HomeMy WebLinkAboutStamped Joseph Hamel - PlansetCOVER PAGE NEW PHOTOVOLTAIC SYSTEM 14.85 KW DC4206 SUNRISE BLVD, FORT PIERCE, FL 34982, USAGENERAL NOTESVICINITY MAPSATELLITE VIEWSHEET INDEXCOVER PAGET-001G-001A-101SITE PLANATTACHMENT PLANRESOURCE DOCUMENT1.1.1 PROJECT NOTES:1.1.2 THISPHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THENATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’SLISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODESAS SPECIFIED BY THE AUTHORITY HAVINGJURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVEDAND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH NEC690.41(B)1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIEDAND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDEDTEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGECALCULATED ACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES,PHOTOVOLTAICPANELS, AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN APHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FORTHE APPLICATIONPER 690.4 (D). SHALL BE INSTALLED ACCORDING TOANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3].1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCALBUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT.ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THENEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTINGONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THEEXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMSDETAILED IN THIS DOCUMENT1.3.1 WORK INCLUDES:1.3.2 PV RACKING SYSTEM INSTALLATION - QUICK MOUNT PV1.3.3 PV MODULE AND INVERTER INSTALLATION - Silfab 330W NL /SOLAREDGE SE11400H-US / SOLAREDGE POWER OPTIMIZER P3701.3.4 PV EQUIPMENT ROOF MOUNT1.3.5 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.6 PV LOAD CENTERS (IF INCLUDED)1.3.7 PV METERING/MONITORING (IF INCLUDED)1.3.8 PV DISCONNECTS1.3.9 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.10 PV FINAL COMMISSIONING1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODESCOPE OF WORKSYSTEM SIZE: PTC: 45 x 307.56W = 13.84 kW DC(45)SILFAB 330W NL ATTACHMENT TYPE: ROOF MOUNT MSP UPGRADE: NOPROJECT INFORMATIONOWNERNAME:ELECTRICAL PLANLINE DIAGRAMRESOURCE DOCUMENTA-102E-601R-001R-002A-103RESOURCE DOCUMENTE-602ELECTRICAL CALCULATIONSRESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004R-005REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -T-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA TATIANA HAMELSTC:45 X 330W= 14.85 kW DC(1)SOLAREDGE SE11400H-USNOTESAUTHORITIES HAVING JURISDICTIONBUILDING: ST. LUCIE COUNTYZONING: ST. LUCIE COUNTYUTILITY: FLORIDA POWER & AMP; LIGHT CODESIGN SPECIFICATIONOCCUPANCY: R3/SINGLE FAMILY RESIDENTIAL CONSTRUCTION TYPE / FIRE RATING: 5-BGROUND SNOW LOAD LOCAL: 0 PSFWIND EXPOSURE: BWIND SPEED : 150 MPHAPPLICABLE CODES & STANDARDSBUILDING: IBC 2015 IRC 2015FLORIDA BUILDING CODE (7TH EDITION) ELECTRICAL: NEC 2017FIRE : IFC 2015(45) SOLAREDGE POWER OPTIMIZER P370CONTRACTOR INFORMATION:CONTRACTOR NAME: PALMETTOCONTRACTOR ADDRESS: 1505 KING ST,CHARLESTON,SC 29405CONTRACTOR PHONE: (855) 339-1831PHONE: (904) 703-0170AC SIZE: 11.4 kW ACPLACARDE-603
NOTESREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-2.1.1 SITE NOTES:2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITHOSHA REGULATIONS.2.1.3 THE PV MODULESARECONSIDERED NON-COMBUSTIBLE AND THISSYSTEM IS A UTILITY INTERACTIVE SYSTEM WITHOUT STORAGEBATTERIES.2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.2.1.5 PROPERACCESS AND WORKING CLEARANCE AROUND EXISTINGAND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED ASPERSECTION NEC 110.26.2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, ANDMAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVEDMANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERINGSERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1 EQUIPMENT LOCATIONS:2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BYNEC 110.26.2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATEDFOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31(A),(C) AND NEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C).2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PVMODULES ACCORDING TO NEC 690.34.2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THEINVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT.2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIEDPERSONNEL ACCORDING TO NEC APPLICABLE CODES.2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATEDFOR OUTDOOR USAGE WHEN APPROPRIATE.2.3.1 STRUCTURAL NOTES:2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE ADESIGNATED SPACE BETWEEN MODULES, AND RAILS MUSTALSOEXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THEARRAY/SUBARRAY, ACCORDING TO RAI MANUFACTURER’SINSTRUCTIONS.2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS'SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED &SEALED PER LOCAL REQUIREMENTS.2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILLBE COMPLETEDAND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY ALICENSED CONTRACTOR.2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATERTHAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.2.4.1 