PROJECT INFORMATION
v-7 wrlgn1 project Summary Jo Date AHU 1 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: RAMOS RESIDENCE 1071 S. HEADER CANAL ROAD, FORT PIERCE, FL Notes: Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 °F Inside db 70 °F Design TD 28 °F Heating Summary Structure 18596 Btuh Ducts 4766 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23363 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heatingg Coolingg Area (ft2) 1877 1877 Volume (ft3) 20329 20329 Air changes/hour 0.22 0.12 Equiv. AVF (cfm) 73 39 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 6.7 kW 22915 Btuh 21 °F 980 cfm 0.042 cfm/Btuh 1.00 in H2O Mar 08, 2021 Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 15170 Btuh Ducts 6714 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipmenf sensible load 20791 Btuh Latent Cooling Equipment Load Sizing Structure 3143 Btuh Ducts 1844 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4987 Btuh Equipment Total Load (Sen+Lat) 25778 Btuh Req. total capacity at 0.70 SHR 2.5 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond CA16NW03000GOA0 Coil FX4DNF037L AHRI ref 9201884 Efficiency 13.5 EER, 16 SEER Sensible cooling 20580 Btuh Latent cooling 8820 Btuh Total cooling 29400 Btuh Actual air flow 980 cfm Air flow factor 0.045 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 30 t" 'ord- wrigl 2021-Mar-08 15:24:08 _ Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E v-7 wrlgn1 project Summary Jo Date AHU 2 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: RAMOS RESIDENCE 1071 S. HEADER CANAL ROAD, FORT PIERCE, FL Notes: Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 °F Inside db 70 °F Design TD 28 °F Heating Summary Structure 21962 Btuh Ducts 3247 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 25209 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Coolingg Area (ft2) 1460 1460 Volume (ft3) 16604 16604 Air changes/hour 0.36 0.19 Equiv. AVF (cfm) 99 53 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 100 EFF 17.5 kW 59813 Btuh 69 °F 787 cfm 0.031 cfm/Btuh 1.00 in H2O Mar 08, 2021 Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 13188 Btuh Ducts 4682 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipmenf sensible load 16977 Btuh Latent Cooling Equipment Load Sizing Structure 2714 Btuh Ducts 1230 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 3944 Btuh Equipment Total Load (Sen+Lat) 20920 Btuh Req. total capacity at 0.70 SHR 2.0 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond CA16NW02400GOA0 Coil FX4DNF025L AHRI ref 9201324 Efficiency 13.0 EER, 16 SEER Sensible cooling 16520 Btuh Latent cooling 7080 Btuh Total cooling 23600 Btuh Actual air flow 787 cfm Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 30 t" 'ord- wrigl 2021-Mar-08 15:24:08 _ Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU 1 MASTER BEDROOM 2 Exposed wall 108.0 ft 36.0 ft 3 Room height 10.8 ft 11.0 ft heat/cool 4 Room dimensions 25.0 x 15.0 ft 5 Room area 1877.0 ft2 375.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 515 355 1421 777 275 179 717 392 2 glazing, clr low-e 0.650 n 18.20 14.99 24 0 437 360 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 40 0 728 600 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 24 0 437 256 24 0 437 256 2 glazing, clr low-e 0.650 n 18.20 10.68 72 0 1310 769 72 0 1310 769 W 13A-40cs 0.143 e 4.00 2.19 276 231 925 505 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 45 3 819 1459 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 260 212 849 464 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 12 12 218 180 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 36 36 655 540 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 tVf✓ 13A-40cs 0.143 w 4.00 2.19 193 145 581 317 121 73 292 160 t CG 2 glazing, clr low-e 0,650 w 18,20 14,11 48 32 874 677 48 32 874 677 C 16X19-0ad 0.408 1.59 1.37 1877 1877 2976 2568 375 375 595 513 F 22A-tph 1.358 38.02 0.00 1877 108 4107 0 375 36 1369 0 6 c) AED excursion 0 502 Envelope loss/gain 16337 9472 5593 3269 12 a) Infiltration 2260 648 719 206 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 5050 0 Subtotal (lines 6 to 13) 18596 15170 6313 3476 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 6 5 14 Subtotal 18596 15170 6319 3481 15 Duct loads 26% 44% 47661 6714 26% 44% 1620 1541 Total room load 23363 21885 7938 5022 Air required (cfm) 980 980 333 225 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 2 M WIC 1 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 16.0 ft 11.0 x 5.0 ft 5 Room area 96.0 ft2 55.