HomeMy WebLinkAboutEvaluation Report; Smart Vent Automatic Foundation Flood VentsDIVISION: 08.00 00—OPENINGS
SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VET_
RECE EVI p
FEB 2 0 2019
ST. Lucie County, permitting
REPORT HOLDER:
SMARTVENT PRODUCTS, INC.
430 ANDBRO DRIVE, UNIT 1
PITMAN, NEW JERSEY 08071
EVALUATION SUBJECT:
SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540-520;
#1540-521; #1540-510; #1540-511; #1540-570; #1540-574; #1540-524; #1540-514
ICC ICC A ICC
C�
PMG LlSTfD
Look for the trusted marks of Conformity!
"2014 Recipient of Prestigious Western States Seismic Policy Council
(WSSPC) Award in Excellence" A Subsidiary of.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not s"CSM
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a l
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied as
=A=WW� 0
to arty finding or other matter in this report, or as to any product covered by the report. r pep+nm
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
IMES Evaluation Report ESR-2074 FBC Supplement
Reissued February 2015
Revised March 2016
This report is subject to renewal February 2017.
www.icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMARTVENT PRODUCTS, INC.
430 ANDBRO DRIVE, UNIT 1
PITMAN,'NEW JERSEY 08071
(877)441-8368
www.smartvent.com
infoD-smartvent.com
EVALUATION SUBJECT:
SMART VElviro AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540.620; #1540-521; #1540-510; #1640-611; #1640-570;
#1540-574; #1540-624; #1540-614
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this. evaluation reportsupplement is to indicate that Smart Vent® Automatic Foundation Flood Vents, recognized
in ICC-ES master report ESR-2074, have also been evaluated for compliance with the codes noted below.
Applicable code editions:
■ 2014 Florida Building Code —Building (FBC)
■ 2014 Florida Building Code —Residential (FRC)
2.0 CONCLUSIONS
The Smart Vente Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comply with the FBC and the FRC, provided the design and installation are in accordance with the International
Building Code! provisions noted in the master report.
Use of the Smart Vent! Automatic Foundation Flood Vents has also been found to be in compliance with the High -Velocity
Hurricane Zone provisions of the FBC and the FRC.
For products falling under Florida Rule 9N-3, verification that the report holder's quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued February 2015 and revised May 2016.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as '
to any finding or other matter in this report, or as to any product covered by the report.
copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1
IMES Evaluation Report ESR-2074
Reissued February 2015 -
Revised May 2016
This report is subject to renewal February 2017.
www.icc-es.ora 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council°
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMARTVENT PRODUCTS, INC.
430 ANDBRO DRIVE, UNIT 1
PITMAN,, NEW -JERSEY 08071
(877)441-8368
www.smartvent.com
info(alsmartvent.com
EVALUATION SUBJECT:
SMART VENT' AUTOMATIC FOUNDATION FLOOD VENTS:
MODELS #1540-520; #1540-521; #1540-510; #1540-511;
#1640-570; #1640-574; #1540-624; #1540-514
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2015, 2012, 2009 and 2006 Intemational Building
Code® (IBC)
■ 2015, 2012, 2009 and 2006 Intemational Residential
Code® (IRC)
■ 2013 Abu Dhabi lntemational Building Code (ADIBC)t
"The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced
in this report are the same sections in. the ADIBC.
Properties evaluated:
■ Physical operation
■ Water flow
2.0 USES
The -Smart Vent® units are engineered mechanically
operated flood vents (FVs) employed to equalize
hydrostatic pressure on walls of enclosures subject to
rising or falling flood waters. Certain models also allow
natural ventilation.
3.0 DESCRIPTION
3.1 General:
When subjected to rising water, the Smart Vent® FVs
internal floats are activated, then'pivot open to allow flow in
either direction to equalize water level and hydrostatic
pressure from one side of the foundation to the other. The
FV pivoting door is normally held in the closed position by
a buoyant release device. When subjected to rising water,
the buoyant release device causes the unit to unlatch,
allowing the door to rotate out of the way and allow flow.
The water level stabilizes, equalizing the lateral forces.
Each unit is fabricated from stainless steel. Smart Vent®
Automatic Foundation Flood Vents are available in
various models and sizes as described in Table 1. The
SmartVENT® Stacking Model #1540-511 and FloodVEN7o
Stacking Model #1540-521 units each contain two
vertically arranged openings per unit.