WIRING & CONDUIT NOTES:2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FORTHEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS AREBASED ONMINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMITUP-SIZING.2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.4.4 VOLTAGE DROP LIMITED TO 1.5%.2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTERWIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAYW/ SUITABLE WIRING CLIPS.2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE AOR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREEPHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHERCONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTEDSYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE[NEC 110.15].2.5.1 GROUNDING NOTES:2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIRPURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTSSHALL BE RATED FOR SUCH USE.2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43AND MINIMUM NEC TABLE 250.122.2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, ANDENCLOSURES CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND250.136(A).2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALLBE SIZEDACCORDING TO NEC 690.45 AND MICROINVERTERMANUFACTORERS’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“LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITYPERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGSSHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCESHOCK HAZARD FOR EMERGENCY RESPONDERS INACCORDANCE WITH 690.12(A) THROUGH (D).2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDINGTO NEC 690.8, 690.9, AND 240.2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLEBREAKER OR GROUPED FUSES IN ACCORDANCE WITH NEC110.3(B).2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULTCIRCUIT PROTECTION ACCORDING TO NEC 690.11 ANDUL1699B.2.7.1 INTERCONNECTION NOTES:2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE INACCORDANCE WITH [NEC 705.12 (B)]2.7.3 THE SUM OF THE UTILITY OCPD AND INVERTERCONTINUOUS OUTPUT MAY NOT EXCEED 120% OF BUSBARRATING [NEC 705.12(D)(2)(3)].2.7.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE RATING OF THEOVERCURRENT DEVICE PROTECTING THE BUSBAR SHALLNOT EXCEED 120 PERCENT OF THE AMPACITY OF THEBUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BELOCATED OPPOSITE END OF THE BUS FROM THE UTILITYSOURCE OCPD [NEC 705.12(B)(2)(3)].2.7.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUTCOMBINER PANEL, TOTAL RATING OF ALL OVERCURRENTDEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR.HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BEEXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).2.7.6 FEEDER TAP INTERCONECTION (LOADSIDE) ACCORDINGTO NEC 705.12 (B)(2)(1)2.7.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TONEC 705.12 (A) WITH SERVICE ENTRANCE CONDUCTORS INACCORDANCE WITH NEC 230.42 2.7.8BACKFEEDING BREAKERFOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROMADDITIONAL FASTENING [NEC 705.12 (B)(5)].G-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA
JB
INVMSPUMACDSITE PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-A-101TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA1SITE PLANSCALE:1/32" = 1'-0"LEGEND- JUNCTION BOXJB- VENT, ATTIC FAN (ROOF OBSTRUCTION)- PROPERTY LINE- FIRE SETBACK- CHIMNEY (ROOF OBSTRUCTION)- SKYLIGHT (ROOF OBSTRUCTION)NSEW(N) SOLAREDGE SE11400H-US INVERTER(E) UTILITY METER(E) MAIN SERVICE PANEL SUNRISE BLVD(N) VISIBLE LOCKABLE LABELED AND FUSED ACDISCONNECT (UTILITY DISCONNECT)DRIVEWAY106'-11"29'-0"46'-3"137'-10"191'-6"172'-2"60'-6"33'-8"42'-8"57'-11"AUSTRALIAN AVE
JB
INVMSPUMACD11 11 11 11 11 11 11 12 22 22 22 22
2
22
2
22
3 3
33 33
3 3
33 3
3 3
33
ELECTRICAL PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -A-102TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA1ELECTRICAL PLANROOF SECTION(S)TILT - 18°AZIMUTH - 91°MODULE - 22TILT - 18°AZIMUTH - 91°MODULE - 23ROOF 1ROOF 21- MODULE STRING2- MODULE STRING3- MODULE STRINGSCALE:3/32" = 1'-0"LEGEND- JUNCTION BOXJB- VENT, ATTIC FAN (ROOF OBSTRUCTION)- PROPERTY LINE- FIRE SETBACK- CHIMNEY (ROOF OBSTRUCTION)- SKYLIGHT (ROOF OBSTRUCTION)NSEW(N) CONDUIT RUNIN THE ATTICROOF 1ROOF 2(N)SOLAREDGE SE11400H-US INVERTER(E) UTILITY METER(E) MAIN SERVICE PANEL(N) VISIBLE LOCKABLE LABELED AND FUSED ACDISCONNECT (UTILITY DISCONNECT)
1'-10"11'-1"2'-9"37'-1"2'-9"1'-10"16'-7"1'-9"27'-0"4'-0"6'-0"ATTACHMENT PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-A-103TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA - CLAMP- MODULE MOUNT- RAIL1ATTACHMENT PLAN- RAFTERSCALE:1/8" = 1'-0"ROOF 1TILT- 18 DEGAZIMUTH - 91 DEGROOF 2TILT- 18 DEGAZIMUTH - 91 DEGROOF SECTION(S)ROOF MATERIAL -COMPOSITE SHINGLERAFTER SIZE - 2"X4"O.C. SPACING - 24"ROOF 1ROOF 2ROOF MATERIAL -COMPOSITE SHINGLERAFTER SIZE - 2"X4"O.C. SPACING - 24"NOTE TO INSTALL: VERIFY THE ROOF FRAMING INFO BEFORE INSTALLATION AND NOTIFY THE EOR IF THERE IS ANY INCONSISTENCY BETWEEN SITE VERIFICATION AND FOLLOWINGS: 2x4 RAFTERS @ 24" OC SPACING WITH MAX UNSUPPORTED SPAN EQUAL OR LESS THAN 8 FT.