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 l; GCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 18,20 14,11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 96 96 152 131 55 55 87 75 F 22A-tPh 1.358 38.02 0.00 96 0 0 0 55 0 0 0 6 c) AED excursion -26 -13 Envelope loss/gain 152 105 87 62 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 250 Subtotal (lines 6 to 13) 152 605 87 312 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 152 605 87 312 15 Duct loads 26% 44% 39 268 26% 44% 22 138 FFTotal room load 191 873 110 450 Air required (cfm) 8 39 5 20 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 2 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET M HALL 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 4.0 x 5.0 ft 4.0 x 4.0 ft 5 Room area 20.0 ft2 16.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 tVf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 t GG 2 glazing, clr low-e 0,650 w 18,20 14,11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 20 20 32 27 16 16 25 22 F 22A-tph 1.358 38.02 0.00 20 0 0 0 16 0 0 0 6 c) AED excursion -11 -1 Envelope loss/gain 32 16 25 21 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13) 32 266 25 21 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -25 -21 14 Subtotal 32 266 0 0 15 Duct loads 26% 44% 8 118 26% 44% 0 0 FFT-o.tal room load 40 384 0 0 required (cfm) 2 1717T 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 3 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name PANTRY LAUNDDRY 2 Exposed wall 0 ft 8.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 75.0 ft 8.0 x 8.0 ft 5 Room area 75.0 ft2 64.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 80 68 272 149 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 12 12 218 180 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 18,20 14,11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 75 75 119 103 64 64 101 88 F 22A-tph 1.358 38.02 0.00 75 0 0 0 64 8 304 0 6 c) AED excursion -4 -27 Envelope loss/gain 119 98 896 389 12 a) Infiltration 0 0 145 42 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 200 Subtotal (lines 6 to 13) 119 98 1042 631 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 5 14 12 14 Subtotal 125 104 1056 643 15 Duct loads 26% 44% 321 46 26% 44% 271 284 Total room load 157 150 1327 927 Air required (cfm) 7 7 56 42 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 4 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name ENTRY HALL DINING RM 2 Exposed wall 0 ft 23.0 ft 3 Room height 10.0 ft heat/cool 12.0 ft heat/cool 4 Room dimensions 6.0 x 4.0 ft 15.0 x 12.0 ft 5 Room area 24.0 ft2 180.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 24 24 96 53 2 glazing, clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 180 144 577 315 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 01 0 36 36 655 540 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 tVf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 72 72 288 158 t CG 2 glazing, clr low-e 0.650 w 18.20 14.11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 24 24 38 33 180 180 285 246 F 22A-tph 1.358 38.02 0.00 24 0 0 0 180 23 875 0 6 c) AED excursion -1 -68 Envelope loss/gain 38 31 2776 1243 12 a) Infiltration 0 0 501 144 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 200 Subtotal (lines 6 to 13) 38 31 3277 1587 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -38 -31 0 0 14 Subtotal 0 0 3277 1587 15 Duct loads 26% 44% 0 0 26% 44% 840 702 Total room load 0 0 4117 2289 Air required (cfm) 01 0 173 103 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 5 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name STORAGE CLST M BATH 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 6.0 x 5.0 ft 15.0 x 12.0 ft 5 Room area 30.0 ft2 180.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T GG 2 glazing, clr low-e 0,650 w 18,20 14,11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 30 30 48 41 180 180 285 246 F 22A-tph 1.358 38.02 0.00 30 0 0 0 180 0 0 0 6 c) AED excursion -12 -27 Envelope loss/gain 48 29 285 220 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 250 400 Subtotal (lines 6 to 13) 48 279 285 620 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 14 12 6 5 14 Subtotal 62 291 292 625 15 Duct loads 26% 44% 16 129 26% 44% 75 277 FFTotal room load 78 420 367 901 Air required (cfm) 3 19 15 40 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 6 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 1 Date: Mar08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FAMILY RM KITCHEN 2 Exposed wall 41.0 ft 0 ft 3 Room height 12.