FL# FL21580-R2
Application Type Revision
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer Florida Metal Products Inc.
Address/Phone/Email 6940 Stuart Ave
Jacksonville, FL 32254
(904)783-8400
Clark@flamco.com
Authorized Signature FLPA Services
Flpaserv@yahoo.com
Technical Representative Clark jones
Address/Phone/Email p c box 6310
jacksonville, FL 32236
(904) 783-8400
Clark@Flamco.com
Quality Assurance Representative Clark jones
Address/Phone/Email. p o box 6310
jacksonville, FL 32236
(904)783-8400
Clark@flamco,com
Category Roofing
Subcategory Roofing Accessories that are an Integral Part of the Roofing System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report- Hardcopy Received
Florida Engineer or Architect Name who developed the James L. Bucker, P.E.@ CBUCK Engineering
Evaluation Report
Florida License PE-31242
Quality Assurance Entity Keystone Certifications,Inc.
Quality Assurance Contract Expiration Date 12/31/2024
Validated By Steven M. Urich,PE
Validation Checklist- Hardcopy Received
Certificate of Independence FL21580 R2 C0I Certific&e-Offndep_pdif
Referenced Standard and Year(of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
1708.2
Product Approval Method Method 2 Option B
Date Submitted 09/25/2020
Date Validated 09/27/2020
Date Pending FBC Approval 10/04/2020
Date Approved 12/16/2020
Summary of Products
I'IL# Model, Number or Name Description
21580.1 1-FLAMCO"Off-Ridge Roof Vent" Low profile, off-ridge roof vent for pitched roofs fabricated from
26 gauge, G-90 primed, galvanized steel
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL21580 R2 II 1 OffRidgeRoofVent EVALREPORT.pdr
Approved for use outside HVHZ:Yes Verified By: James L. Buckner,P.E. @ CBUCK Engineering P.E.
Impact Resistant: No #31242
Design Pressure: +N/A/-46 Created by Independent Third Party: Yes
Other: Refer to Evaluation Report for Limitations and Evaluation Reports
Conditions of Use. Refer to manufacturer's installation FL21580 R2 AE 1 OffRidgeRoofVent EVALREPORT,pdf
instructions as a supplemental guide for attachment. Created by Independent Third Party:Yes
21580.2 IA�MCO
Gooseneck Roof Vent" Gooseneck style roof vents for sloped shingle or tile roofs
21580.2
fabricated from 26 gauge,G-90 primed,galvanized steel
Limits of Use "V Installation Instructions
Approved for use in HVHZ: No FL21580 R2 II 2 Goose neckRoofVent EVALREPORT.pdf
Approved for use outside HVHZ:Yes Verified By: James L. Buckner, P.E. @ CBUCK Engineering P.E.
Impact Resistant: No #31242
Design Pressure: +N/A/-90 Created by Independent Third Party: Yes
Other: Refer to Evaluation Report for Limitations and Evaluation Reports
Conditions of Use. Refer to manufacturer's installation FL21580 R2 AE 2 GooseneckRoofVent EVALREPORT.pdf
instructions as a supplemental guide for attachment. Created by Independent Third Party: Yes
21580.3 3-FLAMCO "RV 10.Ridge Vent" Aluminum Ridge Vents for pitched roofs fabricated from 0.025"
Aluminum
Limits of Use Installation Instructions --II
Approved for use in HVHZ: No FL21580 R2 II 3 RV10 RidgeVent EVALREPORT.pdf
Approved for use outside HVHZ:Yes Verified By:James L. Buckner, P.E. @ CBUCK Engineering P.E.
Impact Resistant: No #31242
Design Pressure: N/A Created by Independent Third Party: Yes
Other: Refer to Evaluation Report for Limitations and Evaluation Reports
Conditions of Use. Refer to manufacturer's installation FL21580 R2 AE 3 RV10 RidgeVent EVALREPORT.pdf
instructions as a supplemental guide for attachment. Created by Independent Third Party:Yes
0
Contact Us::2601 Blair Stone Road,Tallahassee FL 32399 Phone:950-487-1824
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility statement::Refund Statement
Under Florida law,email addresses are public records.if you do not want your e-mail address released in response to,a public-records request,do not send electronic
mall to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.'Pursuant to Section 455.275(1),
Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if they have one.The emails
provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply a personal address,please
provide the Department with an email address which can be made available to the public.To determine If you are a licensee under Chapter 455,F.S.,please click here.
Product Approval Accepts:
igi�
Credit Card
Safe
A.