=SOLAREDGE SE11400H-US (240V)OUTPUT: 240 VAC, 47.5A99% CEC WEIGHTED EFFICIENCYNEMA 3R, UL LISTED, INTERNAL GFDIWITH INTEGRATED DC DISCONNECTACDC-+-++-++++---2-+-13==========JUNCTION BOX600 V, NEMA 3UL LISTED-+-++-++++---2-+-13==========SOLAREDGE POWER OPTIMIZER P370DC INPUT POWER - 370 WATTSMAXIMUM INPUT VOLTAGE -60 VDCMPPT RANGE - 8 TO 60 VDCMAXIMUM INPUT CURRENT - 11 ADCMAXIMUM OUTPUT CURRENT - 15 ADC STRINGLIMITATIONS - 8 TO 25 OPTIMIZERS,6000 WATTS STC PER STRING MAXIMUM214151415-+-++-++++---2-+-13==========SILFAB 330W NL14151(E) MAIN BREAKER TOHOUSE 240 V, 200A/2P(TOP FED)(E) MAIN SERVICE200A RATED, 240VNL2L1TO UTILITY GRIDGECGEXISTING GROUNDINGELECTRODE SYSTEMTO EARTHREF. NEC 250.52,250.53(A)MNLOAD/LINE SIDEINTERCONNECTIONAT MAIN PANELPER ART. 705.12(D)GN(E)BI-DIRECTIONALUTILITY METER1-PHASE, 3-W,120V/240VMETER NO.: 751853LOADLINEGL1L2NAC DISCONNECT:VISIBLE, LOCKABLE, LABELED60A FUSED, (2) 60A FUSES, 240VNEMA 3R, UL LISTED4SUPPLY SIDE TAPLINE DIAGRAMREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-E-601TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA (45) SILFAB 330W NL MODULES(3) STRING OF 15 MODULES CONNECTED IN SERIESPROJECTS CAN NOT BE BUILT TO EXCEED 100%OFFSET UP TO A MAXIMUM OF 10 KW AC.PALMETTO USES A 1.35 AC-DC CONVERSION TOARRIVE AT AN INTERNAL MAX DC SYSTEM SIZEIDPHASE CONDUCTOR QTY, SIZEAND TYPE PER CONDUITGROUND CONDUCTOR QTY, SIZEAND TYPE PER CONDUITCONDUITSIZECONDUIT TYPE16AWG #10PV-WIRE/USE-2,COPPER1AWG #6BARE COPPER EGCN/AFREE AIR26AWG #10THWN-2,COPPER1AWG #103/4"EMT32AWG #61AWG #103/4"4THWN-2,COPPERTHWN-2,COPPER EGCTHWN-2,COPPER EGCBARE,COPPER EGCAWG #61NAFREE AIRNEUTRALN/A1AWG #6THWN-2,COPPERN/AEMT52AWG #6AWG #103/4"THWN-2,COPPERTHWN-2,COPPER EGC1AWG #6THWN-2,COPPEREMT1DC SYSTEM SIZE:14.85 kW DC AC SYSTEM SIZE: 11.4 kW AC
ELECTRICALCALCULATIONSREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -E-602TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA DC CONDUCTOR AMPACITY CALCULATIONS:ARRAY TO JUNCTION BOX :DC CONDUCTOR AMPACITY CALCULATIONS:FROM JUNCTION BOX TO INVERTER:AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUITPER NEC 310.15(B)(2)(c)NO. OF CURRENT CARRYING CONDUCTORSCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)CIRCUIT CONDUCTOR SIZE0.810 AWG622°TEMP. CORRECTION PER TABLE (310.16)0.76CIRCUIT CONDUCTOR AMPACITY40AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 1.25 X Isc18.75ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.1624.32ARESULT SHOULD BE GREATER THAN (18.75A) OTHERWISE LESS THE ENTRY FORCIRCUIT CONDUCTOR SIZE AND AMPACITYEXPECTED WIRE TEMP (In Celsius)33°+22° = 55°AC CONDUCTOR AMPACITY CALCULATIONS:No. OF INVERTERNO. OF CURRENT CARRYING CONDUCTORSCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)CIRCUIT CONDUCTOR SIZE16 AWG31TEMP. CORRECTION PER TABLE (310.16)0.96CIRCUIT CONDUCTOR AMPACITY65AEXPECTED WIRE TEMP (In Celsius)33°REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B)1.25 X MAX INVERTER OUTPUT CURRENT59.38ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16TEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) XCIRCUIT CONDUCTOR AMPACITY62.40AResult should be greater than (59.38A) otherwise less the entry