pumps that operate solar- and waste-heat-recovery pool heating systems.
Where pumps are powered exclusively from on-site renewable generation.3.
2.
1.
4/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation—Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice-melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1.A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2.A variable capacity system sized for optimum performance during base load periods is utilized.
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer’s product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1.
2.
Attached single- and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida-registered engineer, in attached single- and multiple-family units, the capacity of
equipment may be sized in accordance with good design practice.
The published value for AHRI total capacity is a nominal, rating-test value and shall not be used for equipment sizing. Manufacturer’s
expanded performance data shall be used to select cooling-only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water-source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens-per-watt or shall utilize lamps with an efficacy of not less than 65 lumens-per-watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
SECTION R404
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions-Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14.
ELECTRICAL POWER AND LIGHTING SYSTEMS
Page 5 of 54/6/2021 3:14 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software
All gas- and oil-fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.4 Gas- and oil-fired pool and spa heaters.
Where more than 70 percent of the energy for heating, computed over an operation season, is from site-recovered
energy, such as from a heat pump or solar energy source, covers or other vapor-retardant means shall not be required.
Exception:
Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
R403.10.3 Covers.
R403.13 Dehumidifiers (Mandatory
Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
R403.13.1 Ducted dehumidifiers.
If installed, a dehumidifier shall conform to the following requirements:
1.The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2.The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3.Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4.Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
1.If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2.If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3.A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4.Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
Project Name:
Owner:
Builder Name:
Permit Office:
Jurisdiction:
WATERSTONE LOT-33
Street:
City, State, Zip:FT. PIERCE , FL , 34951
5117 Armina Pl
Permit Number:
Design Location:FL, Fort Pierce CHECKAIR BARRIER CRITERIA
A continuous air barrier shall be installed in the building envelope.
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
The junction of the foundation and sill plate shall be sealed.
The junction of the top plate and the top of exterior walls shall be
sealed.
Knee walls shall be sealed.
The space between window/door jambs and framing, and
skylights and framing shall be sealed.
Rim joists shall include the air barrier.
The air barrier shall be installed at any exposed edge of
insulation.
Exposed earth in unvented crawl spaces shall be covered with
a Class I vapor retarder with overlapping joints taped.
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Narrow cavities
Shafts, penetrations
Crawl space walls
Floors
(including
above-garage
and cantilevered
floors)
Rim joists
Windows, skylights
Walls
Ceiling/attic
General
COMPONENT
Garage separation
Recessed lighting
Plumbing and wiring
S h o w e r / t u b
HVAC register boots HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub-floor, wall covering or
The air barrier shall be installed behind electrical or communication
boxes or air-sealed boxes shall be installed.
The air barrier installed at exterior walls adjacent to showers and
tubs shall separate them from the showers and tubs.
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Recessed light fixtures installed in the building thermal envelope
shall be sealed to the finished surface.
Air sealing shall be provided between the garage and conditioned spaces.
When required to be sealed, concealed fire sprinklers shall only be
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings.
C o n c e a l e d
Electrical/phone box on
exterior walls
Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
INSULATION INSTALLATION CRITERIA
EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software4/6/2021 3:15 PM Page 1 of 1
Air-permeable insulation shall
not be used as a sealing material.
The insulation in any dropped ceiling/soffit
shall be aligned with the air barrier.
Cavities within corners and headers of frame walls
shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Rim joists shall be insulated.
Floor framing cavity insulation shall be installed to
maintain permanent contact with the underside of
subfloor decking, or floor framing cavity insulation
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
and doors
on exterior wall
requirements
Recessed light fixtures installed in the building
thermal envelope shall be air tight and IC rated.
sprinklers
Where provided instead of floor insulation, insulation
shall be permanently attached to the crawlspace walls.
Exterior walls adjacent to showers and tubs shall
be insulated.
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
a
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: Permit #:
Job Information
Builder: Community: Lot: NA
Address: 5117 Armina Pl
City: FT. PIERCE State: FL Zip: 34951
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
PRESCRIPTIVE METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
PERFORMANCE or ERI METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub-section ACH50.
ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERI): 7.000
_________ x 60 ÷ ______________ = ____________19032
CFM(50) Building Volume ACH(50)
PASS
When ACH(50) is less than 3, Mechanical Ventilation installation
must be verified by building department.
