In-Place Density Test Report
Client:RJM CUSTOM HOMES, INC.UES Technician:Timothy Watson
6917 Vista Parkway North, Suite 1
West Palm Beach, FL 33411
Date Tested:05/18/2021
Project:RJM CUSTOM HOMES
Various Locations, TBD County, FL
Type of Test:
Area Tested:5766 Pinetree Drive, Ft. Pierce Field:ASTM D-6938 Nuclear Gauge Method
Material:Fill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Bottom of Final Grade
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Center of pad.0-1 ft 107.8 11.2 103.8 10.8 96 Pass
2 Southeast corner of pad.0-1 ft 107.8 11.2 105.1 12.0 97 Pass
3 Northwest corner of pad.0-1 ft 107.8 11.2 104.1 11.7 97 Pass
Remarks: 1-2’, 2-3’ HCP=60+, > 95 % Compaction, PASS. HCP tests are empirically correlated to the relative density of the
soil.
Permit: SCL2101-0370
Reviewed By
GFA International, Inc
FBPE Registry No.4930
John Kent
Senior Project Engineer
STATE OF FLORIDA
Professional Engineer No. 63218
This item has been digitally signed and sealed by John Kent on
the date adjacent to the seal. Printed copies of this document are
not considered signed and sealed and the signature must be
verified on any electronic copies.