HomeMy WebLinkAboutRegulator SpecsBulletin LP-7: R122H
6lolcn Min
Type R122H First -Stage Regulator
Introduction
The Type R122H is an Undeiwnters Laboratories listed
regulator designed for Two -Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks- The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
• 20 Year Recommended Replacement Life -The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both internally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps -Built-in 1/6 inch NPT gauge
taps onficed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easytesting.
• Durability - A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation - A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation -The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the lightest Installations.
FISHER
Figure 1, type R122H Fcil514ge RegWalm
Superior overpressure Protection - The
combination of a high capacity relief valve and large
vent provide overpressure protection that exceeds
t II standards When used in conjunction with a
R622 or R652. the two -stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
Corrosion -Resistant - Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
sprang and retainer and a corrosion resistant relief
valve seat.
Positive Draining Spring Case- When installed
property with the spring case vent pointed down,
the design allows moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
4r
EMERSON
Process Management
Bulletin LP-7: R122H
Table 1. Ordenng Information
TYPE NUMBER
CAFACRI/ STUINR
CONNECTIONS
PROPANEnI
INLET x 0VT,Er
NOMN4AL OUTLET wrmmG
R 122H.AM
1.100.000
114-arch x 124ftch NPT
to pug (0.69 Char)
1 CO2M s eased on 2e PSIG W Out adel puma am 20%drm
W4.fe 19
0
C.,
I;
Flgure 2. Type R122H Ounensrons ottllss
lafml
LMas equipment
emelson Process LUmSement
Reg hftr Tochnekhghhs, Inc.
USA -Headgmt lg
MdO m . Texas 75w2-f a72 USA
Telephone: 1 (NO) 5595953
Telephone: 1(972) 5403574
For hnther mbffnvoan visit www kheeegutators.mmAp
nor I Pope Is a OadORfile u d UPON RVA Of EM&M E*CIrC G AD WW mVb am em pVWV d UW OIWOaWfe afYlMlfe I1slfera d afate daffaa W ffilfer Calxepa efC i
bfA mmarEdperepePfoeeet II —ON melu
The a01001d al0xa pdi COM am praaeneW IN edonaaadful 9"Fam aft, av aWo OW" qdM ON OM am" of emfae ww accuracy. 0 "rwt lb00 4onsaw ee Oalt W 0p . e'VfM W' p0e4leee+ae I ft OOdaOe m+rrraee mxaNd hU nor IM use a appersemy Vft MS ft apm b malt O, ,"j, ohs oleaYp» a spetlQph�n a►awn MORM d iffy titre ven d Ream.
fe O i g solaM ieCn eq paiufa (a► pr abtOaf faO ar"awa "*' WN v@'a ROMOnO IV Ow 0100 ameaoon- UK W4 MOUROW d aft Eff�msan
EMERSON..
Goner=Oft k"naDMOd RIWMW TMV"M ft..2M.2010:AMRgebRRwvW Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Comp=r+ no.i n
Prot&
Scree
uinh Cnnnrjt%/
2elief
leight
Inlet and Outlet Pressure Gauge Taps
Fpure t. rvor R62i Free. my Pngeranr
Introduction
Type R622 direct -operated. spring -loaded regulators
provide economical pressure reducing control in
a variety of residential, commercial. and industrial
FISHER'
appl¢ations. These regulators can he used with
natural. manufactured. or propane gases and have the
same inlet and outlet pressure capabilities.
EMERSON
Bulletin 71.1:R622
Specifications
Body Size and End Connection StyleM Pressure Registration
112 NPT inlet and cutlet Internal
Maximum Allowable Inlet Pressurelll
Operating: 125 psig (8.6 bar)
Emergency: 125 psig (8,6 bar)
Except 1.8 to 2.2-inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4.1 bar)
Maximum Allowable Outlet (Casing) PressureM
Operating to Avoid Internal Part Damage:
3 psid (0.21 bar d) above outlet pressure setting
Emergency: 20 psi (1.4 bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
1/8-inch (3.2 mm) orifice
Flow Coefficients
Wide -Open CO for Relief Sizing: 12.5
Wide -Open C„ for Relief Sizing: 0.36
C1: 35
IEC Sizing Coefficients
XT 0.78
Fo: 0.82
FL: 0.89
Flow Capacities
See Table 2
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22-inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20-inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200% over setpoint
from 20-inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
314 NPT with removable screen
Temperature Capabilities(')
-20° to 160°F (-29° to 71 •C)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case,
Orifice: Aluminum
Diaphragm Plate, and
Diaphragm, Disk, and O-ring: Nitrile (NBR)
Adjusting Screw and Pushpost: Delrins
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc -plated steel
Machine Screw, Spring Seat,
and Lever. Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer.
Lever Pin, and Vent Screen: Stainless steel
1 T11e0 1 1, OU I I MnWMffl*ftBU2M0rVVa99"' Mtin"MIaoonSWAnotnaaw�a
DMVP ncow tvr1.0uPm4aeNffl= aawCo
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
Table 1. Outlet Pressure Ranges
Specifications
The Spedfcations section lists specifications tar Type R622
Pressure Reducing Regulators. As it originally comes
from the factory. specifications for a given regulator
are stamped on the spring case nameplate.
01Jn flT PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WIRE DIAMETER
INCHES (mm)
SPRING FREH LENGTH.
INCHES (ran)
18 to 2.24aches wx (4 to 5 anal)
T 14453TOO 12
Purple
0051(1,30)
3.40 (86.4)
5 to 7-4ftchn w C. (12 to 17 mbar)
T 14398TC012
Orange
0.062 (1.30)
3A0 (86.4)
6.5 to "C1es we. (1610 22 mbar)
T 1439910012
Yellow
0.067 (1.70)
3.61 191.71
9 to 13anC1es w.c. (22 to 32 MWO
T 144O0T0012
Stever
0 072 (1.63)
4.10 (1041
13 to 204MC11Cs w.e (3210 50 mbar)
T 14401T0012
Gray
0 060 (2.03)
3.60 (91.4)
16 t0 354%ches w.c. (40 t0 87 nmar)
T 1440270012
PM%
0093(2.36)
3.52 (89.4)
1 b 2.2 pslg (69 to 152 mbar)
T14403T0012
L1gnt eR1e
0 105 (2.67)
3.66 (93.0)