I
i
t.SUCK &nq1nPer1nQ .
rMPP�1f0WW S�rW=rLJreDl (�roQl�aPL-r1nQ
- CBUCK,Inc.Certificate of Authorization#8064
Evaluation Report
FLAME® "RV10"'
Ridge Vent
Manufacturer:
HoNda Metal products, Deco
6940 Stuart.Avenue
Jacksonville, FL 32254
for
Florida Product Approval
FL 21580.3 R2
Florida Building Code 1th Edition (2020)
Method: 2 - B
Category: Roofing
Sub - Category: Roofing Accessories that are an Integral
Part of the Roofing System
Product Name: "Ridge Vent"
Product Description: Roof Vent
Attached To: Wood Deck
Prepared by: This item has been electronically signed and sealed by
James L.Buckner,P.E.,on this date using a Digital Signature.
James L. Buckner, P.E., SECB Printed copies of this document are not considered signed
and sealed, and the signature must be verified on any
Florida Professional Engineer# 31242 electronic copies. `,ttltlllll/,�/
Florida Evaluation ANE ID: 1916 `. �a,\GEN&
`�P�•'•LtCENSF'•��,p
Project Manager: Diana Galloway. = *' No31242
Report No. 20-244-RV10-ER
(Revises 17-185-RV10-ER,FL 21580.3 RI) LUZ
Date: 09/25/20 T . STATE OF •��
��s •.FCORtOP.•' j�?�
///JONA%-S
Contents:
Evaluation Report Pages 1—9 2020.09.25 14:33:30-04'00'
CBUCK,Inc.dba CBUCK Engineering
Phone:(561)491-9927•Email:cbuck@cbuckinc.net•Website:www.cbuc.kinc.net
Business:1374 Community Dr.,Jupiter,FL 33458•Corp/Mailing:2637 E.Atlantic Blvd,tt34069,Pompano Beach,FL 33062
FL#: FL 21580.3 R2
Date: 09/25/20
CBU EngineerInQ
Report No.: 20-244-RV10-ER
Page 2 of 5.
Spealc3tfl-j Sz)tr 8a$urc3ll E 1 gineerliraq CBUCK,Inc.Certificate of Authorization#8064
1.0 Manufacturer: Florida Metal Products,Inc. dba FLAMCO
6940 Stuart Avenue
Jacksonville, Florida 32254
(800) 634-8400
http://flamco.com
2.0 Manufacturing Plant: Jacksonville, Florida
3.0 Product:
3.1 Product Name: "RV10"
3.2 Product Description: Ridge Vent
4.0 Evaluation Scope:
4.1 Compliance with the following
Florida Building Code 7th Edition (2020)
4.2 Evaluation Method:
Florida!Product Approval Rule 61G20-3.005 (2) (b)
4.3 Evaluation Classification:
Category: Roofing
Sub Category: Roofing Accessories that are an Integral part of the Roofing System
4.4 Properties Evaluated
Structural (Wind Resistance) Properties
4.5 Limits of Evaluation:
This product assembly evaluation is limited to compliance with section 4.1 to section 4.4 of
this report.
5.0 Evaluated Uses:
FLAMCO "RV10" ridge vent is used as a roof ventilator.
6.0 Product Assembly Description:
6.1 General:
The FLAMCO "RV10" are ridge vents for pitched roofs fabricated from nominal 0.025" coated
aluminum mechanically attached to Plywood Deck.
7.0 General Assembly as Evaluated:
Refer to section 15.0 of this report for product assembly components/materials&standards.
8.0 Support System:
(Design of support system 'is outside the scope of this evaluation.)
8.1 Type: Wood Deck
8.2 Description: 15/32" (min.) or greater plywood, or
Wood plank deck(based on minimum density/specific gravity of 0.42)
9.0 Slope:
Minimum slope shall be 2:12: (and in compliance with FBC Chapter 15 based on the type of roof covering,
applicable code sections and in accordance with manufacturer's recommendations.)
FL#: FL 21580.3 R2
Date: 09/25/20
C: Report No.: 20-244-RV10-ER
Page 3 of 5
Speala f-U Structural E plineerinq CBUCK,Inc.Certificate of Authorization#8064
10.0 Performance:
The following test protocols were performed to demonstrate compliance with the intent of the code:
10.1 TAS-100(A)-95 - Wind and Wind Driven Rain Resistance and/or Increased Windspeed Resistance of
Soffit Ventilation Strip and Continuous or Intermittent Ventilation System Installed at the Ridge Area.
11.0Code Compliance:
11.1 The product assembly described herein has demonstrated compliance with the Florida Building Code
7th Edition (2020) Section 1708.2.
12.0 Limitations and Conditions of Use:
12.1 Design of support system is outside the scope of this report. Support shall be structural framing
members complying with the code and shall be designed by others.
12.2 Scope of"Limitations and Conditions of Use"for this evaluation:
This evaluation report for "State Approval" contains technical documentation, specifications and
installation method(s) which include "Limitations and Conditions of Use" throughout the report in
accordance with Rule 61G20-3.005. Per Rule 61G20-3.004, the Florida Building Commission is the
authority to approve products under"State Approval".
