Loading...
HomeMy WebLinkAboutdoc02426320210524113407V SAINT LUCIE COUNTY FIRE DISTRICT PLAN REVIEW FORM 5160 N.W. Milner Drive Port Saint Lucie, FL 3.4983 Telephone: 772-621-3322 Fax: 772-,-;21-3604 Web Address: ; ,.-.,w.slcfd.com I S LC Sailfish Bldg 481G Ocean palms Drive Unit 1-9 -- --- --_ _ —'� Ft Pierce IB-21-172 i908-0214 Cardinal S.uthem Equities P.O. Box 643328 i Architect/Engineer FrankCSnedakerJr 6 -- IAoartmeni (Condo) Number of Stories i4 AFS Permit Requ red FA Permit lReouired _ I I --- 1 � Telephone (954) 410-3030 (954) 561-4155 32,464 1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only. 2. All revisions, including the electronic copy must be received prior to pennitting. 3. The Fire Marshal requires 24 hour notice on all inspections. 4. A Radio coverage Pre -Survey Signal Strength inspection is required before any final inspection is scheduled. S. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office. 6. Failed inspections require payment of fee prior to rescheduling of further inspections. 7. Penetrations through rated assemblies shall he of the proper UL design. Design criteria shall be submitted with the construction plans. 8. Fire alarm panels shall be located indoors within air conditioned space. 9. Plans and construction are subject to corrections in the field to maintain code compliance. 10. Automatic fan shutdown is required for HVAC systemis that exceed 2,^00 cfm design capacity. 11. The Installation or Alteration of Fire Sprinklers, Fire Alarrns, and Fixed Fire Protection. Systems require a separate review and permit. THE CURRENTLY ADOPTED VERSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED. BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY ARMING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING A CERTIFICATE OF OCCUPANCY. See General Notes Above and Required Revisions Below 1. A separate review and permit is required for the installation or alteration of the fire alarm and fire. 2. Automatic fan shutdown is required for HVAC system,'s that exceed 2,000 cfm design capacity. Provide a remote test and inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s) shall be tied into the `ire alarm system,. 3. Stair detail: Tread min : 11 - Risers rTiax 7 Reviewed by :O^yJergEi —__ ---- 1 Date'05 11-2C2?