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 412.0 ft 1.0 x 350.0 ft 5 Room area 412.0 ft2 350.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 240 176 705 385 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 24 0 437 360 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 40 0 728 600 0 0 0 0 11 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 252 207 829 453 0 0 0 0 2 glazing, clr low-e 0.650 a 18.20 32.42 45 3 819 1459 0 0 0 0 l; GCI 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 18,20 14,11 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 412 412 653 564 350 350 555 479 F 22A-tph 1.358 38.02 0.00 412 41 1559 0 350 0 0 0 6 c) AED excursion -168 -143 Envelope loss/gain 5730 3652 555 336 12 a) Infiltration 894 256 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 3000 Subtotal (lines 6 to 13) 6623 3909 555 3336 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 5 10 8 14 Subtotal 6630 3914 564 3344 15 Duct loads 26% 44% 16991 1732 26% 44% 145 1480 Total room load 8329 5646 709 4823 Air required (cfm) 349 253 30 216 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 7 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name AHU 2 OFFICE 2 Exposed wall 153.0 ft 23.0 ft 3 Room height 11.4 ft 12.0 ft heat/cool 4 Room dimensions 15.0 x 14.0 ft 5 Room area 1460.0 ft2 210.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 440 297 1189 650 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 15 0 273 225 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 128 0 2330 1919 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 542 512 2050 1120 72 72 288 158 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 l; GCI 2 glazing, clr low-e 0.650 a 18.20 27.15 30 2 546 814 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 460 346 1385 757 180 144 577 315 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 36 36 655 540 36 36 655 540 2 glazing, clr low-e 0.650 s 18.20 13.26 18 18 328 239 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 12 12 218 128 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 48 48 874 513 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 234 234 937 512 24 24 96 53 T CG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 1460 1460 2315 1998 210 210 333 287 F 22A-tph 1.358 38.02 0.00 1460 153 5818 0 210 23 875 0 6 c) AED excursion 0 -12 Envelope loss/gain 18918 9414 2824 1340 12 a) Infiltration 3044 874 501 144 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2900 100 Subtotal (lines 6 to 13) 21962 13188 3325 1584 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 97 34 14 Subtotal 21962 13188 3422 1618 15 Duct loads 15% 36% 3247 4682 15% 36% 506 574 FFTotal room load 25209 17870 3928 2192 Air required (cfm) 787 787 123 97 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 8 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING ROOM CLST 2 2 Exposed wall 20.0 ft 2.0 ft 3 Room height 13.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 368.0 ft 2.0 x 8.0 ft 5 Room area 368.0 ft2 16.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 260 132 529 289 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 128 0 2330 1919 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 20 20 80 44 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T GG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 368 368 583 503 16 16 25 22 F 22A-tph 1.358 38.02 0.00 368 20 760 0 16 2 76 0 6 c) AED excursion -25 -1 Envelope loss/gain 4202 2687 181 65 12 a) Infiltration 472 136 36 10 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13) 4674 3322 218 76 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 152 50 -218 -76 14 Subtotal 4826 3372 0 0 15 Duct loads 15% 36% 714 1197 15% 36% 0 0 FFTotal room load 5540 4569 0 0 Air required (cfm) 173 201 0 0 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 9 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 WIC 3 2 Exposed wall 26.0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 176.0 ft 5.0 x 5.0 ft 5 Room area 176.0 ft2 25.