for circuit conductor sizeand ampacityPOWER OPTIMIZER (OPTIMIZER P370) MAXIMUM INPUT POWER 370W MINIMUM INPUT VOLTAGE 8 VDC MAXIMUM INPUT VOLTAGE 60 VDC MAXIMUM MODULE ISC11 ADC MAXIMUM OUTPUT CURRENT 15 ADCPERCENT OFVALUESNUMBER OF CURRENTCARRYING CONDUCTORS IN EMT0.804-60.707-90.5010-20AMBIENT TEMPERATURE SPECS RECORD LOW TEMP0° AMBIENT TEMP (HIGH TEMP 2%)33° CONDUIT HEIGHT0.5" ROOF TOP TEMP55° CONDUCTOR TEMPERATURE RATE90° MODULE TEMPERATURE COEFFICIENT OF Voc-0.28%/°CTEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) XCIRCUIT CONDUCTOR AMPACITYSOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # SILFAB 330W NL VMP33.3V IMP9.46A VOC40.5V ISC10.03A TEMP. COEFF. VOC-0.29%/°C PTC RATING291.5W MODULE DIMENSION66.9"L x 39.4W x 1.5"D (In Inch)INVERTER SPECIFICATIONS MANUFACTURER / MODEL #SolarEdge SE11400H-US NOMINAL AC POWER11400 W NOMINAL OUTPUT VOLTAGE 240 VAC NOMINAL OUTPUT CURRENT 47.5EXPECTED WIRE TEMP (In Celsius)55°TEMP. CORRECTION PER TABLE (310.16)0.76NO. OF CURRENT CARRYING CONDUCTORS6CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)1CIRCUIT CONDUCTOR SIZE10AWGCIRCUIT CONDUCTOR AMPACITY40AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B)18.75A1.25 X IscDERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.1630.40ATEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUITCONDUCTOR AMPACITYRESULT SHOULD BE GREATER THAN (18.75A) OTHERWISE LESS THE ENTRY FORCIRCUIT CONDUCTOR SIZE AND AMPACITY
INVMSPUMACDJB (N) PV DISCONNECTMAIN SERVICE PANELUTILITY METERPV ARRAYPLACARDSPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:CAUTION! CAUTION !SOLAR POINT OF INTERCONNECTION! WARNING !
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/28/2021NBSHEET NUMBERREVIEWED BY -E-603LUZ VIZCAINO
13329 WILLOW
BLUESTAR LOOP,
RIVERVIEW, FL 33579,
USAN WARNING: PHOTOVOLTAICPOWER SOURCESOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRIC PV PANELSTURN RAPID SHUTDOWNSWITCH TO THE 'OFF'POSITION TO SHUTDOWN PV SYSTEM ANDREDUCE SHOCK HAZARDIN THE ARRAYAC DISCONNECTWARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALS.TERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZED IN THEOPEN POSITION!!PHOTOVOLTAIC SYSTEM AC DISCONNECT!!OPERATING VOLTAGE:____VOLTSOPERATING CURRENT:____AMPSSOLARBREAKERAC COMBINER BOXPHOTOVOLTAICMICROINVERTERSLOCATED UNDEREACH PV MODULE INROOFTOP ARRAYPHOTOVOLTAIC SYSTEM EQUIPPED WITHRAPID SHUTDOWNRATED AC OUTPUT CURRENT:____NOM. OPERATING VOLTAGE:____DUAL POWER SUPPLYSOURCES: UTILITY GRID AND PVSOLAR ELECTRIC SYSTEMWARNING!!___________KW SOLARDISCONNECT LOCATEDFT___FT___INVERTER OUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNING!LABEL 11AT AC DISCONNECTPHOTOVOLTIC AC DISCONNECT SWITCHRATED OUTPUT CURRENT: 21 ANOMINAL OPERATING VOLTAGE: 240VMAXIMUM VOLTAGE :MAXIMUM CIRCUIT :CURRENTMAX RATED OUTPUTCURRENT OF THECHARGE CONTROLLER :OR DC TO DCCONVERTER (IF INSTALLED)480 V13.5 A15 A
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-002TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-003TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-004TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-005TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT