HomeMy WebLinkAboutfire dept approvalSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
Al60 N.W. Milner Drive
Port Saint Lucie, FL :34983
Telephone: 772-621-3322
Fax. 772-621-3604
Web Address: www.slcfd.com
Building Dept. SLC `—' - y�— —� FMO Permit # i B-21-187
Project Name Maverick Boat Phase li — _ _— -- — —j BLDG Permit # 12105-0262
Address 4.551 St Lude Bv!d _ — i ^--� City I Ft Pierce
Contractor IRichard KDavis
Address P.O. B.f. 86 City i Fo(t Pierce
State �j FL — — — Zip 14954 —-- — — —� Telephone i (772) 461-8335
-- — r
Architect/Engineer Brent A VJ..d Architecture j Telephone j (772) 220-1217
Occupancy Type Industrial Construction Type li-t: j Square Feet 106,250 i
Occupant Load 534 per clans Number of Stories 1 Access Box j Required Access Key Switch I
AFSPermit Required — —J FAPermit lRRequired —_ FFPPermit Required
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION 15 CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. The Installation or Alteration of Fire Sprinkiers, Fire Alar-ns, and Fixed;=ire Protection Systems require a separate review and
permit. Spray booth(S) shaii be protected with an U'.L. approved Fire Protection Suppression System.
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,00, cfm design capacity. Provide a remote test and
inspect appliance Equipped with an audible/visuai indicator for each HVAC duct Ernoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm system.
Page of �1 Reviewed by l ony Jerger — �— �— Date 05-25-2021