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 120 120 480 263 0 0 0 0 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 I; GCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 140 122 488 267 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 18 18 328 239 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 176 176 279 241 25 25 40 34 F 22A-tph 1.358 38.02 0.00 176 26 989 0 25 0 0 0 6 c) AED excursion -11 0 Envelope loss/gain 2564 998 40 34 12 a) Infiltration 472 136 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 400 0 Subtotal (lines 6 to 13) 3036 1533 40 34 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 121 42 0 0 14 Subtotal 3158 1575 40 34 15 Duct loads 15% 36% 467 559 15% 36% 6 12 FFTotal room load 7 3624 2134 45 46 Air required (cfm) 1 1113 94 1 2 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 10 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 BEDROOM 3 2 Exposed wall 0 ft 14.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 5.0 x 5.0 ft 1.0 x 186.0 ft 5 Room area 25.0 ft2 186.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 140 110 440 241 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 30 2 546 814 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 25 25 40 34 186 186 295 254 F 22A-tph 1.358 38.02 0.00 25 0 0 0 186 14 532 0 6 c) AED excursion -2 86 Envelope loss/gain 40 32 1814 1396 12 a) Infiltration 0 0 254 73 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 300 100 Subtotal (lines 6 to 13) 40 332 2068 1569 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 152 50 152 50 14 Subtotal 191 382 2220 1619 15 Duct loads 15% 36% 28 136 15% 36% 328 575 FFTotal room load 220 517 2548 2193 Air required (cfm) 7 23 80 97 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 11 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 4 BATH 3 2 Exposed wall 6.0 ft 0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 7.0 x 6.0 ft 7.0 x 6.0 ft 5 Room area 42.0 ft2 42.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 60 60 240 131 0 0 0 0 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 l; CCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 Vf✓ 13A-40cs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 42 42 67 57 42 42 67 57 F 22A-tph 1.358 38.02 0.00 42 6 228 0 42 0 0 0 6 c) AED excursion -5 -5 Envelope loss/gain 535 183 67 53 12 a) Infiltration 109 31 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 600 Subtotal (lines 6 to 13) 644 715 67 653 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 228 75 14 Subtotal 644 715 294 728 15 Duct loads 15% 36% 951 254 15% 36% 44 258 Total room load 739 968 338 986 Air required (cfm) 23 43 11 43 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 12 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W 111 1y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 WIC 4 2 Exposed wall 33.0 ft 12.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 Room dimensions 1.0 x 186.0 ft 6.0 x 6.0 ft 5 Room area 186.0 ft2 36.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 120 105 420 230 60 60 240 131 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 15 0 273 225 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 150 150 601 328 0 0 0 0 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 l; GCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 01 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 0 0 0 0 tVf✓ 13A-40cs 0.143 w 4.00 2.19 60 60 240 131 60 60 240 131 t CG 2 glazing, clr low-e 0.650 w 0.00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 186 186 295 254 36 36 57 49 F 22A-tph 1.358 38.02 0.00 186 33 1255 0 36 12 456 0 6 c) AED excursion -13 -3 Envelope loss/gain 3084 1156 994 309 12 a) Infiltration 599 172 218 63 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 400 0 Subtotal (lines 6 to 13) 3683 1728 1212 372 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 114 38 152 50 14 Subtotal 3797 1765 1364 422 15 Duct loads 15% 36% 561 627 15% 36% 202 150 Total room load 4359 2392 1565 571 Air required (cfm) 136 105 49 25 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 13 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E IL .r W III I,y111 1111 Right-J® Worksheet Job: AHU 2 Date: near08,2021 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALLWAY FOYER 2 Exposed wall 9.0 ft 8.0 ft 3 Room height 10.0 ft heat/cool 15.0 ft heat/cool 4 Room dimensions 4.0 x 13.0 ft 8.0 x 12.0 ft 5 Room area 52.0 ft2 96.