Method for calculating building volume:_____________________________
Retrieved from architectural plans
Code software calculated
Field measured and calculated
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: ______________________________________ Phone: ________________________
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: ____________________________________ Date of Test: ______________________
Printed Name of Tester: _________________________________
License/Certification #: _____________________________ Issuing Authority: _________________________
4/6/2021 3:15:10 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 1
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
Job:Manual S Compliance Report Apr 6, 2021Date:Entire House By:
Project Information
WATERSTONE LOT-33For:
5117 Armina Pl, FT. PIERCE, FL 34951
Cooling Equipment
Design Conditions
°F77.3Entering coil DB:Btuh33602Sensible gain:°F90.4Outdoor design DB:
°F63.7Entering coil WB:Btuh9131Latent gain:°F77.4Outdoor design WB:
Btuh42734Total gain:°F75.0Indoor design DB:
cfm1567Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
ML14XC1-047-230A**+CBA27UHE-048-230*++TDRModel:LennoxManufacturer:
cfm1567Actual airflow:
% of load112Btuh37480Sensible capacity:
% of load103Btuh9370Latent capacity:
%80SHR:% of load110Btuh46850Total capacity:
Heating Equipment
Design Conditions
°F70.0Entering coil DB:Btuh23104Heat loss:°F41.0Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Elec stripEquipment type:
Model:Manufacturer:
cfm0Actual airflow:
°F50Temp. rise:% of load112kW7.6Output capacity:
Meets all requirements of ACCA Manual S.
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 1
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
Job:Load Short Form Apr 6, 2021Date:Entire House By:
Project Information
WATERSTONE LOT-33For:
5117 Armina Pl, FT. PIERCE, FL 34951
Design Information
InfiltrationClgHtg
SimplifiedMethod9041Outside db (°F)
Semi-tightConstruction quality7570Inside db (°F)
0Fireplaces1529Design TD (°F)
L-Daily range
5040Inside humidity (%)
5713Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make Lennox
Trade Trade LENNOX
Model Cond ML14XC1-047-230A**
AHRI ref Coil CBA27UHE-048-230*++TDR
AHRI ref 10259428
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.6 Sensible cooling Btuh32900
Heating output Btuh25976 Latent cooling Btuh14100
Temperature rise °F0 Total cooling Btuh47000
Actual air flow cfm0 Actual air flow cfm1567
Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0.047
Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.79
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
DINING AREA 122 1329 3642 0 170
GREAT ROOM 288 3371 3454 0 161
EX STE BED 163 2560 2408 0 112
KITCHEN 171 3110 3364 0 157
FOYER 110 1989 675 0 31
EX STE BATH 64 527 180 0 8
2ND FL HALL BATH 68 717 645 0 30
2ND FL OS BATH 98 586 590 0 28
2ND FL OS WIC 53 102 448 0 21
2ND FL OS BED 229 2269 5740 0 268
2ND FL HALL 151 1180 1232 0 57
2ND FL MECH 16 0 0 0 0
2ND FL LAUNDRY 47 56 854 0 40
2ND FL LOFT 157 1061 1897 0 88
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 2
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
2ND FL BED 2 164 1524 2931 0 137
2ND FL BED 3 157 1044 2527 0 118
2ND FL BED 4 165 1678 3014 0 141
2ND FL STAIR 48 0 0 0 0
Entire House 2272 23104 33602 0 1567
Other equip loads 0 0
Equip. @ 0.95 RSM 32057
Latent cooling 9131
TOTALS 2272 23104 41188 0 1567
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 1
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
Job:Project Summary Apr 6, 2021Date:Entire House By:
Project Information
WATERSTONE LOT-33For:5117 Armina Pl, FT. PIERCE, FL 34951
Notes:
Design Information
St Lucie Co Intl, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75
Design TD °F29 Design TD °F15Daily range L
Relative humidity %50Moisture difference gr/lb57
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh19544 Structure Btuh23350
