May 28, 2021
CONTRACTOR: St. Lucie Site Development
P.O. Box 1132
Fort Pierce, Florida
JOB LOCATION: 4906 Buchanan Drive
Fort Pierce, Florida
PERMIT #: 2103-0018
To Whom it may concern,
Mailing
ENGINEERING PO Box 78-1377
AND TESTING Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
As requested, we tested the compacted fill for the Compacted Foundation Fill.
KSM JOB #: 213912-1d/CFAo
To determine if the fill was properly compacted on the pad to a depth of 3 feet, we performed nucleardensity
tests on the top two feet. To estimate the soil density below a depth of 2 feet we used a Static Cone
Penetrometer. During the tests, a shaft with a conical point is pushed through soil and the soil resistance
measured on a calibrated gauge. After the soil resistance is measured, the hole is advanced with a hand -auger in
1-foot increments to permit a continuation of measurement of density versus depth. Test Results:
Nuclear density tests performed on the top 2 feet indicates the compaction exceeds the project specifications of
95% (ASTM 1557). Static Cone Penetrometer readings indicate the compacted backfill
below 2 feet are generally well compacted to a depth of 3 feet.
Based on the nuclear density tests and Static Cone Penetrometer readings, it appears the fill on the house pad
was properly compacted.
Should you have any questions, please feel free to contact our office.
Respectfully,
This Item has been electronically signed and
sealed by Bryan E. Dahlke, PE FL, Lic. 81439
n the date stated directly t, the right using
a digital signature.
Printed copies of this documents are not
nsidered signed and sealed and the
signature must be verified -any electronic
mpies.
Bryan E. Dahlke, P.E. V.P. of Engineering
PE # 81439 05/28/21
Digitally
signed by
Bryan E Dahlke
Date:
2021.05.28
13:37:03
-04'00'
Email: St Lucie Building Department; slsdevinc@aol.com
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
Proudly Serving Florida since 1990
Certified Women Owned Business - WBE
Headquarters
11345 U.S. Highway 1
Sebastian, FL. 32958
Orlando
723 Progress Way
Sanford, FL. 32771
DATE TESTED
PERMIT #:
CONTRACTOR:
JOB LOCATION:
1P 40 1 t ENGINEERING
i117iVi AND TESTING
SOIL COMPACTION REPORT
ASTM D 1557 and ASTM D 6938
May 27, 2021
2103-0018
St. Lucie Site Development
4906 Buchanan Drive
Fort Pierce, Florida
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net
KSM JOB #
NUC #
Nuc Model:
Nuc Serial #:
213912-1d/CF/jo
234
MC -DR
M D60308234
ITEM TESTED:
Compacted Foundation Fill
TEST LOCATION
PEN
DRY
MAX. DRY
PERCENT
DEPTH
OF SAMPLE
READ
DENSITY
PROCTOR VALUE (P.C.F)
COMPACTION
1 N.W.
0" - 12"
45
108.1
111.3
97.1%
2 N.E.
50
109.6
98.5%
3 Center
45
108.4
97.4%
4 S.E.
50
108.8
97.8%
5 S.W.
45
109.3
98.2 %
6 N.E.
12" - 24"
50+
108.3
97.3%
7 S.W.
"
50+
108.7
97.7%
Soil Description:
Gray/Brown Sand with traces
of Clay
In Place Moisture:
7.4%
Proctor Optimum Moisture:
11.0%
Proctor Max. Dry Density: P.C.F.
111.3
@ Test Locations the Density &
Penetrometer readings indicate the
Degree of Compaction Meets
Minimum Requirement
for Unstaked Foundation
Respectfully Submitted:
113.0 I I I I I I I
W
E 112.0.. ..—�.—.—.. ..—�..—.�.—..� _
G111.0..�..-4.—.�—.. I.—..�.._
H I I I I I I
T 1R0.0 —.
—1..—.I. ..r.._
P Y I I I I I I
109.0 _..—......
C
I I I I I I
108.0 �..�. _l._.1—..�..�.._.I._..�.._
F I I I I I I
107.0 rt.._I._.1—..�..�.._.I._..r.._
106.0 �..rt..—:——..t..�..—.�.—..�..�
6 7 8 9 10 11 12 13 14
Moisture - % of Dry Weight
Disclaimer: Contractor is responsible to maintain the tested area
in the condition that KSM completed the indicated passed
compaction test. KSM is not responsible if the tested area has
been altered from the approved inspected condition.
Bryan E. Dahlke, P.E. V.P. of Engineering
PE# 81439 5/28/2021
Email: St Lucie Building Department; slsdevinc@aol.com
Test report shall not be reproduced, except in full, without the written approval of KSM Engineering & Testing
Geotechnical Engineering - Construction Materials Testing - Special Inspections - Civil and Structural Consulting
Headquarters
11345 U.S. Highway 1
Sebastian, FL. 32958
Orlando
723 Progress Way
Sanford, FL. 32771
*l 40 1 t ENGINEERING
i117jVi AND TESTING
Proudly Serving Florida since 1990
Certified Women Owned Business - WBE
Mailing
PO Box 78-1377
Sebastian, FL. 32978
Phone: 772-589-0712
C.A.# 5693
KSMengineering.net