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft� °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 n 0.00 0.00 0 0 0 0 0 0 0 0 W 13A-40cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 a 0.00 0.00 0 0 0 0 0 0 0 0 I; CCI 2 glazing, clr low-e 0.650 a 18.20 27.15 0 0 0 0 0 0 0 0 13A-4ocs 0,143 s 4.00 2.19 0 0 0 0 120 60 240 131 2 glazing, clr low-e 0.650 s 0.00 0.00 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 13.26 0 0 0 0 0 0 0 0 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 12 12 218 128 2 glazing, clr low-e 0.650 s 18.20 10.68 0 0 0 0 48 48 874 513 Vf✓ 13A-40cs 0.143 w 4.00 2.19 90 90 360 197 0 0 0 0 T CG 2 glazing, clr low-e 0,650 w 0,00 0.00 0 0 0 0 0 0 0 0 C 16X19-0ad 0.408 1.59 1.37 52 52 82 71 96 96 152 131 F 22A-tph 1.358 38.02 0.00 52 9 342 0 96 8 304 0 6 c) AED excursion -2 -7 Envelope loss/gain 785 266 1789 897 12 a) Infiltration 163 47 218 63 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 01 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 948 313 2007 959 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -948 -313 0 0 14 Subtotal 0 0 2007 959 15 Duct loads 15% 36% 0 0 15% 36% 297 341 Total room load 0 0 2303 1300 Air required (cfm) 0 0 72 57 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - >fit' -Ill wrigl 2021-Mar-0815:24:08 Right -Suite® Universal 2021 21.0.02 RSU08101 Page 14 mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E t-T wrignI Duct System Summary Job: Date AHU 1 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: RAMOS RESIDENCE 1071 S. HEADER CANAL ROAD, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 980 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 980 cfm 184 ft Mar 08, 2021 Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk DINING RM h 4117 173 103 1.000 7.0 Ox0 VIFx 34.0 115.0 st2 FAMILYRM h 4164 175 126 1.000 7.0 Ox0 VIFx 27.5 135.0 st5 FAMILY RM-A h 4164 175 126 1.000 7.0 Ox0 VIFx 31.5 135.0 st5 KITCHEN c 2412 15 108 1.000 7.0 Ox0 VIFx 27.0 115.0 st2 KITCHEN -A c 2412 15 108 1.000 7.0 Ox0 VIFx 32.4 115.0 st2 LAUNDDRY h 1327 56 42 1.000 6.0 Ox0 VIFx 34.2 115.0 st2 M BATH c 901 15 40 1.000 6.0 Ox 0 V I Fx 14.4 115.0 st 1 M TOILET c 384 2 17 1.000 4.0 Ox0 VIFx 16.7 115.0 st1 M WIC 1 c 450 5 20 1.000 5.0 Ox0 VIFx 13.1 115.0 st1 M W I C 2 c 873 8 39 1.000 5.0 Ox 0 V I Fx 15.1 115.0 st 1 MASTER BEDROOM h 3969 167 112 1.000 7.0 Ox0 VIFx 32.1 135.0 st5 MASTER BEDROOM -A h 3969 167 112 1.000 7.0 Ox0 VIFx 23.6 135.0 st5 PANTRY c 150 7 7 1.000 4.0 Ox0 VIFx 35.6 115.0 st2 STORAGE CLST c 420 3 19 1.000 4.0 Ox0 VIFx 33.7 150.0 st2 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st2 Peak AVF 268 385 1.000 491 12.0 0 x 0 VinlFlx st5 Peak AVF 682 478 1.000 869 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 712 595 1.000 666 14.0 0 x 0 VinlFlx -- - -- ift-f'1111111- wrigl 2021-Mar-0815:24:17 .,,,.� .. Right -Suite® Universal 2021 21.0.02 RSU08101 Page 1 L ✓ ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox0 980 980 0 0 0 0 Ox 0 VIFx - -- 311ft-l""1111IF wrigl Right -Suite® Universal 2021 21.0.02 RSU08101 �� ✓ ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E f z4➢0i E P, ETail..i M 16wZ1 E VA Page 2 t-T wrignI Duct System Summary Job: Date AHU 2 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM For: RAMOS RESIDENCE 1071 S. HEADER CANAL ROAD, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 787 cfm Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H 20 1.000 i n/ 100ft 787 cfm 173 ft Mar 08, 2021 Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 c 517 7 23 1.000 5.0 Ox 0 VIFx 16.5 115.0 st4 BATH 3 c 986 11 43 1.000 6.0 Ox 0 VIFx 7.3 115.0 st3 BATH 4 c 968 23 43 1.000 6.0 Ox 0 VIFx 12.3 115.0 st3 BEDROOM 2 h 3624 113 94 1.000 7.0 Ox0 VIFx 16.5 115.0 st4 BEDROOM 3 c 2193 80 97 1.000 7.0 Ox0 VIFx 13.8 115.0 st4 BEDROOM 4 h 4359 136 105 1.000 7.0 Ox0 VIFx 9.6 115.0 st3 FOYER h 2303 72 57 1.000 6.0 Ox0 VIFx 38.1 135.0 st6 LIVING ROOM c 2285 86 101 1.000 7.0 Ox0 VIFx 35.8 135.0 st6 LIVING ROOM -A c 2285 86 101 1.000 7.0 Ox0 VIFx 36.6 135.0 st6 OFFICE h 3928 123 97 1.000 7.0 Ox0 VIFx 35.3 135.0 st6 WIC 3 c 46 1 2 1.000 4.0 Ox0 VIFx 16.2 115.0 st4 WIC h 1565 49 25 1.000 5.0 Ox0 VIFx 12.3 115.0 st3 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st3 Peak AVF 219 217 1.000 626 8.0 0 x 0 VinlFlx st6 Peak AVF 367 355 1.000 674 10.0 0 x 0 VinlFlx st4 st4 Peak AVF 568 570 1.000 726 12.0 0 x 0 VinlFlx -- - -- ift-f'1111111- wrigl 2021-Mar-0815:24:17 .,,,.� .. Right -Suite® Universal 2021 21.0.02 RSU08101 Page 3 L ✓ ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 787 787 0 0 0 0 Ox 0 VIFx - -- 311ft-l""1111IF wrigl Right -Suite® Universal 2021 21.0.02 RSU08101 �� ✓ ...mnets\Wrightsoft HVAC\RAMOS REVISION 3-8-21.rup Calc = MJ8 Front Door faces: E f z4➢0i E P, ETail..]Mi 16wZ1 E VA Page 4 This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.