Ducts Btuh3560 Ducts Btuh10252Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0
(none) (none)Humidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh23104 Use manufacturer's data n
Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh32057
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Semi-tight0Fireplaces Structure Btuh6363
Ducts Btuh2768Central vent (0 cfm) Btuh0
CoolingHeating (none)22722272Area (ft²) Equipment latent load Btuh9131
1924419244Volume (ft³)Air changes/hour 0.110.22 Equipment Total Load (Sen+Lat)Btuh41188
Equiv. AVF (cfm) 3571 Req. total capacity at 0.70 SHR ton3.8
Heating Equipment Summary Cooling Equipment Summary
Make Make LennoxTrade Trade LENNOX
Model Cond ML14XC1-047-230A**AHRI ref Coil CBA27UHE-048-230*++TDR
AHRI ref 10259428Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input kW7.6 Sensible cooling Btuh32900Heating output Btuh25976 Latent cooling Btuh14100
Temperature rise °F0 Total cooling Btuh47000Actual air flow cfm0 Actual air flow cfm1567
Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0.047Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.79
Job #:
Performed for:
WATERSTONE LOT-33
5117 Armina Pl
FT. PIERCE, FL 34951
Scale: 1 : 58
Page 1
Right-Suite® Universal 2021
21.0.05 RSU29964
2021-Apr-06 14:39:30
...tsoft HVAC\WATERSTONE LOT-33.rup
N
Sheet 1
DINING AREA
GREAT ROOM
EX STE BED
KITCHEN
FOYERGARAGE
EX STE BATH
1ST FL STAIR
157 cfm 170 cfm
81 cfm 81 cfm
112 cfm12 x 8
8 cfm
31 cfm
4 "
6 "
7 "
8 "
5 "
8 "
6 "
14 "
Sup Riser
14 "
Job #:
Performed for:
WATERSTONE LOT-33
5117 Armina Pl
FT. PIERCE, FL 34951
Scale: 1 : 58
Page 2
Right-Suite® Universal 2021
21.0.05 RSU29964
2021-Apr-06 14:39:30
...tsoft HVAC\WATERSTONE LOT-33.rup
N
2ND FL
2ND FL HALL BATH
2ND FL OS BATH
2ND FL OS WIC
2ND FL OS BED
2ND FL HALL
2ND FL STAIR 2ND FL MECH
2ND FL LAUNDRY
2ND FL LOFT
2ND FL BED 22ND FL BED 32ND FL BED 4
1567 cfm
16 "
57 cfm
141 cfm 118 cfm
88 cfm
30 cfm
40 cfm
28 cfm
21 cfm
134 cfm
134 cfm
10 x 6
10 x 610 x 6
7 "
7 "4 "
4 "
4 "
6 "
16 "
12 "
137 cfm
14 "
Sup Riser
14 "
5 "
7 "
7 "7 "
12 "
4 "
Bold/italic values have been manually overridden
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 1
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
Job:Duct System Summary Apr 6, 2021Date:Entire House By:
Project Information
WATERSTONE LOT-33For:
5117 Armina Pl, FT. PIERCE, FL 34951
CoolingHeating
External static pressure in H2O0.50in H2O0.50
Pressure losses in H2O0.31in H2O0.31
Available static pressure in H2O0.19in H2O0.19
Supply / return available pressure 0.095 / 0.095 in H2O in H2O0.095 / 0.095
Lowest friction rate in/100ft0.116in/100ft0.116
Actual air flow cfm1567cfm0
Total effective length (TEL) ft164
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st290.021.4VlFx0x07.00.17113702931c2ND FL BED 2
st290.011.7VlFx0x07.00.18711802527c2ND FL BED 3
st290.020.7VlFx0x07.00.17214103014c2ND FL BED 4
st290.026.8VlFx0x05.00.1635701232c2ND FL HALL
70.012.2VlFx0x04.00.231300645c2ND FL HALL BATH
70.08.4VlFx0x04.00.242400854c2ND FL LAUNDRY
70.03.5VlFx0x06.00.2588801897c2ND FL LOFT
70.012.9VlFx0x04.00.229280590c2ND FL OS BATH
70.013.3VlFx0x07.00.22813402870c2ND FL OS BED
70.08.5VlFx0x07.00.24213402870c2ND FL OS BED-A
70.06.5VlFx0x04.00.248210448c2ND FL OS WIC
st3120.034.5VlFx0x08.00.12317003642cDINING AREA
st3110.021.3VlFx0x04.00.14580180cEX STE BATH
st3110.026.6VlFx0x07.00.13911202408cEX STE BED
st3110.023.0VlFx0x05.00.143310675cFOYER
st3110.027.3VlFx0x06.00.1388101727cGREAT ROOM
st3110.030.1VlFx0x06.00.1368101727cGREAT ROOM-A
st3120.043.5VlFx0x08.00.11615703364cKITCHEN
2021-Apr-06 14:39:08
Right-Suite® Universal 2021 21.0.05 RSU29964 Page 2
...Documents\Wrightsoft HVAC\WATERSTONE LOT-33.rup Calc = MJ8 Front Door faces: E
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st3 Peak AVF 0 640 0.116 599 14.0 0x0 VinlFlx st1
st1 Peak AVF 0 640 0.116 599 14.0 0x0 VinlFlx
st2 Peak AVF 0 453 0.163 576 12.0 0x0 VinlFlx
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 00 1567 0 0 0 0 x0 0 VlFx