12.3 Option for application outside "Limitations and Conditions of Use'-'
Rule 61G20-3.005(1)(e) allows engineering analysis for "project specific approval by the local
authorities having jurisdiction in accordance with the alternate methods and materials authorized in
the Code". Any modification of the product as evaluated in this report and approved by the Florida
Building Commission is outside the scope of this evaluation and will be the responsibility of others.
12.4 This report is a building code product evaluation per FLPE rule (FAC) 61G15-36 to comply with
Florida product approval rule (FAC) 61G20-3. This evaluation report is part of the Florida Building
Commission approval for the listed code related criteria. This report by James Buckner, P.E. and
CBUCK Engineering is not a design certification of code compliance construction submittal
documentation, per FBC section 107,for any individual structure,site specific or permit design.
12.5 This product has been evaluated to a maximum height of 33 feet.
12.6 Refer to applicable building code for ventilation requirements.
12.7 All metal components and fasteners shall be corrosion resistant in accordance with FBC.
12.8 Fire Classification is outside the scope of Rule 61G20-3, and is therefore not included in this
evaluation.
12.9 This report does not evaluate the use of this product assembly as described in this report for use in
the High Velocity Hurricane Zone code section. (Dade & Broward Counties)
13.0 Quality Assurance:
The manufacturer has demonstrated compliance of products in accordance with the Florida Building Code
and Rule 61G20-3.005 (3) for manufacturing under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc., (FBC Organization#QUA ID:1824).
FL#: FL 21580.3 R2
Date: 09/25/20
ne L
ring Report No.: 20-244-RV10-ER.BO NCK r=nq- me
Page 4 of 5
�pscilermj SI"rucfrurc5l EngineerIng CBUCK,Inc.Certificate of Authorization#8064
14.0 System/Components
14.1"RV 10 Ridge Vent"
14.1.1 Material: Aluminum
14.1.2 Thickness: 0.025" (nominal,with coating)
14.1.3 Corrosion Resistance: In compliance with FBC Section 1507.4.3:
ASTM B209
14.1.4 Overall Product Dimensions (nominal):
14.1.4.1 Length(s): 10 ft. (max.)
14.1.4.2 Width: 8-3/8 in. (±%" nominal)
14.1.4.3 Height: 2-1/4 in. (±%" nominal)
14.2 Fastener:
14.2.1 Base Fastener: Attaches Roof Vent to Deck
14.2.1.1 Type: Smooth or Ring Shank Roofing Nails
14.2.1.2 Size: 6d x 2" (Long)
14.2.1.3 Material: Aluminum
14.2.1.4 Corrosion Resistance: Per FBC Section 1506.5
14.2.1.5 Standard: Per ASTM F 1667
14.3 Roof Adhesive:
14.3.1 Type: Standard Heavy bodied Flashing Cement
14.3.2 Description: Asbestos-free asphalt based roof cement
14.3.3 Application Size: 1/4"thick (min.)
14.3.4 Standard: Per ASTM D 4586 Type I
15.0 Installation Method:
(Refer to installation method at the end of this evaluation report.)
Prepare deck opening by trimming any shingles or tiles & existing nails that may interfere with ridge vent
installation. Apply roof cement to the underside, back and side flanges of the ridge vent. Cement should
be a 1/4"thick and extend 2" onto roof underlayment. (Install cement in compliance with manufacturer's
installation guidelines.) Position vent base flange beneath loosened shingles and align with deck opening.
Attach the unit side flanges to deck with fasteners per Section 14.2 spaced 6" o.c. and 1-1/2"- 2" from
each end. Apply Roofing Cement to exposed fastener heads. Minimum fastener penetration thru bottom
of support, 3/16".
The FLAMCO "RV 10 Ridge Vent" shall be installed in compliance with the installation method listed in
this report and applicable code sections of FBC 7th Edition (2020). The installation method described
herein is in accordance with the scope of this evaluation report. Refer to manufacturer's installation
instructions as a supplemental guide for attachment.
16.0Evaluation Reference Data:
16.1 TAS 100 (A)Wind Driven Rain Test
By Fenestration Testing Laboratory, Inc. (FTL) (FBC Organization#TST ID: 1657)
Project#16-6647, Lab#9124, Dated: 11/09/16
16.2 Quality Assurance
By Keystone Certifications, Inc. (FBC Organization#: QUA 1824)
Licensee#440
16.3 Engineering Analysis
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization#ANE 1916)
16.4 Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization#ANE 1916)
FL#: FL 21580.3 R2
Date: 09/2S/20
Report No.: 20-244-kV10-ER
Page 5 of 5
�peala Lj Structural ural r=ng1r =L=r1 q CBUCK,Inc.Certificate of Authorization#8064
Florida Metal Products, Inc.
FLAMCO
"RV 10" Ridge Vent
2-1/4"
(fi/s'I
8-3/811 1/4„)
"RV 10 Ridge Vent"
Profile View