3.2 Engineered Opening:
The FVs comply with the design principle noted in Section
2.7.2.2 and Section 2.7.3 of ASCE/SEI 24-14 [Section
2.6.2.2 of ASCE/SEI 24-05 (2012, 2009, 2006 IBC and
IRC)] for a maximum rate of rise and fall of 5.0 feet per
hour (0.423 mm/s). In order to comply with the engineered
opening requirement of ASCE/SEI 24, Smart Vent FVs
must be installed in accordance with Section 4.0.
3.3 Ventilation:
The SmartVENT® Model #1540-510 and SmartVENT®
Overhead Door Model #1540-514 both have screen covers
with 1/4-inch-by 1/4-inch (6.35 by 6.35 mm) openings,
yielding 51 square inches (32 903 mmZ) of net free area to
supply natural ventilation. The SmartVENT® Stacking
Model #1540-511 consists of two Model #1540-510 units
in one assembly, and provides 102 square inches
(66 806 mmZ) of net free area to supply natural ventilation.
Other FVs recognized in this report do not offer natural
ventilation.
4.0 DESIGN AND INSTALLATION
SmartVENT® and FloodVENT® are designed to be
installed into walls or overhead doors of existing or new
construction from the exterior side. Installation of the
vents must be in accordance with the manufacturer's
instructions, the applicable code and this report.
Installation clips allow mounting in masonry and concrete
walls of any thickness. In order to comply with the
engineered opening design principle noted. in Section
2.7.2.2 and 2.7.3 of ASCE/SEI 24-14 [Section 2.6.2.2 of
ASCE/SEI 24-05 (2012, 2009, 2006 IBC and IRC)], the
Smart Vent® FVs must be installed as follows:
• With a minimum of two openings on different sides of
each enclosed area.
■ With a minimum of one FV for every 200 square
feet (18.6 mZ) of enclosed area, except that the
SmarIVENT® Stacking Model #1640-511 and
FloodVENT® Stacking Model #1540-521 must be
installed with a minimum of one FV for every
400 square feet (37.2 mZ) of enclosed area.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to ay finding or other matter in this report, or as to any product covered by the report.
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 3
ESR-2074 I Most Widely Accepted an% _;ted Page 2 of 3
■ Below the base flood elevation.
■ With the bottom of the. FV located a maximum of
12 inches (305.4 mm) above the higher of the final
grade or floor and finished exterior grade immediately
under each opening.
5.0 CONDITIONS OF USE
The Smart Vent® FVs described in this report comply with,
or are suitable alternatives to what is specified in, those.
codes listed in Section 1.0 of this report, subject to the
following conditions:
5.1 The Smart Vent® FVs must be installed in accordance
with this report, the applicable code and the
manufacturers installation instructions. In the event of
a conflict, the instructions in this reportgovern.
5.2 The Smart Vent® FVs must not be used in the place
of "breakaway walls" in coastal high hazard areas, but
are permitted for use in conjunction with breakaway
walls in other areas.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Mechanically Operated Flood Vents (AC364), dated
August 2015.
7.0 IDENTIFICATION
The Smart VENT® models recognized in this report must
be identified by a label bearing the manufacturer's name
(Smartvent Products, Inc.), the model number, and the
evaluation report number (ESR-2074).
TABLE 1—MODEL SIZES
MODEL NAME
MODEL NUMBER
MODEL SIZE (in.)
COVERAGE (sq. ft.)
FloodVEN
1540-520
153/a'-X 73/4"
200
SmartVENT®
1540-510
153/4" X 73/4"
200
FloodVENr Overhead Door
1540-524
153/a' X 73/4"
200
SmartVENT® Overhead Door
1540-514
153/4" X 73/a'
200
Wood Wall FloodVENT®
1540-570
14" X 83/4'
200
Wood Wall FloodVENT® Overhead Door
1540-574
14" X 83/4"
200
SmartVENr Stacker
1540-511
16" X 16"
400
FloodVent® Stacker
1540-521
16" X .16"
400 .
For SI: 1 inch = 25.4 mm; 1 square foot = m2
ESR-2074 I Most Widely Accepted; ;crusted Page 3 of 3
FIGURE 1—SMART VENT: MODEL 1540-510
FIGURE 2—SMART VENT MODEL 1540-520
FIGURE 3—SMART VENT: SHOWN WITH FLOOD DOOR PIVOTED OPEN